This document is a Statement of Need (SON) for a federal solicitation to replace two standby diesel generator systems at Beale Air Force Base facilities B810 and B845. The solicitation, identified as FA4686R0025, is for the installation of new 20kW Cummins generator systems, including fuel tanks, bypass automatic transfer switches, and other required appurtenances. The work includes demolition of the existing generator systems and providing temporary rental generators during the replacement. The solicitation has two contract line items (CLINs) - CLIN 0001 for the B810 generator and CLIN 0002 for the B845 generator. Contractors must comply with various NFPA, DAFMAN, and UFC standards and perform testing, commissioning, and close-out documentation. A site visit is scheduled for July 22, 2024, with a proposal deadline of July 26, 2024. The estimated value of the contract is between $500,000 and $1,000,000.

View the file

Other files

File Type Posted
Solicitation Amendment - FA468624R00250004.pdf PDF
Solicitation Amendment FA468624R00250004 SF 30.pdf PDF
Attachment 7.docx DOCX document
Solicitation Amendment - FA468624R00250003.pdf PDF
Solicitation Amendment FA468624R00250003 SF 30.pdf PDF
Solicitation Amendment - FA468624R00250001.pdf PDF
Attachment 5. FA468624R0025 Section M (25Jul24).docx DOCX document
Attachment 7. Resp_RFIs for Cummins Generator Installation (B810, B845) Version 2.pdf PDF
Solicitation Amendment FA468624R00250002 SF 30.pdf PDF
Attachment 4. FA468624R0025 Section L (25Jul24).docx DOCX document
Solicitation Amendment FA468624R00250001 SF 30.pdf PDF
Attachment 1. FA468624R0025 - B810 and B845 SON Version 2 (24 July 24).pdf PDF
Attachment 2. BAEY 240021 - Site Plan Version 2 (24Jul24).pdf PDF
Attachment 8. B845 - Site Pictures, Combined.pdf PDF
Solicitation Amendment - FA468624R00250001.pdf PDF
Attachment 7. Responses_RFIs for Cummins Generator Installation (B810 B845).pdf PDF
Attachment 5. FA468624R0025 Section M.docx DOCX document
Attachment 6. AF 3064 Progress Schedule.xlsx XLSX spreadsheet
Solicitation - FA468624R0025.pdf PDF
Attachment 3. BAEY 240021 - AF 66.xls XLS spreadsheet
Attachment 4. FA468624R0025 Section L.docx DOCX document
Attachment 2. BAEY 240021 - Site Plan.pdf PDF
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CLIN 0001 Base Bid BAEY240021 Replace Standby Generator B810 CLIN 0002 Base Bid BAEY240022 Replace Standby Generator B845

Statement of Need

Introduction The 9th Contracting Squadron is soliciting a proposal for repair by replacement of two separate standby diesel generator systems. The Contract Line Item (CLN) for bid are identified as:

· CLIN 0001 Base Bid Project Number BAEY 240021 is located at Facility B810.

· CLIN 0002 Option 2 Project Number BAEY 240022 is located at Facility B845.

The Contractor shall provide a work plan for a complete and usable system within the negotiated and accepted contract construction cost and meeting all requirements of this statement of work. The government will not accept requests for additional funds unless approved in writing by the Contract Officer.

The work shall include removal and disposal of the existing standby diesel generator system Automatic Transfer Switch (ATS). The Contractor shall install a new Cummins 20kW generator system, complete with fuel tank, a Cummins Diesel compatible Bypass ATS, and specified appurtenances in accordance with (IAW) UFC 3-540-01, NFPA 70, and NFPA 110 and applicable references Specified in UFC 3-540-01. Contractor shall furnish all supervision, labor, tools, equipment, materials, operations, and incidentals required. Contractor shall perform all necessary connections to the generator and bypass ATS so that they are fully operational in accordance with all current NFPAs, DAFMANs, UFCs, State and local codes and regulations.

Install Cummins Compatible Onan ATS, 150A, open transition, four-pole with bypass capability.

Install manual transfer switch to connect portable generator if the emergency back-up generator fails.

The installation a permanently installed generator and a connection for a portable generator, do not connect the conductors for both generators directly onto the emergency side of the associated ATS. Install a double-throw switch upstream of the ATS; connect the permanently installed generator and the portable generator connection to this double-throw switch, with the output of the switch connected to the ATS emergency source connection.

Install load bank connections on the emergency side of the ATS, with cam-lock connectors.

Commissioning of generation system shall comply with UFC-3-540-01. Prior to acceptance by the government, the Contractor shall turn-over the O&M manuals, manufacture’s technical specifications, technical drawings, and line diagrams.

The contractor shall be responsible for applying for the Air Quality permits from the Feather River Air Quality Management District in coordination with 9 CES Environmental Section for compliance. The contractor shall initiate an Authority to Construct (AF103) and field verify existing underground utilities related to the project. The contractor will be provided escort(s) while performing all phases of this work.

CLIN 001 – BASE BID STANDBY GENERATION SYSTEM B810

Install new Cummins 20kW generator, 3 wire, remote start, 120/208 VAC, 60Hz, to include battery charger.

Demolition:

Remove existing 17kW standby generator and fuel tank. Provide 20kW backup rental generator for emergency power in the event of a power outage. Remove all existing conduit and conductors from the generator to the ATS, and ATS to the 100A, 120/208 VAC main disconnect switch. Note: If upon testing, it is determined that the existing cabling/conduit is compliant with current standards and is functional, it may remain in place.

REFERENCES

· UFC 3-540-01

Prior to Commissioning

1. Install hazard identification signs as specified in NFPA 704, Standard System for the Identification of the Hazards of Materials for Emergency Response, on stationary aboveground tanks.

2. Install all previously removed conduit and conductors with NEW approved cabling IAW with the current Beale Installation Specific Guide (ISG)

3. Install Automatic External Defibrillators (AED) due to the proximity of medical services in the event of an emergency.

4. Perform Arc Flash analysis and install warning labels.

5. Perform integrity test of generator system set tank.

6. Ensure equipment grounds are tested.

7. Ensure that the generator and ATS are initially tested IAW with all current NFPA, DAFMAN, UFC references, to include initial load bank testing.

8. Due to the mission this generator supports, all NFPA testing will be IAW with NEC Article 701, Legally Required Standby Systems, and NFPA 110, Level 1 criteria.

Ensure the Electrical Power Production shop and the Electrical Sub-AMP manager are present for all testing and commissioning. Ensure that 9 CES is provided all warranty and close out documents.

CLIN 002 – OPTION 1 STANDBY GENERATOR SYSTEM B845

Install new Cummins 20kW generator, 3 wire, remote start, 120/240 VAC, 60Hz, to include battery charger.

Demolition:

Remove existing 20 kW standby generator and tank. Provide 20 kW rental generator for emergency power in the event of a power outage. Remove all existing conduit and conductors from the generator to the ATS, and ATS to the 100A, 120/240 VAC main disconnect switch. Note: If upon testing, it is determined that the existing cabling/conduit is compliant with current standards and is functional, it may remain in place as it is a direct burial.

REFERENCES

· UFC 3-540-01

Prior to Commissioning

9. Install hazard identification signs as specified in NFPA 704, Standard System for the Identification of the Hazards of Materials for Emergency Response, on stationary aboveground tanks.

10. Install all previously removed conduit and conductors with NEW approved cabling IAW with the current Beale Installation Specific Guide (ISG)

11. Install Automatic External Defibrillators (AED) due to the proximity of medical services in the event of an emergency.

12. Perform Arc Flash analysis and install warning labels.

13. Perform integrity test of generator system set tank.

14. Ensure equipment grounds are tested.

15. Ensure that the generator and ATS are initially tested IAW with all current NFPA, DAFMAN, UFC references, to include initial load bank testing.

16. Due to the mission this generator supports, all NFPA testing will be IAW with NEC Article 701, Legally Required Standby Systems, and NFPA 110, Level 1 criteria.

Ensure the Electrical Power Production shop and the Electrical Sub-AMP manager are present for all testing and commissioning. Ensure that 9 CES is provided all warranty and close out documents.

END OF SON – STATEMENT OF NEED