Atch 2 - Drawings_MUHJ 24-4024 Repair MWD Kennel Interior Facility 1030.pdf
PDF 16 MB Posted
- Solicitation number
- FA480026B0001
About this file
These are architectural and engineering design documents for the Repair of Military Working Dog Kennels Facility 1030 at Joint Base Langley-Eustis in Hampton, Virginia. The comprehensive set of drawings covers demolition, new construction, architectural, structural, mechanical, electrical, and plumbing plans for a facility renovation. The project involves comprehensive upgrades including new floor plans, roof modifications, structural reinforcements, HVAC systems, electrical systems, plumbing infrastructure, and specialized kennel design. Key design firms involved include Vansant & Gusler, Inc. as consulting engineers, with Lynch Mykins as the primary design firm, and IMEG Consultants Corp. providing additional engineering services. The project number is MUHJ 24-4024, with a planned completion date of July 22, 2025, and is being executed for the Department of the Air Force, Air Combat Command at Langley AFB.
The facility redesign includes detailed plans for multiple kennel spaces, offices, support rooms, and associated infrastructure. Specific technical elements include new electrical panelboards, dedicated outside air systems, updated lighting fixtures, mechanical ventilation, domestic water and sanitary waste systems, and structural modifications. The design emphasizes functional improvements for military working dog facilities, with careful attention to spatial layout, environmental controls, and building systems integration. Drawings provide comprehensive technical details across multiple disciplines, including demolition plans, new construction layouts, structural reinforcements, mechanical and electrical system configurations, and specialized kennel design elements.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A
B
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
VANSANT & GUSLER, INC.
CONSULTING ENGINEERS
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D O
G
REPAIR MILITARY WORKING
JOINT BASE LANGLEY-EUSTIS
COORDINATION
DOG KENNELS FACILITY 1030
MUHJ 24-4024
NORTH
PLAN
LANGLEY AFB, LOCATION PLANA1
INDEX OF DRAWINGS
G-001
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
VANSANT & GUSLER, INC.
CONSULTING ENGINEERS
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
PLAN
NORTH
0' 4' 8' 12'
GENERAL SHEET NOTES
PHASING PLANA1
G-002
10 PSFGROUND SNOW LOAD (Pg) 10 PSFFLAT ROOF LOAD (Pf)
1.2THERMAL FACTOR (Ct) 1.0IMPORTANCE FACTOR (Is)
SNOW LOADS:
1.0EXPOSURE FACTOR (Ce)
118 MPHBASIC WIND SPEED (Vult)
CEXPOSURE CATEGORY
WIND LOADS:
ULTIMATE WIND BASE SHEARS (FOR MWFRS):
2.43 KIPSVE-W
4.52 KIPSVN-S
DSITE CLASSIFICATION
ASEISMIC DESIGN CATEGORY
1.0IMPORTANCE FACTOR (IE)
SEISMIC LOADS:
SPECTRAL RESPONSE ACCELERATIONS:
0.093S 0.040S 0.149S 0.097S 0.099S 0.065S
EQUIVALENT LATERAL FORCEANALYSIS PROCEDURE
STEEL SYSTEMS NOT
SPECIFICALLY DETAILED FOR
SEISMIC RESISTANCE
LATERAL FORCE RESISTING SYSTEM
3.0RESPONSE MODIFICATION COEFFICIENT (R)
0.033SEISMIC RESPONSE COEFFICIENT (Cs)
0.21 KIPSULTIMATE SEISMIC BASE SHEAR (V)
WINDCONTROLLING LATERAL LOADS
LATERAL DESIGN CONTROL
2FLOOD DESIGN CLASS
FLOOD LOADS: (PER ASCE 24 AND ASCE 7)
AEFLOOD ZONE
NAV88VERTICAL DATUM
9BASE FLOOD ELEVATION (BFE)
11DESIGN FLOOD ELEVATION (DFE)
6.81 IN/HRRAIN INTENSITY (15 MINUTE)
RAIN LOADS:
IIRISK CATEGORY
CLASSIFICATION OF BUILDING
1. THE STRUCTURAL DRAWINGS MUST BE USED IN CONJUNCTION WITH
THE ARCHITECTURAL, CIVIL, MECHANICAL, PLUMBING, AND
ELECTRICAL DRAWINGS, AND THE SPECIFICATIONS. THE
CONTRACTOR MUST VERIFY THE REQUIREMENTS OF OTHER TRADES
AS TO SLEEVES, CHASES, HANGERS, INSERTS, ANCHORS, HOLES,
AND ADDITIONAL ITEMS TO BE PLACED OR SET IN THE STRUCTURAL
WORK.
2. THIS STRUCTURE HAS BEEN DESIGNED IN ACCORDANCE WITH THE
PROVISIONS OF THE UNIFIED FACILITIES CRITERIA UFC-1-200-01
INCLUDING CHANGES, DATED FEBRUARY 26,2024.
3. THE WORK OUTLINED IN SPECIFICATION SECTION 014535 IS SUBJECT
TO SPECIAL INSPECTIONS AS DESCRIBED IN THE TECHNICAL
SPECIFICATIONS.
4. THE CONTRACTOR MUST PROVIDE TEMPORARY SHORING AND
BRACING REQUIRED TO ERECT AND HOLD THE STRUCTURE IN
PROPER ALIGNMENT UNTIL PERMANENT SUPPORTS AND LATERAL
BRACING ARE IN PLACE.
5. DISCREPANCIES WITHIN DRAWINGS, BETWEEN THE SPECIFICATIONS
AND THE DRAWINGS, OR WITHIN THE SPECIFICATIONS, MUST BE
BROUGHT TO THE ATTENTION OF THE ARCHITECT AND ENGINEER
DURING THE BIDDING PROCESS IN TIME TO PERMIT CLARIFICATION
BY ADDENDUM. IF INCONSISTENCIES, DISCREPANCIES OR
CONTRADICTIONS IN THE CONTRACT DOCUMENTS ARE DISCOVERED
AFTER THE CLOSE OF BIDDING QUESTIONS, THE CONTRACTOR MUST
BE DEEMED BY SUBMITTAL OF THEIR BID, TO HAVE BID THE MOST
COSTLY AS TO LABOR, MATERIALS, DURATION, SEQUENCE AND
METHOD OF CONSTRUCTION TO PROVIDE THE WORK.
6. THESE STRUCTURAL DRAWINGS ARE ISSUED ON THE DATE
INDICATED FOR THE PURPOSE DESIGNATED. THESE DRAWINGS MUST
NOT BE ISSUED OR RELEASED FOR ANY OTHER PURPOSE WITHOUT
THE WRITTEN AUTHORIZATION OF THE STRUCTURAL ENGINEER OF
RECORD.
7. DETAILS LABELED "TYPICAL DETAIL" WITHIN THE DOCUMENTS APPLY
TO SITUATIONS ON THE PROJECT THAT MAY OCCUR THROUGHOUT
THE PROJECT. SUCH DETAILS APPLY WHETHER OR NOT THE DETAIL
IS SPECIFICALLY REFERENCED AT EACH INSTANCE. NOTIFY
ENGINEER IF CLARIFICATIONS ARE REQUIRED REGARDING THE
APPLICABILITY OF THE "TYPICAL DETAIL".
8. DESIGN CRITERIA:
GENERAL NOTES:
S 1
MS M1
DS D1
1. SHOP DRAWINGS AND SUBMITTALS MUST BEAR THE CONTRACTOR'S
REVIEW STAMP WITH CHECKER'S INITIALS BEFORE BEING SUBMITTED
TO THE ARCHITECT FOR APPROVAL.
2. WHEN THE CONTRACTOR HAS BEEN AUTHORIZED TO USE THE
ARCHITECT'S AND / OR ENGINEER'S DRAWINGS AS SHOP DRAWINGS,
THE CONTRACTOR MUST REMOVE ALL TITLE BLOCKS, PROFESSIONAL
SEALS, AND ANY OTHER REFERENCE TO THE ARCHITECT AND / OR
ENGINEER FROM THAT SHOP DRAWING.
SHOP DRAWINGS AND SUBMITTALS:
1. FOUNDATIONS HAVE BEEN DESIGNED IN ACCORDANCE WITH THE
RECOMMENDATIONS IN THE PRESUMPTIVE LOAD-BEARING VALUES
OF SOILS IN SECTION 1806.2 OF UFC 1-200-01 FOR A CLASS 4
MATERIAL.
2. FOUNDATIONS HAVE BEEN DESIGNED FOR A NET ALLOWABLE SOIL
BEARING PRESSURE OF 2,000 PSF.
3. TOP OF FOOTING ELEVATIONS MUST BE A MINIMUM DEPTH OF 1'-4"
BELOW LOWEST ADJACENT SOIL GRADE.
4. PRIOR TO PLACING FOUNDATION CONCRETE, ALL FOUNDATION
EXCAVATIONS MUST BE INSPECTED BY THE OWNER'S
GEOTECHNICAL TESTING AGENCY [SPECIAL INSPECTOR] TO EXPLORE
THE EXTENT OF LOOSE, SOFT, EXPANSIVE, OR OTHERWISE
UNSATISFACTORY SOIL MATERIAL AND TO VERIFY DESIGN BEARING
PRESSURE. DIRECTION FOR CORRECTIVE ACTION WILL BE PROVIDED
BY THE OWNER'S GEOTECHNICAL TESTING AGENCY [SPECIAL
INSPECTOR] WHERE UNSATISFACTORY SOILS ARE PRESENT.
5. NO UNBALANCED BACKFILLING MUST BE DONE AGAINST MASONRY
OR CONCRETE WALLS UNLESS WALLS ARE SECURELY BRACED
AGAINST OVERTURNING, EITHER BY TEMPORARY CONSTRUCTION
BRACING OR BY PERMANENT CONSTRUCTION.
6. CONTROL GROUNDWATER AND SURFACE RUNOFF THROUGHOUT THE
CONSTRUCTION PROCESS. INUNDATION AND LONG TERM EXPOSURE
OF BEARING SURFACES WHICH RESULT IN DETERIORATION OF
BEARING MUST BE PREVENTED.
FOUNDATION NOTES:
1. CONCRETE MUST BE IN ACCORDANCE WITH AMERICAN CONCRETE
INSTITUTE (ACI) 301 AND 318.
2. CONCRETE MUST BE NORMAL WEIGHT [UNLESS OTHERWISE
DENOTED AS LW (LIGHTWEIGHT)] AND MUST OBTAIN 28 DAY
COMPRESSIVE STRENGTHS AS FOLLOWS:
A. CONCRETE NOT OTHERWISE NOTED.......................... 3,000 PSI
3. REINFORCING MATERIALS MUST BE AS FOLLOWS:
A. REINFORCING BARS - ASTM A615, GRADE 60, DEFORMED.
4. ALL REINFORCING STEEL AND EMBEDDED ITEMS SUCH AS ANCHOR
RODS AND WELD PLATES MUST BE ACCURATELY PLACED AND
ADEQUATELY TIED AND SUPPORTED BEFORE CONCRETE IS PLACED
TO PREVENT DISPLACEMENT BEYOND PERMITTED TOLERANCES.
5. CONCRETE COVER TO REINFORCING STEEL MUST EQUAL THE
FOLLOWING, UNLESS OTHERWISE NOTED:
A. SURFACES AGAINST EARTH ................................................ 3"
B. SURFACES NOT CAST AGAINST EARTH, BUT
EXPOSED TO EARTH OR WEATHER IN THE
FINAL CONDITION
#5 AND SMALLER ...................................................... 1 1/2"
#6 AND LARGER .............................................................. 2"
6. LAP CONTINUOUS REINFORCING STEEL PER SCHEDULES AND
TYPICAL DETAILS
7. DO NOT EMBED CONDUIT AND PIPING IN OR PENETRATE THROUGH
CAST-IN-PLACE CONCRETE ELEMENTS UNLESS OTHER NOTED.
CAST-IN-PLACE CONCRETE NOTES:
1. MIX DESIGNS COMPRESSIVE STRENGTHS (f'c) BASED ON 28 DAY
DESIGN STRENGTH, UNLESS OTHERWISE NOTED.
2. CONCRETE NOT OTHERWISE NOTED:
A. MINIMUM COMPRESSIVE STRENGTH (f'c) = 3500 PSI
3. FOUNDATIONS (SPREAD FOOTINGS, MAT FOOTINGS):
A. EXPOSURE CLASS = ACI 318 F0, S0, W0, C1
B. MINIMUM COMPRESSIVE STRENGTH (f’c) = 3,000PSI
C. MAXIMUM W/CM = 0.5
D. SLUMP = 5” MAX PLUS OR MINUS 1”, OR 8” MAX, PLUS OR MINUS 1”
FOR CONCRETE WITH A VERIFIED SLUMP OF 3” PLUS OR MINUS 1”
BEFORE ADDING HIGH-RANGE WATER-REDUCING OR
PLASTICIZING ADMIXURE
E. AIR CONTENT = NO REQUIREMENTS
F. AGGREGATE = NORMAL WEIGHT, 1 1/2” NOMINAL
G. LIMIT WATER-SOLUBLE, CHLORIDE-ION CONTENT IN HARDENED
CONCRETE TO 0.30 PERCENT BY WEIGHT OF CEMENT
4. INTERIOR FLOOR SLAB-ON-GRADE:
A. EXPOSURE CLASS = ACI 318 F0, W0, C0
B. MINIMUM COMPRESSIVE STRENGTH (f'c) = 3,500PSI
C. MAXIMUM W/CM = 0.5
D. SLUMP = 5" MAX PLUS OR MINUS 1", OR 8" MAX. PLUS OR MINUS 1"
FOR CONCRETE WITH A VERIFIED SLUMP OF 3" PLUS OR MINUS 1"
BEFORE ADDING HIGH-RANGE WATER-REDUCING OR PLASTICIING
ADMIXTURE
E. AIR CONTENT = DO NOT ALLOW AIR CONTENT IN TROWEL
FINISHED FLOORS TO EXCEED 3%
F. AGGREGATE = NORMAL WEIGHT, 3/4" NOMINAL
G. LIMIT WATER-SOLUABLE, CHLORIDE-ION CONTENT IN HARDENED
CONCRETE TO 1.00 PERCENT BY WEIGHT OF CEMENT
5. INTERIOR CONCRETE WALLS:
A. EXPOSURE CLASS = ACI 318 F0, S0, W0, C0
B. MINIMUM COMPRESSIVE STRENGTH (f'c)
C. MAXIMUM W/CM = 0.45
D. BLENDED HYDROLIC CEMENT = ASTM C595 TYPE 1L(MS)A
E. SLUMP = 5" MAX PLUS OR MINUS 1", OR 8" MAX, PLUS OR MINUS 1"
FOR CONCRETE WITH A VERIFIED SLUMP OF 3" PLUS OR MINUS 1"
BEFORE ADDING HIGH-RANGE WATER-REDUCING OR
PLASTICIZING ADMIXTURE.
F. AIR CONTENT = 5.5% PLUS OR MINUS 1.5% AT POINT OF DELIVERY
G. AGGREGATE = NORMAL WEIGHT, 3/4" NOMINAL
H. LIMIT WATER-SOLUBLE, CHLORIDE-ION CONTENT IN HARDENED
CONCRETE TO 1.00 PERCENT BY WEIGHT OF CEMENT.
CONCRETE MIX DESIGN NOTES:
1. CONCRETE MASONRY MATERIALS AND CONSTRUCTION MUST
CONFORM TO THE AMERICAN CONCRETE INSTITUTE (ACI) "BUILDING
CODE REQUIREMENTS FOR MASONRY STRUCTURES" (TMS 402 / ACI
530 / ASCE 5) AND "SPECIFICATIONS FOR MASONRY STRUCTURES"
(TMS 602 / ACI 530.1 / ASCE 6).
2. CONCRETE MASONRY UNITS MUST CONFORM TO ASTM C90 AND MUST
BE MADE WITH [LIGHTWEIGHT] [NORMAL WEIGHT] AGGREGATE.
3. COMPRESSIVE STRENGTH OF MASONRY MUST BE DETERMINED BY
THE UNIT STRENGTH METHOD AS SET FORTH IN ACI 530.1. THE NET
AREA COMPRESSIVE STRENGTH OF MASONRY, f'm, MUST BE 2,000 PSI
AT 28 DAYS.
4. MORTAR MUST BE TYPE 'M' OR 'S' AND MUST COMPLY WITH ASTM
C270, PROPORTIONS OR PROPERTIES SPECIFICATION.
5. GROUT MUST COMPLY WITH EITHER THE PROPORTIONS OR
PROPERTIES SPECIFICATION OF ASTM C476 AND AS FOLLOWS:
A. PROPORTIONS SPECIFICATION: THIS MIX CANNOT CONTAIN
ADMIXTURES. WATER MUST BE ADDED IN THE FIELD IN ORDER TO
ACHIEVE A SLUMP OF 8-11 INCHES WHEN PLACED IN THE
CONCRETE MASONRY UNITS. MORTAR, PEA-GRAVEL CONCRETE,
OR "CHAT" MIXES ARE NOT ACCEPTABLE SUBSTITUTES FOR THE
SPECIFIED GROUT.
B. PROPERTIES SPECIFICATION: THIS MIX MUST BE PROPORTIONED
TO OBTAIN A DOCUMENTED 28 DAY COMPRESSIVE STRENGTH OF
2,500 PSI, WITH 3/8" MAX AGGREGATE AND AN 8-11 INCH SLUMP
WHEN PLACED IN THE CONCRETE MASONRY UNITS.
6. REINFORCING STEEL MUST COMPLY WITH ASTM A615, GRADE 60.
SHOP FABRICATE REINFORCING BARS WHICH ARE SHOWN TO BE
BENT OR HOOKED.
7. ALL BOND BEAMS, REINFORCED CELLS AND CELLS WITH EXPANSION
BOLTS, EMBED PLATES OR OTHER ANCHORS AND ALL CELLS BELOW
GRADE MUST BE GROUTED SOLID. GROUT PROCEDURE MUST
COMPLY WITH ACI 530.1.
8. ALL CMU WALLS MUST BE REINFORCED CONTINUOUSLY FROM
FOUNDATION TO TOP OF WALL. WHERE REINFORCING IS
INTERRUPTED, OFFSET AND LAP ADDITIONAL BARS PER THE “TYPICAL
OFFSET SPLICE AT MASONRY WALL DETAILS.”
LAP ALL REINFORCING PER SCHEDULE BELOW, TYPICAL UNLESS
OTHERWISE NOTED:
CONCRETE MASONRY NOTES:
REINF SIZE 52 x BAR DIAMETER
MASONRY LAP SCHEDULE
#4
#5
#6
#7
#8
26"
33"
39"
46"
52"
10. PROVIDE ONE VERTICAL BAR EACH SIDE OF ALL OPENINGS AND
CONTROL JOINTS, AND AT CORNERS AND INTERSECTIONS OF ALL
MASONRY WALLS, BOTH BEARING AND NON-BEARING WALLS. SHOW
CONTROL JOINT LOCATIONS ON THE REINFORCING STEEL SHOP
DRAWINGS.
11. ALL NON-BEARING MASONRY WALLS MUST BE REINFORCED WITH #4
VERTICAL BARS AT 40 INCHES ON CENTER, TYPICAL UNLESS
OTHERWISE NOTED.
12. PROVIDE STANDARD 9 GAGE TRUSS TYPE HORIZONTAL JOINT
REINFORCING IN CMU WALLS AT 16 INCHES ON-CENTER VERTICALLY
AND AT 8 INCHES ON-CENTER VERTICALLY AT PARAPETS.
ADDITIONALLY PROVIDE IN THE TWO JOINTS IMMEDIATELY ABOVE
AND BELOW ALL OPENINGS, EXTENDING A MINIMUM OF 2 FEET
BEYOND THE JAMB ON EACH SIDE OF THE OPENING, EXCEPT AT
CONTROL JOINTS.
13. PLACE GROUT WITH POUR HEIGHT NOT EXCEEDING 5 FEET.
CONSOLIDATE EACH POUR BY MECHANICAL VIBRATION.
RECONSOLIDATE AFTER INITIAL WATER LOSS AND SETTLEMENT
OCCUR.
14. MASONRY MUST BE CONSTRUCTED IN RUNNING BOND PATTERN AND
ALL CORNERS TO BE TIED BY MASONRY BOND.
15. SUBMITTALS FOR CONCRETE MASONRY MUST INCLUDE THE
FOLLOWING:
A. PRODUCT DATA/MATERIAL CERTIFICATES: SUBMIT DATA AND
CERTIFICATES FOR MASONRY UNITS, CEMENTITOUS MATERIALS,
MORTAR ADMIXTURES, PRE-BLENDED DRY MORTAR MIXES,
REINFORCING BARS, JOINT REINFORCEMENT, ANCHORS, TIES,
AND METAL ACCESSORIES.
B. REINFORCEMENT SHOP DRAWINGS: SHOW ELEVATIONS OF
REINFORCED WALLS. MUST COMPLY WITH ACI DETAILING
MANUAL: DETAIL BENDING, LAP LENGTHS, AND PLACEMENT OF
UNIT MASONRY REINFORCING BARS.
C. MIX DESIGNS: SUBMIT MIX DESIGNS FOR EACH TYPE OF MORTAR
AND GROUT AND INCLUDE DESCRIPTION OF TYPE AND
PROPORTIONS OF INGREDIENTS. INCLUDE TEST REPORTS FOR
GROUT MIXES ACCORDING TO ASTM C1019
D. SHOP DRAWINGS MUST INDICATE THE DATE OF THE STRUCTURAL
DRAWINGS THAT WERE USED IN PREPARATION.
IMEG RESERVES PROPRIETARY RIGHTS,
INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN
THEREON. SAID DRAWING AND/OR DATA
ARE THE EXCLUSIVE PROPERTY OF IMEG
AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG.
©2025 IMEG CONSULTANTS CORP.
G
N
W E
IA
R
B SA
ID
D A
T E
R E
V
IE
W E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C H
E C
K E
D B
Y
R E
V D
E S
C R
IP
T
IO
N
A P
P R
V D
O C
I
A
R
A
O M B C
T
D
M
N M A
A
B
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
W
LT
K E
N N
E
LS
F A
C
IL
IT
Y
R E
P A
IR
M
IL
IT
A R
Y W
O R
K
IN
G D
O G
D A
T E
F
IL
E N
A M
E
D E
P A
R
TM
E N
T O
F T
H E
A
IR
F O
R C
E
A
IR
C O
M B
A T
C O
M M
A N
D
LA
N
G
LE
Y A
F B
V A
C
IV
IL
E
N G
IN
E
E R
IN
G
O F
F
IC
E
PROJECT NUMBER
JB
LE
M -1
MUHJ 24-4024
P L O
T D
A T
E
P L O
T S
C A
L E
S
U B
M
IT
T E
D B
Y
LMJA
P
JD
T
07/22/2025
J
U L
X
THESE DRAWINGS ARE RELEASED FOR THE
FOLLOWING USE, ANY OTHER USE OF THESE
DRAWINGS IS AT THE RISK OF THE CONTRACTOR
OR OTHERS USING THESE DRAWINGS FOR THAT
UNAUTHORIZED USE. LYNCH MYKINS IS NOT
RESPONSIBLE FOR ADDITIONAL COSTS DUE TO
CHANGES, COORDINATION OR ADDITIONAL
SCOPE OF WORK REQUIRED DUE TO SUCH
UNAUTHORIZED USE.
EARLY FOUNDATION PACKAGE
PRELIMINARY BUDGET PRICING
EARLY STEEL PACKAGE
MILL ORDER PACKAGE
100% REVIEW SUBMITTAL
PERMIT SET
now lynch
400 GRANBY STREET, SUITE 401
NORFOLK, VA 23510
919.782.1833 www.imegcorp.com mykins
ESE-001
JD
T
1. ANCHORS TO BE POST-INSTALLED ONLY WHERE INDICATED ON
CONSTRUCTION DOCUMENTS. ANY SUBSTITUTE OF CAST-IN ANCHOR
TO POST-INSTALLED ANCHORS MUST BE SUBMITTED AS A REQUEST
FOR DEVIATION TO THE ENGINEER OF RECORD PRIOR TO
CONSTRUCTION.
2. ALL POST INSTALLED ANCHORS INDICATED ON THE DRAWINGS ARE
BY HILTI, INC, AND MUST BE CONSIDERED THE BASIS OF DESIGN
PRODUCT. WHERE NOT EXPLICITLY INDICATED IN THE DRAWINGS,
THE FOLLOWING ANCHORS/ADHESIVES MUST BE USED:
A. ANCHORAGE TO CONCRETE
1. ADHESIVE ANCHORS FOR CRACKED AND UNCRACKED
CONCRETE USE:
a. HILTI HIT-HY 200 SAFE SET SYSTEM WITH HILTI HOLLOW
DRILL BIT (TE-CD OR TE-YD) AND VC 20/40 VACUUM
SYSTEM (VC 20-U OR VC40U) WITH STEEL THREADED
ROD PER ICC ESR-3187.
2. SCREW ANCHORS FOR CRACKED AND UNCRACKED
CONCRETE USE:
a. HILTI KWIK HUS EZ SCREW ANCHORS PER ICC ESR-3027.
B. REBAR DOWELING INTO CONCRETE
1. ADHESIVE ANCHORS FOR CRACKED AND UNCRACKED
CONCRETE USE:
a. HILTI HIT-HY 200 SAFE SET SYSTEM WITH HILTI HOLLOW
DRILL BIT (TE-CD OR TE-YD) AND VC 20/40 VACUUM
SYSTEM (VC 20-U OR VC 40-U) WITH CONTINUOUSLY
DEFORMED REBAR PER ICC ESR-3187.
C. ANCHORAGE TO SOLID GROUTED MASONRY
1. ADHESIVE ANCHORS USE:
a. HILTI HIT-HY 270 MASONRY ADHESIVE ANCHORING
SYSTEM (ICC PENDING).
b. STEEL ANCHOR ELEMENT MUST BE HILTI HAS-E
CONTINUOUSLY THREADED ROD.
2. MECHANICAL ANCHORS USE:
a. HILTI KWIK HUS EZ SCREW ANCHORS PER ICC ESR 3056.
D. ANCHORAGE TO HOLLOW / MULTI-WYTHE MASONRY
1. ADHESIVE ANCHORS USE:
a. HILTI HIT-HY 270 MASONRY ADHESIVE ANCHORING
SYSTEM PERICCESR-3342.
b. STEEL ANCHOR ELEMENT MUST BE HILTI HAS-E
CONTINUOUSLY THREADED ROD OR CONTINUOUSLY
DEFORMED STEEL REBAR.
c. THE APPROPRIATE SIZE SCREEN TUBE MUST BE USED
PER ADHESIVE MANUFACTURER'S RECOMMENDATION.
3. ALTERNATE POST INSTALLED ANCHOR PRODUCTS MAY BE
SUBMITTED TO THE ENGINEER FOR REVIEW AND POSSIBLE
APPROVAL. ALL SUBSTITUTION REQUESTS MUST BE ACCOMPANIED
BY AN ICC ESR SHOWING COMPLIANCE WITH THE RELEVANT
BUILDING CODE FOR SEISMIC USES, LOAD RESISTANCE,
INSTALLATION CATEGORY, AND COMPREHENSIVE INSTALLATION
INSTRUCTIONS. ADHESIVE ANCHOR EVALUATION WILL ALSO
CONSIDER CREEP, IN-SERVICE TEMPERATURE AND INSTALLATION
TEMPERATURE. ALTERNATE PRODUCTS MAY REQUIRE
MODIFICATIONS TO ANCHOR DIAMETER, SPACING, AND EMBEDMENT.
4. INSTALL ANCHORS PER THE MANUFACTURER INSTRUCTIONS, AS
INCLUDED IN THE ANCHOR PACKAGING.
5. THE CONTRACTOR MUST ARRANGE FOR AN ANCHOR
MANUFACTURER'S REPRESENTATIVE TO PROVIDE ONSITE
INSTALLATION TRAINING FOR ALL OF THEIR ANCHORING PRODUCTS
SPECIFIED. THE STRUCTURAL ENGINEER OF RECORD MUST RECEIVE
DOCUMENTED CONFIRMATION THAT ALL OF THE CONTRACTOR'S
PERSONNEL WHO INSTALL ANCHORS ARE TRAINED PRIOR TO THE
COMMENCEMENT OF ANCHOR INSTALLATION.
6. ANCHOR CAPACITY IS DEPENDANT UPON SPACING BETWEEN
ADJACENT ANCHORS AND PROXIMITY OF ANCHORS TO EDGE OF
CONCRETE. INSTALL ANCHORS IN ACCORDANCE WITH SPACING AND
EDGE CLEARANCES INDICATED ON THE DRAWINGS.
7. EXISTING REINFORCING BARS IN THE CONCRETE STRUCTURE MAY
CONFLICT WITH SPECIFIC ANCHOR LOCATIONS. UNLESS NOTED ON
THE DRAWINGS THAT THE BARS CAN BE CUT, THE CONTRACTOR
MUST LOCATE THE POSITION OF THE REINFORCING BARS AT THE
LOCATIONS OF THE CONCRETE ANCHORS, BY FERROSCAN OR GPR.
8. POST INSTALLED ANCHORS MAY REQUIRE CONTINUOUS
INSPECTIONS BY THE OWNER'S MATERIALS TESTING AGENCY TO
VERIFY INSTALLATION HAS BEEN PERFORMED IN ACCORDANCE WITH
THE MANUFACTURER'S WRITTEN INSTRUCTIONS.
POST-INSTALLED ANCHOR NOTES:
1. STRUCTURAL STEEL MUST BE IN ACCORDANCE WITH THE AMERICAN
INSTITUTE OF STEEL CONSTRUCTION (AISC) 360.
2. STRUCTURAL STEEL FABRICATOR MUST PARTICIPATE IN THE AISC
QUALITY CERTIFICATION PROGRAM AND BE A DESIGNATED AISC-
CERTIFIED PLANT.
3. STRUCTURAL STEEL MUST COMPLY WITH THE FOLLOWING
SPECIFICATIONS:
A. STRUCTURAL STEEL SHAPES, PLATES AND BARS UNLESS
OTHERWISE NOTED - ASTM A572, Fy = 50 KSI B. STRUCTURAL STEEL W-SHAPES - ASTM A992, Fy = 50 KSI
C. HOLLOW STRUCTURAL SECTIONS (HSS):
a. SQUARE & RECTANGULAR - ASTM A500, GRADE C, Fy = 50 KSI
D. ANCHOR RODS - ASTM F1554, GRADE 36
E. HIGH STRENGTH BOLTS - ASTM F3125, TYPE A325 (TYPICAL UON)
F. WASHERS - ASTM F436
G. NUTS - ASTM A563
4. UNLESS OTHERWISE NOTED, ALL REQUIRED DESIGN STRENGTHS AND
REACTIONS INDICATED ARE BASED ON THE "LOADING COMBINATIONS
USING STRENGTH DESIGN OR LOAD AND RESISTANCE FACTOR
DESIGN" PER SECTION 1605.2 OF THE BUILDING CODE.
5. STRUCTURAL STEEL FRAME IS CONSIDERED AS UNRESTRAINED FOR
FIRE PROTECTION PURPOSES.
6. HIGH STRENGTH BOLTS MAY BE TIGHTENED TO THE "SNUG TIGHT"
CONDITION, UNLESS OTHERWISE NOTED.
7. WELDING MUST BE IN ACCORDANCE WITH AWS D1.1, "STRUCTURAL
WELDING CODE - STEEL." WELD ELECTRODES MUST BE E70XX LOW
HYDROGEN. UNLESS OTHERWISE NOTED, PROVIDE CONTINUOUS
FILLET WELDS WITH MINIMUM SIZE REQUIRED BY TABLE J2.4 AISC 360.
8. COORDINATE ALL MEMBER LOCATIONS, UNIT WEIGHTS, OPENING
SIZES, AND CURB DIMENSIONS FOR MECHANICAL EQUIPMENT WITH
THE ACTUAL EQUIPMENT FURNISHED.
9. SHOP PRIME STEEL SURFACES, EXCEPT THE FOLLOWING:
A. SURFACES EMBEDDED IN CONCRETE OR MORTAR. EXTEND
PRIMING OF PARTIALLY EMBEDDED MEMBERS TO A DEPTH OF 2
INCHES.
B. SURFACES TO BE WELDED.
C. GALVANIZED SURFACES.
10. CLEAN ALL STEEL SURFACES TO BE PAINTED. REMOVE LOOSE RUST,
MILL SCALE, SPATTER, SLAG, OR FLUX DEPOSITS. PREPARE
SURFACES IN ACCORDANCE WITH SSPC-SP3 SPECIFICATION AND
STANDARD.
11. HOT-DIP GALVANIZE AFTER FABRICATION THE FOLLOWING:
1. ALL STEEL EXPOSED TO WEATHER IN THE FINAL CONSTRUCTION.
2. ITEMS IDENTIFIED AS GALVANIZED ON ARCHITECTURAL OR
STRUCTURAL DRAWINGS.
12. STEEL MEMBERS MUST BE SPLICED ONLY WHERE INDICATED.
STRUCTURAL STEEL NOTES:
IMEG RESERVES PROPRIETARY RIGHTS,
INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN
THEREON. SAID DRAWING AND/OR DATA
ARE THE EXCLUSIVE PROPERTY OF IMEG
AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG.
©2025 IMEG CONSULTANTS CORP.
G
N
W E
IA
R
B SA
ID
D A
T E
R E
V
IE
W E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C H
E C
K E
D B
Y
R E
V D
E S
C R
IP
T
IO
N
A P
P R
V D
O C
I
A
R
A
O M B C
T
D
M
N M A
A
B
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
W
LT
K E
N N
E
LS
F A
C
IL
IT
Y
R E
P A
IR
M
IL
IT
A R
Y W
O R
K
IN
G D
O G
D A
T E
F
IL
E N
A M
E
D E
P A
R
TM
E N
T O
F T
H E
A
IR
F O
R C
E
A
IR
C O
M B
A T
C O
M M
A N
D
LA
N
G
LE
Y A
F B
V A
C
IV
IL
E
N G
IN
E
E R
IN
G
O F
F
IC
E
PROJECT NUMBER
JB
LE
M -1
MUHJ 24-4024
P L O
T D
A T
E
P L O
T S
C A
L E
S
U B
M
IT
T E
D B
Y
LMJA
P
JD
T
07/22/2025
J
U L now lynch
400 GRANBY STREET, SUITE 401
NORFOLK, VA 23510
919.782.1833 www.imegcorp.com mykins
ESE--002
SLAB POST-TENSION STRANDS
CONCENTRATED MILD SLAB REINFORCING
SLAB REINFORCING
EVENLY DISTRIBUTED MILD SLAB REINFORCING
SLAB REINFORCING
MISC ANNOTATIONS
CONNECTIONS
COMPOSITE BEAMS
MISC ANNOTATIONS
WALLSSECTIONS
COLUMNS
GENERAL PLANS
FOUNDATIONS
SHALLOW FOUNDATIONS
DEEP FOUNDATIONS
FLOOR AND ROOF FRAMING
FLOORS AND ROOF
GENERAL ANNOTATIONSGENERAL ANNOTATIONS
DRAWINGS LEGEND
ELEVATIONSELEVATIONS CONCRETECONCRETE
STEELSTEEL
ABBREVIATIONS
BOTTOM OF DECK ELEVATION
MEASURED FROM REFERENCED
FINISHED FLOOR ELEVATION = 0'-0"
MECHANICAL UNIT SUPPORTED
ABOVE FRAMING (WEIGHT IN
POUNDS) - COORD W/ MECH DWGS
(-X'-X")
WARP LINE OF ROOF DECK
SFSF
PIPE
X
SX SECTION/DETAIL MARK=
SECTION/DETAIL NUMBER/LETTER
SHEET NUMBER WHERE
SECTION/DETAIL MARK IS DRAWN
SECTION/DETAIL MARK=
SHEET NUMBER WHERE
SECTION/DETAIL MARK IS DRAWN
SHEET NUMBER WHERE
SECTION/DETAIL MARK IS CUT
SECTION/DETAIL NUMBER/LETTER
X
SX SX
WFX
S-X
SL
X
BOD = +X'-X"
X'-X"
BANDED TENDON EFFECTIVE
FORCE AFTER ALL LOSSES
F = XXX k F = XX k/ft
DISTRIBUTED TENDON EFFECTIVE
FORCE AFTER ALL LOSSES
STRESSING
END
DEAD END
ANCHOR
TENDON 'CGS' ABOVE
SOFFIT AT SUPPORT
AND CENTER SPAN
(10) #5T x 15'-0"
BAR SIZE
BAR LOCATION
(T = TOP, M = MID, B = BOT)
LENGTH (IF NOT SHOWN,
REF TYPICAL DETAIL)
QUANTITY
#5T x 15'-0" AT 12" OC
BAR SIZE
BAR LOCATION
(T = TOP, M = MID, B = BOT)
LENGTH (IF NOT SHOWN,
REF TYPICAL DETAIL)
SPACING
CONCRETE FIREWALL=
CONCRETE SHEARWALL=
RTU-X
XXXX#
MECHANICAL UNIT SUPPORTED
BELOW FRAMING (WEIGHT IN
POUNDS) - COORD W/ MECH DWGS
RTU-X
XXXX#
PLAN KEY NOTE MARK=
EXISTING COLUMN GRID MARK=
COLUMN GRID MARK=
X
TRUSS BEARING ELEVATION
MEASURED FROM REFERENCED
FINISHED FLOOR ELEVATION = 0'-0"
TBE = +X'-X"
TOP OF MASONRY ELEVATION
MEASURED FROM REFERENCED
FINISHED FLOOR ELEVATION = 0'-0"
TOM = +X'-X"
BOTTOM OF STEEL ELEVATION
MEASURED FROM REFERENCED
FINISHED FLOOR ELEVATION = 0'-0"
BOS = +X'-X"
TOP OF STEEL ELEVATION
MEASURED FROM REFERENCED
FINISHED FLOOR ELEVATION = 0'-0"
TOS = +X'-X"
= FLOOR / ROOF OPENING
TOP OF FOOTING ELEVATION
MEASURED FROM REFERENCED
FINISHED FLOOR ELEVATION = 0'-0"
(-X'-X") =
TOP OF PILE CAP / GRADE BEAM
ELEVATION MEASURED FROM
REFERENCED FINISHED FLOOR
ELEVATION = 0'-0"
<-X'-X"> =
TOP OF EXISITNG FOOTING
ELEVATION MEASURED FROM
REFERENCED FINISHED FLOOR
ELEVATION = 0'-0"
TOP OF SLAB ELEVATION
MEASURED FROM REFERENCED
FINISHED FLOOR ELEVATION = 0'-0"
CHANGE IN ELEVATION=
CHANGE IN SLOPE=
DIRECTION OF SLOPE=
SLAB-ON-GRADE JOINT=
HORIZONTAL BRIDGING=
CROSS BRIDGING=
WALL FOOTING MARK=
CFX COLUMN FOOTING MARK=
PCX PILE CAP MARK=
GBX GRADE BEAM MARK=
TPX TEST PILE MARK=
CBX CONCRETE BEAM MARK=
FIELD VERIFY=
SLAB MARK / SPAN DIRECTION=
PIPE CROSSING FOOTING=
(xx") (xx")(xx")
SR1
STUD
RAIL
MARK
COLUMN
FACE - REF
SCHEDULE
(TYP)
SR1 F4
F1 F3
F2 SR1 SR1
F1
F2 F4
F3
F3
F4 F2
F1
F2
F3 F1
F4
GRID
KB
MOMENT CONNECTION=
AXIAL CONNECTION=
JOIST BOTTOM CHORD EXTENSION=
BEAM BOTTOM FLANGE BRACE=
BEAM SPLICE=
KNUCKLED BEAM=
FULL DEPTH STIFFENER
CONNECTION
W16x26 (36) [2"]
BEAM SIZE NUMBER OF
HEADED STUDS
CAMBER
SHEAR REACTION (KIPS)
IF GREATER THAN LOADS
GIVEN IN "MINIMUM BEAM
REACTION SCHEDULE"
COMPOSITE BEAM
NOTATION=
AXIAL
REACTION
(KIPS)
MOMENT
REACTION
(KIP-FT)
SJ
JOIST GIRDER MOMENT MARK=
JOIST SLIP CONNECTION=
SG JOIST GIRDER SLIP CONNECTION=
SB BEAM SLIP CONNECTION=
EXTERIOR WALL TERMINATING
BELOW FLOOR / ROOF
BEARING WALL TERMINATING
BELOW FLOOR / ROOF
BEARING WALL EXTENDING ABOVE
FLOOR / ROOF
W1 WALL TYPE MARK=
V M A
V M A
AFF
ARCH
BD
BF
BEJ
BLDG
BM
BOD
BOS
BOT, B
BRG
BTWN
C TO C
CFMF
CJ
CL
CLR
CMU
COL
CONC
CONN
CONSTR
CONT
COORD
CTR
CTRD
DBA
DBL
DC
DCJ
DIA, Ø
DIST
DJ
DWGS
EA
EF
EJ
EL
ELEV
EMBED
EOD
EOS
EQ
EW
EXIST
EXP
EXT
FD
FDN
FO
FF EL
FIN
FIN FLR
FOB
FOC
FOM
FOS
FRMG
FTG
FS
FV, ±
GALV
GC
GEN
GR BM
H
HK
HORIZ
HSS
HSA
HT
HVY
INT
JBE
JT
KCJ
ABOVE FINISHED FLOOR
ARCHITECT
BAR DIAMETER
BRACED FRAME
BUILDING EXPANSION JOINT
BUILDING
BEAM
BOTTOM OF DECK
BOTTOM OF STEEL
BOTTOM
BEARING
BETWEEN
CENTER TO CENTER
COLD-FORMED METAL
FRAMING
CONTROL JOINT
CENTERLINE
CLEAR
CONCRETE MASONRY UNIT
COLUMN
CONCRETE
CONNECTION
CONSTRUCTION
CONTINUOUS
COORDINATE
CENTER
CENTERED
DEFORMED BAR ANCHOR
DOUBLE
DIAPHRAGM CHORD
DOWELED CONSTRUCTION
JOINT
DIAMETER
DISTANCE
DOUBLE JOIST
DRAWINGS
EACH
EACH FACE
EXPANSION JOINT
ELEVATION
ELEVATOR
EMBEDMENT
EDGE OF DECK
EDGE OF SLAB
EQUAL
EACH WAY
EXISTING
EXPANSION
EXTERIOR
FLOOR DRAIN
FOUNDATION
FACE OF
FINISHED FLOOR
ELEVATION
FINISH
FINISHED FLOOR
FACE OF BUILDING
FACE OF CONCRETE
FACE OF MASONRY
FACE OF SLAB/ STUD
FRAMING
FOOTING
FAR SIDE
FIELD VERIFY
GALVANIZED
GENERAL CONTRACTOR
GENERAL
GRADE BEAM
HIGH
HOOK
HORIZONTAL
HOLLOW STRUCTURAL
SECTION
HEADED STUD ANCHOR
HEIGHT
HEAVY
INTERIOR
JOIST BEARING ELEVATION
JOINT
KEYED CONSTRUCTION
JOINT
KCJ
Ld
Ldc
Ldh
Ls
Lsc
L
LLH
LLV
LSH
LSV
LTWT
LWC
MAS
MATL
MAX
MECH
MF
MFR
MID
MIN
MOD
MOS
NOM
NS
NTS
OC
OPH
OPNG
PAF
PAR
PC
PEMB
PEN
PERP
PL
PT
R
REF
REINF
REQD
REQMTS
SCHED
SF
SGB
SIM
SJ
SL
SOG
SPF
STD
STIFF
TBE
T&B T&G
THK
TOC
TOF
TOM
TOCP
TOS
TS
TS/STR
TYP
UON
VERT
W/
WP
WSP
WWR
KEYED CONSTRUCTION JOINT
REBAR TENSION
DEVELOPMENT LENGTH
REBAR COMPRESSION
DEVELOPMENT LENGTH
HOOKED REBAR TENSION
DEVELOPMENT LENGTH
REBAR TENSION SPLICE
LENGTH
REBAR COMPRESSION SPLICE
LENGTH
LOW
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LONG SIDE HORIZONTAL
LONG SIDE VERTICAL
LIGHTWEIGHT
LIGHTWEIGHT CONCRETE
MASONRY
MATERIAL
MAXIMUM
MECHANICAL
MOMENT FRAME
MANUFACTURER
MIDDLE
MINIMUM
MODIFY
MIDDEPTH OF SLAB
NOMINAL
NEAR SIDE
NOT TO SCALE
ON CENTER
OPPOSITE HAND
OPENING
POWDER ACTUATED
FASTENER
PARALLEL
PIECE
PRE-ENGINEERED METAL
BUILDING
PENETRATE, PENETRATION
PERPENDICULAR
PLATE
POST-TENSIONED (CONC)
PRESSURE TREATED (WOOD)
RADIUS
REFERENCE, REFER TO
REINFORCE, REINFORCED,
REINFORCING
REQUIRED
REQUIREMENTS
SCHEDULE
STEPPED FOOTING
STEPPED GRADE BEAM
SIMILAR
SAWED JOINT
SLOPE
SLAB-ON-GRADE
SIDEPLATE FRAME
STANDARD
STIFFENER
TRUSS BEARING ELEVATION
TOP & BOTTOM
TONGUE AND GROOVE
THICKNESS
TOP OF CONCRETE
TOP OF FOOTING
TOP OF MASONRY
TOP OF CONCRETE PEDESTAL
TOP OF STEEL
THICKENED SLAB
THICKENED SLAB AT STAIR
TYPICAL
UNLESS OTHERWISE NOTED
VERTICAL
WITH
WORKING POINT
WOOD STRUCTURAL PANEL(S)
WELDED WIRE REINFORCING
IMEG RESERVES PROPRIETARY RIGHTS,
INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN
THEREON. SAID DRAWING AND/OR DATA
ARE THE EXCLUSIVE PROPERTY OF IMEG
AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG.
©2025 IMEG CONSULTANTS CORP.
G
N
W E
IA
R
B SA
ID
D A
T E
R E
V
IE
W E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C H
E C
K E
D B
Y
R E
V D
E S
C R
IP
T
IO
N
A P
P R
V D
O C
I
A
R
A
O M B C
T
D
M
N M A
A
B
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
W
LT
K E
N N
E
LS
F A
C
IL
IT
Y
R E
P A
IR
M
IL
IT
A R
Y W
O R
K
IN
G D
O G
D A
T E
F
IL
E N
A M
E
D E
P A
R
TM
E N
T O
F T
H E
A
IR
F O
R C
E
A
IR
C O
M B
A T
C O
M M
A N
D
LA
N
G
LE
Y A
F B
V A
C
IV
IL
E
N G
IN
E
E R
IN
G
O F
F
IC
E
PROJECT NUMBER
JB
LE
M -1
MUHJ 24-4024
P L O
T D
A T
E
P L O
T S
C A
L E
S
U B
M
IT
T E
D B
Y
LMJA
P
JD
T
07/22/2025
J
U L now lynch
400 GRANBY STREET, SUITE 401
NORFOLK, VA 23510
919.782.1833 www.imegcorp.com mykins
ESE- -3-00
X01
X02
X03
X04
< -4'-0" >
< -2'-8" >
< -4'-0" >
< -2'-8" >
< -1'-4" >
< -1'-4" >
5'-0"
S101
D1
S101
D3
A1
S301S301
B1
S301S301
A2
S301S301
A3
S301S301
X03
X05
X06
X06
X06
SL
SL
+0'-0"±
-0'-2 1/2"±
+0'-1/2"±
B3
S301S301
104 (TYP.)
X03
103 103
101 101 101
101 101
104(TYP)
103 103
103 103
(TYP)
106 (TYP)
B. TOP OF ALL FOOTINGS MUST BE -1'-4" BELOW ADJACENT GRADES
UNLESS OTHERWISE NOTED.
C. REFERENCE CIVIL AND LANDSCAPE DRAWINGS FOR EXTERIOR
CONCRETE SLABS AND PAVING.
D. DIMENSIONS SHOWN ON FOUNDATION PLAN ARE TO COLUMN
GRIDLINES UNLESS OTHERWISE NOTED.
E. COORDINATE AND VERIFY ALL MEMBER LOCATIONS. DIMENSIONS.
WEIGHTS. OPENING SIZES. AND CURB DIMENSIONS FOR ALL
MECHANICAL EQUIPMENT WITH THE ACTUAL EQUIPMENT FURNISHED
INCLUDE THIS INFORMATION ON THE JOIST AND STRUCTURAL STEEL
SHOP DRAWINGS.
GENERAL PLAN NOTES
A. UNLESS OTHERWISE NOTED, ALL ELEVATIONS ARE BASED ON
FINISHED FIRST FLOOR REFERENCE OF 0'-0". EXISTING FINISHED
FLOOR ELEVATION IS 8.50±. REFERENCE ARCHITECTURAL DRAWINGS
FOR FINISHED FLOOR MATERIALS.
1 2
B
A
13'-7"
HSS6x 6x
3/
BPL
-1
HSS6x 6x
3/
BPL
-1
HSS6x 6x
3/
BPL
-1
HSS6x 6x
3/
BPL
-1CF3
CF3
CF3
CF3
( -1'-4" )
( -1'-4" )
( -1'-4" )
( -1'-4" )
1 2
B
A
13'-7"
W12x30
W x
W12x30
W x
0 105 (TYP)
SCALE: 1/4" = 1'-0"
EQUIPMENT FOUNDATION PLAN
D1 SCALE: 1/4" = 1'-0"
EQUIPMENT FRAMING PLAN
D3
COLUMN FOOTING SCHEDULE
MARK
SIZE REINFORCING
REMARKSLENGTH WIDTH DEPTH BOTTOM TOP
CF3 3' - 0" 3' - 0" 1'-0" (3) #5 EW (3) #5 EW -
IMEG RESERVES PROPRIETARY RIGHTS,
INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN
THEREON. SAID DRAWING AND/OR DATA
ARE THE EXCLUSIVE PROPERTY OF IMEG
AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG.
©2025 IMEG CONSULTANTS CORP.
G
N
W E
IA
R
B SA
ID
D A
T E
R E
V
IE
W E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C H
E C
K E
D B
Y
R E
V D
E S
C R
IP
T
IO
N
A P
P R
V D
O C
I
A
R
A
O M B C
T
D
M
N M A
A
B
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
W
LT
K E
N N
E
LS
F A
C
IL
IT
Y
R E
P A
IR
M
IL
IT
A R
Y W
O R
K
IN
G D
O G
D A
T E
F
IL
E N
A M
E
D E
P A
R
TM
E N
T O
F T
H E
A
IR
F O
R C
E
A
IR
C O
M B
A T
C O
M M
A N
D
LA
N
G
LE
Y A
F B
V A
C
IV
IL
E
N G
IN
E
E R
IN
G
O F
F
IC
E
PROJECT NUMBER
JB
LE
M -1
MUHJ 24-4024
P L O
T D
A T
E
P L O
T S
C A
L E
S
U B
M
IT
T E
D B
Y
LMJA
P
JD
T
07/22/2025
J
U L
3/16" = 1'-0"
FOUNDATION AND SLAB-ON-GRADE PLAN
A1
KEY NOTES
101 MINIMUM 4" CONCRETE TOPPING SLAB AT DOGHOUSE.
REINFORCE WITH 6x6 W2.9xW2.9 WELDED WIRE. MAINTAIN
REINFORCEMENT 1" CLEAR FROM TOP OF SLAB WITH
BOLSTERS OR CHAIRS. REFER TO ARCHITECTURAL DRAWINGS
FOR ADDITIONAL INFORMATION.
102 6" TALL BY 6" WIDE CONCRETE CURB. REINFORCE WITH (2) #3
MIDDLE OF CURB. ADHESIVE DOWEL 2" INTO EXISTING CURB
WITH #3 AT 1'-0" ON CENTER.
103 6" CONCRETE WALL REINFORCED WITH #4 AT 12" ON CENTER
EACH WAY MIDDLE OF WALL. DOWEL INTO EXISTING CONCRETE
OR MASONRY WALL 4" MINIMUM WITH #4 x 1'-6" REINFORCING AT
2'-0" ON CENTER.
104 4" CONCRETE MASONRY DOGHOUSE GROUTED SOLID. REFER
TO ARCHITECTURAL DRAWINGS FOR ADDITIONAL
INFORMATION.
105 TOP OF STEEL ELEVATION SHALL BE 4 FEET ABOVE FINISHED
GRADE. CONTRACTOR TO VERIFY AND COORDINATE ELEVATION
WITH CIVIL DRAWINGS.
106 REFER TO ARCHITECTURAL DRAWING FOR EXACT LOCATIONS,
DIMENSIONS, ELEVATIONS, AND OPENINGS OF ALL WALLS.
X01 EXISTING 8" MASONRY WALL WITH BRICK VENEER.
X02 EXISTING WALL FOOTING.
X03 EXISTING 6" CONCRETE WALL.
X04 EXISTING 1'-0" WIDE BY 8" THICKENED SLAB BELOW EXISITNG
WALL.
X05 EXISITNG 4" CONCRETE SLAB-ON-GRADE.
X06 EXISTING TRENCH DRAIN.
PLAN
NORTH
PLAN
NORTH
now lynch
400 GRANBY STREET, SUITE 401
NORFOLK, VA 23510
919.782.1833 www.imegcorp.com mykins
PLAN
NORTH
ESE--101
2'-0"
TS - REF PLANEXIST SLAB
1 1/2" (TYP)
#4 AT 2'-0" OC
(3) #4 CONT
REF
S501
B4
6" CONC WALL
REINF W/ #4 AT 12"
OC EW MOW
EL = +4'-0" +/-
EXIST SLABEXIST 6" ±
CONC WALL
REF ARCH DWGS
6" CONC
WALL REINF
W/ #4 AT 12"
OC EW MOW
REF
S501
A4
(+8'-0" MAX)
4" CMU REINF W/ #4
AT EA CORNER AND
AT OPENING JAMBS
(TYP)
EXIST CONC SLAB
KENNEL LID - REF
ARCH DWGS
TOM EL - REF
ARCH DWGS
/2
EXIST FTG - REF PLAN
EXISITING BRICK
EXISTING CMU WALL
EXISTING TRECH DRAIN
CONC WALL - REF PLAN
REF
S501
A4
SL
TS - REF PLAN
4" CMU REINF W/ #4
AT EA CORNER
AND AT OPENING
JAMB (TYP)
EXIST CONC SLAB
KENNEL LID - REF
ARCH DWGS
TOM EL - REF
ARCH DWGS
TS - REF PLAN
6" CONC WALL
REINF W/ #4 AT 12"
OC EW MOWREF
S501
B4
/2
IMEG RESERVES PROPRIETARY RIGHTS,
INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN
THEREON. SAID DRAWING AND/OR DATA
ARE THE EXCLUSIVE PROPERTY OF IMEG
AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG.
©2025 IMEG CONSULTANTS CORP.
G
N
W E
IA
R
B SA
ID
D A
T E
R E
V
IE
W E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C H
E C
K E
D B
Y
R E
V D
E S
C R
IP
T
IO
N
A P
P R
V D
O C
I
A
R
A
O M B C
T
D
M
N M A
A
B
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
W
LT
K E
N N
E
LS
F A
C
IL
IT
Y
R E
P A
IR
M
IL
IT
A R
Y W
O R
K
IN
G D
O G
D A
T E
F
IL
E N
A M
E
D E
P A
R
TM
E N
T O
F T
H E
A
IR
F O
R C
E
A
IR
C O
M B
A T
C O
M M
A N
D
LA
N
G
LE
Y A
F B
V A
C
IV
IL
E
N G
IN
E
E R
IN
G
O F
F
IC
E
PROJECT NUMBER
JB
LE
M -1
MUHJ 24-4024
P L O
T D
A T
E
P L O
T S
C A
L E
S
U B
M
IT
T E
D B
Y
LMJA
P
JD
T
07/22/2025
J
U L
3/4" = 1'-0"
SECTION
A1 3/4" = 1'-0"
SECTION
A2 3/4" = 1'-0"
SECTION
A3 now lynch
400 GRANBY STREET, SUITE 401
NORFOLK, VA 23510
919.782.1833 www.imegcorp.com mykins
3/4" = 1'-0"
SECTION
B1 3/4" = 1'-0"
SECTION
B3
ESE--301
GALV COL - REF PLAN
COL BASE PLATE -
REF DETAILS
TOP OF FTG
EL - REF PLAN
2" NON-SHRINK
GROUT
CL OF COL AND
FTG
PAINT ALL
STEEL BELOW
GRADE W/ TWO
HEAVY COATS
OF BLACK
ASPHAULTUM
ANCHOR RODS -
REF DETAILS
3" CLR (TYP)
FTG - REF PLAN
TOP REINF
WHERE
INDICATED
(TYP)
2" CLR
M
IN
FINISHED GRADE -
REF CIVIL DWGS
GALV PL3/8
W/ (3) A325N
BOLTS (TYP)
GALV BEAM
CL OF COL
GALV COLUMN
GALV CAP
PLATE EQUAL
IN SIZE
TO LARGEST
BM FLANGE
THICKNESS
FULL PEN
(TYP)
PROJECTION
AS REQD
BOT OF
FTG
NOTE:
FTG REINF
NOT SHOWN
DEEPEN FTG AS REQD
TO PROVIDE MIN ROD
CLEARANCES SHOWN
TOP OF
FOUNDATION
ANCHOR ROD
HSS
NOTE 'A'
TYP
ANCHOR ROD HOLE -
REF SCHED (TYP)
t = BASE PLATE
THICKNESS
PLATE WASHER - REF
SCHED (TYP AT ALL
ANCHOR RODS)
GROUT HOLE
(TYP OF 2)
GUSSET PLATE -
REF BRACED
FRAME DETAILS
(TYP)
SHEAR LUG
3/4"Ø 2" SQ 13/16"Ø 1/4"
ANCHOR
ROD WASHER
SIZE
WASHER
HOLE
WASHER
THICKNESS
ANCHOR ROD HOLES AND
WASHER SCHEDULE
OVERSIZED HOLE WITH PLATE WASHER
BASE PLATE
HOLE
1 5/16"Ø
NOTE:
A. PROVIDE MINIMUM SIZE WELD PER AISC TABLE J2.4.
CL OF
ANCHOR ROD
HOLE (TYP)
N
N
N
X
X
B
B1 B2
X4X3
ANCHOR ROD
C L R
E M
B E
D
3" C
LR
NOTE 'A'
• DRILL HOLES INTO EXIST
FTG TO RECEIVE DOWELS
• CLEAN HOLES
THOROUGHLY OF DEBRIS
AND FILL W/ EPOXY
• DIA OF HOLES MUST BE AS
RECOMMENDED BY MFR OF
EPOXY MATL
• IF NOT SPECIFIED BY
EPOXY MFR, DIA OF HOLES
MUST BE 1/8" LARGER
THAN DOWEL SIZE EXIST FTG
NOTE: VERT DOWEL
SHOWN. HORIZ
DOWEL SIMILAR
8" EMBED (TYP UON)
L
P
L E
N G
T H
SAWCUT 1" DEEP AT
PERIMETER OF AREA
TO BE REMOVED AND
BREAK OUT EXIST
SLAB
NEW SLABEXISTING SLAB
CONC SLAB -
REF PLAN
(MATCH EXIST
THICKNESS -
4" MIN)
CLEAN SURFACE AND
PAINT WITH BONDING
COMPOUND PRIOR TO
PLACING NEW CONC -
SURFACE OF EXISTING
SLAB MUST BE SOUND
EXISTING CONC
SLAB 6" 6"
#4 x 1'-0" AT 12"OC
DRILL AND EPOXY INTO
EX SLAB
WALL THICKNESS
(T) - REF RELEVANT
SECTION
WALL REINF -
REF RELEVANT
SECTION (TYP)
2" CLR
EXPOSED FACE
DISCONTINUE EVERY
OTHER HORIZ BAR
AT JOINT
PROVIDE CONTROL JOINTS AT A
MAXIMUM OF 15' OR 2X THE WALL
HEIGHT ON CENTER MAXIMUM (UON)
1 1/2" WIDE x 3/4"
DEEP FORMED VEE
CONTROL JOINT
2" CLR
WALL THICKNESS
(T) - REF RELEVANT
SECTION
WALL REINF -
REF RELEVANT
SECTION (TYP)
3" CLR
EXPOSED FACE
DISCONTINUE EVERY
OTHER HORIZ BAR
AT JOINT
1 1/2" WIDE x 3/4"
DEEP FORMED VEE
CONSTRUCTION JOINT
3" CLR
T /3
T /3
T /3
LS
PREVIOUS POUR NEW POUR PREVIOUS POUR NEW POUR
CONT 1 1/2"
DEEP KEY
ALIGN W/ CONTROL JOINT
LOCATION - REF ARCH
DWGS
REF ARCH DWGSFOR
JOINT LOCATIONS
VERT WALL REINF
(TYP)
CONT HORIZ
WALL REINF
(TYP)
CORNER
0" (TYP)
Ls
L s
VERT WALL REINF
(TYP)
CONT HORIZ
WALL REINF
(TYP)
INTERSECTION
0" (TYP)
Ls
L s
ALTERNATE
HOOK DIRECTION
EVERY-OTHER
BAR
NTS
TYPICAL COLUMN & FOOTING DETAIL
A1 NTS
TYPICAL WIDE FLANGE BEAM TO HSS
COLUMN MOMENT CONNECTION DETAILS
A2
NTS
LATERAL COLUMN BASE PLATE AND ANCHOR ROD DETAILS
B1
NTS
TYPICAL DETAIL AT CORNERS AND INTERSECTIONS OF CONCRETE WALLS
D3NTS
TYPICAL CONCRETE WALL VERTICAL JOINT DETAILS
D1
COLUMN BASE PLATE SCHEDULE - LATERAL COLUMNS
MARK
BASE PLATE DIMENSIONS ANCHOR RODS
REMARKSB N t B1 B2 N1 N2 X1 X2 X3 X4 DIAMETER QUANTITY EMBED
BPL-1 12" 12" 3/4" 6" 6" 6" 6" 1 1/2" 1 1/2" 1 1/2" 1 1/2" 3/4" 4 9"
NTS
TYPICAL EPOXY DOWEL DETAIL
A4
NTS
TYPICAL SLAB REMOVAL AND
REPLACEMENT DETAIL
B4
IMEG RESERVES PROPRIETARY RIGHTS,
INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN
THEREON. SAID DRAWING AND/OR DATA
ARE THE EXCLUSIVE PROPERTY OF IMEG
AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG.
©2025 IMEG CONSULTANTS CORP.
G
N
W E
IA
R
B SA
ID
D A
T E
R E
V
IE
W E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C H
E C
K E
D B
Y
R E
V D
E S
C R
IP
T
IO
N
A P
P R
V D
O C
I
A
R
A
O M B C
T
D
M
N M A
A
B
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
W
LT
K E
N N
E
LS
F A
C
IL
IT
Y
R E
P A
IR
M
IL
IT
A R
Y W
O R
K
IN
G D
O G
D A
T E
F
IL
E N
A M
E
D E
P A
R
TM
E N
T O
F T
H E
A
IR
F O
R C
E
A
IR
C O
M B
A T
C O
M M
A N
D
LA
N
G
LE
Y A
F B
V A
C
IV
IL
E
N G
IN
E
E R
IN
G
O F
F
IC
E
PROJECT NUMBER
JB
LE
M -1
MUHJ 24-4024
P L O
T D
A T
E
P L O
T S
C A
L E
S
U B
M
IT
T E
D B
Y
LMJA
P
JD
T
07/22/2025
J
U L now lynch
400 GRANBY STREET, SUITE 401
NORFOLK, VA 23510
919.782.1833 www.imegcorp.com mykins
ESE--501
LD
(TYP)
REINFORCING
AROUND OPNG
EQ TO AMOUNT
INTERRUPTED
(1/2 EA SIDE)
INTERRUPTED
REINF - TERMINATE
W/ 180° HOOK AND
TILT FROM VERT TO
PROVIDE SPECIFIED
CLEARANCES
(1) #5 DIAGONAL
MOW (TYP)
LD
(T Y P
OPNG OPNG
NOTES:
1. ALL OPENINGS IN CONCRETE
WALLS REQUIRE ADDITIONAL
REINFORCING AS INDICATED
EXCEPT WHERE OPENING SIZE
OR LOCATION IS SUCH THAT
REINFORCING STEEL IS NOT
INTERRUPTED.
2. CONDUITS, SMALL PIPES AND
OTHER SMALL SLEEVES THAT
DO NOT REQUIRE PRECISE
LOCATIONS MUST BE SHIFTED
SLIGHTLY TO CLEAR
REINFORCING.
1 1/2" CLR (TYP)
BAR
SIZE
TYPE
TENSION DEVELOPMENT LENGTH
AND LAP SPLICE SCHEDULE
CONCRETE COMPRESSIVE STRENGTH (PSI)
NOTES:
1. ALL VALUES LISTED ARE INCHES.
2. TABLE IS BASE ON VALUES FOR ACI 318-14.
3. VALUES LISTED ARE FOR NORMAL WEIGHT CONCRETE. FOR
LIGHTWEIGHT CONCRETE, MULTIPLY LENGTHS BY 1.33.
4. TOP BARS ARE DEFINED AS BARS WITH MORE THAN 12" OF
CONCRETE COVER BELOW BAR.
5. WHERE DIFFERENT SIZE BARS ARE SPLICED, PROVIDE THE
SPLICE LENGTH ASSOCIATED WITH THE LARGER BARS.
#3 Ld
Ls
#4 Ld
Ls
#5 Ld
Ls
#6 Ld
Ls
BAR
SIZE
TYPE
COMPRESSION DEVELOPMENT
LENGTH AND LAP SPLICE SCHEDULE
CONCRETE COMPRESSIVE STRENGTH (PSI)
NOTES:
1. ALL VALUES LISTED ARE INCHES.
#3 Ldc
Lds
#4 Ldc
Lds
#5 Ldc
Lds
#6 Ldc
Lds
TOP BAR OTHER
TOP BAR OTHER
TOP BAR OTHER
3000 4000 5000
CONT REINF
0" (TYP)
GROUT
SOLID
CORNER INTERSECTION
CLOSED
BOTTOM
OPEN
BOTTOM
WALL THICKNESS
2" 2" 2" 2"
HOOK
1'-0"
(TYP)
CONT REINF
(TYP)
(1) #4
BOT
(2) #4
BOT
(2) #5
BOT
(2) #5
BOT
(2) #5
BOT
(2) #5 T&B
(2) #5 T&B
(1) #5 T&B
(1) #5
BOT
(2) #5
BOT
(2) #5
BOT
(1) #5
BOT
BOND BEAM LINTEL SCHEDULE
DEPTH
'D'
CLEAR SPAN
REINFORCING
8"&10" CMU4" & 6" CMU 12" CMU
FORM MULTI-UNIT LINTELS
BY CASTING OPEN UNIT
ABOVE, MONOLITHICALLY
WITH CLOSED UNIT AT BOT
EL - REF ARCH
OR MECH DWGS
TOP REINF
REF BOND BM
LINTEL SCHED
BOT REINF
NOTES:
1. REFER TO ARCHITECTURAL DRAWINGS
FOR SIZE AND LOCATION OF OPENINGS;
FOR DUCT OPENINGS REFER TO
MECHANICAL DRAWINGS.
2. REFER TO ARCHITECTURAL DRAWINGS
FOR WIDTH OF LINTEL.
3. SCHEDULE APPLIES ONLY TO LINTELS NOT
OTHERWISE SHOWN ON THE DRAWINGS.
0" TO 3'-4"
3'-5" TO 5'-4"
5'-5" TO 6'-8"
6'-9" TO 8'-0" 16"
16"
8"
8"
TYPICAL
SECTION
TYPICAL
JAMB
MAS OPNG
8" BRG
'D
OPENING
BOND BEAM LINTEL PER
DETAILS ON THIS
SHEET
FULL HEIGHT
JAMB REINF
24" EA SIDE, UNLESS
INDICATED TO BE
CONTINUOUS
8" DEEP CMU BOND BEAM REINF
AS FOLLOWS: (1) #4 AT 6" WIDE
(2) #4 AT 8" AND 10" WIDE (2) #5
AT 12" WIDE
24" AT OPENING 48" OR LESS
IN HEIGHT OR WIDTH. EXTEND
FULL HT AT OPENINGS
GREATER THAN 48"
/2
C
L R
M
IN
1/ 2"
C
LR
(M
IN
PLAN
CONDUIT
VERTICAL
WALL REINF
CMU
NOTES:
1. LOCATE CONDUIT IN UNREINFORCED CELLS
TO EXTENT POSSIBLE.
2. DO NOT PLACE CONDUIT PASSING
HORIZONTALLY THROUGH PLANE OF WALL
WITHOUT WRITTEN APPROVAL.
3. CONDUIT SIZES GREATER THAN OR EQUAL TO
1 1/2" DIAMETER MUST BE PLACED IN
UNREINFORCED CELLS.
NOMINAL
CMU SIZE
4"
6"
8"
10"
12"
14"
16"
MAXIMUM AREA OF
GROUT DISPLACEMENT*
NOTE *: PER ACI 530.1
0.284 in²
0.456 in²
0.646 in²
0.884 in²
1.132 in²
1.380 in²
1.628 in²
CONDUIT
SIZE
1/2"Ø
3/4"Ø
1"Ø
1 1/4"Ø
AREA OF DISPLACEMENT
(SINGLE CONDUIT)
0.196 in²
0.442 in²
0.785 in²
1.227 in²
TOTAL DISPLACEMENT CALC
1/2"Ø + 3/4"Ø CONDUIT IN SAME CELL =
0.196 in² + 0.442 in² = 0.638 in²
NTS
TYPICAL CONCRETE WALL OPENING DETAILS
A1
IMEG RESERVES PROPRIETARY RIGHTS,
INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN
THEREON. SAID DRAWING AND/OR DATA
ARE THE EXCLUSIVE PROPERTY OF IMEG
AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG.
©2025 IMEG CONSULTANTS CORP.
G
N
W E
IA
R
B SA
ID
D A
T E
R E
V
IE
W E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C H
E C
K E
D B
Y
R E
V D
E S
C R
IP
T
IO
N
A P
P R
V D
O C
I
A
R
A
O M B C
T
D
M
N M A
A
B
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
W
LT
K E
N N
E
LS
F A
C
IL
IT
Y
R E
P A
IR
M
IL
IT
A R
Y W
O R
K
IN
G D
O G
D A
T E
F
IL
E N
A M
E
D E
P A
R
TM
E N
T O
F T
H E
A
IR
F O
R C
E
A
IR
C O
M B
A T
C O
M M
A N
D
LA
N
G
LE
Y A
F B
V A
C
IV
IL
E
N G
IN
E
E R
IN
G
O F
F
IC
E
PROJECT NUMBER
JB
LE
M -1
MUHJ 24-4024
P L O
T D
A T
E
P L O
T S
C A
L E
S
U B
M
IT
T E
D B
Y
LMJA
P
JD
T
07/22/2025
J
U L now lynch
400 GRANBY STREET, SUITE 401
NORFOLK, VA 23510
919.782.1833 www.imegcorp.com mykins
NTS
TYPICAL REINFORCING SPLICE SCHEDULES
B1
NTS
TYPICAL BOND BEAM REINFORCING DETAILS
A4
NTS
BOND BEAM LINTEL DETAILS
D4
NTS
TYPICAL MASONRY REINFORCING
AT WALL OPENING DETAIL
B4
NTS
TYPICAL EMBEDDED CONDUIT IN MASONRY DETAIL
D1
ESE--5002
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
ABBREVIATIONS
ARCHITECTURAL LEGEND
GENERAL ARCHITECTURAL NOTES
A-201
A2
A-001
A-301
B1
A
B
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
SHEET KEYNOTES
X
0' 3' 6' 9'
SCALE 3/16" = 1'-0"
DEMOLITION FLOOR PLAN
A1
PLAN
AD101
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
S
0' 3' 6' 9'
SCALE 3/16" = 1'-0"
DEMOLITION ROOF PLAN
A1
PLAN
NORTH
AD102
GENERAL SHEET NOT
A-201
D1
A-201
B4
A-201
A1
A-201
B1
A-201
D1
A-201
B4
A-301
B4
A-101
D4
A-402
D2
A-402
D3
A-401
C3
A-401
C1
A
B
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
0' 3' 6' 9'
SCALE 3/16" = 1'-0"
NEW WORK FLOOR PLAN
A1
PLAN
NORTH
SCALE 1/2" = 1'-0"
DETAIL PLAN
D4
ENLARGED KENNEL
A1
A-101
0' 1' 2'
SCALE 1 1/2" = 1'-0"
CURB DETAIL
D3
A1
A-101
A-101
0' 6" 1'
SCALE 1 1/2" = 1'-0"
GRATING DETAIL
D5
A1
A-401
0' 6" 1'
A-501
A5
A-501
A1
A-501
A3
A-501
D5
A-501
A1
A-501
A1
A-501
A1
A-501
D5
A-501
D6
A-501
D5
A-501
D5
A-501
A1
A-201
D1
A-201
B4
A-201
A1
A-201
B1
A-201
D1
A-201
B4
A
B
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
S
0' 3' 6' 9'
SCALE 3/16" = 1'-0"
NEW WORK ROOF PLAN
A1
PLAN
NORTH
SCALE: 3" = 1'-0"
BASE FLASHING DETAILD3
0' 6"3"
A-102
A1
A-501
A1
A-501
A1
A-501
A1
A-501
A1
A
B
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
0' 3' 6' 9'
SCALE 3/16" = 1'-0"
ATTIC PLAN
A1
PLAN
NORTH
SCALE: 3" = 1'-0"
EXISTING ACCESS DETAILD3
SCALE: 3" = 1'-0"
NEW ACCESS DETAILD4
0' 6"3" 0' 6"3"
A-103
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
0' 3' 6' 9'
SCALE 3/16" = 1'-0"
REFLECTED CEILING PLAN
A1
PLAN
NORTH
SHEET KEYNOTES
A-104
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
FLOOR FINISH PLAN
A1
PLAN
A-105
A3
A
B
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
SOUTH EXTERIOR ELEVATION
D1
0' 3' 6' 9'
SCALE 3/16" = 1'-0"
NORTH EXTERIOR ELEVATION
A1
0' 3' 6' 9'
SCALE 3/16" = 1'-0"
EAST EXTERIOR ELEVATION
B1
SHEET KEYNOTES
X
S
0' 3' 6' 9'
SCALE 3/16" = 1'-0"
WEST EXTERIOR ELEVATION
B4
A-201
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
SCALE 1/2" = 1'-0"
DEMOLITION BUILDING SECTION
B1
0' 1' 2' 4'
SCALE 1/2" = 1'-0"
NEW WORK BUILDING SECTION
B4
0' 1' 2' 4'
A-301
A-401
A-401
A1
A-401
D3
A-401
A5
A-401
A3
A-401
D3
A-401
C5
A-401
A1
A-101
D5
A-101
E1
A-401
D3
A-401
D4
A
B
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
SCALE 1/2" = 1'-0"
ENLARGED KENNEL PLAN
C3
0' 1' 2' 4'
SHEET KEYNOTES
X
PLAN
NORTH
SCALE 1/2" = 1'-0"
ENLARGED KENNEL PLAN
C1
0' 1' 2' 4'
PLAN
NORTH
SCALE 1/2" = 1'-0"
TYPICAL KENNEL ELEVATION
A3
0' 1' 2' 4'
SCALE 1/2" = 1'-0"
KENNEL SECTION
A5
0' 1' 2' 4'
0' 6" 9" 1'3"
SCALE 3" = 1'-0"
DOG HOUSE ACCESS HATCH DETAIL
D4
SCALE 1/2" = 1'-0"
PARTIAL KENNEL ELEVATION
A1
0' 1' 2' 4'
0' 6" 9" 1'3"
SCALE 3" = 1'-0"
DOG HOUSE ACCESS HATCH DETAIL
D3
A-401
SCALE 1/2" = 1'-0"
PARTIAL KENNEL ELEVATION
C5
0' 1' 2' 4'
0' 6" 9" 1'3"
SCALE 3" = 1'-0"
DOG HOUSE ACCESS HATCH DETAIL
E1
A-402
A-402
A2
A-402
A3
A-402
A2
A
B
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
SCALE 1 1/2" = 1'-0"
CASEWORK SECTION
A2
0' 6" 1'
SCALE 1 1/2" = 1'-0"
CASEWORK SECTION
A3
0' 6" 1'
SCALE 3/8" = 1'-0"
CASEWORK ELEVATION
D2
0' 1' 2' 4'
SCALE 3/8" = 1'-0"
CASEWORK ELEVATION
D3
0' 1' 2' 4'
A-402
A-102
D3
A-501
A5
A-501
A3
A
B
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
SCALE: 3" = 1'-0"
BASE FLASHING DETAILD6
SCALE: 3" = 1'-0"
RAKE DETAILD5
SCALE: 3" = 1'-0"
RIDGE VENT DETAILD3
SCALE: 3" = 1'-0"
VENT DETAILD2
SCALE: 3" = 1'-0"
VTR DETAILD1
SCALE: 3" = 1'-0"
ROOF EAVE DETAILA1
0' 6"3" 0' 6"3" 0' 6"3" 0' 6"3" 0' 6"3"
0' 6"3"
SCALE: 1 1/2" = 1'-0"
DORMER SECTIONA3
0' 6" 1'
SCALE: 1 1/2" = 1'-0"
DORMER SECTIONA5
0' 6" 1'
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
DETAILS
JAMB
TYPE
DOOR
WIDTH
MARK
HEIGHT
SIZE
THICK
DOOR SCHEDULE
FRAME
TYPE
MATERIAL
DOOR FRAME
L A
B E
L
H D
W
HEAD SILL
NOTES
WALLS
FINISH SCHEDULE
NO
RM
FLOORBASEROOM NAME
MATERIAL PAINT
CEILING
CLG
HT
NOTES
PAINTMATERIAL
MATERIAL TYPE MATERIAL SELECTION
FINISH LEGEND
SCALE: 3" = 1'-0"
DOOR HEAD DETAILC1
0' 6" 9" 1'3"
SCALE: 3" = 1'-0"
DOOR HEAD DETAILA1
0' 6" 9" 1'3"
SCALE: NONE
DOOR TYPESD1
SCALE: NONE
FRAME TYPESD2
SCALE: 3" = 1'-0"
DOOR HEAD DETAILB2
0' 6" 9" 1'3"
SCALE: 3" = 1'-0"
DOOR JAMB DETAILA2
0' 6" 9" 1'3"
FINISH SCHEDULE NOTES:
SCALE: 3" = 1'-0"
DOOR HEAD DETAILA4
0' 6" 9" 1'3"
A-601
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
VANSANT & GUSLER, INC.
CONSULTING ENGINEERS
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
PLUMBING FIXTURE SCHEDULE
WATER HEATER SCHEDULE
GENERAL PLUMBING NOTES
PLUMBING LEGEND
X
XXXX#
ABBREVIATIONS
FLOOR DRAIN SCHEDULE
P-001
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
VANSANT & GUSLER, INC.
CONSULTING ENGINEERS
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
SHEET KEYNOTESX
GENERAL SHEET NOTES
PLAN
NORTH
0' 4' 8' 12'
DEMOLITION PLANA1
PD101
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
VANSANT & GUSLER, INC.
CONSULTING ENGINEERS
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
0' 4' 8' 12'
SANITARY WASTE PLAN - NEW WORKA1
P-101
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
VANSANT & GUSLER, INC.
CONSULTING ENGINEERS
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
NORTH
0' 4' 8' 12'
DOMESTIC WATER PLAN - NEW WORKA1
P-102
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
VANSANT & GUSLER, INC.
CONSULTING ENGINEERS
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
FLOOR DRAIN DETAILC3 TRENCH FLUSH DETAILC5
TYPICAL PIPE SUPPORT DETAILA5INSTANTANEOUS WATER HEATER DIAGRAMA3PHOTO DETAIL - INCOMING WATER LINEA1 P-501
RISER CLAMP
SPACED TO CLEAR BEAM
SECURE TO WALL
WITH 1/2" DIA TOGGLE
BOLT (TYPICAL)
CONDENSER WATER PIPING
3/8" DIA BOLT (TYPICAL)
STEEL PIPE
PROTECTIVE SLEEVE
VERTICAL PIPING SUPPORT DETAILE5
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
VANSANT & GUSLER, INC.
CONSULTING ENGINEERS
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
SANITARY WASTE RISER DIAGRAMB1 DOMESTIC WATER RISER DIAGRAMB4
P-601
M-001
B
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
VANSANT & GUSLER, INC.
CONSULTING ENGINEERS
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
GENERAL MECHANICAL NOTES MECHANICAL LEGEND
SCALE: #" = #' - #"
XXXX#
E-401 A2
ABBREVIATIONS
VENTILATION RATES
DESIGN CONDITIONS
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
VANSANT & GUSLER, INC.
CONSULTING ENGINEERS
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
0' 4' 8' 12'
GENERAL SHEET NOTES
DEMOLITION PLANA1
MD101
T
A
B
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
VANSANT & GUSLER, INC.
CONSULTING ENGINEERS
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
0' 4' 8' 12'
NEW WORK PLANA1
GENERAL SHEET NOTES
M-101
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
VANSANT & GUSLER, INC.
CONSULTING ENGINEERS
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
MECHANICAL SECTIONA4 0' 1' 2' 4'
M-301
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
VANSANT & GUSLER, INC.
CONSULTING ENGINEERS
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
TYPICAL EXTERIOR DUCTWORK SUPPORT DETAILA3
TYPICAL SUPPLY SUPPORT DETAILA5
TYPICAL SUPPLY DIFFUSER CONNECTION DETAILC5COIL CONDENSATE TRAP DETAILC3
TYPICAL RETURN/EXHAUST GRILLE CONNECTION DETAILD5EXHAUST FAN DETAILD3
EXHAUST ROOF CAP DETAILA1
M-501
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
VANSANT & GUSLER, INC.
CONSULTING ENGINEERS
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
DEDICATED OUTSIDE AIR SYSTEM SEQUENCE OF OPERATIONS
DEDICATED OUTSIDE AIR SYSTEM FLOW DIAGRAMC1
EXHAUST FAN SCHEDULE
M-601
DUCT CONSTRUCTION AND LEAK TEST SCHEDULE
DEDICATED OUTSIDE AIR SYSTEM SCHEDULE
GRILLE, REGISTER AND DIFFUSER SCHEDULE
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
VANSANT & GUSLER, INC.
CONSULTING ENGINEERS
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
ABBREVIATIONS ELECTRICAL LEGEND
E
ES
ESx
Ex
X
XXXX#
E
MDP
400-AMP
208Y/120-VOLT
3-PHASE
4-WIRE
MCB
GENERAL ELECTRICAL NOTES
PAD-MOUNTED TRANSFORMER DETAILA1 E-001
SAN SAN
FM
FM
COMM
COMM
COMM
COMMFO
FO
COMM
CO
M
M
CO
M
M
ESx ESx
ESx ESx ESx ESx ESx ESx ESx
E
E
E
E
ES
EEEE
E
E
E
E
E
E
E
E E
E E
E E
E E
E E
E E
E E
E E
E E
E E
E E
E
E E
E E
E E E
E
E E
E
COMMCOMMCOMM
COMM
W W
W
W W
WWWWWWWWWWW
ESx ESx ESx ESx ESx
SAN
FM
SAN
SAN
SAN
W
W W
W
COMMCOMMCOMMCOMMCOMMCOMMCOMMCOMM
COMM
S
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
Ex
Ex
Ex
Ex
Ex
Ex
Ex
Ex
E x
Ex
E
E
EM125
EM124
E X
ES
ES ES ES ES
A
B
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
VANSANT & GUSLER, INC.
CONSULTING ENGINEERS
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
SITE PLANA1 60'0' 30'
FACILITY 1030
ES101
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
VANSANT & GUSLER, INC.
CONSULTING ENGINEERS
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
0' 4' 8' 12'
GENERAL SHEET NOTES
LIGHTING PLAN - DEMOLITIONA1
ED101
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
VANSANT & GUSLER, INC.
CONSULTING ENGINEERS
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
0' 4' 8' 12'
POWER AND SPECIAL SYSTEMS PLAN - DEMOLITIONA1
SHEET KEYNOTESX
ED102
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
VANSANT & GUSLER, INC.
CONSULTING ENGINEERS
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
0' 4' 8' 12'
GENERAL SHEET NOTES
SHEET KEYNOTESX
LIGHTING PLAN - NEW WORKA1
E-101
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
VANSANT & GUSLER, INC.
CONSULTING ENGINEERS
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
0' 4' 8' 12'
POWER AND SPECIAL SYSTEMS PLAN - NEW WORKA1
SHEET KEYNOTESX
E-102
C
D
E
1 2 3 4 5 6
1 2 3 4 5 6
VANSANT & GUSLER, INC.
CONSULTING ENGINEERS
KE
NN
EL
S
FA
CI
LI
TY
RE
PA
IR
M
IL
IT
AR
Y W
O
RK
IN
G
D
POWER RISER DIAGRAM - DEMOLITIONB2
POWER RISER DIAGRAM - NEW WORKA2
GENERAL SHEET NOTES
SHEET KEYNOTES
MSD
400-AMP
208Y/120-VOLT
3-PHASE
4-WIRE
MCB
P2
100-AMP
240/120-VOLT
1-PHASE
3-WIRE
MLO
P1
255-AMP
240/120-VOLT
1-PHASE
3-WIRE
MCB
LP
225-AMP
240/120-VOLT
1-PHASE
3-WIRE
MCB
P2
100-AMP
240/120-VOLT
1-PHASE
3-WIRE
MLO
MDP
400-AMP
208Y/120-VOLT
3-PHASE
4-WIRE
MLO
E-601
LUMINAIRE SCHEDULE
MARK DESCRIPTION MANUFACTURER MODEL
LIGHT ENGINE INPUT
WATTS MOUNTING REMARKS
TYPE LUMENS VOLTAGE
A LED WRAPAROUND COLUMBIA LIGHTING LAW4-40XW-EU LED 2405 120-277 19 CEILING, SURFACE 1 B LED WRAPAROUND COLUMBIA LIGHTING LAW4-40MW-EU LED 3784 120-277 31 CEILING, SURFACE 1 C 6" DOWNLIGHT LEDRA BRANDS NU6-RD-SW-20LM-40K- 80-WH70-120-DIM10-NC-WH-WH LED 1639 120-277 17 CEILING, RECESSED D LINEAR VAPORTITE COLUMBIA LIGHTING LXEM4-40LW-DFA-EDU LED 4451 120-277 33 CEILING, SURFACE 1 F WALLPACK CURRENT LIGHTING LNC2-48L25-4K7-4W-UNV-BLS LED 2862 120-277 25 WALL, SURFACE, 8' AFF 1, 2 G EXTERIOR LIGHTING CURRENT LIGHTING LSQ1-25-4K7-UNV-BLT LED 3055 120-277 34 CEILING, SURFACE 1, 2
NOTES:
1. PROVIDE EMERGENCY BATTERY BACKUP WHERE INDICATED.
2. PROVIDE PHOTOCELL CONTROL WHERE INDICATED.
PANELBOARD MDP SCHEDULE
400-AMP MCB, 208/120-VOLT, 3-PHASE, 4-WIRE, 10,000-AMP SCCR, SURFACE MOUNTED
LOAD SERVED
LOAD (AMPS)
BKR RTG CKT NO CKT NO BKR RTG
LOAD (AMPS)
LOAD SERVED
A B C A B C
DOAS-1 170 175 1 2 100 71 PANEL P2
170 71
170 6 20 EXISTING CIRCUIT (P1-2)
EXISTING CIRCUIT (P1-1) 3 20 7 8 20 9 EXISTING CIRCUIT (P1-4)
EXISTING CIRCUIT (P1-3) 3 20 9 10 20 9 EXISTING CIRCUIT (P1-6)
EXISTING CIRCUIT (P1-5) 9 20 11 12 20 9 EXISTING CIRCUIT (P1-8)
EXISTING CIRCUIT (P1-7) 3 30 13 14 20 SPARE
EXISTING CIRCUIT (P1-9) 3 50 15 16 20 SPARE
EXISTING CIRCUIT (P1-11) 24 30 17 18 20 16 EXISTING CIRCUIT (P1-14)
24 16
AH (P1-15) 32 60 21 22 20 EXISTING CIRCUIT (P1-14)
32 24 20 EXISTING CIRCUIT (P1-20)
EXISTING CIRCUIT (P1-19) 20 25
EXISTING CIRCUIT (P1-21) 20 27 28 20 EXISTING CIRCUIT (P1-24)
BITI 20 29 30 20 EXISTING CIRCUIT (P1-26)
EXISTING CIRCUIT (P1-25) 20 31 32 60 EXISTING CIRCUIT (P1-28)
EXISTING CIRCUIT (P1-27) 100 33
36 20 F.A
EXISTING CIRCUIT (P1-31) 3 20 37 38 30 EXISTING CIRCUIT (P1-36)
EXISTING CIRCUIT (P1-33) 3 20 39
EXISTING CIRCUIT (P1-35) 20 41 42 20 2 GFCI RECEPTACLE
SPARE 20 43 44 20 SPARE
SPARE 20 45 46 20 SPARE
ICE MACHINE RECEPT 4 15 47 48 20 11 IWH-1
SPACE 49 11
SPACE 51 52 30 16 CU (P1-10)
SPACE 53 16
TOTAL 203 211 239 107 96 54 TOTAL
TOTAL CONNECTED AMPS A:310 B:307 C:293
EXISTING PANELBOARD P2 SCHEDULE
SQUARE D E2, 100-AMP MLO, 240/120-VOLT, 1-PHASE, 3-WIRE, 10,000-AMP SCCR, SURFACE MOUNTED
LOAD SERVED
LOAD (AMPS)
BKR RTG CKT NO CKT NO BKR RTG
LOAD (AMPS)
LOAD SERVED
A B A B
SPACE 1 2 SPACE
SPACE 3 4 SPACE
SPARE 0 20 5 6 20 12 EXISTING CIRCUIT
0 12
SPARE 0 20 9 10 20 0 SPARE
0 0
KENNEL EF 3 20 13 14 20 12 EXISTING CIRCUIT
3 12
SPRINKLER AIR COMPRESSOR 6 20 17 18 20 6 EXISTING CIRCUIT
SPARE 20 19 20 20 12 ICE MACHINE
RANGE 32 40 21 22 SPACE
32 24 SPACE
27 28 29 30
TOTAL 41 35 30 36 TOTAL
| Sheets and Views |
| G-001 TITLE SHEET |
| G-002 PHASING PLAN |
| P-001 GENERAL NOTES, LEGEND, ABBREVIATIONS AND SCHEDULES |
| PD101 DEMOLITION PLAN |
| P-101 SANITARY WASTE PLAN - NEW WORK |
| P-102 DOMESTIC WATER PLAN - NEW WORK |
| P-501 DETAILS |
| P-601 RISER DIAGRAMS |
| M-001 GENERAL NOTES, LEGEND AND ABBREVIATIONS |
| MD101 DEMOLITION PLAN |
| WORKING(2) |
| M-101 NEW WORK PLAN |
| WORKING |
| M-301 SECTIONS |
| M-501 DETAILS |
| M-601 SCHEDULES |
| E-001 GENERAL NOTES, LEGEND, DETAIL, AND ABBREVIATIONS |
| ES101 SITE PLAN |
| ED101 LIGHTING PLAN - DEMOLITION |
| ED102 POWER AND SPECIAL SYSTEMS PLAN - DEMOLITION |
| WORKING |
| E-101 LIGHTING PLAN - NEW WORK |
| WORKING |