Attachment 06a - 100 Percent Drawings.pdf
PDF 9 MB Posted
- Attached to
- Y1DA--VISN 8 MATOC - Mainland
- Solicitation number
- 36C77624R0131
About this file
This file contains comprehensive architectural and engineering design drawings for a project at the Viera VA Medical Center in Melbourne, Florida. The project, titled "Address Viera Site Deficiencies" (Project Number 675-23-151), involves multiple scope improvements to the Chiller Building, including installing new epoxy flooring, creating a new bathroom and office, upgrading physical security and safety systems, replacing the marquee sign, enclosing a concrete pad for secure storage, repairing damaged asphalt in parking and roadway areas, and addressing stormwater drainage issues.
The drawings cover architectural, civil, mechanical, plumbing, electrical, fire protection, and special systems design aspects. Key specific improvements include installing a 5,000 sq ft epoxy flooring system in the Chiller Plant, creating a 150 sq ft office with oversized windows, adding a 100 sq ft bathroom, implementing camera surveillance and access control systems, replacing the electronic marquee sign, and improving site drainage. The project involves modifications to existing infrastructure while maintaining the facility's operational capabilities, with careful attention to infection control measures, safety protocols, and VA design guidelines.
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID SETOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
CONSULTANT
321 4 5 6 7 8 9 10
VIERA VA MEDICAL CENTER, 2900 VETERANS
WAY, MELBOURNE, FL 32940
675-23-151
.1
.1
.2
\J o b s \J o b s \2
V A
A d d re s s V ie ra
S it e
D e fi c ie n c ie s \1 a A rc h it e c tu ra l\ M o d e l\
-2
-1
V ie ra
D e fi c ie n c ie s d e ta c h e d
.r v t
/2 /2
:5
:5
A
M
GI-001
COVER SHEET
AESUS DESIGN GROUP
1050 E. Southern Ave., Suite D
Temple, AZ, 85282
480-454-2861
David Combs
ADDRESS VIERA SITE
DEFICIENCIES
NOV. 3, 2023 AESUS AESUS
DX
A3-301
X
XX
X
DETAIL FLAG NUMBER
DOOR NUMBER
AE-501
BUILDING SECTION CUT
OTHER SECTION CUT
SHEET WHERE APPEARS (TYPICAL)
AE-301
AA
SHEET WHERE APPEARS
ELEVATION NUMBER
SHEET WHERE APPEARS
x x x x
EXISTING COLUMN CENTER LINEA
X
WINDOW TAG
AE-301
AA
AE-301
AA
ELEVATION NUMBER
AE-710
4 2
DASHED LINE
AROUND
AREA DETAILED
PLAN OR DETAIL NUMBERX
NOTE: IN ADDITION TO THE FOLLOWING INFECTION CONTROL MEASURES OF ICRA
CLASS & PERMIT LEVEL IV, THE CONTRACTOR SHALL REVIEW THE VA SAFETY-QUALITY
CONTROL-INFECTION CONTROL DOCUMENTS IN THE SPECIFICATIONS. THE AE WILL
PROVIDE A FORM FOR THE CONTRACTOR TO FILL OUT
DURING CONSTRUCTION:
A. ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT
CONTAMINATION OF DUCT SYSTEM.
B. COMPLETE ALL CRITICAL BARRIERS I.E. SHEET ROCK, PLYWOOD, PLASTIC,
TO SEAL AREA FROM NON-WORK AREA OR IMPLEMENT CONTROL CUBE
METHOD (CART WITH PLASTIC COVERING AND SEALED CONNECTION TO
WORK SITE WITH HEPA VACUUM FOR VACUUMING PRIOR TO EXIT) BEFORE
CONSTRUCTION BEGINS.
C. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA
EQUIPPED AIR FILTRATION UNITS. PROVIDE NEGATIVE AIR PRESSURE
MONITOR.
D. SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES APPROPRIATELY.
E. CONSTRUCT ANTEROOM AND REQUIRE ALL PERSONNEL TO PASS THROUGH
THIS ROOM SO THEY CAN BE VACUUMED USING A HEPA VACUUM CLEANER
BEFORE LEAVING WORK SITE OR THEY CAN WEAR CLOTH OR PAPER
COVERALLS THAT ARE REMOVED EACH TIME THEY LEAVE THE WORK SITE.
F. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT
IS INSPECTED BY A SAFETY OFFICER AND INFECTION CONTROL
COORDINATOR AND THOROUGHLY CLEANED BY THE ENVIRONMENTAL
MANAGEMENT SERVICES.
UPON COMPLETION OF PROJECT:
A. REMOVE BARRIER MATERIAL CAREFULLY TO MINIMIZE SPREADING OF DIRT
AND DEBRIS ASSOCIATED WITH CONSTRUCTION.
B. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY
COVERED CONTAINERS.
C. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS
SOLID LID.
D. VACUUM WORK AREA WITH HEPA FILTERED VACUUMS.
E. WET MOP AREA WITH DISINFECTANT.
F. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE WORK IS BEING
PERFORMED.
Approved: Associate Director
Approved: Chief Facilities Management
Approved: Manager / Engineer
Approved: Director
Approved: Union representative
Approved: Safety Officer
EQ-X
CPT1
W-X
E
EA EACH
E EAST
EWC ELECTRIC WATER COOLER
ELEC ELECTRIC (AL)
EL ELEVATION
ELEV ELEVATOR
EMER EMERGENCY
ENGR ENGINEER
EQ EQUAL
EQUIP EQUIPMENT
EXIST EXISTING
ETR EXISTING TO REMAIN
EXP EXPANSION
EXP BT EXPANSION BOLT
EJ EXPANSION JOINT
EXP EXPOSED
EXT EXTERIOR
EIFS EXTERIOR INSULATION AND
FINISH SYSTEM
F
FWC FABRIC WALL COVERING
FT FEET, FOOT
FGL FIBERGLASS
FIN FINISH
FIN GR FINISH GRADE
FDV FIRE DEPARTMENT VALVE
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER
CABINET
FHC FIRE HOSE CABINET
FP FIREPROOF
FIXT FIXTURE
FLASH FLASHING
FLEX FLEXIBLE
FLR FLOOR
FD FLOOR DRAIN
FLUOR FLUORESCENT
FTG FOOTING
FDTN FOUNDATION
FRMG FRAMING
FURN FURNACE, FURNITURE
G
GA GAGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GL GLASS
GL BLK GLASS BLOCK
GB GRAB BAR
GR GRADE
GRAN GRANITE
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GUT GUTTER
GYP BD GYPSUM BOARD
H
HNDRL HANDRAIL
HDW HARDWARE
HDWD HARDWOOD
HD HEAD
HVAC HEATING, VENTILATING, AIR CONDITIONING
HT HEIGHT
HPT HIGH POINT
HC HOLLOW CORE
HM HOLLOW METAL
HORIZ HORIZONTAL
HB HOSE BIBB
HOSP HOSPITAL
HR HOUR
I
IN INCH
INFO INFORMATION
ID INSIDE DIAMETER
INSUL INSULATED,INSULATION
INT INTERIOR
J
JAN JANITOR
JT JOINT
K
KPL KICKPLATE
KIT KITCHEN
KB KNEE BRACE
L
LAB LABORATORY
LAM LAMINATE
LC LAUNDRY CHUTE
LV LAVATORY
LT LIGHT
LD LINEAR DIFFUSER
L CL LINEN CLOSET
LL LIVE LOAD
LLV LONG LEG VERTICAL
LPT LOW POINT
M
MACH MACHINE
MH MANHOLE
MFD MANUFACTURED
MFR MANUFACTURER
MRB MARBLE BASE
MRF MARBLE FLOOR
MKR BD MARKER BOARD
MO MASONRY OPENING
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MED MEDICAL
MC MEDICINE CABINET
MEMB MEMBRANE
MTL METAL
MIN MINIMUM, MINUTE
MISC MISCELLANEOUS
MOD MODIFIED
MLDG MOLDING
N
NAT FIN NATURAL FINISH
NOM NOMINAL
N NORTH
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NTS NOT TO SCALE
NO NUMBER
O
OFF OFFICE
OC ON CENTER
OPNG OPENING
OPP OPPOSITE
OPH OPPOSITE HAND
ORCH ORCHESTRA
ORN ORNAMENTAL
OD OUTSIDE DIAMETER
OH OVERHANG, OVERHEAD
OF/CI OWNER FURNISHED/
CONTRACTOR INSTALLED
O OXYGEN
P
P PAINT
PR PAIR
PNL PANEL
PTD PAPER TOWEL DISPENSER
PTN PARTITION
PERF PERFORATED
PC PIECE
PLAM PLASTIC LAMINATE
PLAS PLASTIC, PLASTER
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PCC PRECAST CONCRETE
PREFAB PREFABRICATE
PREFIN PREFINISH
PROD PRODUCTION
Q
QTY QUANTITY
QT QUARRY TILE
A
AFF ABOVE FINISHED FLOOR
ACST ACOUSTIC (AL)
ACT ACOUSTICAL CEILING TILE
APC ACOUSTICAL PANEL CEILING
AWP ACOUSTICAL WALL PANEL
AWT ACOUSTICAL WALL
ADJ ADJUSTABLE
A/C AIR CONDITIONING
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM ALUMINUM
AB ANCHOR BOLT
AL ANGLE
APPROX APPROXIMATE
ARCH ARCHITECT (URAL)
ASPH ASPHALT
ASSY ASSEMBLY
AUTO AUTOMATIC
AWN AWNING
B
BALC BALCONY
BSMT BASEMENT
BM BEAM, BENCHMARK
BR BEDROOM
BLKG BLOCKING
BD BOARD
BOT BOTTOM
BRKT BRACKET
BRK BRICK
B CL BROOM CLOSET
BLDG BUILDING
BLT IN BUILT-IN
BUR BUILT-UP ROOFING
C
CAB CABINET
CPT CARPET
CSMT CASEMENT
CI CAST IRON
CB CATCH BASIN
CLG CEILING
CEM CEMENT
CL CENTER LINE
CER CERAMIC
CT CERAMIC TILE
CO CLEANOUT, CASED OPENING
CLR CLEAR, COLOR
CLO CLOSET
COL COLUMN
CMPST COMPOSITE
CONC CONCRETE
CMU CONCRETE MASONRY UNIT
CONSTR CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
COTR CONTRACTING OFFICER
CJ CONTROL JOINT
COP COPING
CU COPPER
CG CORNER GUARD
CORR CORRIDOR
CNTR COUNTER
CSK COUNTER SUNK
D
DMPF DAMPPROOFING
DL DEAD LOAD
DEMO DEMOLITION
DET DETAIL
DIA DIAMETER
DIFF DIFFUSER
DIM DIMENSION
DR DOOR, DRAIN
DH DOUBLE HUNG
DN DOWN
DS DOWNSPOUT
DWR DRAWER
DWG DRAWING
DF DRINKING FOUNTAIN
DUPL DUPLICATE
R
R RADIUS, RISER
RWD REDWOOD
REF REFERENCE, REFRIGERATOR
REINF REINFORCE
REQD REQUIRED
RB RESILIENT BASE
RF RESILIENT FLOORING
RA RETURN AIR
REV REVISION
RD ROOF DRAIN
RM ROOM
RO ROUGH OPENING
RS ROUGH SAWN
S
SCHED SCHEDULE
SECT SECTION
SHTHG SHEATHING
SHT SHEET
SHV SHELVING
SIM SIMILAR
S SOUTH
SP FIN SPECIAL FINISH
SPEC SPECIFICATION
SQ SQUARE
SF SQUARE FEET
SST STAINLESS STEEL
STD STANDARD
STL STEEL
STL JST STEEL JOIST
STOR STORAGE
STRUCT STRUCTURAL
S4S SURFACED FOUR SIDES
SUSP SUSPEND
SW SWITCH
SYMM SYMMETRICAL
T
TK BD TACKBOARD
TEL TELEPHONE
TV TELEVISION
TMPD TEMPERED
TEMP TEMPORARY
TER TERRAZZO
THK THICKNESS
TPD TOILET PAPER DISPENSER
T&G TONGUE AND GROOVE
TOS TOP OF SLAB, STEEL
T TREAD
TYP TYPICAL
U
UC UNDERCUT
UNFIN UNFINISH
UNO UNLESS NOTED OTHERWISE
V
VAC VACUUM
VR VAPOR RETARDER
VNR VENEER
VP VENEER PLASTER
VIF VERIFY IN FIELD
VERT VERTICAL
VEST VESTIBULE
VCT VINYL COMPOSITION TILE
VWC VINYL WALL COVERING
W
W CAB WALL CABINETS
WC WALL COVERING, WATER CLOSET
WP WATERPROOFING, WEATHER
PROOF, WORKING POINT
WT WEIGHT
WWF WELDED WIRE FABRIC
W WEST
WF WIDE FLANGE
WDW WINDOW
W/ WITH
W/O WITHOUT
WD WOOD
WDP WOOD PANELING
Department of Veterans Affairs
KEYED NOTE
WALL TYPE
X
X WINDOW TREATMENT TYPE
EQUIPMENT
INTERIOR FINISH TYPE
FURNITURE, FIXTURE, EQUIPMENT
CONTRACT LIMIT LINE
COLUMN CENTER LINE
NEW WALL
DEMOLITION
EXISTING WALL
NORTH
APPROVED FOR CONSTRUCTION
Project No: 675-23-151
DESIGN TEAM
ABBREVIATIONS OWNER
CODE REFERENCES
PROJECT DESCRIPTIONSYMBOL LEGEND
BUILDING INFORMATION
GENERAL NOTES
VICINITY MAP - LAKE VIERA
INFECTION CONTROL MEASURES
THIS PROJECT IS LOCATED IN MELBOURNE, FLORIDA AT THE VIERA VA MEDICAL
CENTER. THIS PROJECT WILL ADDRESS A VARIETY OF SITE DEFICIENCIES AT THE
VIERA VA CLINIC, TO INCLUDE THE INSTALLATION OF NEW EPOXY FLOORING,
CREATING A NEW BATHROOM AND OFFICE, UPGRADE PHYSICAL SECURITY AND
SAFETY EYE WASH SYSTEMS AS REQUIRED FOR THE CHILLER PLANT, REPLACING
THE MARQUEE SIGN AND CONTROLLER AT THE CLINIC MAIN ENTRANCE, ENCLOSING
AN EXISTING CONCRETE PAD AREA FOR SECURE STORAGE ADJACENT TO LOADING
DOCK, REPAIR DAMAGED AND CRACKED ASPHALT THROUGHOUT THE CLINIC
PARKING AND ROADWAY AREAS, ADDRESS POOR STORM WATER STORAGE AT THE
NORTHEAST CORNER OF THE PROPERTY.
THIS WORK SHALL INCLUDE BUT NOT BE LIMITED TO ARCHITECTURAL, CIVIL,
MECHANICAL, PLUMBING, & ELECTRICAL.
DESCRIPTIONSYMBOL
ADDRESS VIERA SITE DEFICIENCIES 675-23-151
VIERA VA MEDICAL CENTERS
Department of Veterans Affairs
Architect
1050 E. Southern Ave. Suite 5, Tempe, Arizona 85282
AESUS Design Group
David Combs (dcombs@aesusdesign.com)
480-454-2861
PROJECT AREA
A. ANY CHANGES MUST BE APPROVED BY COR BEFORE DOING ANY
ADDITIONAL WORK. WORK SCHEDULE TO BE PERFORMED DURING
REGULAR DAY SHIFT HOURS (8AM-4:30PM) ANY WORK OUTSIDE OF
REGULAR SCHEDULE REQUIRES APPROVAL FROM COR.
B. COORDINATE STAGING AREA WITH COR, AND FIND INTERIOR
COVERED STORAGE ON SITE FOR MATERIALS THAT MUST BE
PROTECTED FROM ELEMENTS - COORDINATE WITH COR.
C. PERFORM WORK IN ACCORDANCE WITH VHA DIRECTIVE 2004-012
SAFETY AND HEALTH DURING CONSTRUCTION ACTIVITIES AND VHA
DIRECTIVE 7701 OCCUPATIONAL SAFETY AND HEALTH (OSH) .
D. WORK PERFORMED FOR THIS PROJECT MAY INTERRUPT SERVICE TO
ADJACENT AREAS AT TIMES BUT WILL NOT INTERRUPT OVERALL
FACILITY OPERATION. SEE ELECTRICAL FOR POWER INTERRUPTION
AND OUTAGE REQUIREMENTS.
E. CONTRACTOR TO VERIFY ALL DETAILS AGAINST EXISTING
CONDITIONS PRIOR TO PURCHASE OF EQUIPMENT AND PRIOR TO
CONSTRUCTION. CONTRACTOR IS RESPONSIBLE FOR BRINGING ANY
DISCREPANCIES IN PLANS AND EXISTING SITE CONDITIONS TO
IMMEDIATE ATTENTION OF CONTRACTING OFFICER
REPRESENTATIVE.
F. CONTRACTOR SHALL PERFORM ALL WORK AND PROVIDE ALL
MATERIALS IN ACCORDANCE WITH VA MASTER CONSTRUCTION
SPECIFICATIONS, WHICH CAN BE FOUND AT
HTTP://WWW.CFM.VA.GOV/TIL/. WHERE DISCREPANCIES ARE FOUND
THE MORE STRINGENT SHALL APPLY.
G. NOT ALL KEYNOTES ARE ON ALL SHEETS.
MPE Engineers
BUILDING CODE:
INTERNATIONAL BUILDING CODE (IBC)
INTERNATIONAL EXISTING BUILDING CODE (IEBC)
ACCESSIBILITY CODE & GUIDELINES:
ABAAS & BFDG
MECHANICAL CODE:
INTERNATIONAL MECHANICAL CODE (IMC)
PLUMBING CODE:
INTERNATIONAL PLUMBING CODE (IPC)
ELECTRICAL CODE:
NATIONAL ELECTRICAL CODE (NEC)
NO EXISTING LIFE SAFETY FEATURES WILL BE MODIFIED AS A RESULT
OF NEW CONSTRUCTION.
NFPA
NFPA NATIONAL FIRE CODES
NFPA 101 LIFE SAFETY CODE
NFPA 99 (2021)
NFPA 70
NFPA 13 (2022)
NFPA 900 (OSHA)
Viera VA Medical Center, 2900 Veterans Way, Melbourne, FL 32940
ISSUED SHEETS
Sheet Number Sheet Name
GENERAL
GI-001 COVER SHEET
CIVIL
CS-001 CIVIL LEGEND AND NOTES
CS-100 CIVIL OVERALL EXISTING CONDITIONS SITE PLAN
CS-101 CIVIL OVERALL SITE PLAN
CS-102 CIVIL SITE PLAN
CS-103 CIVIL DRAINAGE SITE PLAN AND EROSION CONTROL DETAILS
ARCHITECTURAL
AE-100 VIERA SCOPE/PHASING
AE-101 ENLARGED PLANS
AE-102 ENLARGED PLANS
AE-103 PARTITION TYPES
AE-104 TOILET LAYOUTS AND MOUNTING HEIGHTS
AE-105 DOOR, SAFETY GLAZING AND LOUVER INFORMATION
AE-106 CEILING DETAILS
AE-107 PARTITION HEAD DETAILS
AE-108 GYP BD DETAILS
STRUCTURAL
S-001 STRUCTURAL NOTES, DESIGN CRITERIA & ABBREVIATIONS
S-101 STRUCTURAL PLANS AND DETAILS
FIRE PROTECTION
F-000 FIRE PROTECTION NOTES, LEGENDS AND DETAILS
F-101 FIRE PROTECTION PLANS
SPECIAL SYSTEMS
E-000 SPECIAL SYSTEMS LEGEND, NOTES & ABBREVIATIONS
EY-100 VIERA - OVERALL PLAN
EY-101 SPECIAL SYSTEMS & TELECOMM. FLOOR PLAN
ET-500 TELECOMMUNICATION DETAILS
ET-600 FIBER BACKBONE RISER DIAGRAM
1050 E. Southern Ave. Suite 5, Tempe, Arizona 85282
AESUS Design Group
Orlando Gonzalez (ogonzales@aesusdesign.com)
480-457-0129
Civil / Structural Engineers
8822 South Ridgeline Boulevard, Suite 310 Highlands Ranch, CO 80129 (303) 730-0434 www.calibre-engineering.com
Calibre Engineering, Inc.
Fire Proctection / Special System
MES GROUP, INC
550 North Reo Street Tampa, FL, 33609 813-289-4700
Revisions: Date:
STAMPSTAMP
11.03.2023
ISSUED SHEETS
Sheet Number Sheet Name
GENERAL
GI-001 COVER SHEET
CIVIL
CS-001 CIVIL LEGEND AND NOTES
CS-100 CIVIL OVERALL EXISTING CONDITIONS SITE PLAN
CS-101 CIVIL OVERALL SITE PLAN
CS-102 CIVIL SITE PLAN
CS-103 CIVIL DRAINAGE SITE PLAN AND EROSION CONTROL DETAILS
ARCHITECTURAL
AE-100 VIERA SCOPE/PHASING
AE-101 ENLARGED PLANS
AE-102 ENLARGED PLANS
AE-103 PARTITION TYPES
AE-104 TOILET LAYOUTS AND MOUNTING HEIGHTS
AE-105 DOOR, SAFETY GLAZING AND LOUVER INFORMATION
AE-106 CEILING DETAILS
AE-107 PARTITION HEAD DETAILS
AE-108 GYP BD DETAILS
STRUCTURAL
S-001 STRUCTURAL NOTES, DESIGN CRITERIA & ABBREVIATIONS
S-101 STRUCTURAL PLANS AND DETAILS
MECHANICAL
M-001 MECHANICAL LEGEND AND ABBREVIATIONS
M-201 MECHANICAL PLAN - CENTRAL PLANT
PLUMBING
P-001 PLUMBING LEGEND AND ABBREVIATIONS
P-201 PLUMBING PLAN - CENTRAL PLANT
FIRE PROTECTION
F-000 FIRE PROTECTION NOTES, LEGENDS AND DETAILS
F-101 FIRE PROTECTION PLANS
ELECTRICAL
EP-000 SYMBOLS AND ABBREVIATIONS
ED-101 ELECTRICAL DEMOLITION PLAN
EP-101 ELECTRICAL POWER PLAN
EP-100 ELECTRICAL SITE PLAN - OVERALL
EP-601 ELECTRICAL ONE-LINE DIAGRAM
EL-101 ELECTRICAL LIGHTING PLAN
EL-401 LIGHTING DETAILS
SPECIAL SYSTEMS
E-000 SPECIAL SYSTEMS LEGEND, NOTES & ABBREVIATIONS
EY-100 VIERA - OVERALL PLAN
EY-101 SPECIAL SYSTEMS & TELECOMM. FLOOR PLAN
ET-500 TELECOMMUNICATION DETAILS
ET-600 FIBER BACKBONE RISER DIAGRAM
Architecture, Engineering, and, Sustainable DesignAESUS 1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 454-2861 design group
EP-100
EP-101
Calibre 8822 South Ridgeline Boulevard, Suite 310 Highlands Ranch, CO 80129 (303) 730-0434 www.calibre-engineering.com Construction Management Civil Engineering Surveying
Calibre Engineering, Inc.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID SET
J:
\A
E S
U S
V
IE
R A
V A
S
IT
E D
E
FI
C
IE
N C
IE
S
\C A
D D
\C
IV
IL
\C
1.
0.
D W
G 3/
9/
1:
:1
A M
ADDRESS VIERA SITE
DEFICIENCIES
VIERA VA MEDICAL CENTER, 2900 VETERANS
WAY, MELBOURNE, FL 32940
675-23-151
NOVEMBER 3, 2023 RAZ BLG
AESUS DESIGN GROUP
1050 E. Southern Ave., Suite D Temple, AZ, 85282 480-454-2861 David Combs
Revisions: Date:
ABBREVIATIONS
CIVIL TABLE OF CONTENTSGENERAL CIVIL NOTES CIVIL LEGEND
CS-001
CIVIL LEGEND AND NOTES
GRADING NOTES
11/03/2023
Architecture, Engineering, and, Sustainable DesignAESUS 1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 454-2861 design group
VIERA VA MEDICAL CENTER
NORTH
CIVIL LEGEND
Calibre 8822 South Ridgeline Boulevard, Suite 310 Highlands Ranch, CO 80129 (303) 730-0434 www.calibre-engineering.com Construction Management Civil Engineering Surveying
Calibre Engineering, Inc.
SHEET NOTES:
SD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID SET
J:
\A
E S
U S
V
IE
R A
V A
S
IT
E D
E
FI
C
IE
N C
IE
S
\C A
D D
\C
IV
IL
\C
1.
0.
D W
G 3/
9/
1:
:1
A M
ADDRESS VIERA SITE
DEFICIENCIES
VIERA VA MEDICAL CENTER, 2900 VETERANS
WAY, MELBOURNE, FL 32940
675-23-151
NOVEMBER 3, 2023 RAZ BLG
AESUS DESIGN GROUP
1050 E. Southern Ave., Suite D Temple, AZ, 85282 480-454-2861 David Combs
Revisions: Date:
CS-100
CIVIL OVERALL EXISTING
CONDITIONS SITE PLAN
11/03/2023
Architecture, Engineering, and, Sustainable DesignAESUS 1050 E. Southern Ave, Suite #D, CS-102
VIERA VA MEDICAL CENTER
CS-102
CS-102
CS-102
NORTH
CIVIL LEGEND
Calibre 8822 South Ridgeline Boulevard, Suite 310 Highlands Ranch, CO 80129 (303) 730-0434 www.calibre-engineering.com Construction Management Civil Engineering Surveying
Calibre Engineering, Inc.
SHEET NOTES:
SD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID SET
J:
\A
E S
U S
V
IE
R A
V A
S
IT
E D
E
FI
C
IE
N C
IE
S
\C A
D D
\C
IV
IL
\C
1.
0.
D W
G 3/
9/
1:
:1
A M
ADDRESS VIERA SITE
DEFICIENCIES
VIERA VA MEDICAL CENTER, 2900 VETERANS
WAY, MELBOURNE, FL 32940
675-23-151
NOVEMBER 3, 2023 RAZ BLG
AESUS DESIGN GROUP
1050 E. Southern Ave., Suite D Temple, AZ, 85282 480-454-2861 David Combs
Revisions: Date:
CS-101
CIVIL OVERALL SITE PLAN
11/03/2023
Architecture, Engineering, and, Sustainable DesignAESUS 1050 E. Southern Ave, Suite #D, NORTH
CIVIL LEGEND
Calibre 8822 South Ridgeline Boulevard, Suite 310 Highlands Ranch, CO 80129 (303) 730-0434 www.calibre-engineering.com Construction Management Civil Engineering Surveying
Calibre Engineering, Inc.
SHEET NOTES:
SD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID SET
J:
\A
E S
U S
V
IE
R A
V A
S
IT
E D
E
FI
C
IE
N C
IE
S
\C A
D D
\C
IV
IL
\C
1.
0.
D W
G 3/
9/
1:
:1
A M
ADDRESS VIERA SITE
DEFICIENCIES
VIERA VA MEDICAL CENTER, 2900 VETERANS
WAY, MELBOURNE, FL 32940
675-23-151
NOVEMBER 3, 2023 RAZ BLG
AESUS DESIGN GROUP
1050 E. Southern Ave., Suite D Temple, AZ, 85282 480-454-2861 David Combs
Revisions: Date:
CS-102
CIVIL SITE PLAN
11/03/2023
Architecture, Engineering, and, Sustainable DesignAESUS 1050 E. Southern Ave, Suite #D, CS-103
CIVIL DRAINAGE SITE PLAN AND
EROSION CONTROL DETAILS
NORTH
CIVIL LEGEND
Calibre 8822 South Ridgeline Boulevard, Suite 310 Highlands Ranch, CO 80129 (303) 730-0434 www.calibre-engineering.com Construction Management Civil Engineering Surveying
Calibre Engineering, Inc.
SHEET NOTES:
SD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID SET
J:
\A
E S
U S
V
IE
R A
V A
S
IT
E D
E
FI
C
IE
N C
IE
S
\C A
D D
\C
IV
IL
\C
1.
0.
D W
G 3/
9/
1:
:1
A M
ADDRESS VIERA SITE
DEFICIENCIES
VIERA VA MEDICAL CENTER, 2900 VETERANS
WAY, MELBOURNE, FL 32940
675-23-151
NOVEMBER 3, 2023 RAZ BLG
AESUS DESIGN GROUP
1050 E. Southern Ave., Suite D Temple, AZ, 85282 480-454-2861 David Combs
Revisions: Date:
11/03/2023
Architecture, Engineering, and, Sustainable DesignAESUS 1050 E. Southern Ave, Suite #D, C R
/AE-102 1
/AE-102 3
ITEM A
ITEM E
ITEM D
ITEM B
/AE-102 10
ITEM C
ITEM G
/AE-101 1
CHILLER BUILDING
A. ANY CHANGES MUST BE APPROVED BY COR BEFORE DOING ANY
ADDITIONAL WORK. WORK SCHEDULE TO BE PERFORMED DURING
REGULAR DAY SHIFT HOURS (8AM-4:30PM) EXCEPT FOR THE
ASPHALT REPAIRS, FOG COATING AND PARKING LOT RESTRIPING,
ANY WORK OUTSIDE OF REGULAR SCHEDULE REQUIRES APPROVAL
FROM COR.
B. COORDINATE STAGING AREA WITH COR, AND FIND INTERIOR
COVERED STORAGE ON SITE FOR MATERIALS THAT MUST BE
PROTECTED FROM ELEMENTS - COORDINATE WITH COR.
C. PERFORM WORK IN ACCORDANCE WITH VHA DIRECTIVE 2004-012
SAFETY AND HEALTH DURING CONSTRUCTION ACTIVITIES AND VHA
DIRECTIVE 7701 OCCUPATIONAL SAFETY AND HEALTH (OSH) .
D. WORK PERFORMED FOR THIS PROJECT MAY INTERRUPT SERVICE
TO ADJACENT AREAS AT TIMES BUT WILL NOT INTERRUPT OVERALL
FACILITY OPERATION. SEE ELECTRICAL FOR POWER INTERRUPTION
AND OUTAGE REQUIREMENTS.
E. CONTRACTOR TO VERIFY ALL DETAILS AGAINST EXISTING
CONDITIONS PRIOR TO PURCHASE OF EQUIPMENT AND PRIOR TO
CONSTRUCTION. CONTRACTOR IS RESPONSIBLE FOR BRINGING
ANY DISCREPANCIES IN PLANS AND EXISTING SITE CONDITIONS TO
IMMEDIATE ATTENTION OF CONTRACTING OFFICER
REPRESENTATIVE.
F. CONTRACTOR SHALL PERFORM ALL WORK AND PROVIDE ALL
MATERIALS IN ACCORDANCE WITH VA MASTER CONSTRUCTION
SPECIFICATIONS, WHICH CAN BE FOUND AT
HTTP://WWW.CFM.VA.GOV/TIL/. WHERE DISCREPANCIES ARE FOUND
THE MORE STRINGENT SHALL APPLY.
GENERAL NOTES
A. THE CONTRACTORS SHALL COORDINATE EQUIPMENT AND
MATERIAL TRAFFIC AND STORAGE WITH COR.
B. ALL UTILITY WORK SHALL BE COORDINATED WITH MECHANICAL,
PLUMBING ELECTRICAL, AND FIRE PROTECTION.
C. ALL ASPECTS OF CONTRACTOR STAGING AND CONSTRUCTION
PHASING SHALL BE APPROVED BY COR.
D. ALL HOSPITAL ACCESS POINTS, AND ALL BUILDING EXITS, MUST
REMAIN ACCESSIBLE, CLEAR AND UNOBSTRUCTED THROUGHOUT
ALL PHASES OF DEMOLITION AND CONSTRUCTION. SHORT-TERM
CLOSURE MAY BE ACCEPTABLE AS COORDINATED WITH COR.
E. THE CONTRACTOR SHALL COORDINATE ALL ROOF TOP WORK AND
ROOF REPAIRS WITH THE COR.
GENERAL PHASING NOTES
FLOOR PLAN LEGEND
NOT INCLUDED IN SCOPE OF WORK
SCOPE OF
WORK
SITE PLAN GENERAL NOTES
1. CONTRACTOR IS RESPONSIBLE FOR PROTECTING EXISTING UTILITIES
THAT ARE NOT MARKED FOR REMOVAL.
2. CONTRACTOR SHALL PHASE ROAD REMOVAL AND CONSTRUCTION SO AS
TO ALWAYS ALLOW AT LEAST ONE LANE OF TRAFFIC ON MAIN ACCESS
DRIVE. CONTRACTOR MAY CLOSE DRIVE TO ER/TRAUMA
ENTRANCE, BUT MUST COORDINATE WITH VA COR. TRAFFIC CLOSURE
SHALL MEET MUTCD REQUIREMENTS AND SHALL HAVE LIGHTED
BARRICADES FOR PROJECT.
3. CONTRACTOR SHALL INSTALL TEMPORARY 6' TALL CHAIN LINK SECURITY
FENCING TO SECURE CONSTRUCTION SITE. CONTRACTOR SHALL INSTALL
GATES TO ALLOW WORKING ACCESS FOR EQUIPMENT
AND PEOPLE.
4. CONTRACTOR SHALL BLOCK OFF SIDEWALK WITH ORANGE SNOW FENCE
AND INSTALL TEMPORARY SIGNAGE INDICATING THAT THE SIDEWALK IS
CLOSED.
5. CONTRACTOR SHALL PROVIDE TEMPORARY GRAVEL FILL, AS NEEDED, TO
ALLOW FOR VEHICULAR TRAFFIC TO USE ROADWAY WHILE NOT ACTIVELY
WORKING IN THE TRENCH. CONTRACTOR WILL BE RESPONSIBLE FOR
ENSURING THE TEMPORARY GRAVEL FILL IS AT GRADE AND WILL RESPOND
IMMEDIATELEY IF TEMPORARY GRAVEL FILL AREA SETTLES, CREATING A
HAZARD.
6. CONTRACTOR SHALL SUPPLY TRAFFIC CONTROL IN COMPLIANCE WITH
ALL MUTCD REGULATIONS. TRAFFIC CONTROL SHALL CONSIST OF AT LEAST
TYPE II BARRICADES WITH LIGHTS ON RESTRICTED
LANES OF TRAFFIC AND AT THE EDGE OF PAVEMENT WITH TEMPORARY
ACCESS OVER THE ROCKED IN LANE. TRAFFIC CONES MAY BE NEEDED ON
A TEMPORARY BASIS TO REDIRECT.
SCOPE OF WORK ITEMS
A. INSTALL EPOXY FLOORING SYSTEM AT THE VIERA CHILLER PLANT
APPROXIMATELY 5000 FT/SQ. SYSTEM SHALL BE NON-SLIP AND
RESISTANT TO CHEMICAL AND MECHANICAL DAMAGE.
B. CREATE OFFICE AREA OF APPROXIMATELY 150 FT/SQ INSIDE THE
VIERA CHILLER PLANT TO INCLUDE OVERSIZE WINDOWS TO VIEW
PLANT SYSTEMS, A NEW DOOR SYSTEM, AND CREATE
APPROXIMATELY A 100 FT/SQ NEW BATHROOM FACILITY UTILIZING
EXISTING ROUGHED IN PLUMBING.
C. UPGRADE VIERA CHILLER PLANT PHYSICAL SECURITY SYSTEMS
AS PER VA DESIGN GUIDES AND REGULATIONS, INCLUDING ALL
REQUIRED CAMERA SURVEILLANCE, ACCESS CONTROL AND
INTRUSION ALARM SYSTEMS.
D. REPLACE THE EXISTING ELECTRONIC MARQUEE SIGN AND
CONTROLLER AT THE CLINIC MAIN ENTRANCE WITH A MULTI-
COLOR NETWORKED SYSTEM CAPABLE OF DISPLAYING A VARIETY
OF LARGE COMPUTER-GENERATED IMAGES AND ALPHA-NUMERIC
DYNAMIC MESSAGES GENERATED FROM REMOTE LOCATIONS.
E. FULLY ENCLOSE AN EXISTING CONCREATE PAD AND WALL AREA
OF APPROXIMATELY 250 FT/SQ ADJACENT TO THE LOADING DOCK
FOR SECURE OUTDOOR STORAGE.
F. REPAIR ALL DAMAGED ASPHALT ROADWAYS AND PARKING AREAS
AND PERFORM FOG COAT APPLICATION(S) AND REPAINTING OF
ALL STRIPING.
G. ADDRESS POOR STORMWATER DRAINAGE AT THE NORTHEAST
AREA OF CLINIC PROPERTY TO MINIMIZE FLOODING.
HAZARDOUS MATERIALS
1. THE CONSTRACTOR AND THE CONTRATOR'S SUBS SHALL HAVE RESPONSIBILITY
FOR THE DISCOVERY, PRESENCE, HANDLING REMOVAL OR DISPOSAL OF OR
EXPOSURE OF PERSONS TO HAZARDOUS MATERIALS IN ANY FORM AT THE
PROJECT SITE, INCLUDING BUT NOT LIMITED TO ASBESTOS, ASBESTOS
PRODUCTS, LEAD-BASED PAINTS, POLYCHLORINATED BIPHENYL (PCB) OR OTHER
TOXIC SUBSTANCES. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION
OF EXISTING HVAC FILTERS WITHIN THE AREA OF WORK.
2. ALL PENETRATIONS IN GYPSUM WALL BOARD CEILINGS SHALL BE TIGHTLY
SEALED.
3. APPROPRIATE PROTECTION OF THE PUBLIC AND WORKMEN SHALL BE TAKEN
REGARDING WORK INVOLVING SAID MATERIALS.
4. ASBESTOS-CONTAINING MATERIALS AFFECTED BY THIS WORK SHALL BE
REMOVED AND DISPOSED OF IN ACCORDANCE WITH 29 CFR 1926.1101 (OSHA)
AND NESHAP's REGULATIONS.
5. ASBESTOS REMOVAL SHALL BE PERFORMED BY A LICENSED ASBESTOS
ABATEMENT CONTRACTOR.
6. THE OWNER SHALL BE PROVIDED WITH COPIES OF ALL NOTIFICATIONS, PERMITS,
AIR SAMPLING RESULTS, DISPOSAL MANIFESTS AND ANY OTHER PAPER WORK
GENERATED IN THE ABATEMENT PROCESS.
7. 'WARNING' ASBESTOS MAY BE PRESENT IN EXTERIOR WALL TRANSITE
PANELS, AS WELL AS, TRANSITE PIPES. CONTRACTOR TO DISPOSE OF ALL
HAZARDOUS WASTE IN ACCORDANCE WITH LOCAL, STATE AND FEDERAL
REGULATIONS. CONTRACTOR TO WEAR PROPER PROTECTIVE GEAR ACTING IN
ACCORDANCE WITH LOCAL, STATE AND FEDERAL REGULATIONS.
8. 'WARNING' ASBESTOS MAY BE PRESENT IN EXISTING FLOORING.
CONTRACTOR TO DISPOSE OF ALL HAZARDOUS WASTE IN ACCORDANCE WITH
LOCAL, STATE AND FEDERAL REGULATIONS. CONTRACTOR TO WEAR PROPER
PROTECTIVE GEAR ACTING IN ACCORDANCE WITH LOCAL, STATE AND FEDERAL
REGULATIONS.
9. 'WARNING' LEAD MAY BE PRESENT IN STRUCTURAL STEEL PAINT AND OTHER
PAINTED SURFACES. CONTRACTOR TO DISPOSE OF ALL HAZARDOUS WASTE IN
ACCORDANCE WITH LOCAL, STATE AND FEDERAL REGULATIONS. CONTRACTOR
TO WEAR PROPER PROTECTIVE GEAR ACTING IN ACCORDANCE WITH LOCAL,
STATE AND FEDERAL REGULATIONS.
10. REMOVE ALL ASBESTOS CONTAINING MATERIALS AFFECTING BY SCOPE OF
WORK.
12. THE CONTRACTOR SHALL REMOVE ENVIRONMENTALLY REGULATED MATERIALS
SUCH AS ASBESTOS AND LEAD-CONTAINING PAINTS IF ENCOUNTERED OR
SUSPECTED IN THE SCOPE OF WORK. IT SHALL BE THE CONTRACTOR'S OBLIGATION
TO UNDERSTAND THE NATURE, CHARACTER, QUALITY AND SIZES OF MATERIALS
LIKELY TO BE ENCOUNTERS AND IMPACTED BY THE PROJECT. FAILURE TO SO, DOES
NOT RELIEVE THE CONTRACTOR FROM THE OBLIGATION TO FURNISH ALL MATERIALS
AND LABOR TO CARRY OUT THE PROVISIONS OF THIS CONTRACT.
13. CONTRACTOR IS SOLELY RESPONSIBLE FOR COORDINATING WORK
ACTIVITIES THAT MAY IMPACT ENVIRONMENTALLY-REGULATED MATERIALS WITH
WORK SPECIFIED IN OTHER CONTRACT DOCUMENT SECTIONS.
14. CONTRACTOR SHALL BE RESPONSIBLE FOR ADEQUATELY PROTECTING ANY
ITEMS TO REMAIN INCLUDING, RETAINING WALLS, MECHANICAL, ELECTRICAL,
PLUMBING AND OTHER UTILITIES NOT SPECIFIED TO BE DEMOLISHED. REFER TO
SPECIFICATIONS, ARCHITECTURAL, DEMOLITION AND MEP DRAWINGS.
15. ENERGIZED EQUIPMENT AND UTILITIES (ELECTRICAL TRANSFORMERS AND
MECHANICAL, ELECTRICAL AND PLUMBING SYSTEMS) AS TAGGED BY THE
OWNERS REPRESENTATIVE MUST REMAIN ENERGIZED DURING ABATEMENT
ACTIVITIES. CONTRACTOR SHALL ADEQUATELY PROTECT EQUIPMENT AND
UTILITIES AND TAKE APPROPRIATE PRECAUTIONS TO PREVENT PERSONNEL
INJURIES OR DAMAGE TO THE STRUCTURE.
16. SEAL ALL AREAS. FLOOR PENETRATIONS WITH PLASTIC, TAPE, EPOXY OR FOAM
OR A COMBINATION THEREOF TO PREVENT MIGRATION OF LIQUID OR DEBRIS
FROM THE WORK.
17. INSTALL VISIBLE WARNING PLACARDS ON STATIONARY EQUIPMENT TO REMAIN
ENERGIZED. PLACARDS SHALL MEET OSHA REQUIREMENTS INCLUDING, BUT NOT
LIMITED TO CFR 1926.416-1926.417, AND BE SUFFICIENTLY SIZED, COLORED AND
WORDED TO WARN PERSONNEL ENTERING THE AREA TO ITS PRESENCE. AT A
MINIMUM THE SIGNS SHALL BE 8.5"X11" IN SIZE AND CONTAIN THE LANGUAGE
"HIGH VOLTAGE" IN BLACK ON A YELLOW BACKGROUND.
18. ALL LEAD-RELATED REMOVAL AND DEMOLITION WORK SHALL BE PERFORMED BY
CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH) CERTIFIED SUPERVISORS
AND WORKERS.
19. CONTRACTOR SHALL DISMANTLE FLUORESCENT LIGHT FIXTURES AND
CONTAINERIZE FIXTURE BALLASTS FOR DISPOSAL BY OWNER.
20. CONTRACTOR SHALL REMOVE AND RECYCLE ALL MERCURY-CONTAINING
AMPOULES IN SWITCHBOARDS, PNEUMATIC CONTROLS, WALL RECEPTACLES,
EXIT SIGNS, FIRE DETENTION / ALARM DEVICES, AND THERMOSTATS. SUBMIT FOR
APPROVAL TO THE GOVERNMENT'S REPRESENTATIVE, THE NAME OF THE
CALIFORNIA EPA DEPARTMENT OF TOXIC SUBSTANCES AND CONTROL (CAL/EPA
DTSC) RECYCLE CENTER TO BE UTILIZED. PACKAGE AMPOULES IN ORDER TO
PREVENT DAMAGE FROM THE TIME OF REMOVAL, DURING TEMPORARY ON SITE
STORAGE, AND TRANSPORT TO THE RECYCLE CENTER.
21. CONTRACTOR SHALL REMOVE AND RECYCLE OZONE DEPLETING SUBSTANCES
(ODS) SUCH AS CHLOROFLUOROCARBONS (CFCS) AND
HYDROCHLOROFLUOROCARBONS (HCFCS), AS WELL AS HALON, SULFUR DIOXIDE
(SO2) AND AMMONIA (NH3) FROM SYSTEMS, EQUIPMENT AND COMPONENTS.
22. CONTRACTOR SHALL KEEP ASBESTOS, LEAD, PCBS, METALS AND ETC. WASTES
IN SEPARATE CONTAINERS.
23. CONTRACTOR SHALL PROVIDE ALL WASTE CHARACTERIZATION / TESTING AND
PROFILES FOR DISPOSAL OF ALL REMOVED AND DEMOLISHED BUILDING
MATERIALS AND EQUIPMENT COATED WITH LEAD PAINT OR CONTAMINATED WITH
LEAD AND METALS. COLLECT CHARACTERIZATION SAMPLES WITH GOVERNMENT
REPRESENTATIVE.
25. LEAD-CONTAINING PAINTS, COATINGS AND GLAZING MABY BE
PRESENT ON THE PROJECT SITE. THE GOVERNMENT HAS A ZERO-TOLERANCE
POLICY FOR UNCONTROLLED LEAD RELEASES DURING LEAD RELATED
CONSTRUCTION ACTIVITIES. EACH EMPLOYER WHO HAS A WORKPLACE OR
OPERATION COVERED BY THIS STANDARD SHALL INITIALLY DETERMINE IF ANY
EMPLOYEE MAY BE EXPOSED TO LEAD AT OR ABOVE THE ACTION LEVEL AND TAKE
ALL NECESSARY STEPS TO COMPLY WITH THE REGULATIONS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID SETOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
VIERA VA MEDICAL CENTER, 2900 VETERANS
WAY, MELBOURNE, FL 32940
675-23-151
.1
.1
.2
\J o b s \J o b s \2
V A
A d d re s s V ie ra
S it e
D e fi c ie n c ie s \1 a A rc h it e c tu ra l\ M o d e l\
-2
-1
V ie ra
D e fi c ie n c ie s d e ta c h e d
.r v t
/2 /2
:5
:4
A
M
AE-100
VIERA SCOPE/PHASING
AESUS DESIGN GROUP
1050 E. Southern Ave., Suite D
Temple, AZ, 85282
480-454-2861
David Combs
ADDRESS VIERA SITE
DEFICIENCIES
NOV. 3, 2023 AESUS AESUS
1/32" = 1'-0"1 LEVEL 01 - VIERA_PHASING
N
Revisions: Date:
STAMPSTAMP
11.03.2023
Architecture, Engineering, and, Sustainable DesignAESUS 1050 E. Southern Ave, Suite #D, A
OFFICE
BATHROOM
DC
CR
DC
CR
ACID WASH ENTIRE SPACE AND POLYURETHANE COAT
TRAFFIC COATING, SEE SPECIFICATIONS.
NEW CAMERA, VERIFY
EXACT LOCATION WITH COR.
NEW CAMERA, VERIFY
EXACT LOCATION WITH COR.
NEW CAMERA, VERIFY
EXACT LOCATION WITH COR.
NEW CAMERA, VERIFY
EXACT LOCATION WITH COR.
NEW CAMERA, VERIFY
EXACT LOCATION WITH COR.
NEW CAMERA, VERIFY
EXACT LOCATION WITH COR.
PHONE
/AE-102 1
EXISTING GATE TO REMAIN
EXISTING GATE TO REMAIN
EXISTING DOOR TO REMAIN EXISTING DOOR TO REMAIN
NEW KEYPAD/CARD READER,
TYPICAL. PATCH AND REPAIR WALL
AS REQ'D FOR INSTALLATION.
MODIFY EXISTING DOOR AS REQ'D
FOR ACCESS CONTROL. SEE
ELECTRICAL FOR ADDITIONAL INFO.
NEW KEYPAD/CARD READER,
TYPICAL. PATCH AND REPAIR WALL
AS REQ'D FOR INSTALLATION.
MODIFY EXISTING DOOR AS REQ'D
FOR ACCESS CONTROL. SEE
ELECTRICAL FOR ADDITIONAL INFO.
EXISTING DOOR TO REMAIN
C R
NEW CAMERA, VERIFY
EXACT CAMERA
LOCATION WITH COR.
ALL PENETRATIONS
SHALL BE SEALED TO
MATCH EXISTING
RATING AND FINISH
TYPICAL.
NEW TELECOMM EQUIPMENT,
SEE ELECTRICAL FOR
ADDITIONAL INFORMATION.
PROVIDE A 4' HIGH X 8' WIDE
X 3/4" FRT PLYWOOD
BACKBOARD, A/C GRADE.
PAINT PLYWOOD SURFACE
GLOSS WHITE PER ISTS.
CARD READER
DOOR BUZZER LOCATION.
CONTROL ROOM TO HAVE
VIDEO MONITORING AND
REMOTE DOOR CONTROL.
REF. SPECIAL EQUIPMENT
PLANS 1/EY-101.
GC TO INSTALL THE NEW
WALL 4" PAST THE EXISTING
PULL BOX TO ALLOW FOR
CLEARANCE AND
MAINENANCE.
4"
EXISTING FEC
EXISTING FIRE
ALARM PULL
STATION
EXISTING
SWITCH
CHILLER BUILDING
DOOR SYMBOLS
DOOR CONTACT
CARD READER
DC
CR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID SETOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
VIERA VA MEDICAL CENTER, 2900 VETERANS
WAY, MELBOURNE, FL 32940
675-23-151
.1
.1
.2
\J o b s \J o b s \2
V A
A d d re s s V ie ra
S it e
D e fi c ie n c ie s \1 a A rc h it e c tu ra l\ M o d e l\
-2
-1
V ie ra
D e fi c ie n c ie s d e ta c h e d
.r v t
/2 /2
:5
:5
A
M
AE-101
ENLARGED PLANS
AESUS DESIGN GROUP
1050 E. Southern Ave., Suite D
Temple, AZ, 85282
480-454-2861
David Combs
ADDRESS VIERA SITE
DEFICIENCIES
NOV. 3, 2023 AESUS AESUS
1/4" = 1'-0"1 ENLARGED CHILLER BUILDING
1. THE ARCHITECTURAL DRAWINGS SHOW PRINCIPAL AREAS AND LIMITS OF
CONSTRUCTION WHERE WORK MUST BE ACCOMPLISHED UNDER THIS CONTRACT.
WORK MUST BE ACCOMPLISHED IN AREAS NOT SHOWN ON ARCHITECTURAL
DRAWINGS DUE TO CHANGES AFFECTING ELECTRICAL, MECHANICAL, PLUMBING AND
TECHNOLOGY ALONG WITH OTHER SYSTEMS. THIS WORK SHALL BE PART OF THIS
CONTRACT, AND ALL TRADES SHALL INSPECT THESE AREAS, ASCERTAIN WORK
REQUIRED AND DO THE WORK IN ACCORDANCE OF CONTRACT REQUIREMENTS AT NO
ADDITIONAL COST. SEE MECHANICAL, ELECTRICAL, PLUMBING AND TECHNOLOGY
PLANS FOR ADDITIONAL WORK.
2. CONTRACTORS SHALL VISIT THE SITE DURING BIDDING TO BECOME FAMILIAR WITH
THE EXISTING CONDITIONS. THE GENERAL CONTRACTOR SHALL LOCATE, INSPECT
AND FIELD VERIFYALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS PRIOR TO
DEMOLITION AND CONSTRUCTION. NOTIFY ARCHITECT IMMEDIATELY OF ANY
DISCREPANCIES
3. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES.
4. WHEREVER OPENINGS ARE CUT THROUGH FIRE RATED PARTITIONS, IT SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR FOR WHOM THE HOLE IS CUT TO PATCH AND
REPAIR ANY OPENING TO MAINTAIN THE INTEGRITY OF THE FIRE RATING.
5. GENERAL CONTRACTOR TO CHECK MECHANICAL DRAWINGS FOR EXISTING PIPES AND
DUCTSFURRED IN WALLS. VERIFY SIZE AND LOCATION WITH MECHANICAL
CONTRACTOR PRIOR TO PROCEEDING WITH REMODELING.
6. FIREPROOFING SHALL BE UNPIERCED. ANY SUBCONTRACTOR PENETRATING THE
FIREPROOFING SHALL BE REQUIRED TO REPLACE FIREPROOFING TO THE ORIGINAL
CONDITION AND FIRE RATING, AT THE SUBCONTRACTORS EXPENSE.
7. EQUIPMENT UNIT DIMENSIONS ARE FOR PRODUCT DESCRIPTION ONLY, VERIFY SIZE
WITH MANUFACTURER.
8. ALL DIMENSIONS PERTAINING TO MECHANICAL OR ELECTRICAL SERVICES OR
EQUIPMENT SHALL BE VERIFIED WITH THE RESPECTIVE TRADE.
9. ALL CONTRACTORS THAT PENETRATE AND/OR DISTURB ANY AREAS AT EXISTING
CONDITIONS SHALL PATCH AREA TO MATCH EXISTING ADJACENT AREA OR SURFACE
AND PREPARE FOR SCHEDULED FINISH APPLICATION. COORDINATE WORK WITH
GENERAL CONTRACTOR PRIOR TO PROCEEDING.
10. VERIFY HEIGHTS AND LOCATIONS OF ACCESS PANELS (AP) AND COORDINATE TYPES
WITH TRADES WHICH REQUIRE THEM.
11. PROVIDE LINTELS AND FRAMING FOR GRILLES, LOUVERS, AND ROOF VENTS AS
REQUIRED BY MECHANICAL CONTRACTOR, VERIFY SIZE AND LOCATION.
12. STRUCTURAL, MECHANICAL, AND ELECTRICAL ABBREVIATIONS AND SYMBOLS MAY
DIFFER FROM ARCHITECTURAL. SEE RESPECTIVE SECTIONS AND/OR DRAWINGS FOR
DEFINITIONS.
13. AT MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS, PROVIDE 3/4" FRT PLYWOOD
BACKING BEHIND ALL SURFACE MOUNTED FIXTURES AND EQUIPMENT, UNLESS NOTED
OTHERWISE.
14. CONTRACTOR SHALL EVALUATE INTEGRITY OF ALL PARTITIONS INDICATED BY
SYMBOLS ON THE LIFE SAFETY PLAN(S) WITHIN THE PROJECT SCOPE AND UPGRADE
AS REQUIRED. ALL FIRE RESISTIVE RATED WALLS SHALL BE CONSTRUCTED OF
MATERIALS / ASSEMBLIES MEETING THE RATING INDICATED, TERMINATE AT THE DECK
ABOVE WITH A TESTED HEAD OF WALL ASSEMBLY AND ALL PENETRATIONS SHALL BE
SEALED WITH A TESTED ASSEMBLY. ALL SMOKE PARTITIONS SHALL BE CONSTRUCTED
OF MATERIALS THAT RESIST THE PASSAGE OF SMOKE, TERMINATE AT THE DECK
ABOVE WITH A JOINT SEALED WITH FIRE CAULK AND ALL PENETRATIONS SHALL BE
SEALED WITH FIRE CAULK.
15. THE GC SHALL MODIFY AND RELOCATE EXISTING AREA DRAINS AS REQUIRED TO
INSTALL BUILDING FOUNDATIONS.
GENERAL NOTES
Revisions: Date:
STAMPSTAMP
11.03.2023
Architecture, Engineering, and, Sustainable DesignAESUS 1050 E. Southern Ave, Suite #D, VARIES
FIN. GRADE
VARIES
FIN. GRADE
1/4
1/4
3/16 3/16
1/4
1/4
1/4
3/16 3/16
1/4 1/4
3"
2" 2"
1/2"1/2" 3
1 1/2"
CL
LC
WHEEL
1/4" THK. STL.
SUPPORT BRACKET
PAINT TO MATCH
FRAME
6" x 2" THK.
RUBBER WHEEL
W/ STEEL HUB
3/4"∅ STEEL
AXLE BOLT
L 6" X 3" X 5__
" (LLH)
X 4" LONG @ WHEEL
ASSEMBLY LOCATION
STL. SPRING
LINE OF MAX.
DROP
EXTERIORINTERIOR
LC
CL
WHEEL
L6X3X 5__
" (LLH) X 4" LONG -
ALIGNED WITH WHEEL
SUPPORT ASSEMBLY
HSS 9X3X3/16" PAINTED
1_
" GUSSET PLATE - LEG LENGTH =
3" @ 1:1 SLOPE CENTERED ON THE
WHEEL SUPPORT ASSEMBLY WIDTH
STL. SPRING
1/4" THK. STL. SUPPORT
BRACKET PAINT TO
MATCH FRAME
6" x 2" THK. RUBBER
WHEEL W/ STEEL HUB
3/4"∅ STEEL AXLE
BOLT
LINE OF MAX.
DROP
L6X3 ANGLE TO
SUPPORT BRACKET
HSS 9" X 3" X 3__
FRAME BEYOND.
L6X3 ANGLE TO
SUPPORT BRACKET
L6X3 ANGLE TO
HSS FRAME
FLOOR PLAN SYMBOLS
DEMOLITION
EXISITNG WALL
NEW WALL
A
OFFICE
BATHROOM
X3
X
A
A3
A
2' - 4" 5' - 6"
10' - 6" V.I.F
V
.I .F
7' - 0"
6' - 9" V.I.F
EXISTING
DOOR TO
REMAIN
EXISTING
WALL TO
REMAIN
EXISTING
WALL TO
REMAIN
EXISTING
WALL TO
REMAIN
COMBINATION
EYEWASH/SHOWER
STATION
5'-6"W X 4'-0"H
WINDOW 3'-0"
A.F.F.
3'-6"W X 4'-0"H
WINDOW 3'-0"
A.F.F.
1' - 9" 3' - 4" 2' - 1" 1' - 6" 2' - 2"
REMOVE AND REPLACE THE (E)
INTAKE LOUVER WITH A MOTORIZED
LOUVER. PROVIDE ALL FLASHING AND
SEALANT AS REQ'D. SEE MPE FOR
ADDITIONAL INFO.
NEW LIGHT
FIXTURE, TYP.
GYP
BD
ACT
AFF
8' - 0"
AFF
8' - 0"
NEW
DIFFUSER, TYP.
EXHAUST, SEE
MECHANICAL
NOTE: PROVIDE CONT. SOUND
ATTENUATION BLANKETS ON
TOP OF CEILING SYSTEM.
ACCESS
PANEL
SEE TYPICAL
CEILING DETAILS
ON SHEET AE-106.
3' - 6"
3' - 3"
NOTE: THE GC SHALL FIELD
LOCATE AND CONFIRM THE
FINAL SPRINKLER HEAD
LOCATIONS WITH COR.
NEW SPRINKLER,
SEE FP PLAN, TYP.
SUPPLY, SEE
MECHANICAL.
RETURN, SEE
MECHANICAL
NEW LIGHT
FIXTURE, TYP.
EQ EQ
CORE DRILL FOR NEW
EXHAUST. PROVIDE ALL
FLASHING AND SEALANT AS
REQ'D.
NOTE: THE GC MUST LOCATE
AND AVOID CUTTING (E) WALL
REINFORCING AND SUPPORTS.
DEMO EXISTING EQUIPMENT PAD,
PATCH, GRIND, AND REPAIR SLAB
AS REQUIRED. MATCH ADJACENT
FINISH AND TEXTURE. NOTE,
DIMENSIONS MAY VARY DUE TO
FIELD CONDTIONS.
NEW DOUBLE
SWING GATE
EXISTING WALL TO
REMAIN
14' - 5"
AE-102
REF. AE-102/ 6
AE-102
15' - 2 1/2"
/4
3' - 1 1/4" 8' - 2" 3' - 11 1/4"
/4
NOTE: SEE ELECTRICAL AND
FP PLANS FOR ADDITIONAL
INFO.
STEEL BEAM TO BE PAINTED,
SEE STRUCTRAL FOR
ADDITIONAL INFO
METAL ROOF
DECK
EXISTING
WALL TO
REMAIN
PATCH AND REPAIR
EXISTING SLAB AS
REQ'D
1/4"/12"
SLOPE
TPO ROOF OVER
TAPERED INSULATION
CONT. GRAVEL STOP
AT ROOF EDGE,
TYPICAL.
EXISTING
WALL TO
REMAIN
/AE-106 1
8' - 2" V.I.F. +/- 4' - 1"
AE-102
1/4"/12"
SLOPE
16' - 7"
NEW ROOF
HPLP
OUTLINE
OF WALL
BELOW
AE-102
NOTE: ALL EXPOSED STEEL
SHALL BE PAINTED TO MATCH
EXISTING
RELOCATED GATE
PROVIDE NEW STANLEY BB852
PRISON HINGES TYP. OF EACH
LEAF
EXISTING CONCRETE WALL
SECTION 'A'
HSS 4" X 4" X 1/4" POST
M
IN
JAMB ANCHOR PLATE, SEE STRUCTURAL
NOTE: ALL EXPOSED
STEEL SHALL BE
PAINTED
3/16
CL
EXTERIOR INTERIOR
HSS 4" X 4" X 1_
PAINTED
HSS 3" X 3" X 3__
PAINTED
GATE IN CLOSED
POSITION
PERFORATED
STEEL PLATE
GATE IN OPEN POSITION
JAMB ANCHOR PLATE, SEE
STRUCTURAL.
EXISTING CONCRETE WALL
1/4"/12"
SLOPE
NEW 3/4" X 3" STEEL SLEEVES SET
IN CONC. ONE EA. IN "OPEN" &
"CLOSED" POSITIONS.
CORRUGATED METAL PANELS, PAINTED
EXISTING SLAB
PROVIDE STANLEY
BB852 PRISON HINGES
TYP. OF EACH LEAF
PADLOCK
HASP W/ GATE
1/2" DIA. W/ 3" EMBEDMENT
BOLTS W/ GATE
HSS 4" X 4" X 1/4" POST -
TYPICAL AT EACH JAMB. SEE
STRUCTURAL FOR POST
ATTACHMENT. PROVIDE CAP
PLATES AT TOP OF POST.
V.I.F. 15' - 3"
AE-102
AE-102
/AE-102 9
TPO ROOF OVER
TAPERED INSULATION
CONT. GRAVEL STOP
AT ROOF EDGE,
TYPICAL.
EXISTING WALLS TO
REMAIN
/AE-106 1
C L R
NOTE: THE GC TO LOCATE
AND AVOID CUTTING (E) SLAB
REINFORCING
STRUCTURAL STEEL, PAINTED. SEE
STRUCUTRAL FOR ADDITIONAL INFO.
EDGE OF SLAB OUTLINE OF
EXISTING SIGN
8' - 7"
VA
U.S. Department of Veterans Affairs
DEMOLISH EXISTING
MARQUEE SIGN,
KEEPING STRUCTURAL
COMPONENTS INTACT
EXISTING FOUNDATION
AND STRUCTURAL
COMPONENTS TO
REMAIN
CEILING SYMBOLS
GYP BD
SUPPLY AIR
FLUORESCENT LIGHT
EXHAUST AIR
ACT - ACOUSTIC CEILING
TILE
DOWNLIGHT
A.F.F.1'-0"
CEILING HEIGHT ABOVE
FINISH FLOOR
SPRINKLER, SEE FP
PLANS, TYP.
ROOF PLAN GENERAL NOTES
1. ROOF TYPE: MODIFIED BUILT UP ROOF
2. ALL ROOFING SURFACES TO SLOPE 1/4" VERTICAL PER 1' - 0" HORIZONTAL MINIMUM,
U.N.O.
3. HATCHING INDICATES AREAS WHERE THE ROOF SLOPE SURFACE SLOPE IS ACHIEVED
WITH TAPERED INSULATION. THE ROOF SURFACE SLOPE IN AREAS WITHOUT
HATCHING IS ACHIEVED WITH SLOPING STRUCTURE, U.N.O.
4. TOP OF INSULATION HEIGHTS, HIGH POINTS AND LOW POINTS, ARE INDICATED AS
THE TOP OF ROOF SURFACE ABOVE THE ROOF DRAIN(S). (I.E. + 3.5" WHERE HIGH
POINT OF ROOF DRAIN SUMP IS +0"
5. REFER TO SHEET A7.51/A7.52 FOR TYPICAL ROOF DETAILS.
6. ALL ROOF TOP MECHANICAL, ELECTRICAL AND/OR PLUMBING EQUIPMENT SHOWN
FOR INFORMATION ONLY. REFERENCE MECHANICAL, ELECTRICAL AND PLUMBING
DOCUMENTS AND SPECIFICATIONS FOR SPECIFIC DESIGN INFORMATION.
7. PROVIDE WALKWAY PROTECTION TO MAJOR MECHANICAL, ELECTRICAL AND
PLUMBING EQUIPMENT AS REQUIRED TO PROVIDE SERVICE ACCESS. WALKWAY
PROTECTION IS INDICATED AS A GENERAL LAYOUT AND MAY NOT SHOW ALL FINAL
LOCATIONS OF ALL EQUIPMENT.
8. EXISTING ROOFS TO REMAIN, U.N.O.
9. REFERENCE DEMOLITION PLANS AND SECTIONS.
10. PATCH AND REPAIR EXISTING ROOFS DAMAGED DURING CONSTRUCTION.
REFLECTED CEILING PLAN GENERAL NOTES
A. THE GC SHALL VISIT THE SITE PRIOR TO BIDDING TO BETTER UNDERSTAND THE
EXISTING CONDITIONS, TYPICAL.
B. IN THE CASE OF MINOR DISCREPANCIES BETWEEN MEP AND ARCHITECTURAL
DOCUMENTS IN THE LOCATION OF CEILING MOUNTED COMPONENTS, THE
ARCHITECTURAL REFLECTED CEILING PLAN SHALL GOVERN. IN THE CASE OF MAJOR
DISCREPANCIES, THE ARCHITECT SHALL BE NOTIFIED AS SOON AS THE
DISCREPANCY IS DISCOVERED PRIOR TO PROCEEDING WITH THE WORK.
C. REFERENCE MECHANICAL AND ELECTRICAL DRAWINGS FOR MOUNTING LOCATIONS
OF ITEMS WHERE NO CEILING IS REQUIRED OR INDICATED.
D. LIGHTS, DIFFUSERS, EXIT SIGNS, SMOKE DETECTORS, SPEAKERS, STROBES, AND
MISCELLANEOUS DEVICES SHALL BE REMOVED AND RE-INSTALLED AS REQUIRED TO
INSTALL THE NEW CABLE TRAY, SEE MPE FOR ADDITIONAL INFO.
E. ALL SPRINKLER HEADS SHALL REMAIN UNDISTURBED UNLESS NOTED OTHERWISE.
F. ACCESS DOOR LOCATIONS IN GYPSUM BOARD CEILINGS ARE INDICATED ON RCP'S
ONLY WHERE ARCHITECTURALLY SIGNIFICANT. REFERENCE SPECIFICATIONS AND
MEP DRAWINGS FOR OTHER ACCESS DOOR LOCATIONS.
G. EXIT SIGNS ARE SHOWN ON REFLECTED CEILING PLAN ONLY WHERE LOCATION IS
ARCHITECTURAL SIGNIFICANT.
H. AT NEW DUCTWORK IN EXISTING CEILING TO REMAIN. REMOVE AND SALVAGE
CEILING GRID, CEILING TILES, AND CEILING FIXTURES. REINSTALL IN PLACE, PATCH
AND REPAIR AS REQUIRED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID SETOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
VIERA VA MEDICAL CENTER, 2900 VETERANS
WAY, MELBOURNE, FL 32940
675-23-151
.1
.1
.2
\J o b s \J o b s \2
V A
A d d re s s V ie ra
S it e
D e fi c ie n c ie s \1 a A rc h it e c tu ra l\ M o d e l\
-2
-1
V ie ra
D e fi c ie n c ie s d e ta c h e d
.r v t
/2 /2
:5
:5
A
M
AE-102
ENLARGED PLANS
AESUS DESIGN GROUP
1050 E. Southern Ave., Suite D
Temple, AZ, 85282
480-454-2861
David Combs
ADDRESS VIERA SITE
DEFICIENCIES
NOV. 3, 2023 AESUS AESUS
1. THE ARCHITECTURAL DRAWINGS SHOW PRINCIPAL AREAS AND LIMITS OF
CONSTRUCTION WHERE WORK MUST BE ACCOMPLISHED UNDER THIS CONTRACT.
WORK MUST BE ACCOMPLISHED IN AREAS NOT SHOWN ON ARCHITECTURAL
DRAWINGS DUE TO CHANGES AFFECTING ELECTRICAL, MECHANICAL, PLUMBING AND
TECHNOLOGY ALONG WITH OTHER SYSTEMS. THIS WORK SHALL BE PART OF THIS
CONTRACT, AND ALL TRADES SHALL INSPECT THESE AREAS, ASCERTAIN WORK
REQUIRED AND DO THE WORK IN ACCORDANCE OF CONTRACT REQUIREMENTS AT NO
ADDITIONAL COST. SEE MECHANICAL, ELECTRICAL, PLUMBING AND TECHNOLOGY
PLANS FOR ADDITIONAL WORK.
2. CONTRACTORS SHALL VISIT THE SITE DURING BIDDING TO BECOME FAMILIAR WITH
THE EXISTING CONDITIONS. THE GENERAL CONTRACTOR SHALL LOCATE, INSPECT
AND FIELD VERIFYALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS PRIOR TO
DEMOLITION AND CONSTRUCTION. NOTIFY ARCHITECT IMMEDIATELY OF ANY
DISCREPANCIES
3. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES.
4. WHEREVER OPENINGS ARE CUT THROUGH FIRE RATED PARTITIONS, IT SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR FOR WHOM THE HOLE IS CUT TO PATCH AND
REPAIR ANY OPENING TO MAINTAIN THE INTEGRITY OF THE FIRE RATING.
5. GENERAL CONTRACTOR TO CHECK MECHANICAL DRAWINGS FOR EXISTING PIPES AND
DUCTSFURRED IN WALLS. VERIFY SIZE AND LOCATION WITH MECHANICAL
CONTRACTOR PRIOR TO PROCEEDING WITH REMODELING.
6. FIREPROOFING SHALL BE UNPIERCED. ANY SUBCONTRACTOR PENETRATING THE
FIREPROOFING SHALL BE REQUIRED TO REPLACE FIREPROOFING TO THE ORIGINAL
CONDITION AND FIRE RATING, AT THE SUBCONTRACTORS EXPENSE.
7. EQUIPMENT UNIT DIMENSIONS ARE FOR PRODUCT DESCRIPTION ONLY, VERIFY SIZE
WITH MANUFACTURER.
8. ALL DIMENSIONS PERTAINING TO MECHANICAL OR ELECTRICAL SERVICES OR
EQUIPMENT SHALL BE VERIFIED WITH THE RESPECTIVE TRADE.
9. ALL CONTRACTORS THAT PENETRATE AND/OR DISTURB ANY AREAS AT EXISTING
CONDITIONS SHALL PATCH AREA TO MATCH EXISTING ADJACENT AREA OR SURFACE
AND PREPARE FOR SCHEDULED FINISH APPLICATION. COORDINATE WORK WITH
GENERAL CONTRACTOR PRIOR TO PROCEEDING.
10. VERIFY HEIGHTS AND LOCATIONS OF ACCESS PANELS (AP) AND COORDINATE TYPES
WITH TRADES WHICH REQUIRE THEM.
11. PROVIDE LINTELS AND FRAMING FOR GRILLES, LOUVERS, AND ROOF VENTS AS
REQUIRED BY MECHANICAL CONTRACTOR, VERIFY SIZE AND LOCATION.
12. STRUCTURAL, MECHANICAL, AND ELECTRICAL ABBREVIATIONS AND SYMBOLS MAY
DIFFER FROM ARCHITECTURAL. SEE RESPECTIVE SECTIONS AND/OR DRAWINGS FOR
DEFINITIONS.
13. AT MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS, PROVIDE 3/4" FRT PLYWOOD
BACKING BEHIND ALL SURFACE MOUNTED FIXTURES AND EQUIPMENT, UNLESS NOTED
OTHERWISE.
14. CONTRACTOR SHALL EVALUATE INTEGRITY OF ALL PARTITIONS INDICATED BY
SYMBOLS ON THE LIFE SAFETY PLAN(S) WITHIN THE PROJECT SCOPE AND UPGRADE
AS REQUIRED. ALL FIRE RESISTIVE RATED WALLS SHALL BE CONSTRUCTED OF
MATERIALS / ASSEMBLIES MEETING THE RATING INDICATED, TERMINATE AT THE DECK
ABOVE WITH A TESTED HEAD OF WALL ASSEMBLY AND ALL PENETRATIONS SHALL BE
SEALED WITH A TESTED ASSEMBLY. ALL SMOKE PARTITIONS SHALL BE CONSTRUCTED
OF MATERIALS THAT RESIST THE PASSAGE OF SMOKE, TERMINATE AT THE DECK
ABOVE WITH A JOINT SEALED WITH FIRE CAULK AND ALL PENETRATIONS SHALL BE
SEALED WITH FIRE CAULK.
15. THE GC SHALL MODIFY AND RELOCATE EXISTING AREA DRAINS AS REQUIRED TO
INSTALL BUILDING FOUNDATIONS.
GENERAL NOTES
1/4" = 1'-0"1 ENLARGED OFFICE AND BATHROOM
1/4" = 1'-0"2 LEVEL 01 - VIERA_RCP_1 - AREA A1
1/4" = 1'-0"3 ENLARGED ENCLOSURE
1/4" = 1'-0"4 ENCLOSURE SECTION
1/4" = 1'-0"5 ENCLOSURE ROOF PLAN
1 1/2" = 1'-0"7 GATE SECTION
1 1/2" = 1'-0"8 GATE JAMB
1 1/2" = 1'-0"9 GATE WHEEL
1/4" = 1'-0"6 GATE ELEVATION
1/2" = 1'-0"10 ENLARGED MARQUEE SIGN
1/2" = 1'-0"11 MARQUEE SIGN DEMO ELEVATION
Revisions: Date:
STAMPSTAMP
11.03.2023
Architecture, Engineering, and, Sustainable DesignAESUS 1050 E. Southern Ave, Suite #D, REFER TO
PARTITION
HEAD DETAILS
SEALANT
MTL RUNNER
SEALANT
MTL RUNNER
5/8" GYP BD EACH
SIDE
LINE OF
STRUCTURE
LINE OF
CEILING
BOTTOM OF
EXISTING
STRUCTURE
FLOOR PLAN
DESIGNATION
NO SOUND
ATTENUATION
FLOOR PLAN
DESIGNATION
WITH SOUND
ATTENUATION
STUD
SIZE
PART
WIDTH
FIRE
RATING
UL LISTING
WITH SOUND
STC:
NO SOUND
REMARKS
3 5/8" 4 7/8"
NON-
RATED
N/A 49
W/3" SAB
A3 A3
TYPE "A"
PARTITION WIDTH
REFER TO SCHEDULE
BELOW FOR
NOTES
PARTITION TYPE INCLUDED IN
SCOPE OF WORK
PARTITION TYPE NOT
INCLUDED IN SCOPE OF
WORK
1. PARTITIONS ARE DISTINGUISHED ON FLOOR PLANS BY SYMBOL DESIGNATION, GRAPHIC DESIGNATION OR A
COMBINATION OF BOTH DESIGNATIONS.
2. THERE ARE TWO TYPES OF SYMBOL DESIGNATIONS, ONE FOR PARTITONS NOT REQUIRING SOUND
ATTENUATION
AND ANOTHER FOR PARTITIONS WHICH REQUIRE SOUND ATTENUATION. REFER TO PARTITION MATRICES
FOR
SOUND ATTENUATION BLANKET (SAB) MINIMUM THICKNESS FOR STC INDICATED.
3. THERE ARE TWO SYMBOL DESIGNATION SYSTEMS USED. THE FIRST SYSTEM CONSISTS OF TWO AND THREE CHARACTERS, THE FIRST CHARACTER IS A LETTER INDICATING THE PARTITION TYPE. THE SECOND
CHARACTER IS
NUMERIC INDICATING THE STUD OR CMU WIDTH. REFER TO LEGEND BELOW. THIS SYSTEM IS USED TO
DEFINE
WALL TYPES: A, B, C, D, E, F, H, J, K, M, R
THE # CHARACTER BELOW THE LINE INDICATES THE HEIGHT OF THE SPECIFIC WALL COMPONENT. THE HEIGHT OF A SPECIFIC WALL COMPONENT. REFER TO THE LEGEND BELOW. THIS SYSTEM IS USED TO DEFINE
WALL TYPES: RA THRU RR
4. IF NO SYMBOL DESIGNATION IS PROVIDED, THE STUD SIZE WILL BE 3 5/8".
5. THE GRAPHIC DESIGNATION IS INCORPORATED FOR PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT. REFER TO NOTE 18.
6. "LINE OF STRUCTURE" INDICATED FOR EACH PARTITION IS DIAGRAMMATIC ONLY AND DOES NOT INDICATE
EXACT CONSTRUCTION CONDITIONS OR GEOMETRY.
7. ALL DIMENSIONS ARE FROM FACE OF GYPSUM BOARD TO FACE OF GYPSUM BOARD. REFER TO PARTITION
MATRICES FOR PARTITION WIDTH DIMENSIONS UNLESS INDICATED TO BE SHOWN ON PLAN.
8. SEALANT:
1. FIRE RESISTANCE RATED PARTITIONS SHALL USE RATED FIRE/SMOKE FIRE RESISTANT FILL
MATERIAL IN
CONJUNCTION WITH AN APPROPRIATE RATED FIRE/SMOKE FIRE STOPPING SYSTEM.
2. NON-RATED PARTITIONS AND NON-RATED SMOKE RESISTANT PARTITIONS SHALL USE ACOUSTICAL
SEALANT.
9. INSULATION: - HEAD CONDITIONS AT FLOOR/ROOF DECK
1. FIRE RESISTANCE RATED PARTITIONS SHALL USE MINERAL WOOL INSULATION.
2. NON-RATED PARTITIONS REQUIRING SOUND ATTENUATION SHALL USE SOUND ATTENUATION
BLANKETS (SAB).
3. PROVIDE FULL THICKNESS INSULATION INSIDE ALL STUD BOX BEAMS AND HEADERS WHICH OCCUR
IN
WALLS WITH SOUND ATTENUATION.
10. REFER TO SPECIFICATIONS FOR MINIMUM STUD THICKNESS, MAXIMUM SPACING AND ALLOWABLE LIMITING
HEIGHTS DEFLECTION CRITERIA FOR GYPSUM BOARD ASSEMBLIES.
11. FOR PARTITIONS INDICATED TO RECEIVE SOUND ATTENUATION BLANKETS (SAB), EXTEND SAB TO FULL
HEIGHT
OF PARTITION UNLESS OTHERWISE INDICATED. FLOOR TRACK TO BE SET IN A CONT BED OF SEALANT.
12. FIRE RESISTANT AND FIRE RESISTANT SMOKE BARRIER RATINGS ARE TO SURROUND ALL OPENINGS IN
RATED
PARTITIONS.
NUMERIC
CHARACTER
STUD
WIDTH
CMU
WIDTH
1 5/8" 2 1/2" 3 5/8"
4" 6"
3 5/8" 5 5/8" 7 5/8"
11 5/8"
13. SMOKE RESISTANT, FIRE RESISTANT, AND FIRE RESISTANT SMOKE BARRIER PARTITIONS SHALL EXTEND AND SEAL TO INSIDE FACE OF EXTERIOR SHEATHING, INCLUDING EXTENSIONS THROUGH
SOFFITS.
14. EACH PARTITION SHOWN ON THE DRAWINGS TO HAVE A FIRE AND SMOKE RESISTANT RATING SHALLBE IDENTIFIED AS SUCH WITH A LABEL ABOVE THE CEILING ON EACH SEGMENT OF THE WALL
AND 6' - 0" OC MAX EACH SIDE.
15. REFER TO TOILET ACCESSORIES SHEET AND CASEWORK SHEET FOR MOUNTING DETAIL
INFORMATION.
16. REFER TO THE METAL FABRICATIONS DETAILS FOR MF REFERENCES IN PARTITIONS SECTION.
17. REFER TO STRUCTURAL DRAWINGS FOR REINFORCING INFORMATION.
18. GRAPHIC DESIGNATION
19. DO NOT APPLY BULLNOSE BLOCK AT CORNER GUARD LOCATIONS.
20. MASONRY REINFORCEMENT: REFERENCE STRUCTURAL DRAWINGS.
21. HW (HEAD OF WALL) DETAILS DO NOT ALTER PARTITION TYPES NOTED ON PLANS.
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT WALL
1 HR SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT WALL
SMOKE PARTITION (NON RATED)
PRIORITY
1 HIGHEST
5 LOWEST
NOTE:
1. NOT ALL PARTITION TYPES SHOWN ON THIS SHEET ARE USED ON THIS PROJECT.
2. THE SHADED PORTIONS OF A PARTITION TYPE ARE NOT INCLUDED IN THE SCOPE OF THE
WORK.
3. THE UN-SHADED PORTIONS OF ALL PARTITION TYPES ARE INTENDED TO BE IN THE SCOPE OF
THE WORK.
HATCHING:
NUMERIC
CHARACTER
CMU/BRICK
HEIGHT
9' - 4" 10' - 8" 12' - 8" 18' - 8" 14' - 0"
SYMBOL DESIGNATIONS
(NO…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .