This document is a set of cut sheets for repairing Military Working Dog Kennels at Facility 1030, located at Joint Base Langley-Eustis in Hampton, Virginia. The project is identified by the reference number MUHJ 24-4024 and was prepared by Vansant & Gusler Consulting Engineers on July 22, 2025. The documentation includes detailed technical specifications for a Dedicated Outdoor Air System (DOAS-1), specifically a Valent VX-212-20I-1-D2 model unit. The system is designed for an outdoor installation with a packaged DX cooling system, electric heating, and features like a modulating inverter scroll compressor, electronic expansion valve, and a 65.6 kW electric heater. The unit has a total cooling capacity of 275.0 MBH, a supply air volume of 3,400 CFM, and is configured to meet ASHRAE 90.1 energy efficiency standards. Additional components include variable frequency drives, sound-dampening features, and compatibility with BACnet MSTP building management systems.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Repair Military Working Dog Kennels
Facility 1030
MUHJ 24-4024
Joint Base Langley-Eustis
Hampton, Virginia
CUT SHEETS
Prepared By:
July 22, 2025
DOAS-1
VX-212-20I-1-D2
Unit Performance
Design Conditions
Elevation (ft) Summer Winter DB (F) Supply
(CFM)
Outdoor Air
(CFM)
Exhaust Air
(CFM)DB (F) WB (F)
16 92.0 76.6 22.0 3,400 3,400 3,125
Unit Specifications Qty Weight (lb) Cooling Type Heating Type Unit Installation Unit ETL Listing 1 4,212 (+/- 5%) Packaged DX Electric Outdoor UL\cUL 1995/ 60335-2-40
Configuration Outdoor Air Exhaust Air
Intake Discharge Intake Discharge End Side Side Side
ASHRAE 90.1 Compliance ASHRAE 90.1 Min. Efficiency Calculated Efficiency Compliance
ISMRE2 (ASHRAE 90.1-2022) 3.8 7.6 ✓
Cooling Specifications
Type Total
Capacity
(MBH)
Sensible Capacity
(MBH)
Lead Compressor
Type
Coil (DB/WB) Reheat EAT (F) LAT (F) Capacity
(MBH) LAT (F)
Packaged DX 275.0 140.3 Inverter Scroll 92.0 / 76.6 51.7 / 51.4 139.8 91.0
Heating Specifications
Type Capacity (kW) Full Load Amps (FLA) Capacity Control Performance
EAT (F) LAT (F)
Electric 65.6 182.1 Modulating (SCR) 22.0 83.0
Motor Specifications Motor Qty Operating
Power (hp) Size (hp) Enclosure Efficiency RPM Supply 2 0.8 2 ODP NEMA Premium 1165 Exhaust 1 0.69 1 ODP NEMA Premium 1150
Electrical Specifications Power Supply Rating (V/C/P) MCA (A) MOP (A) FLA (A) Fan Power (W/CFM)*
Unit 208/60/3 203.6 225.0 199.3 0.503 *Fan Power (W/CFM) = (Supply BHP + Exhaust BHP) / Supply CFM
06/12/2025Printed Date:
LAFB Bldg. 1030 Working Dog FacilityJob:
DOAS-1Mark:
VX-212-20I-1-D2Model:
Generated by: Trever.Tomes@damuth.comCAPS 4.47.1071 Page 1 of 24 C:\Users\ttomes\OneDrive\Documents\CAPS\Jobs\V&G - LAFB Bldg. 1030.valj
Construction Features And Accessories
Unit Unit Installation - Outdoor Std Unit Construction - Double Wall Std Insulation - 2 inch 2.4# R13 foam Std Corrosion Resistant Fasteners Std Hinged Access Std Factory Wired Non-Fused Disconnect Switch Std Direct Drive Plenum Blower & Motor Assemblies X Factory Wired VFDs Std Unit Finish - Permatector, Concrete Gray (RAL 7023) X Stainless Steel Condensate Drain Pan and Connection Std Condensate Drain Trap Std Short Circuit Current - 5 kA X
Controls Unit Controls - Full Factory Control Std Internally Mounted Control Center with 24 VAC control transformer(s) and control circuiting fusing Std
BMS Protocol - BACnet MSTP X BMS Monitoring Points Supply Fan Control - Constant Volume - Adj. Setpoint X Exhaust Fan Control - Space Static Press.-By Factory X Exhaust Fan Only Power Energy Wheel Rotation Sensor Web-Based User Interface Std Damper Control - 100% OA-Unocc. Recirculation X Economizer Control Unoccupied Recirc Mode X
Control Accessories Remote Display Dirty Filter Sensor(s) - Supply X Airflow Monitor - Exhaust Air, Supply Air X Return Duct Sensor - Temp and RH X Phase/Brownout Protection Std Economizer Fault Detection Diagnostics
Accessories Recirc Air Damper - Low Leakage X Outdoor Air Damper - Low Leakage X Return Air Damper Roof Curb Supply Air Filters - 2" Merv 13, 3-16x20x2, 6-20x20x2 X Service Outlet - Factory mounted and wired X Piping Vestibule Service Lights Condensate Overflow Switch X Spare Filters Exhaust Discharge Gravity Backdraft Damper X ElectroFin Coil Coating Motor Shaft Grounding X Bipolar Ionization Smoke Detector(s) Barometric Relief Damper UV Lights Hail Guards X
Warranty Options Unit Warranty - 18 Months (Std.) Std Compressor Warranty - 5.5 Yrs. (4 Yrs. Extended) X
Standard Option Std Not Included
Included X
Notes Verify that the correct BMS Protocol has been selected before ordering Outdoor Air Damper supplied is low leakage, motorized VCD-23 (leakage rate of 3 CFM/ft^2 @ 1 in. wg), Class 1A Leak detection sensors
06/12/2025Printed Date:
LAFB Bldg. 1030 Working Dog FacilityJob:
DOAS-1Mark:
VX-212-20I-1-D2Model:
Generated by: Trever.Tomes@damuth.comCAPS 4.47.1071 Page 2 of 24
Supply Fan Charts And Performance
Supply Fan Performance
Total Volume
(CFM)
External SP
(in. wg)
Total SP
(in. wg) RPM Operating
Power (hp) Motor Fan
Qty Size
(hp) Qty Type Drive-Type
3,400 1.5 1.91 1372 0.8 2 2 2 Plenum Direct
Pressure Drop (in. wg) Weatherhood Filter Damper Cooling Heating External Total
0.064 0.057 0.02 0.125 0.13 1.5 1.91
Sound Performance in Accordance with AMCA Sound Power by Octave Band Lwa dBA Sones62.5 125 250 500 1000 2000 4000 8000
81.0 78.1 82.4 71.9 63.8 65.8 75.0 64.3 79.2 67.7 17.1
Supply Fan
06/12/2025Printed Date:
LAFB Bldg. 1030 Working Dog FacilityJob:
DOAS-1Mark:
VX-212-20I-1-D2Model:
Generated by: Trever.Tomes@damuth.comCAPS 4.47.1071 Page 3 of 24
Exhaust Fan Charts And Performance
Exhaust Fan Performance
Mode Total Volume
(CFM)
External SP
(in. wg)
Total SP
(in. wg) RPM Operating
Power (hp) Motor Fan
Qty Size
(hp) Qty Type Drive-
Type Normal 3,125 0.75 0.775 860 0.69 1 1 1 Plenum Direct
Pressure Drop (in. wg) Mode Weatherhood Filter Damper Cooling Heating External Total
Normal 0.025 - - - - 0.75 0.775
Sound Performance in Accordance with AMCA
Mode Sound Power by Octave Band Lwa dBA Sones62.5 125 250 500 1000 2000 4000 8000 Normal 97.2 76.2 68.9 64.2 57.4 56.5 53.2 54.9 73.1 61.6 14.9
Exhaust Fan
06/12/2025Printed Date:
LAFB Bldg. 1030 Working Dog FacilityJob:
DOAS-1Mark:
VX-212-20I-1-D2Model:
Generated by: Trever.Tomes@damuth.comCAPS 4.47.1071 Page 4 of 24
Cooling Performance
Cooling Specifications
Nominal Tonnage
Entering Air (F) Leaving Air (F) Capacity (MBH) Reheat Condensing Ambient Temp
(F)DB WB DB WB Total Sensible Capacity
(MBH) LAT (F)
20 92.0 76.6 51.7 51.4 275.0 140.3 139.8 91.0 92.0
Coil Information
PDX Coil Model Fins Per Inch
Rows Deep
Face Vel.
(ft/min)
Coil PD
(in. wg) Refrigerant
Refrig.
Velocity (ft/min)
Face Area (ft2)
Suction Temp (F)
DR38S06H14-58x56-LH 14 6 151 0.125 R-454B 1,289 22.56 48.8
Compressor Details Lead Compressor
Type Compressor
Qty Compressor RLA/MRC (A) Compressor LRA (A)
Comp. #1 Comp. #2 Comp. #1 Comp. #2 Inverter Scroll 2 38.4 33.3 NA 255
A2L Installation Requirement - UL 60335-2-40 Largest Circuit Charge Minimum Circulation Airflow Minimum Total Conditioned Room Area
48.6lb / 22.06kg 1,318 CFM 730 ft2 Local codes and standards may have requirements regarding the installation of A2L refrigerants in addition to manufacturing instructions provided for listed and labeled equipment.
Unit Details Refrigerant charges provided by the factory are approximate and may require adjustment in the field Hermetic scroll type compressors Compressors mounted on neoprene vibration isolation Crankcase heater on staged compressor Electronic expansion valve on lead circuit, thermostatic expansion valve on staged circuit Stainless steel double sloped drain pan Moisture-indicating sight glass Service/charging valves Refrigerant high pressure switch (manual reset) Liquid-Line filter drier Leak detection sensors Multiple low sound condensing fans with Lead ECM condensing fan for modulating head pressure control Inverter scroll compressor Refrigerant low pressure switch (auto reset) Unit cannot be mounted in an enclosed space.
Important Notes:
Capacity is based on incoming voltage selected. If incoming power varies it may affect the capacity of your selection.
06/12/2025Printed Date:
LAFB Bldg. 1030 Working Dog FacilityJob:
DOAS-1Mark:
VX-212-20I-1-D2Model:
Generated by: Trever.Tomes@damuth.comCAPS 4.47.1071 Page 5 of 24
Heating Performance
Heating Specifications
Type Capacity (kW) Full Load Amps (FLA) Capacity Control Performance
EAT (F) LAT (F)
Electric 65.6 182.1 Modulating (SCR) 22.0 83.0
Unit Details Open coil heating elements High grade Nickel-Chrome alloy coils SCR controller Unit can run compressors or electric heater independently. Simultaneous operation of heating and cooling cannot occur, and will be locked out. Unit MCA/MOCP will be sized for greater of the compressor or heater load.
Unit controller maximum allowable supply discharge air set point is 100F (37.8C)
06/12/2025Printed Date:
LAFB Bldg. 1030 Working Dog FacilityJob:
DOAS-1Mark:
VX-212-20I-1-D2Model:
Generated by: Trever.Tomes@damuth.comCAPS 4.47.1071 Page 6 of 24
Isometric Drawings
EXHAUST BLOWER ACCESS DOOR
*OPTIONAL ELECTRIC PREHEAT*
COMPRESSOR / ELECTRICAL
ACCESS DOOR
ACCESS DOOR
SUPPLY BLOWER
ACCESS DOOR
ELECTRICAL
ACCESS DOOR
SUPPLY DISCHARGE
OPTIONAL UNIT DISCONNECT
COIL ACCESS DOOR
FILTER ACCESS DOOR
ACCESS DOOR
*OPTIONAL INVERTER COMPRESSOR DRIVE
OUTDOOR AIR
WEATHERHOOD
RETURN AIR INLET
CONDENSATE DRAIN
Component Layout
PROVIDED WIRING
LOCATIONS
SERVICE OUTLET
ALTERNATE WIRING
LOCATIONS
Back Right Isometric
CLEARANCE
OUTDOOR AIR
WEATHERHOOD
EXHAUST AIR
WEATHERHOOD
Service Clearances
Front Left Isometric
06/12/2025Printed Date:
LAFB Bldg. 1030 Working Dog FacilityJob:
DOAS-1Mark:
VX-212-20I-1-D2Model:
Generated by: Trever.Tomes@damuth.comCAPS 4.47.1071 Page 7 of 24 C:\Users\ttomes\OneDrive\Documents\CAPS\Jobs\V&G - LAFB Bldg. 1030.valj
Ensure SA/RA Ductwork is Routed To Allow Access To Filter & Coil Access Doors
Overview Drawings
CONDENSING COIL
SUPPLY BLOWER OUTDOOR AIR DAMPER
COMPRESSORS
CONDENSATE DRAIN
HGRH COIL
DX COIL
SUPPLY FINAL FILTERS
CONTROL CENTER
EXHAUST BLOWER
OUTDOOR AIR
WEATHERHOOD
CONDENSING FANS
OUTDOOR AIR INLET
EXHAUST AIR DISCHARGE
SUPPLY AIR DISCHARGE RETURN AIR INLET
RECIRC DAMPER
EXHAUST AIR
WEATHERHOOD
1" NPT
Dimensional Overview
PROVIDED WIRING
LOCATIONS
Electrical Connections
PROVIDED WIRING
LOCATIONS ALTERNATE WIRING
LOCATION
ALTERNATE WIRING
LOCATION
POST HEATER
CONTROL CENTER
Dimensional Overview
Plan
Left End Elevation Right End
163.2
54.1
8.4
27.1
32.227.0
34.0
6.0
21.1 31.2
23.2
6.0
68.2
73.1
30.1
76.2
21.8
11.6
22.9
7.7
9.5
27.2
24.0
32.8 2.2
33.0
37.3
4.0
7.0
7.0 5.0
2.25 3.75
8.3
7.0
06/12/2025Printed Date:
LAFB Bldg. 1030 Working Dog FacilityJob:
DOAS-1Mark:
VX-212-20I-1-D2Model:
Generated by: Trever.Tomes@damuth.comCAPS 4.47.1071 Page 8 of 24
Unit Corner Weights 1,457 lb 1,121 lb
924 lb 711 lb
Note Estimated corner weights are shown looking down on unit and the outside air intake will be on the right. Weights are applied at the base of the unit. Images not drawn to scale.
06/12/2025Printed Date:
LAFB Bldg. 1030 Working Dog FacilityJob:
DOAS-1Mark:
VX-212-20I-1-D2Model:
Generated by: Trever.Tomes@damuth.comCAPS 4.47.1071 Page 9 of 24
Wiring Diagram
LEGEND
CAUTION
UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.
POWER MUST BE OFF WHILE SERVICING.
NOTES
USE COPPER CONDUCTORS ONLY
60° C FOR TERMINALS RATED LESS THAN 100 AMPS.
75° C FOR TERMINALS RATED 100 AMPS OR MORE.
FIELD CONTROL WIRING RESISTANCE SHOULD
NOT EXCEED 0.75 OHM.
FIELD WIRED
FACTORY SUPPLIED AND WIRED
WIRE COLOR CODE
Wiring Diagram Code:
BK BLACK BL BLUE BR BROWN
GY GRAY LT BL LIGHT BLUE O ORANGE
PK PINK PR PURPLE R RED
W WHITE Y YELLOW
Wiring Template: F31
CC# COMPRESSOR CONTACTOR
CF# CONDENSING FAN CONTACTOR
CH# COMPRESSOR SUMP HEATER
DB# POWER DISTRIBUTION BLOCK
DS DISCONNECT SWITCH
FU# FUSES
PM PHASE VOLTAGE MONITOR
R3 EXHAUST BLOWER VFD RELAY
R4 SUPPLY BLOWER VFD RELAY
R20 A2L SUPPLY FAN AND DAMPER RELAY
TR# TRANSFORMER
VFD VARIABLE FREQUENCY DRIVE
DOC NUMBER: 2839791 REV: 9
AIR MANAGEMENT SYSTEMS
GROUND
L2
L3
MAIN POWER
TO UNIT
L1
DS1
24V
TR1
CR
TO FU20 IN
FACTORY WIRED
DS3
SERVICE OUTLET
ENCLOSURE
DB1 DB3
NETWORK TX/RX
TO EVD CONTROLLER
TERMINALS +, -
TO ELECTRIC POST HEATER
(SEE ELECTRIC HEATER FOR
SPECIFIC WIRING DIAGRAM)
C1
R1
24V
TR2
R4
11 14
L2 L3
L1
S1
VFD-S1
A1SN AC
T1 T2
T3
WBKPKPR
SUPPLY FAN 1
MOTOR
L2 L3
L1 T1 T2
T3
C
OR
SUPPLY FAN 2
MOTOR
VFD-S2
A1 AC
WBK
C10
BK
BK
BK
BK
BK
BK
R20
11 12
S2
R4
21 24
R20
21 22
S2S1 SN
5S
TORS485
1 2 3
COMPRESSOR 2
CC2FU11
T3L3
T1L1
T2L2
FU10
COMPRESSOR 1
VFD-C
L1
L2
L3
U
V
W
BLACK
BLACK
BLACK
YELLOW
YELLOW
TO 61 AND 62 ON
MAIN UNIT
CONTROL BOARD
R E
D
B K
C1
C2
ADDRESS
1 2 3 4
ON
FU1
BR
Y
R3 11 14
L2 L3
L1
S1
VFD-E1
A1SN AC
T1 T2
T3
WRYBR
EXHAUST FAN 1
MOTOR
C
BK
BK
BK
CF3
CF2
T1 L1
T1 L1
T2 L2
T3 L3
T2 L2
T3 L3
L1 L2 L3
C E1
GND
10v
24v D1
2CBL-EC
RED
2CBL-EC
BLACK
CONDENSING
FAN 1
CONDENSING
FAN 2
CONDENSING
FAN 3
REDTO "Y3"
ON DDC
CONTROLLER
CH2 CC2
21 22H21H12
BLACK
RED
FU14321
PM
DB4
PM
4 5
TO U8
ON DDC
V13N2A1BK40X05X16HJ23D0030BF31
06/12/2025Printed Date:
LAFB Bldg. 1030 Working Dog FacilityJob:
DOAS-1Mark:
VX-212-20I-1-D2Model:
Generated by: Trever.Tomes@damuth.comCAPS 4.47.1071 Page 10 of 24
Wiring Diagram 2
LEGEND
CONTACTS
USER ALARM
NO8 C8
J15
NC8
PINK/H
CAUTION
UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.
POWER MUST BE OFF WHILE SERVICING.
NOTES
USE COPPER CONDUCTORS ONLY
60° C FOR TERMINALS RATED LESS THAN 100 AMPS.
75° C FOR TERMINALS RATED 100 AMPS OR MORE.
FIELD CONTROL WIRING RESISTANCE SHOULD
NOT EXCEED 0.75 OHM.
FIELD WIRED
FACTORY SUPPLIED AND WIRED
WIRE COLOR CODE
Wiring Diagram Code:
BK BLACK BL BLUE BR BROWN
GY GRAY LT BL LIGHT BLUE O ORANGE
PK PINK PR PURPLE R RED
W WHITE Y YELLOW
Wiring Template: G31
RED/H
RHV
R
HOT GAS REHEAT VALVE
C NO
PS4
RED
CCT COOLING COIL LEAVING TEMP
CC# COMPRESSOR CONTACTOR
CF# CONDENSING FAN CONTACTOR
CS CONDENSATE OVERFLOW SWITCH
D2 OUTDOOR AIR DAMPER
D3 RECIRC AIR DAMPER
DP1 DISCHARGE PRESSURE TRANSDUCER CKT A
DP2 DISCHARGE PRESSURE TRANSDUCER CKT B
HPS# HIGH PRESSURE SWITCH (MANUAL RESET)
OAT OUTDOOR AIR TEMP
PS4 SUPPLY FILTER PRESSURE SWITCH
R3 EXHAUST BLOWER VFD RELAY
R4 SUPPLY BLOWER VFD RELAY
R7 CKT A INTERLOCK RELAY
R10 COMPRESSOR 2 RELAY
R20 A2L SUPPLY FAN AND DAMPER RELAY
R21 A2L AIR TUNNEL SECTION ALARM RELAY
RHV MODULATING HOT GAS REHEAT VALVE
RH HEAT RELAY
SAT SUPPLY AIR TEMP
S1 REMOTE START INPUT
REMOTE START SWITCH OR EXTERNAL INTERLOCKS
REMOVE JUMPER IF FIELD DEVICES ARE INSTALLED
S6 BUILDING FIRE ALARM
NORMALLY CLOSED SWITCH OPENS ON ALARM.
INSTALL JUMPER FROM TERMINAL R TO 70 IF
NO FIRE DEVICES ARE INSTALLED.
VFD VARIABLE FREQUENCY DRIVE
BROWN RH
A2 A1
POST HEAT
TO "C" AND "1"
IN ELECTRIC
ORANGE
POSTHEATER
WHITE/H
4CBL-EH
BLUE
4CBL-EH
TERMINALS J6 BMS T+, T-
TO EXPANSION BOARD
GND T+
J26
T-
R BK
NOTE: 1
MODBUS COMMUNICATION WIRING. DAISY CHAIN TO ALL MODBUS
DEVICES. CONNECT ALL SHIELD GROUNDS TOGETHER.
DOC NUMBER: 2839791 REV: 9
BLACKBLUE
RED
R3 A2 A1
EXHAUST FAN
TO A1 A1
ORANGE/HBLUE/H
VFD-E
MC MA
AIR MANAGEMENT SYSTEMS
DRAIN
GND
U4
GND J3
J4 Y3
Y4
Y2
SAT
OAT
ID8
U3
U1
U2
GND
J2
ID5
ID6
ID7
B
LU
E R
ID2
ID3
ID4G J5
ID1
IDC1
CONTROLLER
DDC
J13
Y1
NO6
NO5
J12
GOG
J1
C4
NO2
NO1
C1 W H
ITE
C
U5
GND
U7
U8
J20
J6
C
C9
J16
VG VGO
J4
NO10
NO11
C12
NC12
NO13
IDC9
ID9
ID11
ID12
C13
NO14
ID10
J7
J17
J18
GND
U10
GND
U9
C14
NO15
C15
C16
NO16
J21
J22
ID13
IDC13
ID14
J8
PINK CF3
A2 A1
CONDENSING FAN 329
TB
CF3 O.L.
TB
BLACK
2CBL
RED
2CBL
LT BL CF2
A2 A1
CONDENSING FAN 227
TB
CF2 O.L.
TB
BLACK
2CBL
RED
2CBL
63RED TO "E1" ON
CONDENSING FAN 1
WHITE/HTO DDC J6
TERMINAL GND
ON VFD-E
+RED
4CBL-EH
BLACK
4CBL-EH
ELECTRIC POST _
CS
C NO
BLACK
2CBL-CS
RED
2CBL/RED-CS
RED
TO DDC J5
TERMINAL ID4
LT BLUE/H TO DDC J5
TERMINAL ID1
PINK/H
TO DDC J12
TERMINAL C1
LT BLUE/H
BLUE/H TO DDC J14
TERMINAL C7
TO DDC J21
TERMINAL C14
LT BLUE/H
PINK/H
BLUE/H TO DDC J4
TERMINAL VG
S1
YELLOW
PURPLE
SCAN FOR SUPPORT FAQ'S
Y5
Y6
J20
HEATER
ID15
IDC15 J19
NO18
NO17
BLACK/H
R4 A2 A1
SUPPLY FAN
NO3
TO DDC J4
TERMINAL VGO
WHITE/H
R C
BLUE/H
WHITE/H
ID17
IDC17
J20
LT BLUE/H
LT BLUE/H
MC MA
VFD-S1
BLUE/H
MC MA
VFD-S2
LT BL/H
ID16
ID18
NO4
NO9
WHITETO DDC J7
TERMINAL IDC9
PINK
R21
CCT
R7
61BR BR Y
YYELLOW
TO 4, 5 ON
VFD-C LOCATED IN
CONDENSING SECTION
ORANGE
R7
31 34
R7
R10 COMPRESSOR 2
A1A2
BROWN BROWN
DP1
WHITE
GREEN
BLACKTO J24
+5 Vref
C
GND
J25 BMS2
BACNET MSTP CONNECTION
FIELD WIRED
Tx/Rx
CONTROLLER BACNET MSTP CONNECTION
O
USER INTERFACE A2L LEAK ALARM CONNECTION
11 14
R21
MITIGATION
SEQUENCE ENABLED
12 11
R21
71 72 73
ALARM STATE SHOWN, SWITCHES ON UNIT POWER UP
S6
(FIRE)
Y BRPR
RED
BLUE/H
RED/H
J14
RC7
NO7 4
D2 OUTDOOR
D3
RECIRCULATING
DAMPER
DAMPERU6J6
R20
DAMPER ACTUATOR WIRING REF
3 CONDUCTOR
CABLE
(D2, D3) (3CBL-D)
3 - Y WHITE
1 - COM BLACK
2 - + RED
BLUE
BLACK
RED
BLUE BLACK
RED
3CBL-D
3CBL-D
3CBL-D
ACTUATOR
PIGTAIL
O
V13N2A1BK40X05X16HJ23D0030BG31
06/12/2025Printed Date:
LAFB Bldg. 1030 Working Dog FacilityJob:
DOAS-1Mark:
VX-212-20I-1-D2Model:
Generated by: Trever.Tomes@damuth.comCAPS 4.47.1071 Page 11 of 24
Wiring Diagram 3
CAUTION
UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.
POWER MUST BE OFF WHILE SERVICING.
NOTES
USE COPPER CONDUCTORS ONLY
60° C FOR TERMINALS RATED LESS THAN 100 AMPS.
75° C FOR TERMINALS RATED 100 AMPS OR MORE.
FIELD CONTROL WIRING RESISTANCE SHOULD
NOT EXCEED 0.75 OHM.
FIELD WIRED
FACTORY SUPPLIED AND WIRED
LEGEND
WIRE COLOR CODE
Wiring Diagram Code:
BK BLACK BL BLUE BR BROWN
GY GRAY LT BL LIGHT BLUE O ORANGE
PK PINK PR PURPLE R RED
W WHITE Y YELLOW
Wiring Template: L31
A2L# A2L REFRIGERANT LEAK SENSOR
CC# COMPRESSOR CONTACTOR
DT1 DISCHARGE LINE TEMP CKT A
EXV ELECTRONIC EXPANSION VALVE
R7 CKT A INTERLOCK RELAY
R10 COMPRESSOR 2 RELAY
R20 A2L SUPPLY FAN AND DAMPER RELAY
R21 A2L AIR TUNNEL SECTION ALARM RELAY
R22 BUILDING FIRE ALARM RELAY
RH HEAT RELAY
SP1 SUCTION PRESSURE TRANSDUCER CKT A
ST1 SUCTION LINE TEMP CKT A
VFD VARIABLE FREQUENCY DRIVE
DOC NUMBER: 2839791 REV: 9
AIR MANAGEMENT SYSTEMS
BOARD TERMINALS
TO EXPANSION
J6 BMS T+, T-
SP1
3V
GND
ST1
S1
EVD
CONTROLLER
BLACK
WHITE
G GO
Power Supply co nn ec tio n A
S3 Analog - D igital Input
EXVREF
S4
S2
WHITE
YELLOW
BROWN
GREEN
Tx /R x N et w or k
GND
R
BK
GREEN
BLACK
WHITE
Ex V
DT1 WHITE
WHITE
INVERTER DRIVE
TO COMPRESSOR
RS485
R
BK
HPS1
R7
A2 A1
YELLOWBLUE
A2L1
1 2 EVAP COIL SECTION
A2L SENSOR
A2L2
1 2 SUPPLY FAN SECTION
A2L SENSOR
CKT A INTERLOCK
R10
11 14
RH
21 22
BROWN CC2
A2 A1
PURPLE COMPRESSOR 2
A2L1
5 6
R22
11 12
A2L2
5 6 77 78 79
A2L MITIGATION
R21
31 34
R22 A2 A1
70 BUILDING FIRE ALARM RELAY
R1 C1
R20
A2 A1 (SUPPLY FAN/DAMPER)
A2L RELAY
R21
A2 A1 (AIR TUNNEL ALARMS)
A2L RELAY
B
LU
E
W H
ITE
JUMPER
RED BLACK
RED BLACK
WHITE GREEN WHITE GREEN PURPLE
ORANGE
RED
R22
21 24
PINK
LT. BLUE
DRAIN
V13N2A1BK40X05X16HJ23D0030BL31
06/12/2025Printed Date:
LAFB Bldg. 1030 Working Dog FacilityJob:
DOAS-1Mark:
VX-212-20I-1-D2Model:
Generated by: Trever.Tomes@damuth.comCAPS 4.47.1071 Page 12 of 24
Monitoring Points Wiring Diagram
CAUTION
UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.
POWER MUST BE OFF WHILE SERVICING.
NOTES
USE COPPER CONDUCTORS ONLY
60° C FOR TERMINALS RATED LESS THAN 100 AMPS.
75° C FOR TERMINALS RATED 100 AMPS OR MORE.
FIELD CONTROL WIRING RESISTANCE SHOULD
NOT EXCEED 0.75 OHM.
FIELD WIRED
FACTORY SUPPLIED AND WIRED
LEGEND
WIRE COLOR CODE
Wiring Diagram Code:
BK BLACK BL BLUE BR BROWN
GY GRAY LT BL LIGHT BLUE O ORANGE
PK PINK PR PURPLE R RED
W WHITE Y YELLOW
Wiring Template: Y07
DTH
EA
PS8
SA
NOTE: 1
MODBUS COMMUNICATION WIRING. DAISY CHAIN TO ALL MODBUS
DEVICES.
DOC NUMBER: ---- REV: ----
AIR MANAGEMENT SYSTEMS
U7
U8
GND
U6
U5
U4
GND
U3
U1
U2 c.pCOe
J11 NO4
J10
GOG
J1
NO3
C3/4/5
NO2
C1/2
NO1
GND
U10
U9
J2
EXPANSION
BOARD
NO6
C3/4/5
NO5
NC6
C6
J12
T+GND T-
J6 BMS
+5
GND
+V
J9
Address Ext Baud Prot Down
Up
(ON)
TO MAIN UNIT
DDC CONTROLLER
TERMINALS J26 T+, T-
TO EVD CONTROLLER
NETWORK TX/RX
DRAIN
R
ED
BK
TERMINALS +, -
R
ED
BL
AC
K
O
SA
RED+
WHITEC
BLUER
BLACK
O
EA
BLUE
BLACK
O
PS8
+ _R
WHITEC
B
LU
E
R
W H
ITE
C
3CBL-SA
3CBL-SA 3CBL-SA
3CBL-EA
RED
3CBL-EA3CBL-EA
EXPANSION BOARD
WIRING DIAGRAM
RETURN DUCT TEMPERATURE AND HUMIDITY SENSOR
EXHAUST AIRFLOW TRANSDUCER
SPACE PRESSURE SENSOR
SUPPLY AIRFLOW TRANSDUCER
TMP
DTH
O
TMP
VD0BB12XX000003BY07
06/12/2025Printed Date:
LAFB Bldg. 1030 Working Dog FacilityJob:
DOAS-1Mark:
VX-212-20I-1-D2Model:
Generated by: Trever.Tomes@damuth.comCAPS 4.47.1071 Page 13 of 24
Valent Network Interface v10.001 Modbus/BACnet Points List
Variable Description BACnet Object
ModBus Object
Read or Write Text or Unit of M Included
Active Inactive Space_Temp_Analog_Input Space Temperature AI-1 30002 R °F Supply_Temp_Analog_Input Supply Temperature AI-2 30004 R °F X
Outside_Air_Temp_Analog_Input Outside Air Temperature AI-3 30006 R °F X Mixed_Temp_Analog_Input Mixed Temperature AI-4 30008 R °F
Cold_Coil_1_Temp_Analog_Input Cold Coil 1 Temperature AI-5 30010 R °F X Return_Temp_Analog_Input Return Temperature AI-7 30014 R °F X
Exhaust_Temp_Analog_Input Exhaust Temperature AI-8 30016 R °F Space_RH_Analog_Input Space % Relative Humidity AI-9 30018 R %
Outside_RH_Analog_Input Outside % Relative Humidity AI-10 30020 R % Return_RH_Analog_Input Return % Relative Humidity AI-11 30022 R % X
Return_Duct_Static_Pressure_Analog_Input Return Duct Static Pressure AI-12 30024 R "wc Space_Static_Pressure_Analog_Input Space Static Pressure AI-13 30026 R "wc X
Supply_Duct_Static_Pressure_Analog_Input Supply Duct Static Pressure AI-14 30028 R "wc Space_CO2_1_Analog_Input Space 1 CO2 ppm AI-15 30030 R ppm Return_CO2_Analog_Input Return CO2 ppm AI-17 30034 R ppm
Circuit_A_Discharge_Temp_Analog_Input Circuit A Discharge Temperature AI-20 30040 R °F X Circuit_A_Suction_Temp_Analog_Input Circuit A Suction Temperature AI-21 30042 R °F X
Circuit_B_Discharge_Temp_Analog_Input Circuit B Discharge Temperature AI-22 30044 R °F X Circuit_B_Suction_Temp_Analog_Input Circuit B Suction Temperature AI-23 30046 R °F X
Circuit_A_Discharge_Pressure_Analog_Input Circuit A Discharge Pressure AI-28 30056 R psig X Circuit_A_Suction_Pressure_Analog_Input Circuit A Suction Pressure AI-29 30058 R psig X
Circuit_B_Discharge_Pressure_Analog_Input Circuit B Discharge Pressure AI-30 30060 R psig X Circuit_B_Suction_Pressure_Analog_Input Circuit B Suction Pressure AI-31 30062 R psig X
Aux_In_Customer_1 Customer defined auxiliary input AI-36 30072 R selectable Aux_In_Customer_2 Customer defined auxiliary input AI-37 30074 R selectable Aux_In_Customer_3 Customer defined auxiliary input AI-38 30076 R selectable Aux_In_Customer_4 Customer defined auxiliary input AI-39 30078 R selectable Aux_In_Customer_5 Customer defined auxiliary input AI-40 30080 R selectable Aux_In_Customer_6 Customer defined auxiliary input AI-41 30082 R selectable Aux_In_Customer_7 Customer defined auxiliary input AI-42 30084 R selectable Aux_In_Customer_8 Customer defined auxiliary input AI-43 30086 R selectable Aux_In_Customer_9 Customer defined auxiliary input AI-44 30088 R selectable Aux_In_Customer_10 Customer defined auxiliary input AI-45 30090 R selectable
Temperature_Setpoint Main Temperature Set point Supply, Space, or Return target temperature AV-1 40002 RW °F X
Temperature_Heat_Cool_Deadband Heat/Cool Spt Deadband when Room or Return control is active Clg Spt = Deadband /2 + Temp Spt Htg Spt = Deadband /2 - Temp Spt
AV-2 40004 RW Delta in °F X
Temperature_Setpoint_Unoccupied Main Temperature Set point Supply, Space, or Return target temperature AV-3 40006 RW °F
Temperature_Heat_Cool_Deadband_Unoccupied Heat/Cool Spt Deadband when Room or Return control is active Clg Spt = Deadband /2 + Temp Spt Htg Spt = Deadband /2 - Temp Spt
AV-4 40008 RW Delta in °F
Cooling_Coil_Setpoint_Min Cooling Coil Leaving Air Setpoint AV-5 40010 RW °F X Cooling_Coil_Setpoint_Max Maximum Coil Leaving Setpoint AV-6 40012 RW °F X
Dehumidification_Setpoint Dehumidification Setpoint %RH for Space or Return control AV-7 40014 RW %
Outside_Dewpoint_Setpoint Outside Dewpoint Dehumidification Trigger AV-8 40016 RW °F Indoor_Dewpoint_Setpoint Indoor Dewpoint Dehumidification Trigger AV-9 40018 RW °F
Unocc_Indoor_Dewpoint_Setpoint Unoccupied Indoor Dewpoint Dehumidification Trigger AV-10 40020 RW °F
Unoccupied_Dehumidification_Setpoint Unoccupied Dehumidification %RH Setpoint AV-11 40022 RW °F
Economizer_Temp_Enable_Setpoint Economizer Ambient Temp Enable Setpoint Allow Econ when OAT is less than Setpoint AV-12 40024 RW °F
Economizer_Enthalpy_Enable_Setpoint Economizer Enthalpy Enable Setpoint Allow Econ when OA Enthalpy is less than Setpoint AV-13 40026 RW btu/lb
Cooling_Lockout_Setpoint Cooling Ambient Lockout Setpoint AV-17 40034 RW °F X Heating_Lockout_Setpoint Heating Ambient Lockout Setpoint AV-18 40036 RW °F X Preheat_Lockout_Setpoint Preheat Ambient Lockout Setpoint AV-19 40038 RW °F
Economizer_Lockout_Setpoint Economizer Ambient Lockout Setpoint AV-20 40040 RW °F Return_Duct_Static_Pressure_Setpoint Return Duct Static Pressure Setpoint AV-21 40042 R "wc
Space_Static_Pressure_Setpoint Space Static Pressure Setpoint AV-22 40044 RW "wc X Supply_Duct_Static_Pressure_Setpoint Supply Duct Static Pressure Setpoint AV-23 40046 RW "wc
Space_CO2_Setpoint Space_CO2_Setpoint AV-24 40048 RW ppm Outside_Air_Damper_Minimum_Setpoint_Occ Outside Air Damper Minimum Setpoint AV-24 40050 RW %
Outside_RH_from_BMS Outside RH from BMS Used when source selection is set to BMS AV-26 40052 RW % X
Outside_Temp_from_BMS Outside Temp from BMS Used when source selection is set to BMS AV-27 40054 RW °F X
Return_RH_from_BMS Return RH from BMS Used when source selection is set to BMS AV-28 40056 RW % X
Return_Temp_from_BMS Return Temp from BMS Used when source selection is set to BMS AV-29 40058 RW °F X
06/12/2025Printed Date:
LAFB Bldg. 1030 Working Dog FacilityJob:
DOAS-1Mark:
VX-212-20I-1-D2Model:
Generated by: Trever.Tomes@damuth.comCAPS 4.47.1071 Page 14 of 24
Valent Network Interface v8 Modbus/BACnet Points List
BACnet Object
ModBus Object
Read or Write Text or Unit of M Included
Active Inactive
Space_1_CO2_from_BMS Space 1 CO2 from BMS Used when source selection is set to BMS AV-30 40060 RW ppm X
Return_CO2_from_BMS Return CO2 from BMS Used when source selection is set to BMS AV-32 40062 RW ppm X
Space_RH_from_BMS Space RH from BMS Used when source selection is set to BMS AV-33 40066 RW % X
Space_Static_from_BMS Space Static from BMS Used when source selection is set to BMS AV-34 40068 RW "wc X
Space_Temp_from_BMS Space Temp from BMS Used when source selection is set to BMS AV-35 40070 RW °F X
SF_Control_Signal_BMS BMS to control signal for supply fan speed AV-36 40072 RW % X EF_Control_Signal_BMS BMS to control signal for exhaust fan speed AV-37 40074 RW % X
OAD_Control_Signal_BMS Allows the BMS to control OAD position AV-38 40076 RW % Aux_BMS_Analog_Output_1 BMS Commanded auxilary analog output AV-39 40078 RW selectable X
Unit_Status_Mode Unit Status Mode - See Table AV-40 30092 R Real X Supply_Temperature_Calculated_Setpoint Active Supply Temperature Setpoint AV-41 30094 R °F X
Cooling_1_Ramp_Capacity Cooling Ramp 1 Status Value AV-42 30096 R % X Defrost_Ramp Defrost Ramp AV-44 30100 R %
Economizer_Ramp Economizer Ramp AV-45 30102 R % Head_Pressure_Control_Ramp_1_Ramp Head Pressure Control Ramp 1 AV-46 30104 R % X Head_Pressure_Control_Ramp_2_Ramp Head Pressure Control Ramp 2 AV-47 30106 R %
HP_Ramp_Capacity Heat Pump Heating Ramp AV-50 30112 R % Heating_Capacity Heating Ramp AV-51 30114 R % X
Case_Heat_Control_Ramp Case Heat Ramp AV-52 30116 R % Hot_Gas_Reheat_Ramp Hot Gas Reheat Ramp AV-53 30118 R %
Outside_Dewpoint Outside Dewpoint AV-54 30120 R °F Outside_Enthalpy Outside Enthalpy AV-55 30122 R btu/lb Return_Dewpoint Return Dewpoint AV-56 30124 R °F X Return_Enthalpy Return Enthalpy AV-57 30126 R btu/lb X Space_Dewpoint Space Dewpoint AV-58 30128 R °F Space_Enthalpy Space Enthalpy AV-59 30130 R btu/lb
Circuit_A_Superheat Circuit A Superheat AV-60 30132 R °F X Circuit_B_Superheat Circuit B Superheat AV-61 30134 R °F X
Total_Exhaust_Fan_CFM_BMS Total Exhaust Fan CFM AV-64 30140 R CFM X Total_Supply_Fan_CFM_BMS Total Supply Fan CFM AV-65 30142 R CFM X
OAD_CFM_BMS OAD CFM AV-66 30144 R CFM
Active_Temperature_Setpoint Active_Temperature_Setpoint AV-67 30146 R °F X
Chilled_Water_1_Valve_Analog_Output Chilled Water 1 Valve Analog Output AV-68 30148 R % Electric_Heater_1_Analog_Output Electric Heater 1 Analog Output AV-70 30152 R % X Energy_Recovery_Analog_Output Energy Recovery Analog Output AV-72 30156 R %
Exhaust_Fan_Speed_Analog_Output Exhaust Fan Speed Analog Output AV-73 30158 R % X Hot_Water_Valve_1_Analog_Output Hot Water Valve 1 Analog Output AV-74 30160 R %
Mod_Gas_Furnace_1_Analog_Output Mod Gas Furnace 1 Analog Output AV-76 30164 R % Outside_Air_Damper_Analog_Output Outside Air Damper Analog Output AV-78 30168 R % Supply_Fan_Speed_Analog_Output Supply Fan Speed Analog Output AV-79 30170 R % X
Modulating_Compressor_Analog_Output_BMS First Modulating Compressor Analog Output - BMS AV-80 30172 R % X Circuit_A_Sat_Discharge_Temperature Circuit A Saturated Discharge Temperature AV-82 30176 R °F X Circuit_B_Sat_Discharge_Temperature Circuit B Saturated Discharge Temperature AV-83 30178 R °F X
Circuit_A_Sat_Suction_Temperature Circuit A Saturated Suciton Temperature AV-86 30184 R °F X Circuit_B_Sat_Suction_Temperature Circuit B Saturated Suciton Temperature AV-87 30186 R °F X
Coil_Temperature_Calculated_Setpoint Calculated Coil Leaving Set point AV-90 30192 R °F X Unoccupied_Cooling_Setpoint Active Cooling Setpoint - Unoccupied AV-91 30194 R °F Unoccupied_Heating_Setpoint Active Heating Setpoint - Unoccupied AV-92 30196 R °F
Temperature_Reset_Mode Occupied Reset Type Setpoint 1-No Reset(Supply Temp Control) 2-Space 3-Return 4-Outside IV-1 40080 RW Integer X
Temperature_Reset_Mode_Unoccupied Unoccupied Reset Type Setpoint 1-No Reset(Supply Temp Control) 2-Space 3-Return 4-Outside IV-2 40082 RW Integer
Active_Temperature_Reset_Mode Active Occupied Reset Type Setpoint 1-No
Reset(Supply Temp Control) 2-Space 3-Return 4- Outside
IV-3 30198 R Integer X
Active_Temperature_Reset_Mode_Unocc Active Unoccupied Reset Type Setpoint 1-No
Reset(Supply Temp Control) 2-Space 3-Return 4- Outside
IV-4 30200 R Integer
LatestAlm Most recent alarm - See Alarm Table IV-5 30202 R Integer X Device_Enable_DO_Word Device Enable DO Word - See Table IV-6 30206 R Bit Pack X
Ref_Ckt_PressTemp_Alarm_Word Refrigeration Circuit Word - See Table IV-7 30210 R Bit Pack X Device_Offline_Word Device Offline Word - See Table IV-8 30214 R Bit Pack X Device_Alarm_Word Device Alarm Word - See Table IV-9 30218 R Bit Pack X
System_Word System Word - See Table IV-10 30222 R Bit Pack X Unit_Status_Word Unit Status Word - See Table IV-11 30226 R Bit Pack X
Exhaust_Fan_1_Status_Digital_Input Exhaust Fan Status BI-1 10009 R Active Inactive X
Supply_Fan_1_Status_Digital_Input Supply Fan Status B-2 10010 R Active Inactive X
06/12/2025Printed Date:
LAFB Bldg. 1030 Working Dog FacilityJob:
DOAS-1Mark:
VX-212-20I-1-D2Model:
Generated by: Trever.Tomes@damuth.comCAPS 4.47.1071 Page 15 of 24
Valent Network Interface v8 Modbus/BACnet Points List
BACnet Object
ModBus Object
Read or Write Text or Unit of M Included
Active Inactive
BMS_Watchdog BMS Watchdog command Used to determine BMS comm status Must heartbeat within the watch dog timeout delay to detect comm status BV-1 2 RW Active Inactive X
System_Enable Master system enable/disable point BV-2 3 RW Enable Disable X
BMS_Occupancy_Command Occupancy Command BV-3 4 RW Unoccupied Occupied X
Reset_All_Alarms Alarm Reset Command BV-4 5 RW Reset Normal X
Exhaust_Only_Mode_BMS_Cmd Emergancy Exhaust Mode Command BV-5 6 RW Enable Disable Pressurization_Only_Mode_BMS_Cmd Emergancy Pressurization Mode Command BV-6 7 RW Enable Disable
Outside_RH_Source_BMS Outside RH Source Selection BV-7 8 RW BMS Local X
Outside_Temp_Source_BMS Outside Temp Source Selection BV-8 9 RW BMS Local X
Return_RH_Source_BMS Return RH Source Selection BV-9 10 RW BMS Local X
Return_Temp_Source_BMS Return Temp Source Selection BV-10 11 RW BMS Local X
Space_1_CO2_Source_BMS Space 1 CO2 Source Selection BV-11 12 RW BMS Local X
Space_2_CO2_Source_BMS Space 2 CO2 Source Selection BV-12 13 RW BMS Local X
Return_CO2_Source_BMS Return CO2 Source Selection BV-13 14 RW BMS Local X
Space_RH_Source_BMS Space RH Source Selection BV-14 15 RW BMS Local X
Space_Static_Source_BMS Space Static Source Selection BV-15 16 RW BMS Local X
Space_Temp_Source_BMS Space Temp Source Selection BV-16 17 RW BMS Local X
SF_Control_Source_BMS Allows the BMS to control supply fan speed BV-17 18 RW BMS Local X
EF_Control_Source_BMS Allows the BMS to control exhaust fan speed BV-18 19 RW BMS Local X
OAD_Control_Source_BMS Allows the BMS to control OAD position BV-19 20 RW BMS Local Aux_BMS_Digital_Output_1 BMS Commanded auxilary digital output BV-20 21 RW Active Inactive Aux_BMS_Digital_Output_2 BMS Commanded auxilary digital output BV-21 22 RW Active Inactive
Occupied Occupancy BV-22 10002 R Occupied Unoccupied X
Global_Alarm General alarm point Optionally set to indicate any alarm is active, or a shutdown alarm is active BV-23 10003 R Alarm Normal X
BMS_Watchdog_Active Status of the BMS watchdog heartbeat BV-24 10004 R Active Inactive X
OAD_Feedback_Error_Not_Economizing.Active Feedback indicates OAD is not opening during economizer BV-25 10005 R Alarm Normal
OAD_Feedback_Error_Economizing.Active Feedback indicates OAD is open BV-26 10006 R Alarm Normal OAD_Feedback_Error_OAD_Not_Modulating.Active Feedback indicates the OAD is not modulating BV-27 10007 R Alarm Normal
OAD_Feedback_Error_Excess_OA.Active Feedback indicates the OAD is not closing BV-28 10008 R Alarm Normal Supply_Fan_1_Alarm.Active Supply Fan Alarm Active BV-29 10011 R Alarm Normal X
Exhaust_Fan_1_Alarm.Active Exhaust Fan Alarm Active BV-30 10012 R Alarm Normal X
Drain_Pan_Alarm.Active Condensate Drain Pan Alarm Active BV-31 10013 R Alarm Normal X
Fire_Safety_Shutdown_Alarm.Active Fire Safety Shutdown Alarm Active BV-32 10014 R Alarm Normal X
Refrigerant_Leak_Compressor_Alarm.Active Refrigerant Leak Compressor Alarm Active BV-33 10015 R Alarm Normal X
Refrigerant_Leak_Airstream_Alarm.Active Refrigerant Leak Airstream Alarm Active BV-34 10015 R Alarm Normal X
06/12/2025Printed Date:
LAFB Bldg. 1030 Working Dog FacilityJob:
DOAS-1Mark:
VX-212-20I-1-D2Model:
Generated by: Trever.Tomes@damuth.comCAPS 4.47.1071 Page 16 of 24
System_Word (IV-11/AV-102 & AV-103) Unit Status Word Table (IV-11/AV-104 & AV-105)
IV-10 Bit
AV-102
Bit Bit Description IV-11 Bit
AV-104
Bit Bit Description 0 0 Heat Wheel Enable 0 0 Standby 1 1 Preheat Enable 1 1 Occupied Start 2 2 Reversing Valve (Cooling (0)/Heating(1)) 2 2 Unoccupied Start 3 3 3 3 Opening Dampers 4 4 OA Damper End Switch Alarm 4 4 Dampers Open 5 5 EA Damper End Switch Alarm 5 5 Fan Start Delay 6 6 Supply Temp Low Limit Alarm 6 6 Exhaust Fan On 7 7 Supply Temp High Limit Alarm 7 7 Supply Fan On 8 8 Supply High Duct Static Alarm 8 8 System On 9 9 Supply Fan 1 Alarm 9 9 Soft Shutdown 10 10 Exhaust Fan 1 Alarm 10 10 System Disabled 11 11 Drain Pan Alarm 11 11 Remote Off 12 12 Freeze Stat Alarm 12 12 System Shutdown Alarm 13 13 Filter Alarm 13 13 Supply Fan Only 14 14 Space High Static Alarm 14 14 Exhaust Fan Only 15 15 Return Low Static Alarm 15 15 Purge Mode (Supply and Exhaust Only)
IV-10 Bit
AV-103
Bit Bit Description IV-11 Bit
AV-105
Bit Bit Description 16 16 Shutdown Input Alarm 16 16 Case Heat Active 17 17 Energy Recovery Wheel High Diff Pressure 17 17 Fans Only 18 18 Energy Recovery Wheel Rotation Alarm 18 18 Economizing 19 19 19 19 Energy Recovery Active 20 20 Heat Pump Heating Lock Out Alarm 20 20 Cooling 21 21 BMS Frequent Writes - Reduce Num of Writes 21 21 Heating 22 22 BMS Offline Alarm 22 22 Dehumidifying 23 23 23 23 Hot Gas Reheat Active 24 24 24 24 HGRH Purging 25 25 25 25 Dehum w/Heat 26 26 26 26 Energy Recovery Defrost Active 27 27 27 27 Heat Pump Defrost Active 28 28 Heat-Cool Only - Dehumidification Request Active 28 28 Morning Warm Up/Cool Down Active 29 29 Heat-Cool Only - Heating Request Active 29 29 Winter Ramp Active 30 30 Heat-Cool Only - Coil Setpoint Alarm Active 30 30 31 31 Heat-Cool Only - Supply Setpoint Alarm Active 31 31 Overrides Active
Device Enable DO Word Table (IV-6/AV-94 & AV-95) Ref Ckt Press temp Alarm Word Table (IV-7/AV-96 & AV-97) IV-6 Bit AV-94 Bit Bit Description IV-7 Bit AV-96 Bit Bit Description
0 0 Compressor 1 Start 0 0 Circuit A Discharge Pressure Sensor Alarm 1 1 Compressor 2 Start 1 1 Circuit A Discharge Temp Sensor Alarm 2 2 Compressor 3 Start 2 2 Circuit A Suction Pressure Sensor Alarm 3 3 Compressor 4 Start 3 3 Circuit A Suction Temp Sensor Alarm 4 4 4 4 Circuit B Discharge Pressure Sensor Alarm 5 5 5 5 Circuit B Discharge Temp Sensor Alarm 6 6 6 6 Circuit B Suction Pressure Sensor Alarm 7 7 7 7 Circuit B Suction Temp Sensor Alarm 8 8 Condenser Fan Ramp 1 Stage 1 Start 8 8 Circuit A High Pressure Switch Alarm 9 9 Condenser Fan Ramp 1 Stage 2 Start 9 9 Circuit A Low Refrigerant Pressure Alarm 10 10 Condenser Fan Ramp 1 Stage 3 Start 10 10 Circuit B High Pressure Switch Alarm 11 11 11 11 Circuit B Low Refrigerant Pressure Alarm 12 12 Condenser Fan Ramp 2 Stage 1 Start 12 12 Circuit A High Sat Discharge Temp Alarm 13 13 Condenser Fan Ramp 2 Stage 2 Start 13 13 Circuit B High Sat Discharge Temp Alarm 14 14 Condenser Fan Ramp 2 Stage 3 Start 14 14 15 15 15 15
IV-6 Bit AV-95 Bit Bit Description IV-7 Bit AV-97 Bit Bit Description 16 16 Furnace 1 Start (External Furnace Controller Only) 16 16 17 17 Furnace 2 Start (External Furnace Controller Only) 17 17 18 18 18 18 19 19 19 19 20 20 Supply Fan Start 20 20 21 21 Exhaust Fan Start 21 21 22 22 22 22 23 23 23 23 24 24 24 24 25 25 25 25 26 26 26 26 27 27 27 27 28 28 28 28 29 29 29 29 30 30 30 30 31 31 31 31
06/12/2025Printed Date:
LAFB Bldg. 1030 Working Dog FacilityJob:
DOAS-1Mark:
VX-212-20I-1-D2Model:
Generated by: Trever.Tomes@damuth.comCAPS 4.47.1071 Page 17 of 24
Device Offline Word Table (IV-8/AV-98 & AV-99) Device Alarm Word Table (IV-9/AV-100 & AV-101)
IV-8 Bit AV-98 Bit Bit Description IV-9 Bit
AV-100
Bit Bit Description 0 0 Cold Coil Temperature Sensor Alarm 0 0 Space TStat 1 Offline 1 1 1 1 Space TStat 2 Offline 2 2 Mixed Temperature Sensor Alarm 2 2 Space TStat 3 Offline 3 3 Supply Duct Static Pressure Sensor Alarm 3 3 Space TStat 4 Offline 4 4 Supply Fan AFMS Alarm 4 4 VFD Offline Supply Fan 5 5 Supply Air Temp Sensor Alarm 5 5 VFD Offline Exhaust Fan 6 6 Exhaust Fan AFMS Alarm 6 6 7 7 Exhaust Temperature Sensor Alarm 7 7 8 8 Outside Air Temp Sensor Alarm 8 8 Expansion Board 1 Alarm 9 9 Outside RH Sensor Alarm 9 9 Expansion Board 2 Alarm 10 10 OAD AMD Alarm 10 10 Expansion Board 3 Alarm 11 11 Greentrol OAD AFMS Alarm 11 11 Expansion Board 4 Alarm 12 12 Return CO2 Sensor Alarm 12 12 13 13 Return Duct Static Pressure Sensor Alarm 13 13 14 14 Return Temperature Sensor Alarm 14 14 15 15 Return RH Sensor Alarm 15 15
IV-8 Bit AV-99 Bit Bit Description IV-9 Bit
AV-101
Bit Bit Description 16 16 Space CO2 Sensor Alarm 16 16 17 17 Space RH Sensor Alarm 17 17 18 18 Space Static Pressure Sensor Alarm 18 18 19 19 Space Temperature Sensor Alarm 19 19 20 20 IG Furnace Alarm 20 20 21 21 21 21 22 22 Inverter Scroll 1 Alarm 22 22 23 23 23 23 24 24 EVD Valve A Alarm 24 24 25 25 25 25 26 26 SF VFD Alarm 26 26 27 27 EF VFD Alarm 27 27 Primary Unit Offline Alarm 28 28 28 28 Secondary Unit 1 Offline Alarm 29 29 29 29 Secondary Unit 2 Offline Alarm 30 30 30 30 Secondary Unit 3 Offline Alarm 31 31 31 31 Secondary Unit 4 Offline Alarm
UNIT STATUS MODE (AV-40)
0 Standby 20 Economizing 1 Unoccupied Start 21 Cooling 2 Occupied Start 22 Heating 3 Opening Dampers 23 Dehumidifying 5 Dampers Open 24 6 Fan Start Delay 25 HGRH Purging 7 Exhaust Fan Start 26 Energy Recovery Defrost Active 8 Supply Fan Start 27 A2L Refrigerant Leak Alarm 9 Startup Delay 28 A2L Refrigerant Leak Alarm Fan Only Mode 10 System On 29 Dehumifying w/Heat 11 Soft Shutdown 30 Overrides 12 System Disabled 31 Expansion Offline 13 Remote Off 32 14 System Shutdown Alarm 33 Energy Recovery Active 15 Pressurization Only 34 Hot Gas Reheat Active 16 Exhaust Only 35 Morning Sequence Active 17 Fans Only Purge 36 Heat Pump Defrost 18 Case Heat Active 37 Winter Ramp Active 19 Fans Only
06/12/2025Printed Date:
LAFB Bldg. 1030 Working Dog FacilityJob:
DOAS-1Mark:
VX-212-20I-1-D2Model:
Generated by: Trever.Tomes@damuth.comCAPS 4.47.1071 Page 18 of 24
Alarm Table (IV-5/AV-93) 0 Supply Fan 1 Run - Status Not Proven 64 Heat Wheel Rotation - Not Detected 122 First Inverter Alarm - Serious 1 Freeze Protection - Thermostat Tripped 65 Secondary Unit Offline - Unit 1 123 First Inverter Alarm - Irreversible 2 High Supply Duct - Static Pressure 66 Secondary Unit Offline - Unit 2 124 First Inverter PEC - Invalid Data Set 3 Low Return Duct - Static Pressure 67 Secondary Unit Offline - Unit 3 125 First Inverter STO - Safe Torque Off Open 4 Outside Air Temp - Sensor Value Not Valid 68 Secondary Unit Offline - Unit 4 126 First Inverter Offline - Modbus Comms Lost 5 Supply Air Temperature - Sensor Value Not Valid 69 Primary Unit Offline - 133 Space Thermostat 1 - Sensor Offline 6 Cold Coil 1 Temp - Sensor Value Not Valid 71 Multi Devices per Ch - Contact Tech Support 134 Space Thermostat 2 - Sensor Offline 7 Cold Coil 2 Temp - Sensor Value Not Valid 74 Shutdown Contact - In Alarm Position 135 Space Thermostat 3 - Sensor Offline 9 Exhaust Air Temp - Sensor Value Not Valid 75 Comp Maint Alarm - Run Hours Spt Reached 136 Space Thermostat 4 - Sensor Offline
10 Mixed Air Temperature - Sensor Value Not Valid 76 Supply Air Temperature - High Limit Shutdown 137 IG Furnace 1 - No flame after 3 tries 11 Return Air Temperature - Sensor Value Not Valid 77 Space High Static Pres - Shutdown 138 IG Furnace 1 - Large - No flame after 3 tries 12 Space Temperature - Sensor Value Not Valid 78 Internal Board Temp - Exceeds -40F or 158F 139 IG Furnace 1 Combust - Fan High Pressure Sw 13 Return Air RH - Sensor Value Not Valid 79 BMS Offline - Watchdog is FALSE 140 IG Furnace 1 Ignition - Controller Alarm 14 Space RH - Sensor Value Not Valid 78 Internal Board Temp - Exceeds -40F or 158F 138 IG Furnace 1 Large - no flame after 3 tries 15 Outside RH - Sensor Value Not Valid 80 Clg Coil Setpt Input - Value is not valid 141 IG Furnace 1 Pressure - Switch Fault Alarm 16 Low Pressure Switch - Circuit A 81 Sup Air Setpt Input - Value is not valid 142 IG Furnace 1 Combust - Fan Proving Alarm 17 Low Pressure Switch - Circuit B 82 BACnet License - Not Installed 143 IG Furnace 1 - Max Retries 20 High Pressure Switch - Circuit A 83 Low Suction SH ExV A - EVD 1 Alarm 144 IG Furnace 1 - High Limit Trip 21 High Pressure Switch - Circuit B 85 LOP A EVD 1 - Low Operating Pressure 145 IG Furnace - pCOe 1 Offline 24 Damper End Switch Fail - Dampers are not open 87 MOP A EVD 1 - Max Operating Pressure 146 IG Furnace 1 IC Fault - Check Furnace Wiring 25 Exhaust Fan 1 Run - Status Not Proven 89 EEV A EVD 1 - Motor Alarm 147 IG Furnace 2 - No flame after 3 tries 26 Filters are Dirty - Replace Filters 91 LowSuct A EVD 1 - Refrigerant Temp 148 IG Furnace 2 - Large - No flame after 3 tries 27 Cond Drain Pan Full - Check Drain 93 High Condensing Temp - EVD 1 149 IG Furnace 2 Combust - Fan High Pressure Sw 28 Exp Board 1 Status - Board is Offline 94 Sens S1 EVD 1 - Sensor Value Not Valid 150 IG Furnace 2 Ignition - Controller Alarm 29 Exp Board 2 Status - Board is Offline 95 Sens S2 EVD 1 - Sensor Value Not Valid 151 IG Furnace 2 Pressure - Switch Fault Alarm 30 Exp Board 3 Status - Board is Offline 96 Sens S3 EVD 1 - Sensor Value Not Valid 152 IG Furnace 2 Combust - Fan Proving Alarm 31 Exp Board 4 Status - Board is Offline 97 Sens S4 EVD 1 - Sensor Value Not Valid 153 IG Furnace 2 - Max Retries 32 BMS Frequent Writes - Reduce Num of Writes 98 EVD 1 EEPROM Damaged - Call Tech Support 154 IG Furnace 2 - High Limit Trip 33 Space 1 CO2 - Sensor Value Not Valid 99 Incomplete Closing - EVD 1 155 IG Furnace - pCOe 2 Offline 34 Space Static Pressure - Sensor Value Not Valid 100 Emergency Closing - EVD 1 156 IG Furnace 2 IC fault - Check Furnace Wiring 35 Supply Duct Stat Press - Sensor Value Not Valid 101 EVD 1 Battery 157 Outside Air Greentrol - Offline or Flow Error 36 Return Duct Stat Press - Sensor Value Not Valid 102 FW Incompatibility - EVD 1 158 Exhaust Air Greentrol - Offline or Flow Error 37 Sup Fan AFMS - Sensor Value Not Valid 103 EVD 1 Config Error 159 Supply Air Greentrol - Offline or Flow Error 38 Exh Fan 1 AFMS - Sensor Value Not Valid 104 EVD 1 Comm - EVD 1 is Offline 169 ER Wheel High - Differential Pressure 39 Outside Damper AFMS - Sensor Value Not Valid 105 High Discharge Temp - First Inv Envelope 170 OA Damper Fault - Not Econ and should be 40 Space Setpt Adj Slider - Sensor Value Not Valid 106 Low Discharge Pressure - First Inv Envelope 171 OA Damper Fault - Econ and shouldn't be 41 Space 2 CO2 - Sensor Value Not Valid 107 High Suction Pressure - First Inv Envelope 172 OAD Fault - Damper not Modulating 42 Return CO2 - Sensor Value Not Valid 108 Low Suction Pressure - First Inv Envelope 173 OAD Fault - Excess Outdoor Air 43 Discharge Press Ckt A - Sensor Value Not Valid 109 High Current - First Inv Envelope 174 IG Furnace 1 - Combustion Fan Alarm 44 Discharge Press Ckt B - Sensor Value Not Valid 110 High Pressure Ratio - First Inv Envelope 175 IG Furnace 2 - Combustion Fan Alarm 47 Suction Press Ckt A - Sensor Value Not Valid 111 Low Pressure Ratio - First Inv Envelope 176 Supply Fan - VFD Offline 48 Suction Press Ckt B - Sensor Value Not Valid 112 Low Delta P - First Inv Envelope 177 Exhasut Fan - VFD Offline 51 Discharge Temp Ckt A - Sensor Value Not Valid 113 High Discharge Press - First Inv Envelope 180 Embedded EVD Error 52 Discharge Temp Ckt B - Sensor Value Not Valid 114 Compressor Staging - Order Skipped 181 SF VFD Alarm - Check VFD 55 Suction Temp Ckt A - Sensor Value Not Valid 115 Heat Pump Heating - Locked Out 182 EF VFD Alarm - Check VFD 56 Suction Temp Ckt B - Sensor Value Not Valid 116 EVD 1 Error - Unexpected Position 186 Compressor Refrig Leak - Furnace Locked Out 59 Ckt A High Saturated - Discharge Temperature 117 High SDT Lockout - Circuit A 187 Airstream Refrig Leak - SF Mitigation Sequence 60 Ckt B High Saturated - Discharge Temperature 118 High SDT Lockout - Circuit B 188 Fire Shutdown Alarm - Building Fire Alarm 63 Supply Air Temperature - Low Limit Shutdown 121 First Inverter Alarm - Resettable 189 EA Damper End Switch - Damper is not open
06/12/2025Printed Date:
LAFB Bldg. 1030 Working Dog FacilityJob:
DOAS-1Mark:
VX-212-20I-1-D2Model:
Generated by: Trever.Tomes@damuth.comCAPS 4.47.1071 Page 19 of 24
VX-212
Factory Controller Sequence of Operation
FACTORY CONTROLLER: Controller shall be provided with required sensors and programming for rooftop unit.
Controller shall be factory programmed, mounted and tested. Controller shall have a LCD readout for changing set points and monitoring unit operation.
UNIT START COMMAND (Unit will be enabled to start once a jumper is placed between R to G):
• Factory mounted and wired outdoor air and recirculated air damper actuators are powered.
• Exhaust fan starts after a (adj.) delay.
• Supply fan starts after a (adj.) delay.
• Tempering options to function as described below.
UNIT STOP COMMAND (OR DE-ENERGIZED):
• Supply fan, exhaust fan and tempering options de-energized.
• Outdoor air damper actuator is spring return close, and the recirculated air damper actuator is spring open.
OCCUPIED/UNOCCUPIED MODES: Shall be based on a 7-day time clock internal to the controller. The schedule shall be set by the end user. When a user initiates an override input, the controller will switch from unoccupied to occupied mode. The controller will return to the scheduled occupied/unoccupied mode after the override time has expired. If internal time clock is disabled, a remote contact or a BMS can control the occupied/unoccupied mode.
Occupied Mode:
• Damper control per below.
• Exhaust fan ON.
• Supply fan ON.
• Heating per below.
• Cooling per below.
MORNING WARMUP/COOL DOWN: Prior to occupancy, the unit will run using the warmup or cool down sequence until the occupied set point is achieved. The heating or cooling mode must not be locked out and the space temperature is below or above set point by the unoccupied hysteresis (adj.) (This Sequence must be field configured.)
SUPPLY BLOWER SEQUENCE: The supply blower is provided with a factory mounted variable frequency drive. The supply blower speed will be controlled with the following sequence. Minimum supply fan turndown is 50% of the design maximum operation.
Constant Volume-Adj. Setpoint: The supply blower will operate at a constant speed set point (adj.)
during operation.
EXHAUST BLOWER SEQUENCE: The exhaust blower will operate at a constant speed set point (adj.) during operation.
Space Static Pressure by Factory: The exhaust blower is modulated based upon the signal from a building pressure sensor. The controller will modulate the exhaust fan based upon a comparison of the building static pressure set point (adj.) and the building static pressure level reported from the sensor.
COOLING SEQUENCE: The cooling is controlled to maintain the desired return air temperature set point. The mechanical cooling will be locked out when the outside air is < 55 F (adj.).
UNI
T
ST
OP
CO
MM
AN
D
(OR
DE-
EN
ER
GIZ
ED)
06/12/2025Printed Date:
LAFB Bldg. 1030 Working Dog FacilityJob:
DOAS-1Mark:
VX-212-20I-1-D2Model:
Generated by: Trever.Tomes@damuth.comCAPS 4.47.1071 Page 20 of 24
Packaged DX Cooling (Inverter Scroll): The controller will provide a modulating signal for cooling. From 0-50%, the inverter scroll will be controlled to maintain discharge temperature. From 50-100% the second stage will be on in combination with the inverter scroll compressor to maintain the discharge temperature.
The electronic expansion valve will modulate to maintain 8F of superheat.
Modulating Hot Gas Reheat Sequence: During dehumidification the modulating HGRH is controlled to maintain the supply temperature set point.
Modulating Head Pressure Control: Lead condenser fan will have an EC motor and will modulate to maintain a head pressure set point.
DEHUMIDIFICATION CONTROL SEQUENCE: Dehumidification to be enabled and once enabled the cooling coil will be controlled based on the following sequences. The mechanical cooling will be locked out when the outside air is < 55 F (adj.)
Cold Coil Set Point Control: When in dehumidification mode the controller will control the cooling to maintain a constant cold coil set point. The active set point will be set to local control (55 F, adj.) from the factory and can be field adjusted locally or by the BMS.
Dehumidification Enable: Dehumidification mode to be enabled based on the return air humidity condition.
When the return air humidity is greater than the desired set point (adj.), the unit will operate in dehumidification mode.
REHEAT SEQUENCE: While the unit is in dehumidification mode the outdoor air will be reheated via Modulating Hot Gas Reheat for space neutral applications.
Modulating Hot Gas Reheat: The controller will modulate the hot gas reheat reheat valve with a 0-10 V signal to maintain the supply temperature set point (adj.).
HEATING SEQUENCE: The heating is controlled to maintain the return air temperature set point. The heating will be locked out when the outside air is > 80 F (adj.).
Electric Heater: The controller will modulate the SCR electric heater to maintain the return air temperature set point (adj.).
TEMPERATURE CONTROL SEQUENCE: The unit will maintain the supply air discharge setpoint per the following. Adjustable locally or by BMS.
Room Reset: The controller will reset the supply air temperature set point to maintain the room temperature set point (adj.).
Return Set Point Control: The controller will adjust the supply air leaving air temperature set point between the minimum (adj.) and the maximum (adj.) limits, to satisfy the desired return air temperature set point. Adjustable locally or by BMS.
BUILDING FREEZE PROTECTION: If the supply air temperature drops below 35 F (adj.) for 300s (adj.), the controller will de-energize the unit and activate the alarm output.
UNIT LEAK DETECTION AND MITIGATION: The unit will be equipped with refrigerant leak detection…