This document contains mechanical calculations for repairing Military Working Dog Kennels at Facility 1030 on Joint Base Langley-Eustis in Hampton, Virginia, prepared by Vansant & Gusler Consulting Engineers on July 22, 2025. The mechanical calculations focus on outside air requirements and ventilation specifications for two dog kennels, with calculations demonstrating 12 air changes per hour based on the Design Guide for Military Working Dog Facilities from August 5, 2003. The calculations detail room volumes, ventilation rates, and cooling/heating loads for Dog Kennel 01 (1,065 sq ft) and Dog Kennel 02 (925 sq ft), utilizing a Dedicated Outdoor Air System (DOAS) with cooling and heating coils. The system includes two fans and is designed to manage temperature and air quality for the kennel spaces, with peak cooling and heating load analyses provided for different times of the year.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Joint Base Langley-Eustis Hampton, Virginia
MECHANICAL CALCULATIONS
Prepared By:
Repair Military Working Dog Kennels
Facility 1030
MUHJ 24-4024
July 22, 2025
Outside Air Requirements:
Per Design Guide for Military Working Dog Facilities, 5 Aug. 2003, the total air changes in the kennel area should be 10-15 air changes per hour.
• A total of 12 air changes per hour will be chosen to serve Facility 1030.
- Kennel 01 Room Volume: 1,065ft2 floor area x 8ft ceiling height = 8,520ft3
8,520𝑓𝑡3 ×
12𝐴𝐶
1 ℎ𝑜𝑢𝑟
1 ℎ𝑜𝑢𝑟
60 𝑚𝑖𝑛𝑢𝑡𝑒𝑠 = 𝟏, 𝟕𝟎𝟒 𝒇𝒕𝟑 𝒎𝒊𝒏𝒖𝒕𝒆
(𝑪𝑭𝑴)
- Kennel 02 Room Volume: 925ft2 floor area x 8ft ceiling height = 7,400ft3
7,400𝑓𝑡3 ×
12𝐴𝐶
1 ℎ𝑜𝑢𝑟
1 ℎ𝑜𝑢𝑟
60 𝑚𝑖𝑛𝑢𝑡𝑒𝑠 = 𝟏, 𝟒𝟖𝟎 𝒇𝒕𝟑 𝒎𝒊𝒏𝒖𝒕𝒆
(𝑪𝑭𝑴)
- Total Ventilation provided to the kennels: 3,184 CFM
Room Cooling and Heating Loads by Component
ROOM_Dog Kennel 01
Conditions at Time of Space Cooling Peak Peak Time (Mo/D/H:M) 2/21 09:00:00
Outside DB / WB / HR 54.0 °F / 50.6 °F / 49.2 gr/lb Room DB / RH / HR 75.0 °F / 89.2 % / 116.8 gr/lb Supply Air Dry Bulb Temp 55.0 °F
Time Percent Instant Delay of
Sensible Sensible Latent Total Total
(Btu/h) (Btu/h) (Btu/h) (Btu/h) (%) Roof 0 0 0 0 0.0 Other Roof 0 0 0 0 0.0 Glass -1,459 3,185 0 1,726 2.2 Door 0 0 0 0 0.0 Wall 0 -1,495 0 -1,495 -1.9 Below-Grade Wall 0 0 0 0 0.0 Other Wall 0 0 0 0 0.0 Partition 0 9 0 9 0.0 Exterior Floor 0 0 0 0 0.0 Interior Floor 0 0 0 0 0.0 Slab 0 -1,619 0 -1,619 -2.0 Other Floor 0 0 0 0 0.0 Infiltration -2,354 0 -4,858 -7,212 -9.1
Envelope Subtotal -3,813 80 -4858 -8,591 - People 0 0 0 0 0.0
Lights 39,072 41,895 0 80,967 102.3
Miscellaneous Loads 0 0 77,169 77,169 97.5
Internal Subtotal 39,072 41,895 77,169 158,136 - RA (All Other) 0 0 0 0 0.0 DOA Direct to Room 0 0 -72,378 -72,378 -91.5 Ceiling 0 3,335 0 3,335 4.2 Refrigeration 0 0 0 0 0.0 Service Water 0 0 0 0 0.0 HVAC Equipment Losses 0 0 0 0 0.0 Adj Air Transfer Heat 0 0 0 0 0.0 Sizing Factor Correction 0 0 0 0 0.0 Time Delay Correction 0 -1,362 0 -1,362 -1.7
Grand Total 35,259 43,948 -68 79,139 100.0 RA Sensible (Lights) 0 0 0 0 -
Engineering Checks For Cooling
Cooling tons 6.59 No People(max) 0.00 %OA 0 People per 1000 ft² 0 cfm/ft² 4.24 Volume (ft³) 6,785.7 cfm/ton 0.00 ft²/ton 128.63 Btu/h-ft² 93.29
Conditions at Time of Space Heating Peak Peak Time (Mo/D/H:M) 1/21 24:00:00
Outside DB / WB / HR 20.7 °F / 15.6 °F / 5.1 gr/lb Room DB / RH / HR 70.0 °F / 4.7 % / 5.1 gr/lb Supply Air Dry Bulb Temp 75.0 °F
Time Percent Instant Delay of
Sensible Sensible Latent Total Total
(Btu/h) (Btu/h) (Btu/h) (Btu/h) (%) Roof 0 0 0 0 0.0 Other Roof 0 0 0 0 0.0 Glass -4,968 0 0 -4,968 8.6 Door 0 6 0 6 0.0 Wall 0 -3,220 0 -3,220 5.6 Below-Grade Wall 0 0 0 0 0.0 Other Wall 0 0 0 0 0.0 Partition 0 59 0 59 -0.1 Exterior Floor 0 0 0 0 0.0 Interior Floor 0 0 0 0 0.0 Slab 0 -137 0 -137 0.2 Other Floor 0 0 0 0 0.0 Infiltration -5,894 0 0 -5,894 10.2
Envelope Subtotal -10,861 -3,291 0 -14,152 - People 0 0 0 0 0.0
Lights 0 0 0 0 0.0
Miscellaneous Loads -50,880 0 0 -50,880 88.2
Internal Subtotal -50,880 0 0 -50,880 - RA (All Other) 0 0 0 0 0.0 DOA Direct to Room 8,236 0 0 8,236 -14.3 Ceiling 0 -755 0 -755 1.3 Refrigeration 0 0 0 0 0.0 Service Water 0 0 0 0 0.0 HVAC Equipment Losses 0 0 0 0 0.0 Adj Air Transfer Heat 0 0 0 0 0.0 Sizing Factor Correction 0 0 0 0 0.0 Time Delay Correction 0 -130 0 -130 0.2
Grand Total -53,506 -4,177 0 -57,682 100.0 RA Sensible (Lights) 0 0 0 0 -
Engineering Checks For Heating
Heating Mbh -57.68 No People(max) 0.00 %OA 0 People per 1000 ft² 0 cfm/ft² 12.55 Volume (ft³) 6,785.7 cfm/Mbh 0.00 ft²/Mbh -14.71 Btu/h-ft² -67.98
Cooling Airflows
Main Fan cfm 0 Cooling ACH 0.00 Sec Fan cfm 0
Input Ventilation cfm 1,520 Calculated Ventilation cfm 1,520 Calculated Ventilation ACH 13.44
Infiltration cfm 101 Min Stop/RH (%) 100
Heating Airflows
Main Fan cfm 0 Heating ACH 0.00 Sec Fan cfm 0
Input Ventilation cfm 1,520 Calculated Ventilation cfm 1,520 Calculated Ventilation ACH 13.44
Infiltration cfm 101 Min Stop/RH (%) 100
Areas ft²
Roof 0
Other Roof 0
Ceiling 885
Window 217
Door 16
1,006Wall
Below-Grade Wall 0
Other Wall 1,006
Partition 167
Exterior Floor 0
Internal Floor 0
Slab 885
Other Floor 0
Alternative: Primary Calculated at: Aug 15, 2024 - 11:41 AM
B1030 DOAS_Recovery_2024-08-15-112929.mdf TRACE 3D Plus 6.10.289File name:
ROOM_Dog Kennel 02
Conditions at Time of Space Cooling Peak Peak Time (Mo/D/H:M) 12/21 09:00:00
Outside DB / WB / HR 54.2 °F / 54.2 °F / 62.6 gr/lb Room DB / RH / HR 75.0 °F / 98.7 % / 129.5 gr/lb Supply Air Dry Bulb Temp 55.0 °F
Time Percent Instant Delay of
Sensible Sensible Latent Total Total
(Btu/h) (Btu/h) (Btu/h) (Btu/h) (%) Roof 0 0 0 0 0.0 Other Roof 0 0 0 0 0.0 Glass -625 2,549 0 1,924 1.8 Door 0 -34 0 -34 0.0 Wall 0 -1,387 0 -1,387 -1.3 Below-Grade Wall 0 0 0 0 0.0 Other Wall 0 0 0 0 0.0 Partition 0 -1,065 0 -1,065 -1.0 Exterior Floor 0 0 0 0 0.0 Interior Floor 0 0 0 0 0.0 Slab 0 -3,360 0 -3,360 -3.1 Other Floor 0 0 0 0 0.0 Infiltration -1,575 0 -3,340 -4,915 -4.5
Envelope Subtotal -2,200 -3,298 -3340 -8,838 - People 0 0 0 0 0.0
Lights 47,528 54,603 0 102,131 93.9
Miscellaneous Loads 0 0 93,869 93,869 86.3
Internal Subtotal 47,528 54,603 93,869 196,001 - RA (All Other) 0 0 0 0 0.0 DOA Direct to Room 0 0 -81,120 -81,120 -74.6 Ceiling 0 3,884 0 3,884 3.6 Refrigeration 0 0 0 0 0.0 Service Water 0 0 0 0 0.0 HVAC Equipment Losses 0 0 0 0 0.0 Adj Air Transfer Heat 0 0 0 0 0.0 Sizing Factor Correction 0 0 0 0 0.0 Time Delay Correction 0 -1,162 0 -1,162 -1.1
Grand Total 45,328 54,026 9,410 108,764 100.0 RA Sensible (Lights) 0 0 0 0 -
Engineering Checks For Cooling
Cooling tons 9.06 No People(max) 0.00 %OA 0 People per 1000 ft² 0 cfm/ft² 4.37 Volume (ft³) 8,254.1 cfm/ton 0.00 ft²/ton 113.85 Btu/h-ft² 105.40
Conditions at Time of Space Heating Peak Peak Time (Mo/D/H:M) 1/21 24:00:00
Outside DB / WB / HR 20.7 °F / 15.6 °F / 5.1 gr/lb Room DB / RH / HR 70.0 °F / 4.7 % / 5.1 gr/lb Supply Air Dry Bulb Temp 75.0 °F
Time Percent Instant Delay of
Sensible Sensible Latent Total Total
(Btu/h) (Btu/h) (Btu/h) (Btu/h) (%) Roof 0 0 0 0 0.0 Other Roof 0 0 0 0 0.0 Glass -3,300 0 0 -3,300 5.2 Door 0 -6 0 -6 0.0 Wall 0 -2,238 0 -2,238 3.5 Below-Grade Wall 0 0 0 0 0.0 Other Wall 0 0 0 0 0.0 Partition 0 40 0 40 -0.1 Exterior Floor 0 0 0 0 0.0 Interior Floor 0 0 0 0 0.0 Slab 0 -277 0 -277 0.4 Other Floor 0 0 0 0 0.0 Infiltration -3,994 0 0 -3,994 6.3
Envelope Subtotal -7,294 -2,481 0 -9,775 - People 0 0 0 0 0.0
Lights 0 0 0 0 0.0
Miscellaneous Loads -61,892 0 0 -61,892 98.0
Internal Subtotal -61,892 0 0 -61,892 - RA (All Other) 0 0 0 0 0.0 DOA Direct to Room 9,320 0 0 9,320 -14.8 Ceiling 0 -726 0 -726 1.2 Refrigeration 0 0 0 0 0.0 Service Water 0 0 0 0 0.0 HVAC Equipment Losses 0 0 0 0 0.0 Adj Air Transfer Heat 0 0 0 0 0.0 Sizing Factor Correction 0 0 0 0 0.0 Time Delay Correction 0 -88 0 -88 0.1
Grand Total -59,866 -3,295 0 -63,161 100.0 RA Sensible (Lights) 0 0 0 0 -
Engineering Checks For Heating
Heating Mbh -63.16 No People(max) 0.00 %OA 0 People per 1000 ft² 0 cfm/ft² 11.29 Volume (ft³) 8,254.1 cfm/Mbh 0.00 ft²/Mbh -16.34 Btu/h-ft² -61.20
Cooling Airflows
Main Fan cfm 0 Cooling ACH 0.00 Sec Fan cfm 0
Input Ventilation cfm 1,720 Calculated Ventilation cfm 1,720 Calculated Ventilation ACH 12.50
Infiltration cfm 68 Min Stop/RH (%) 100
Heating Airflows
Main Fan cfm 0 Heating ACH 0.00 Sec Fan cfm 0
Input Ventilation cfm 1,720 Calculated Ventilation cfm 1,720 Calculated Ventilation ACH 12.50
Infiltration cfm 68 Min Stop/RH (%) 100
Areas ft²
Roof 0
Other Roof 0
Ceiling 1,064
Window 149
Door 16
682Wall
Below-Grade Wall 0
Other Wall 682
Partition 368
Exterior Floor 0
Internal Floor 0
Slab 1,064
Other Floor 0
Alternative: Primary Calculated at: Aug 15, 2024 - 11:41 AM
B1030 DOAS_Recovery_2024-08-15-112929.mdf TRACE 3D Plus 6.10.289File
Zone Cooling and Heating Loads by Component
ZONE_Dog Kennels
Conditions at Time of Space Cooling Peak Peak Time (Mo/D/H:M) 2/21 09:00:00
Outside DB / WB / HR 54.0 °F / 50.6 °F / 49.2 gr/lb Zone DB / RH / HR 75.0 °F / 91.9 % / 120.4 gr/lb Supply Air Dry Bulb Temp 55.0 °F
Time Percent Instant Delay of
Sensible Sensible Latent Total Total
(Btu/h) (Btu/h) (Btu/h) (Btu/h) (%) Roof 0 0 0 0 0.0 Other Roof 0 0 0 0 0.0 Glass -2,095 5,369 0 3,274 1.8 Door 0 -25 0 -25 0.0 Wall 0 -2,633 0 -2,633 -1.5 Below-Grade Wall 0 0 0 0 0.0 Other Wall 0 0 0 0 0.0 Partition 0 -782 0 -782 -0.4 Exterior Floor 0 0 0 0 0.0 Interior Floor 0 0 0 0 0.0 Slab 0 -4,266 0 -4,266 -2.4 Other Floor 0 0 0 0 0.0 Infiltration -3,950 0 -8,591 -12,540 -7.0
Envelope Subtotal -6,045 -2,337 -8591 -16,973 - People 0 0 0 0 0.0
Lights 86,600 96,054 0 182,654 102.5
Miscellaneous Loads 0 0 171,038 171,038 96.0
Internal Subtotal 86,600 96,054 171,038 353,692 - RA (All Other) 0 0 0 0 0.0 DOA Direct to Zone 0 0 -162,611 -162,610 -91.3 Ceiling 0 6,639 0 6,639 3.7 Refrigeration 0 0 0 0 0.0 Service Water 0 0 0 0 0.0 HVAC Equipment Losses 0 0 0 0 0.0 Adj Air Transfer Heat 0 0 0 0 0.0 Sizing Factor Correction 0 0 0 0 0.0 Time Delay Correction 0 -2,554 0 -2,554 -1.4
Grand Total 80,555 97,802 -163 178,193 100.0 RA Sensible (Lights) 0 0 0 0 -
Engineering Checks For Cooling
Cooling tons 14.85 No People(max) 0.00 %OA 0 People per 1000 ft² 0 cfm/ft² 4.31 Volume (ft³) 15,039.8 cfm/ton 0.00 ft²/ton 126.62 Btu/h-ft² 94.77
Conditions at Time of Space Heating Peak Peak Time (Mo/D/H:M) 1/21 24:00:00
Outside DB / WB / HR 20.7 °F / 15.6 °F / 5.1 gr/lb Zone DB / RH / HR 70.0 °F / 4.7 % / 5.1 gr/lb Supply Air Dry Bulb Temp 75.0 °F
Time Percent Instant Delay of
Sensible Sensible Latent Total Total
(Btu/h) (Btu/h) (Btu/h) (Btu/h) (%) Roof 0 0 0 0 0.0 Other Roof 0 0 0 0 0.0 Glass -8,295 0 0 -8,295 6.9 Door 0 0 0 0 0.0 Wall 0 -5,461 0 -5,461 4.5 Below-Grade Wall 0 0 0 0 0.0 Other Wall 0 0 0 0 0.0 Partition 0 138 0 138 -0.1 Exterior Floor 0 0 0 0 0.0 Interior Floor 0 0 0 0 0.0 Slab 0 -408 0 -408 0.3 Other Floor 0 0 0 0 0.0 Infiltration -9,888 0 0 -9,888 8.2
Envelope Subtotal -18,183 -5,731 0 -23,914 - People 0 0 0 0 0.0
Lights 0 0 0 0 0.0
Miscellaneous Loads -112,772 0 0 -112,772 93.3
Internal Subtotal -112,772 0 0 -112,772 - RA (All Other) 0 0 0 0 0.0 DOA Direct to Zone 17,556 0 0 17,556 -14.5 Ceiling 0 -1,468 0 -1,468 1.2 Refrigeration 0 0 0 0 0.0 Service Water 0 0 0 0 0.0 HVAC Equipment Losses 0 0 0 0 0.0 Adj Air Transfer Heat 0 0 0 0 0.0 Sizing Factor Correction 0 0 0 0 0.0 Time Delay Correction 0 -224 0 -224 0.2
Grand Total -113,399 -7,423 0 -120,822 100.0 RA Sensible (Lights) 0 0 0 0 -
Engineering Checks For Heating
Heating Mbh -120.82 No People(max) 0.00 %OA 0 People per 1000 ft² 0 cfm/ft² 11.86 Volume (ft³) 15,039.8 cfm/Mbh 0.00 ft²/Mbh -15.56 Btu/h-ft² -64.27
Cooling Airflows
Main Fan cfm 0 Cooling ACH 0.00 Sec Fan cfm 0
Input Ventilation cfm 3,240 Calculated Ventilation cfm 3,240 Calculated Ventilation ACH 12.93
Infiltration cfm 169 Min Stop/RH (%) 100
Heating Airflows
Main Fan cfm 0 Heating ACH 0.00 Sec Fan cfm 0
Input Ventilation cfm 3,240 Calculated Ventilation cfm 3,240 Calculated Ventilation ACH 12.93
Infiltration cfm 169 Min Stop/RH (%) 100
Areas ft²
Roof 0
Other Roof 0
Ceiling 1,949
Window 366
Door 33
1,687Wall
Below-Grade Wall 0
Other Wall 1,687
Partition 536
Exterior Floor 0
Internal Floor 0
Slab 1,949
Other Floor 0
Alternative: Primary Calculated at: Aug 15, 2024 - 11:41 AM
B1030 DOAS_Recovery_2024-08-15-112929.mdf TRACE 3D Plus 6.10.289File
ZONE_Office Space (NIS)
Conditions at Time of Space Cooling Peak Peak Time (Mo/D/H:M) 8/21 16:00:00
Outside DB / WB / HR 89.3 °F / 75.8 °F / 112.8 gr/lb Zone DB / RH / HR 74.7 °F / 65.4 % / 84.2 gr/lb Supply Air Dry Bulb Temp 48.0 °F
Time Percent Instant Delay of
Sensible Sensible Latent Total Total
(Btu/h) (Btu/h) (Btu/h) (Btu/h) (%) Roof 0 1,610 0 1,610 2.0 Other Roof 0 0 0 0 0.0 Glass 0 0 0 0 0.0 Door 0 0 0 0 0.0 Wall 0 -573 0 -573 -0.7 Below-Grade Wall 0 0 0 0 0.0 Other Wall 0 0 0 0 0.0 Partition 0 -2,669 0 -2,669 -3.3 Exterior Floor 0 0 0 0 0.0 Interior Floor 0 0 0 0 0.0 Slab 0 -1,246 0 -1,246 -1.5 Other Floor 0 0 0 0 0.0 Infiltration 1,180 0 1,457 2,638 3.2
Envelope Subtotal 1,180 -2,877 1457 -239 - People 0 0 0 0 0.0
Lights 18,870 26,324 0 45,194 55.2
Miscellaneous Loads 0 0 37,269 37,269 45.5
Internal Subtotal 18,870 26,324 37,269 82,463 - RA (All Other) 0 0 0 0 0.0 DOA Direct to Zone 0 0 0 0 0.0 Ceiling 0 0 0 0 0.0 Refrigeration 0 0 0 0 0.0 Service Water 0 0 0 0 0.0 HVAC Equipment Losses 0 0 0 0 0.0 Adj Air Transfer Heat 0 0 0 0 0.0 Sizing Factor Correction 0 0 0 0 0.0 Time Delay Correction 0 -391 0 -391 -0.5
Grand Total 20,050 23,056 38,726 81,832 100.0 RA Sensible (Lights) 0 0 0 0 -
Engineering Checks For Cooling
Cooling tons 6.82 No People(max) 0.00 %OA 0 People per 1000 ft² 0 cfm/ft² 3.60 Volume (ft³) 5,325.5 cfm/ton 215.98 ft²/ton 60.08 Btu/h-ft² 199.73
Conditions at Time of Space Heating Peak Peak Time (Mo/D/H:M) 1/21 24:00:00
Outside DB / WB / HR 20.7 °F / 15.6 °F / 5.1 gr/lb Zone DB / RH / HR 73.0 °F / 5.4 % / 6.4 gr/lb Supply Air Dry Bulb Temp 94.8 °F
Time Percent Instant Delay of
Sensible Sensible Latent Total Total
(Btu/h) (Btu/h) (Btu/h) (Btu/h) (%) Roof 0 -695 0 -695 2.0 Other Roof 0 0 0 0 0.0 Glass 0 0 0 0 0.0 Door 0 0 0 0 0.0 Wall 0 -3,393 0 -3,393 9.7 Below-Grade Wall 0 0 0 0 0.0 Other Wall 0 0 0 0 0.0 Partition 0 -1,207 0 -1,207 3.5 Exterior Floor 0 0 0 0 0.0 Interior Floor 0 0 0 0 0.0 Slab 0 -153 0 -153 0.4 Other Floor 0 0 0 0 0.0 Infiltration -4,801 0 0 -4,884 14.0
Envelope Subtotal -4,801 -5,448 0 -10,332 - People 0 0 0 0 0.0
Lights 0 0 0 0 0.0
Miscellaneous Loads -24,573 0 0 -24,573 70.4
Internal Subtotal -24,573 0 0 -24,573 - RA (All Other) 0 0 0 0 0.0 DOA Direct to Zone 0 0 0 0 0.0 Ceiling 0 0 0 0 0.0 Refrigeration 0 0 0 0 0.0 Service Water 0 0 0 0 0.0 HVAC Equipment Losses 0 0 0 0 0.0 Adj Air Transfer Heat 0 0 0 0 0.0 Sizing Factor Correction 0 0 0 0 0.0 Time Delay Correction 0 -12 0 -12 0.0
Grand Total -29,374 -5,460 0 -34,917 100.0 RA Sensible (Lights) 0 0 0 0 -
Engineering Checks For Heating
Heating Mbh -34.92 No People(max) 0.00 %OA 0 People per 1000 ft² 0 cfm/ft² 3.59 Volume (ft³) 5,325.5 cfm/Mbh -42.19 ft²/Mbh -11.73 Btu/h-ft² -85.25
Cooling Airflows
Main Fan cfm 1,473 Cooling ACH 16.60 Sec Fan cfm 0
Input Ventilation cfm 0 Calculated Ventilation cfm 0 Calculated Ventilation ACH 0.00
Infiltration cfm 77 Min Stop/RH (%) 100
Heating Airflows
Main Fan cfm 1,473 Heating ACH 16.60 Sec Fan cfm 0
Input Ventilation cfm 0 Calculated Ventilation cfm 0 Calculated Ventilation ACH 0.00
Infiltration cfm 77 Min Stop/RH (%) 100
Areas ft²
Roof 431
Other Roof 431
Ceiling 0
Window 0
Door 0
772Wall
Below-Grade Wall 0
Other Wall 772
Partition 327
Exterior Floor 0
Internal Floor 0
Slab 431
Other Floor 0
Alternative: Primary Calculated at: Aug 15, 2024 - 11:41 AM
B1030 DOAS_Recovery_2024-08-15-112929.mdf TRACE 3D Plus 6.10.289File
System Name: Zone Dehum/Cool or Heat
System Type: Dedicated Outdoor Air System (DOAS)
Number of Zones 1
Number of Rooms 2
Component Quantity
Cooling Coils 1
Heating Coils 1
Fans 2
Cooling Coils
Coil Location Coil Selection at Design Airflow Conditions at Design Water Flow Conditions
Time of Peak Total capacity
Sensible capacity
Vent Load
Ov/undr sizing Airflow Vent Enter DB/WB Leave DB/WB Flow
Enter Temp
Leave Temp
Mo/D/Hr (tons) (MBh) (MBh) (MBh) (MBh) (cfm) (cfm) (°F) (°F) (°F) (°F) (gpm) (°F) (°F)
SCC-1 DX Block 20.3 244.2 132.7 244.2 N/A 3,240 3,240 92.2 76.57 55.0 54.99 N/A N/A N/A *Values do not include effects of plenum loads, heat exchangers such as evaporative cooling devices and similar components.
Heating Coils
Coil Location Coil Selection at Design Airflow Conditions at Design Water Flow Conditions
Time of Peak
Total capacity
Vent Load
Ov/undr sizing Airflow Vent Enter DB Leave DB Flow
Enter Temp
Leave Temp
Mo/D/Hr (MBh) (MBh) (MBh) (cfm) (cfm) (°F) (°F) (gpm) (°F) (°F)
SHC-1 Electric Block 1/21 24:00 190.7 190.7 N/A 3,240 3,240 20.7 75.0 N/A N/A N/A
Alternative: Primary Calculated at: Aug 15, 2024 - 11:41 AM
B1030 DOAS_Recovery_2024-08-15-112929.mdf TRACE 3D Plus 6.10.289File name:
System Zone Type
Sizing Method
System Zone Type
Sizing Method
Load/Airflows
Location Cooling Heating
Area
Time of Peak
Supply Airflow
Sensible Load
Minimum Airflow SAT
Time of Peak
Supply Airflow
Sensible Load
Minimum Airflow SAT
(ft²) Mo/D/Hr (cfm) (Btu/h) (cfm) (°F) Mo/D/Hr (cfm) (Btu/h) (cfm) (°F)
Zone Dehum/Cool or Heat 1,880 8/21 14:00 3,240 132,736 3,240 55.0 1/21 24:00 3,240 190,649 3,240 75.0
Dog Kennels 1,880 2/21 09:00 0 71,319 3,240 55.0 1/21 24:00 0 17,562 3,240 75.0
Dog Kennel 01 848 2/21 09:00 0 33,459 1,520 55.0 1/21 24:00 0 8,239 1,520 75.0
Dog Kennel 02 1,032 12/21 09:00 0 37,861 1,720 55.0 1/21 24:00 0 9,323 1,720 75.0
Fans
Efficiency
Efficiency with PRM
Fan Override Static
Pressure Flow Rate Power
Power with PRM
Fan Override
Motor Heat in Air
(%) (%) (in. Wg) (cfm) (kW) (kW) (%)
Dog Kennels _EXHAUST FAN Zone 10.00 N/A 0.00 3,240 .00 N/A 100.00
Zone Dehum/Cool or Heat SF-1 System 53.00 N/A 3.00 3,240 2.14 N/A 100.00
Alternative: Primary Calculated at: Aug 15, 2024 - 11:41 AM
B1030 DOAS_Recovery_2024-08-15-112929.mdf TRACE 3D Plus 6.10.289File name:
System Zone Room
System Zone Type
| PROJECT MUHJ 24-4024 |
| 50% SUBMITTAL |
File details come from the government source that posted it. Updated .