Attachment 06a - Drawings 100CD-Electrical.pdf
PDF 665 KB Posted
- Attached to
- Y1DA--VISN 8 MATOC - CARIBBEAN
- Solicitation number
- 36C77624R0149
About this file
This document is an electrical drawing set for a VA project located at 10 Calle Casia in San Juan, Puerto Rico, specifically for providing high-level disinfection services for the SPS (Sterile Processing Services) area. The electrical drawings include a cover sheet with electrical abbreviations and notes, demolition and new work floor plans, electrical details showing occupancy sensor wiring, and panel schedules for two branch panels (1LSPD1 and 1LSPD2).
The drawings detail electrical work for renovating an existing administrative building, with a focus on the electrical systems supporting medical equipment such as sterilizers, ultrasonic cleaners, washers, and other specialized medical devices. The panel schedules show both existing and new circuit configurations, with specific attention to receptacle and lighting circuits. Notable electrical specifications include using plenum-rated cabling, maintaining fire-rated partition integrity, coordinating with mechanical and plumbing contractors, and ensuring all new materials are UL-listed and installed to meet the National Electrical Code (NEC) standards.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A - AMPERE
AC - ALTERNATING CURRENT
AF - AMP FRAME
AFF - ABOVE FINISHED FLOOR
AHJ - AUTHORITY HAVING JURISDICTION
AL - ALUMINUM
ATS - AUTOMATIC TRANSFER SWITCH
AIC - AMPS INTERRUPTING CAPACITY
BRKR - BREAKER
C or COND - CONDUIT
CD - CANDELA
CKT - CIRCUIT
CT - CURRENT TRANSFORMER
CU - COPPER
DN - DOWN
DW - DISHWASHER
DWG - DRAWING
DC - DIRECT CURRENT
(E) or EXIST - EXISTING
E.C - ELECTRICAL CONTRACTOR
ELEV - ELEVATOR
EMER - EMERGENCY
EMT - ELECTRIC METALLIC TUBING
EUH - ELECTRIC UNIT HEATER
EWC - ELECTRIC WATER COOLER
EWH - ELECTRICAL WATER HEATER
F - FUSE
FA - FIRE ALARM
FCA - FAULT CURRENT AVAILABLE
FCR - FAULT CURRENT RATING
G , GND - GROUND
GFI/GFCI - GROUND FAULT CIRCUIT INTERRUPTER
GFEP - GROUND FAULT EQUIPMENT PROTECTION
HZ - HERTZ
HP - HORSEPOWER
IG - ISOLATED GROUND
J - JUNCTION BOX
KVA - KILOVOLT-AMPERE
KW - KILOWATT
LTG - LIGHTING
M - METER
MCA - MINIMUM CIRCUIT AMPACITY
MCB - MAIN CIRCUIT BREAKER
MCC - MOTOR CONTROL CENTER
MFR - MANUFACTURER
+, MH - MOUNTING HEIGHT
MLO - MAIN LUGS ONLY
MOP, MOCP - MAXIMUM OVERCURRENT PROTECTION
MS, MSB - MAIN SWITCHBOARD
NEC - NATIONAL ELECTRICAL CODE
(N) - NEW
NA - NOT APPLICABLE
NC - NORMALLY CLOSED
NF - NON-FUSED
NIC - NOT IN CONTRACT
NO - NORMALLY OPEN
OCPD - OVERCURRENT PROTECTION DEVICE
P - POLE
PH OR ∅ - PHASE
NEMA - NATIONAL ELECTRIC MANUFACTURERS
ASSOCIATION
PB - PULL BOX
PC - PHOTOCELL
PNL - PANELBOARD
(R) - RELOCATED
RECEPT - RECEPTACLE
RM - ROOM
SPD - SURGE PROTECTIVE DEVICE
THD - TOTAL HARMONIC DISTORTION
TVSS - TRANSIENT VOLTAGE SURGE SUPPRESSION
TYP - TYPICAL
UL - UNDERWRITERS LABORATORIES
UON - UNLESS OTHERWISE NOTED
UPS - UNINTERRUPTIBLE POWER SUPPLY
V - VOLT
VFD - VARIABLE FREQUENCY DRIVE
W - WATT
WP - WEATHERPROOF
XFMR - TRANSFORMER
ELECTRICAL ABBREVIATIONS
CIRCUITING LEGEND
ELECTRICAL NOTES
1. THE CONTRACT DOCUMENTS CONSIST OF DRAWINGS, SPECIFICATIONS AND DESIGN INFORMATION PREPARED BY MULTIPLE DISCIPLINES AND MUST
BE USED AS A WHOLE AND IN COORDINATION WITH EACH OTHER. THE CONTRACTOR SHALL NOTIFY THE ENGINEER OF ANY APPARENT DISCREPANCIES OR OMISSION OF INFORMATION NOT SHOWN ON THE ELECTRICAL DRAWINGS. SHOP DRAWINGS SHALL BE PROVIDED WHERE NECESSARY FOR COORDINATION. THE CONTRACTOR IS RESPONSIBLE FOR CORRECTING ERRORS RESULTING FROM LACK OF COORDINATION OF
DOCUMENTS.
2. THE CONTRACTOR RESPONSIBLE FOR THE EXECUTION OF THIS WORK SHALL BECOME THOROUGHLY FAMILIAR WITH THE PROJECT REQUIREMENTS BEFORE COMMENCING ANY WORK. THE PROJECT SPECIFICATIONS AND DRAWINGS FORM THE BASIS OF THE CONTRACT REQUIREMENTS AND INCLUDE THE TYPE AND GRADE OF MATERIALS TO BE INSTALLED, EQUIPMENT TO BE FURNISHED, THE MANNER BY WHICH TO BE INSTALLED AND WHERE TO BE LOCATED. IN THE EVENT OF A CONFLICT BETWEEN THE PROJECT SPECIFICATIONS AND DRAWINGS, ASSUME THE MOST STRINGENT
AND/OR COSTLY REQUIREMENT APPLIES.
3. ALL WORK SHALL BE DONE IN A FIRST CLASS WORKMANLIKE MANNER BY A LICENSED ELECTRICAL CONTRACTOR. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING A SAFE, CLEAN, AND PROFESSIONAL JOB SITE THAT DOES NOT IMPEDE EGRESS PATHS OR IMPACT OTHER TENANTS.
DISRUPTIONS TO POWER AFFECTING OTHER TENANTS OR AREAS OUTSIDE THE SCOPE OF WORK SHALL BE COORDINATED WITH THE OWNER. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING OF HIS WORK. WHEN THE WORK IS COMPLETE, ALL ELECTRICAL DEVICES AND WORK AREAS SHALL BE VACUUMED CLEAN. THE FINAL PRODUCT SHALL BE A FULLY FUNCTIONAL SYSTEM MEETING THE INTENT OF THE DRAWINGS/DOCUMENTS. WORKMANSHIP AND ALL MATERIALS AND EQUIPMENT SHALL BE GUARANTEED FOR A MINIMUM OF ONE YEAR IN WRITING
COMMENCING UPON ACCEPTANCE OF INSTALLATION BY OWNER.
4. UNLESS PROVIDED WITH DIMENSIONS OR NOTED OTHERWISE, ELECTRICAL PLANS ARE STRICTLY DIAGRAMMATIC ONLY. REFER TO THE ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS, MOUNTING HEIGHTS, ETC. EFFORT HAS BEEN MADE TO PROPERLY ACCOUNT FOR ALL SPACE REQUIREMENTS, CLEARANCES, ETC. BUT SITE CONDITIONS AND PRODUCTS SELECTED MAY VARY AND IT IS THE CONTRACTOR'S RESPONSIBILITY TO
MAINTAIN PROPER ARRANGEMENTS AND CLEARANCES. DRAWINGS SHALL NOT BE SCALED.
5. CONDUITS RUNS SHOWN ON THE DRAWINGS ARE DIAGRAMMATIC. ALL CONDUIT SHALL BE RUN CONCEALED, EXCEPT IN EQUIPMENT ROOMS AND WHERE APPROVED BY ARCHITECT. ANY EXPOSED CONDUITS IN FINISHED AREAS SHALL BE PAINTED TO MATCH SURROUNDING CONSTRUCTION.
VERIFY PAINT COLOR WITH THE ARCHITECT.
6. COORDINATE WITH OTHER TRADES AND INSTALL CONDUIT AND BOXES TO CLEAR EMBEDDED DUCTS, OPENINGS, AND OTHER STRUCTURAL
FEATURES.
7. THE CONTRACTOR IS EXPECTED TO HAVE A FULL FUNCTIONAL KNOWLEDGE OF ELECTRICAL SYSTEMS AND WHETHER INDICATED ON THE DRAWINGS OR NOT SHALL PROVIDE THE CORRECT NUMBER OF WIRES, AT NO ADDITIONAL CHARGE, TO FACILITATE PROPER OPERATION OF ALL EQUIPMENT.
QUANTITY OF WIRES WILL ONLY BE INDICATED WHERE NECESSARY FOR CLARIFICATION.
8. THE INSTALLATION SHALL BE IN COMPLIANCE WITH THE AMERICAN WITH DISABILITIES ACT (ADA), UNLESS INSTALLED FOR SPECIFIC USES EXEMPT
FROM ADA OR IN AREAS NOT NORMALLY ACCESSED BY BUILDING OCCUPANTS.
9. THE ELECTRICAL CONTRACTOR SHALL REFER TO THE MECHANICAL AND PLUMBING DRAWINGS FOR EXACT LOCATIONS OF EQUIPMENT. PRIOR TO ORDERING ELECTRICAL EQUIPMENT SERVING MECHANICAL & PLUMBING EQUIPMENT, THE ELECTRICAL CONTRACTOR SHALL CONFIRM THE EQUIPMENT BEING ORDERED BY THE MECHANICAL OR PLUMBING CONTRACTORS AND PROVIDE WIRING, CONDUIT, AND OVERCURRENT PROTECTION MEETING THE REQUIREMENTS AT NO ADDITIONAL COST TO THE OWNER. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR REVIEWING AND COORDINATING WITH THE MECHANICAL AND PLUMBING CONTRACTORS FOR PROVIDING ANY NECESSARY LINE AND LOW VOLTAGE WIRING.
FINAL TERMINATION TO BE MADE BY THE MECHANICAL CONTRACTOR.
10. ALL MATERIALS AND EQUIPMENT FURNISHED SHALL BE NEW (UNLESS NOTED OTHERWISE) AND BEAR THE U.L. LISTING FOR THEIR INTENDED USE.
EQUIPMENT LABELS AND INSTRUCTIONS REGARDING THE APPLICATION AND INSTALLATION OF THE LISTED EQUIPMENT SHALL BE FOLLOWED TO ENSURE THAT THE EQUIPMENT IS BEING INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S LISTING INSTRUCTIONS. THE TEMPERATURE RATING OF THE EQUIPMENT TERMINATIONS MUST BE CAREFULLY CORRELATED WITH THE CONDUCTOR AMPACITY TO PREVENT OVERHEATING AND
PREMATURE FAILURE.
11. EVEN IF THE PLANS INDICATE, OUTLETS SHALL NOT BE INSTALLED PRECISELY BACK TO BACK ON COMMON WALLS. REFER TO THE ARCHITECTURAL DRAWINGS FOR EXACT MOUNTING METHODS AND LOCATIONS. RECEPTACLES IN DEMISING WALLS OF MULTIPLE DWELLING UNITS SHALL NOT BE
INSTALLED BACK TO BACK UNDER NO CIRCUMSTANCES.
12. JUNCTION AND PULL BOXES ARE ONLY INDICATED WHERE REQUIRED FOR LARGE SCALE COORDINATION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FURNISHING JUNCTION AND PULL BOXES AS REQUIRED BY THE CODE AND PER A STANDARD INSTALLATION, AND SHALL INCLUDE THIS IN THEIR
BID.
13. THE CONTRACTOR SHALL MAINTAIN THE FIRE RATING OF ALL FIRE-RATED PARTITIONS, AS INDICATED IN IEEE RED BOOK. IF A DEVICE WILL VOID THE FIRE RATING OF A WALL, IT SHALL BE INSTALLED IN AN ALTERNATE LOCATION PER THE ARCHITECT OR ENGINEER'S DIRECTION. ALL VOIDS AROUND CONDUITS AND/OR CORE DRILLS PENETRATING FIRE RATED PARTITIONS SHALL BE FILLED WITH FIRE-SAFING MATERIAL OR UL APPROVED FIRE
RATING DEVICE. THE FIRE RATING OF A PARTITION SHALL NEVER BE COMPROMISED.
14. THE CONTRACTOR SHALL MAINTAIN THE INSULATION RATING AND VAPOR BARRIERS ON ALL PERIMETER WALLS. IF A DEVICE WILL DAMAGE OR COMPROMISE THE VAPOR BARRIER OR INSULATION, IT SHALL BE INSTALLED IN AN ALTERNATE LOCATION PER THE ARCHITECT OR ENGINEER'S
DIRECTION.
15. PRIOR TO PENETRATING STRUCTURE, THE CONTRACTOR SHALL X-RAY THE SLABS. CONCRETE CUTTING, CORE DRILLING, AND ANY OTHER ACTION THAT COULD AFFECT OTHER SPACES BY NOISE OR INTRUSION SHALL BE DONE AFTER HOURS. ALL SLAB/STRUCTURE PENETRATIONS SHALL BE
COORDINATED WITH THE STRUCTURAL ENGINEER FOR APPROVAL.
16. ALL EQUIPMENT REQUIRING ACCESS SUCH AS J-BOXES, PULL BOXES, TRANSFORMERS, DRIVERS, ETC. SHALL BE INSTALLED IN ACCESSIBLE
LOCATIONS.
17. CABLE AND CONDUIT ROUTING SHALL BE DONE IN A NEAT AND ORDERLY FASHION. LINES SHALL BE RUN PARALLEL TO ALL BUILDING FEATURES, AND SHALL BE GROUPED TOGETHER TO CREATE AN AESTHETICALLY PLEASING AND EASY TO FOLLOW ROUTE. METAL CLAD CABLES SHALL BE PERMITTED TO BE BUNDLED BUT SHALL NOT EXCEED TEN IN QUANTITY. ROUTING SHALL BE COORDINATED WITH OTHER TRADES TO AVOID CONFLICT.
18. CONDUITS SHALL BE RIGIDLY SUPPORTED TO THE BUILDING STRUCTURE AS REQUIRED BY PROJECT SPECIFICATIONS. ALL SUPPORT SPACINGS FOR ALL RACEWAY TYPES SHALL BE IN ACCORDANCE WITH THE NEC. EXPANSION FITTINGS SHALL BE PROVIDED AT ALL BUILDING EXPANSION JOINTS OR
WHERE NEEDED TO ALLOW FOR THERMAL EXPANSION.
19. CONDUIT SIZES INDICATED IN PANEL SCHEDULES AND ON THE SINGLE LINE ARE BASED ON TYPE THHN IN EMT. AS OTHER TYPES OF CONDUIT AND CONDUCTORS ARE PERMISSIBLE IN THIS PROJECT, THE CONTRACTOR SHALL ADJUST THE DIMENSION OF THE CONDUIT TO COMPLY WITH CHAPTER 9, TABLE 1 IN THE NEC. ADJUSTMENTS TO THE CONDUIT SIZE SHALL BE PART OF THE BID AND SHALL BE AT NO ADDITIONAL EXPENSE TO THE OWNER.
20. WIRE SIZES INDICATED ARE BASED UPON DIRECT ORTHOGONAL PATHS TO THE PANELBOARD. TOTAL VOLTAGE DROP BETWEEN FEEDER AND BRANCH CIRCUIT SHALL NOT EXCEED 5%. IF FIELD CONDITIONS DO NOT ALLOW THESE PATHS OR IF THE CONTRACTOR RUNS ADDITIONAL LENGTHS, THEY SHALL BE RESPONSIBLE FOR INCREASING WIRE SIZE TO ACCOUNT FOR VOLTAGE DROP AT NO ADDITIONAL COST. WIRING SMALLER THAN #12
AWG SHALL NOT BE USED FOR ANY INSTALLATIONS.
21. THE CONTRACTOR SHALL CIRCUIT PANELBOARDS EXACTLY AS INDICATED IN THE PANEL SCHEDULES. IF ANY DEVIATIONS ARE NECESSARY, THE ENGINEER SHALL BE NOTIFIED. TYPED DIRECTORY CARDS SHALL BE PROVIDED AT EACH PANELBOARD INDICATING LOAD SERVED AND FINAL ROOM NUMBERS PER THE NEC. WHEN EXISTING DIRECTORIES ARE REPLACED FOR RENOVATION WORK, EXISTING LOAD INFORMATION SHALL BE DIRECTLY
TRANSFERRED TO THE NEW DIRECTORY CARDS.
22. WHEN A RETURN AIR PLENUM IS UTILIZED, ALL CABLING AND CONDUIT SHALL BE PLENUM RATED OR IN PLENUM RATED CONDUIT. THIS INCLUDES
TELEPHONE, DATA, CONTROL CABLES, ETC. AND RESTRICTS THE USE OF PVC.
23. THE CONTRACTOR SHALL PROVIDE THE PROPER FIXTURE TYPE FOR THE CEILING OR WALL TYPE WHICH THE FIXTURE IS TO BE INSTALLED IN INCLUDING TRIM, MOUNTING ACCESSORIES, ETC. REGARDLESS OF THE MODEL NUMBERS IN THE LIGHT FIXTURE SCHEDULE, THE CORRECT MOUNTING TYPE SHALL BE PROVIDED. THE CONTRACTOR SHALL REFER TO INTERIOR DESIGNER, ARCHITECTURAL, LANDSCAPE, OR OTHER CONSULTANT PLANS FOR ADDITIONAL INFORMATION AND REQUIREMENTS; WHERE THERE IS A DISCREPANCY BETWEEN ELECTRICAL PLANS AND OTHER OCNSULTANT PLANS, THE OTHER CONSULTANT PLANS SHALL TAKE PRIORITY EXCEPT FOR VOLTAGE AND WATTAGE OF FIXTURES. FIXTURE TYPES IN THE LIGHT FIXTURE SCHEDULE ARE TO ESTABLISH A TYPE, NOT A METHOD OF MOUNTING. LIGHT FIXTURES LOCATED IN A WET OR DAMP LOCATION SHALL BE LISED FOR SAID USED. LIGHT FIXTURES INSTALLED IN AREAS HAVING EXPOSED FOOD OR FOOD PREPARATION AREAS OR
KITCHENS SHALL BE PROPERLY LENSED AND HAVE SHATTER PROOF LAMPS.
24. ALL LIGHT FIXTURES SHALL BE SUPPORTED FROM THE BUILDING STRUCTURAL SYSTEM BY SUPPORT WIRES, INDEPENDENT OF CEILING GRID SYSTEMS. TROFFER TYPE FIXTURES SHALL BE SUPPORTED BY WIRES AT ALL FOUR CORNERS. RECESSED DOWNLIGHTS SHALL BE SUPPORTED VIA HANGER BARS SUPPORTED BY WIRES AT ALL FOUR CORNERS. SUPPORT MEANS SHALL BE IN ACCORDANCE WITH LOCAL SEISMIC REQUIREMENTS.
25. THE EQUIPMENT GROUNDING SYSTEM SHALL CONSIST OF AN ELECTRICALLY CONTINUOUS METALLIC CONDUIT SYSTEM TOGETHER WITH INSULATED EQUIPMENT GROUNDING CONDUCTORS. ALL BRANCH CIRCUITS AND FEEDERS SHALL HAVE A GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR OR GROUND ELECTRIDE SIZED IN ACCORDANCE WITH THE NEC. USING METALLIC CONDUIT AS THE ONLY EQUIPMENT GROUNDING
CONDUCTOR IS NOT ALLOWED.
26. FLOOR OUTLETS SHALL BE LISTED FOR INSTALLATION IN THE INSTALLED FLOOR TYPE. THEY SHALL MEET UL REQUIREMENTS FOR SCRUB WATER, DIRT, AND DEBRIS EXCLUSION TESTS.
27. WITHIN 90 DAYS AFTER THE DATE OF THE SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE ACTUAL CONDITIONS SHALL BE PROVIDED TO THE BUILDING OWNER, INCLUDING A SINGLE-LINE DIAGRAM OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM AND FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR ALL DISTRIBUTION. ADDITIONALLY, AN OPERATING MANUAL AND MAINTENANCE MANUAL SHALL BE PROVIDED TO THE BUILDING OWNER INCLUDING THE FOLLOWING: SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE, OPERATION MANUALS AND MAINTENANCE MANUAL FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE INCLUDING CLEARLY IDENTIFIED ROUTINE MAINTENANCE ACTIONS, AND NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED
SERVICE AGENCY.
28. IN ACCORDANCE WITH FLORIDA ENERGY CONSERVATION CODE C408.1.1 - THE BUILDING OPERATIONS AND MAINTENANCE DOCUMENTS SHALL BE PROVIDED TO THE OWNER AND SHALL CONSIST OF MANUFACTURERS INFORMATION, SPECIFICATION, AND RECOMMENDATIONS, PROGRAMMING PROCEDURES AND DATA POINTS, NARRATIVES, AND OTHER MEANS OF ILLUSTRATING TO THE OWNER HOW THE BUILDING EQUIPMENT AND SYSTEMS ARE INTENTED TO BE INSTALLED, MAINTANED AND OPERATED. REQUIRED REGULAR MAINTENANCE ACTIONS FOR EQUIPMENT AND SYSTEMS SHALL BE CLEARLY STATED ON A READILY ACCESSIBLE LABEL. THE LABEL SHALL INCLUDE THE TITLE OR PUBLICATION NUMBER FOR THE OPERATION AND
MAINTENANCE MANUAL FOR THAT PARTICULAR MODEL AND TYPE OF PRODUCT.
29. WITHIN 90 DAYS AFTER THE DATE OF RECEIPT OF THE CERTIFICATE OF OCCUPANCY, A REPORT OF TEST RESULTS SHALL BE PROVIDED AND INCLUDE THE FOLLOWING: (1) RESULTS OF FUNCTIONAL PERFORMANCE TEST. (2) DISPOSITION OF DEFICIENCIES FOUND DURING TESTING, INCLUDING DETAILS OF CORRECTIVE MEASURES USED OR PROPOSED. (FLORIDA ENERGY CONSERVATION CODE C408.3.2.3).
GD - GARBAGE DISPOSAL
MTS - MANUAL TRANSFER SWITCH
MW - MICROWAVE
R - RANGE OVEN
REF - REFRIGERATOR
S
WAP
3-WAY, 20 AMP, SWITCH.
SINGLE POLE, 20 AMP, SWITCH.
DATA OUTLET WITH 1" CONDUIT STUBBED OUT FROM WALL 6" ABOVE CEILING UNLESS
NOTE: NOT ALL SYMBOLS MAY APPLY TO PLANS
LOW VOLTAGE LEGEND
NOTE: NOT ALL SYMBOLS MAY APPLY TO PLANS
20 AMP DUPLEX RECEPTACLE.
20 AMP QUADRUPLEX RECEPTACLE.
20 AMP DUPLEX RECEPTACLE, WITH SELF-TESTING GROUND FAULT CIRCUIT INTERRUPTER.
GFI
20 AMP SIMPLEX RECEPTACLE.
x
RECEPTACLE SUBSCRIPT DEFINITIONS:
a: GFI, WEATHERPROOF (WP), WEATHER RESISTANT (WR), WHILE IN USE.
b: GFI, ABOVE COUNTER.
c: GFI, ABOVE COUNTER, WITH (1) TYPE A AND (1) TYPE C USB PORTS.
20 AMP DUPLEX RECEPTACLE, TOP HALF SWITCHED.
20 AMP DUPLEX RECEPTACLE, CRITICAL BRANCH OF ESSENTIAL SYSTEMS.
20 AMP QUADRUPLEX RECEPTACLE, ONE DUPLEX CONNECTED TO NORMAL CIRCUIT AND ONE DUPLEX
ELECTRICAL SYMBOL LEGEND
x
CEILING MOUNTED HORN/STROBE NOTIFICATION DEVICE WITH 75 CANDELA STOBE.
d: ABOVE COUNTER.
CONNECTED TO EMERGENCY GENERATOR. SUBSCRIPT DEFINITIONS:
a: GFI, ABOVE COUNTER.
b: GFI, ABOVE COUNTER, WITH (1) TYPE A AND (1) TYPE C USB PORTS FOR NORMAL RECEPTACLE.
c: GFI, WITH (1) TYPE A AND (1) TYPE C USB PORTS FOR NORMAL RECEPTACLE.
DATA OUTLET FLOOR RECESS WITH 1" CONDUIT STUBBED UP TO NEAREST WALL UNLESS
CEILING-MOUNTED SPEAKER - IN AREAS OF INACCESSIBLE CEILING, PROVIDE JUNCTION BOX AND 3/4"
CONDUIT TO NEAREST ACCESSIBLE CEILING.
CEILING-MOUNTED WIRELESS ACCESS POINT - IN AREAS OF INACCESSIBLE CEILING, PROVIDE JUNCTION.
AND 3/4" CONDUIT TO NEAREST ACCESSIBLE CEILING.
TELECOM PLYWOOD BACKBOARD. SIZE AS SHOWN ON PLANS.TBB
OTHERWISE NOTED.
OTHERWISE NOTED.
S
S
CR CARD READER WITH 1" CONDUIT STUBBED OUT FROM WALL 6" ABOVE CEILING UNLESS
OTHERWISE NOTED.
PB PUSH TO EXIT BUTTON WITH 1" CONDUIT STUBBED OUT FROM WALL 6" ABOVE CEILING UNLESS
OTHERWISE NOTED.
XX # 1,3,5
PANEL NAME
CIRCUIT NUMBER(S)
HOME RUN SYMBOL
XX # 1,3,5
PANEL NAME
CIRCUIT NUMBER(S)
1,3,5
CIRCUIT NUMBER(S)
ELECTRICAL LEGEND
NEW WORK.
EXISTING TO BE REMOVED (DEMO).
EXISTING TO REMAIN.
APPLICABLE BUILDING CODES
UNIFORM FEDERAL ACCESSIBILITY STANDARDS, LATEST EDITION.
VA FIRE PROTECTION DESIGN MANUAL 2011 EDITION.
NFPA 70, NATIONAL ELECTRICAL CODE 2020 EDITION.
NFPA 101, LIFE SAFETY CODE 2019 EDITION.
INTERNATIONAL BUILDING CODE 2021.
FINISHED FLOOR
AV
OUTLET
RECEPTACLE
DATA OUTLET
CARD
READER
LIGHT
SWITCH
WALL MOUNTED
TELEPHONE
THERMOSTAT
INTERIOR
CEILING
EXTERIOR
AREA
FINISHED GRADE
NOTES:
48"
12"
48" 48"
18" 18" 18"
C
96"
CLOCK OUTLET
102"
EXTERIOR
RECEPTACLE
24" MIN
AV
OUTLET
DUPLEX
RECEPTACLE
8"
42"
DOOR
COUNTERTOP
60"
MOUNTING HEIGHTS NOTED ARE STANDARD, IF
SPECIFIC MOUNTING HEIGHTS ARE NOT NOTED ON THE
PLANS OR IN THE SPECIFICATIONS.
1.
6"
96" AFF OR 6"
FROM CEILING
42" AFF OR 8" ABOVE
CONUTERTOP (TYPICAL)
2" MIN.
EXIT
6" MIN.
EMERGENCY
LIGHTING UNIT
6" MIN.
T
DATA OUTLET
N.T.S
DEVICE MOUNTING HEIGHTS
OS CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR SWITCH.
REVISIONS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
FMS
Project and
Section
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
CD(100%CD-ISSUE FOR BID) SUBMITTAL - 04/22/2024
672-22-810VA PROVIDE HIGH LEVEL
DISINFECTION FOR SPS
10 CALLE CASIA - ADM. BLDG. SUITE
4M456 SAN JUAN, PR 00921-3201
/2
/2
:1
:0
A
M
ELECTRICAL COVER SHEET
E-001
04/22/2024 RGD CDH
CD(100%CD-ISSUE FOR BID)
ELECTRICAL SHEET INDEX
E-001 ELECTRICAL COVER SHEET
EP-101 ELECTRICAL FLOOR PLANS
E-501 ELECTRICAL DETAILS
E-601 PANEL SCHEDULES
NO. DESCRIPTION DATE
E X
E X
E X
EX EX
E X
E X
E X
G F
I G
F I
G F
I
EX EX
M
1LSPD2
1LSPD1
EXISTING ELECTRICAL PANELS
1 (TYP)
EX
9 1LSPD2 - 37
1LSPD2 - 39
1LSPD1 - 6
1LSPD1 - 8
1LSPD2 - 35
1LSPD2
1LSPD1
EXISTING ELECTRICAL PANELS
OS
(TYP)
OS
1LSPD2 - 41
EX
EXISTING
NOTIFICATION DEVICE
DEMOLITION NOTES
1. THE CONTRACTOR SHALL REMOVE ALL UNUSED AND ABANDONED WIRING AND CABLING FROM THE
CEILING PLENUM THAT IS NOT LABELED FOR FUTURE USE, AS REQUIRED BY THE NEC. THIS SHALL INCLUDE BUT IS NOT LIMITED TO FIRE ALARM, POWER, SECURITY, CONTROLS, DATA, TELEPHONE, A/V, ETC.
2. CIRCUITS MADE SPARE SHALL BE UPDATED ON PANEL SCHEDULES. DIRECTORY CARDS SHALL BE REPLACED WITH NEW TYPED DIRECTORIES, INCLUDING ALL NEW LOADS IN ADDITION TO SPARES.
HAND-MARKED NOTES WILL NOT BE ACCEPTED.
3. CARE SHALL BE TAKEN TO RELOCATE ALL EXISTING EQUIPMENT THAT IS BEING MOVED BUT REMAINING AFTER COMPLETION OF WORK. THE CONTRACTOR SHALL BE RESPONSIBLE TO KEEP ALL EXISTING TO REMAIN OR RELOCATED EQUIPMENT AT THE SAME LEVEL OF FUNCTIONALITY FROM THE ACCEPTANCE OF THE CONTRACT TO FINAL COMPLETION. ANY DAMAGE OR LOSS OF FUNCTIONALITY SHALL BE
REMEDIED BY THE CONTRACTOR AT NO ADDITIONAL EXPENSE TO THE OWNER.
4. EQUIPMENT INDICATED TO BE REMOVED AND NOT RE-USED SHALL REMAIN THE PROPERTY OF THE
OWNER AND RETURNED OR STORED AS DIRECTED.
5. CONDUITS AND RACEWAY SYSTEMS MAY BE ABANDONED WHERE CONCEALED HOWEVER SHALL BE REMOVED WHERE EXPOSED. REMOVED OUTLETS SHALL BE PROVIDED WITH BLANK COVERS, COLOR
PER THE ARCHITECTS DIRECTION.
6. EXISTING RACEWAYS AND WIRING ARE ALLOWED TO BE RE-USED PROVIDED THEY MEET THE
SPECIFICATIONS FOR THE NEW SYSTEM(S).
7. ALL OUTAGES SHALL BE COORDINATED WITH THE OWNER. THE CONTRACTOR SHALL PLAN AHEAD TO
MINIMIZE ALL OUTAGES.
8. CIRCUITS SHALL STAY FUNCTIONAL WHERE DEVICES/FIXTURES ARE BEING DEMOLISHED THAT SHARE A COMMON CIRCUIT WITH DEVICES/FIXTURES THAT ARE TO REMAIN. WIRING SHALL BE REMOVED AS
FAR AS POSSIBLE WHILE MAINTAINING EXISTING TO REMAIN OPERATION.
9. THE CONTRACTORS SHALL REMOVE ALL EXISTING ELECTRICAL EQUIPMENT NOT REUSED OF NOT
NECESSARY FOR THE COMPLETION OF THIS PROJECT.
REVISIONS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
FMS
Project and
Section
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
CD(100%CD-ISSUE FOR BID) SUBMITTAL - 04/22/2024
672-22-810VA PROVIDE HIGH LEVEL
DISINFECTION FOR SPS
10 CALLE CASIA - ADM. BLDG. SUITE
4M456 SAN JUAN, PR 00921-3201
/2
/2
:1
:0
A
M
ELECTRICAL FLOOR PLANS
EP-101
04/22/2024 MDB CDH
CD(100%CD-ISSUE FOR BID)
1/4" = 1'-0"
ELECTRIAL DEMOLITION FLOOR PLAN
1/4" = 1'-0"
ELECTRIAL NEW WORK FLOOR PLAN
KEYNOTE LEGEND
1 REMOVE EXISTING LIGHT FIXTURE AND MAKE SAFE EXISTING LIGHTING
CIRCUIT FOR RE-USE IN NEW WORK.
2 EXISTING RECEPTACLES TO REMAIN.
3 ALL NEW RECEPTACLES ARE TO BE FLUSH MOUNTED INTO THE EXISTING
WALLS.
4 PROVIDE DEDICATE GFCI RECEPTACLE OUTLET IN ACCESS PANEL LOCATED
ABOVE EQUIPMENT. COORDINATE WITH ARCHITECTURAL.
5 PROVIDE 2 X 4 LIGHT FIXTURE BY FAIL SAFE CAT.#
BAA-FSP-24-47-40-CA08/DFCL-2448W-U OR EQUAL. CONNECT TO EXISTING
LIGHTING CIRCUIT VIA NEW CEILING MOUNTED OCCUPANCY SENSORS AND
WALL SWITCH.
6 PROVIDE 30AMP SINGLE POLE SWITCH UNDER SINK WITH WEATHERPROOF
COVER AND PROVIDE FINAL CONNECTION TO INSTAHEAT WATER HEATER.
7 EXISTING CEILING MOUNTED HORN/STROBE NOTIFICATION DEVICE TO REMAIN.
8 PROVIDE NEW CEILING MOUNTED HORN/STROBE NOTIFICATION DEVICES TO
MATCH EXISTING. CONNECT TO EXISTING NOTIFICATION CIRCUIT USED BY
INDICATED EXISTING DEVICE. VERIFY CIRCUIT AND BATTERY CAPACITY IN
EXISTING FIRE ALARM PANEL.
9 THERE ARE NO EXISTING FIRE ALARM NOTIFICATION DEVICES LOCATED IN THE
EXISTING AREA OF CONSTRUCTION. THE AREA OF CONSTRUCTION IS
SPRINKLED BY THE EXISTING SPRINKLER SYSTEM.
10 PROVIDE ANY TEMPORARY FIRE ALARM NOTIFICATION DEVICES REQUIRED
DURING CONSTRUCTION IF ANY EXISTING DEVICES ARE BLOCKED OR
REMOVED BY TEMPORARY WALLS OR BARRIERS.
LOAD
N
H
Blue
Blue
White
Black SP20-RD4
Yellow/Orange
Blue
Black
White/Blue
Red
OAC-DT-2000-R
Blue
Black
Red
GMDS-W
OAC-DT-1000-R + SP20-RD4 + GMDS-W
REVISIONS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
FMS
Project and
Section
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
CD(100%CD-ISSUE FOR BID) SUBMITTAL - 04/22/2024
672-22-810VA PROVIDE HIGH LEVEL
DISINFECTION FOR SPS
10 CALLE CASIA - ADM. BLDG. SUITE
4M456 SAN JUAN, PR 00921-3201
/2
/2
:1
:0
A
M
ELECTRICAL DETAILS
E-501 04/22/2024 Checker Author
CD(100%CD-ISSUE FOR BID)
3/64" = 1'-0"
OCCUPANCY SENSOR DETAIL
REVISIONS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
FMS
Project and
Section
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
CD(100%CD-ISSUE FOR BID) SUBMITTAL - 04/22/2024
672-22-810VA PROVIDE HIGH LEVEL
DISINFECTION FOR SPS
10 CALLE CASIA - ADM. BLDG. SUITE
4M456 SAN JUAN, PR 00921-3201
/2
/2
:1
:0
A
M
PANEL SCHEDULES
E-601
04/22/2024 MDB CDH
CD(100%CD-ISSUE FOR BID)
Note: * INDICATES EXISTING CIRCUIT BREAKER AND NEW INDICATED LOAD. TOTAL CONNECTED CURRENT IS THE ADDITIONA LOAD ADDED TO THE PANEL.
Total Estimated Demand Current: 7.26
Total Connected Current: 20 A
Total Estimated Demand (kVA): 7.26
Receptacle 4.26 100.00% 4.26 Total Connected Load (kVA): 7.26
Lighting 3.00 100.00% 3.00 Heat or Cool Dominant: Cooling
Load Classification Connected Load (kVA) Demand Factor Estimated Demand (kVA) Panel Totals
Total Amps: 16 A 7 A 40 A
Total Load: 1.80 kVA 0.86 kVA 4.60 kVA
35 -- -- -- -- -- 0.00 36
33 EF -- -- 20 A 2 0.00 34
31 STERRANX 10 -- -- 20 A 1 0.00 32
29 AUTOCLAVE -- -- 20 A 1 0.00 3.80 -- -- -- -- -- 30
27 -- -- -- -- -- 0.00 0.86 -- -- -- -- -- 28
25 ULTRA SONIC 2 -- -- 20 A 2 0.00 1.00 3 100 A 1LSPD2 26
23 AUTOCLAVE -- -- 20 A 1 0.00 0.00 -- -- -- -- -- 24
21 STERRADNX 9 -- -- 20 A 1 0.00 0.00 -- -- -- -- -- 22
19 SPACE -- -- -- 1 -- 0.00 3 30 A -- -- STERRAD STERILIXER 8 20
17 -- -- -- -- -- 0.00 0.00 -- -- -- -- -- 18
15 -- -- -- -- -- 0.00 0.00 -- -- -- -- -- 16
13 STERRAD STERILIZER 4 -- -- 30 A 3 0.00 0.00 3 30 A -- -- WASHER STERILIZER 14
11 -- -- -- -- -- 0.00 0.00 -- -- -- -- -- 12
9 ULTRA SONIC 1 -- -- 20 A 2 0.00 0.00 2 60 A -- -- WI 10
7 -- -- -- -- -- 0.00 0.80 1 20 A 3/4" 2-#12 1-#12G PASS THRU* 8
5 RINSE DRYER 1 -- -- 30 A 2 0.00 0.80 1 20 A 3/4" 2-#12 1-#12G PASS THUR* 6
3 SPARE -- -- 20 A 1 0.00 0.00 -- -- -- -- -- 4
1 DECO DENTAL WASHER -- -- 20 A 1 0.00 0.00 2 30 A -- -- RINSE DRYER 2 2
CKT Circuit Description WIRE COND BKR P A B C P BKR COND WIRE Circuit Description CKT
Feed Thru Lugs:
Mounting: RECESSED Wires: 4 M.L.O. / M.C.B.: MCB
Fed From: Phases: 3 Bus: 500 A
Location: Volts: 120/208 V A.I.C. Rating: 22,000
BRANCH PANEL: 1LSPD1
Note: * INDICATES EXISTING CIRCUIT BREAKER AND NEW INDICATED LOAD. ** INDICATES NEW CIRCUIT BREAKER AND INDICATED LOAD. TOTAL CONNECTED CURRENT IS THE ADDITIONA LOAD ADDED TO THE PANEL.
Total Estimated Demand Current: 5.66
Total Connected Current: 16 A
Total Estimated Demand (kVA): 5.66
Receptacle 2.66 100.00% 2.66 Total Connected Load (kVA): 5.66
Lighting 3.00 100.00% 3.00 Heat or Cool Dominant: Cooling
Load Classification Connected Load (kVA) Demand Factor Estimated Demand (kVA) Panel Totals
Total Amps: 9 A 7 A 32 A
Total Load: 1.00 kVA 0.86 kVA 3.80 kVA
41 INSTA-HEAT** 2-#10 1-#10G 3/4" 30 A 1 3.00 -- 1 -- -- -- SPACE 42
39 SCOPE STORAGE RECPT** 2-#12 1-#12G 3/4" 20 A 1 0.86 -- 1 -- -- -- SPACE 40
37 SCOPE STORAGE RECPT** 2-#12 1-#12G 3/4" 20 A 1 1.00 -- 1 -- -- -- SPACE 38
35 PASS THRU** 2-#12 1-#12G 3/4" 20 A 1 0.80 0.00 -- -- -- -- -- 36
33 -- -- -- -- -- 0.00 0.00 -- -- -- -- -- 34
31 UNKNOWN -- -- 20 A 2 0.00 0.00 3 30 A -- -- UNKNOWN 32
29 UNKNOWN -- -- 20 A 1 0.00 0.00 1 20 A -- -- UNKNOWN 30
27 CUSTOM ULTRASONIC -- -- 20 A 1 0.00 0.00 1 20 A -- -- UNKNOWN 28
25 CUSTOM ULTRASONIC -- -- 20 A 1 0.00 0.00 1 20 A -- -- COMPUTER RECPT 26
23 POINT GUARD REPEATER -- -- 20 A 1 0.00 0.00 1 20 A -- -- ALARM AREA 1-5 24
21 POINT GUARD REPEATER -- -- 20 A 1 0.00 0.00 1 20 A -- -- POINT GUARD REPEATER 22
19 CLEAN MACHINE DENTAL HAND -- -- 20 A 1 0.00 0.00 1 20 A -- -- STAFF LOUNGE HAC RECPT 20
17 CLEAN WOMENS LIGHTS -- -- 20 A 1 0.00 0.00 1 20 A -- -- STAFF LOUNGE RECPT 18
15 CLEAN MENS LIGHTS -- -- 20 A 1 0.00 0.00 1 20 A -- -- STAFF LOUNGE REFRIGERATOR 16
13 CHASE CART HAC RECPT -- -- 20 A 1 0.00 0.00 1 20 A -- -- TRAINING AREA RECPT 14
11 DRY AREA RECPT -- -- 20 A 1 0.00 0.00 1 20 A -- -- TRAINING AREA PROJECTOR 12
9 DESCONTAMINATION RECPT -- -- 20 A 1 0.00 0.00 1 20 A -- -- COMPUTERIZED AUDIOVISUAL 10
7 HLD RECPT -- -- 20 A 1 0.00 0.00 1 20 A -- -- MONITORS FOR ETO 8
5 HLD RECPT -- -- 20 A 1 0.00 0.00 1 20 A -- -- PREPARATION ETO RECPT 6
3 DECO MENS LIGHTS -- -- 20 A 1 0.00 0.00 1 20 A -- -- SPD CHIEF CLERK RECPT 4
1 DECO WOMEN LIGHTS -- -- 20 A 1 0.00 0.00 1 20 A -- -- PRE SPD CHIEF RECPT 2
CKT Circuit Description WIRE COND BKR P A B C P BKR COND WIRE Circuit Description CKT
Feed Thru Lugs:
Mounting: RECESSED Wires: 4 M.L.O. / M.C.B.: MLO
Fed From: 1LSPD1 Phases: 3 Bus: 100 A
Location: Volts: 120/208 V A.I.C. Rating: 10,000
BRANCH PANEL: 1LSPD2
| Sheets |
| E-001 - ELECTRICAL COVER SHEET |
| E-501 - ELECTRICAL DETAILS |
| E-601 - PANEL SCHEDULES |
| EP-101 - ELECTRICAL FLOOR PLANS |
File details come from the government source that posted it. Updated .