Appendix H3 - BLDG 6 Bid Documents.pdf
PDF 15 MB Posted
- Solicitation number
- IFB1-NHAA-2025000029
- Issued by
- Larimer County, Lakewood City, Colorado
About this file
This document is a comprehensive bid package for the Fort Lyon Life Safety Corrections project, specifically focusing on Building 6, prepared by T.A. Duke & Associates and McShea Consulting LLC located in Colorado Springs, Colorado. The project involves life safety improvements and code corrections for Building 6, a facility within the Fort Lyon Campus in Bent County, which historically served as a Navy Hospital and later a correctional facility before becoming supportive housing for homeless veterans. The bid documents include detailed architectural and engineering specifications for renovations, covering multiple building systems and addressing various code compliance issues, with work including modifications to hardware, restrooms, fire protection systems, electrical systems, and accessibility improvements.
The project is part of a larger state-funded initiative under House Bill 1408, with a total project number of 2021-035M21/HB 1408, targeting multiple buildings on the campus to upgrade life safety and meet current building codes. The specifications indicate a comprehensive renovation approach, including installing new doors, hardware, plumbing fixtures, fire annunciators, emergency lighting, exit signs, and addressing sprinkler system deficiencies. The documents were issued multiple times between December 2022 and October 2023 for pricing, state review, and permitting, with the project utilizing the 2021 International Building Code and related standards. The total building area for Building 6 is 30,472 square feet, and the renovation is designed to be fully sprinklered and meet current accessibility requirements.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MARK DATE DESCRIPTION
SHEET TITLE
CONSULTANTS
PROJECT NO: FORT LYON LS-6-2021
MODEL FILE:
Fort Lyon Bldg 6 Final final LS version 24.pln
DRAWN BY: TAD
ISSUE DATE:
G-001
12/9/2022
/U se rs /ta du ke
/D oc um en ts /A rc hi ca d
Fi le s/ Fo rt Ly on B ld g
Fi na l f in al
L S v er si on
4.
pl n
Cover Sheet
Fort Lyon Life Safety Corrections -
Building 6
T.A. DUKE & ASSOCIATES, Inc.
4220 Brigadoon Lane
Colorado Springs, CO 80906 719 648 7722 taduke@earthlink.net
McShea Consulting LLC 4445 Northpark Dr., Suite 200 Colorado Springs, CO 80907
719 358 8208
12/9/22 ISSUED FOR PRICING AND
PERMIT
3/31/23 CODE COMMENT REVISIONS
4/13/23 ISSUED FOR STATE REVIEW
5/18/23 ISSUED FOR STATE REVIEW
5/25/23
ISSUED FOR CODE
CONSULTANT REVIEW
9/21/2023
5/31/23 ISSUED FOR STATE REVIEW
7/19/23
ISSUED FOR CODE
CONSULTANT REVIEW
8/23/23
ISSUED FOR CODE
CONSULTANT REVIEW
9/12/23
ISSUED FOR CODE
CONSULTANT REVIEW
9/21/23
ISSUED FOR PERMIT
PROJECT NUMBER: 2021-035M21/HB 1408
10/3/23
ISSUED FOR PRICING
Fort Lyon Life Safety Corrections - Building 6
CONSULTANTS
PROJECT NO: FORT LYON LS-6-2021
MODEL FILE:
Fort Lyon Bldg 6 Final final LS version 24.pln
DRAWN BY: TAD
ISSUE DATE:
G-002
12/9/2022
/U se rs /ta du ke
/D oc um en ts /A rc hi ca d
Fi le s/ Fo rt Ly on B ld g
Fi na l f in al
L S v er si on
4.
pl n
Project Notes
Fort Lyon Life Safety Corrections -
Building 6
T.A. DUKE & ASSOCIATES, Inc.
4220 Brigadoon Lane
Colorado Springs, CO 80906 719 648 7722 taduke@earthlink.net
McShea Consulting LLC 4445 Northpark Dr., Suite 200 Colorado Springs, CO 80907
719 358 8208
12/9/22 ISSUED FOR PRICING AND
PERMIT
3/31/23 CODE COMMENT REVISIONS
4/13/23 ISSUED FOR STATE REVIEW
5/18/23 ISSUED FOR STATE REVIEW
5/25/23
ISSUED FOR CODE
CONSULTANT REVIEW
9/21/2023
5/31/23 ISSUED FOR STATE REVIEW
7/19/23
ISSUED FOR CODE
CONSULTANT REVIEW
8/23/23
ISSUED FOR CODE
CONSULTANT REVIEW
9/12/23
ISSUED FOR CODE
CONSULTANT REVIEW
9/21/23
ISSUED FOR PERMIT
PROJECT NUMBER: 2021-035M21/HB 1408
10/3/23
ISSUED FOR PRICING
GENERAL NOTES
PROJECT: BUILDING 6 CODE CORRECTIONS
FORT LYON, CO
APPLICABLE CODES:
2021 INTERNATIONAL BUILDING CODE
2021 INTERNATIONAL EXISTING BUILDING CODE
2021 INTERNATIONAL MECHANICAL CODE
2018 INTERNATIONAL PLUMBING CODE
2020 NATIONAL ELECTRIC CODE
2021 INTERNATIONAL FIRE CODE
2021 INTERNATIONAL ENERGY CONSERVATION CODE
2017 ICC A117.1
DESIGN CRITERIA:
32" FROST DEPTH
100 PSF FLOOR/STAIR LIVE LOAD
20 PSF ROOF LIVE LOAD
30 PSF SNOW LOAD
100 MPH WIND LOAD; EXPOSURE C
WALL INSULATION - R19
ROOF INSULATION - R38
ZONING: NOT APPLICABLE
SEISMIC ZONE: B
SCOPE OF WORK:
MODIFICATIONS TO HARDWARE AND RESTROOMS
TOTAL BUILDING AREA: 30,472 SF
SEPARATION OF EXITS: 1/3 THE DIAGONAL (BUILDING IS SPRINKLERED)
DIAGONAL @ BASEMENT = 154'
DISTANCE TO EXITS = 209'
DIAGONAL @ 1ST FLOOR = 154'
DISTANCE TO EXIT = 158'
DIAGONAL @ 2ND FLOOR = 147'
DISTANCE TO EXIT = 144'
CONSTRUCTION TYPE: NON CONFORMING TYPE IIB (SPRINKLERED)
NOTE: ALL NEW INTERIOR CONSTRUCTION WILL
MEET OR EXCEED FIRE RESISTIVE MATERIALS
REQUIRED BY TYPE IIB CONSTRUCTION
INTERIOR FINISH FIRE RATING:
OCCUPANCY EXIT ENCLOSURES CORRIDORS INTERIOR ROOMS
A-3 B B C B B B C I-1 B C C S C C C
CLASS A: FLAME SPREAD INDEX 0-25; SMOKE DEVELOPED INDEX 0-450
CLASS B: FLAME SPREAD INDEX 26-75; SMOKE DEVELOPED INDEX 0-450
CLASS C: FLAME SPREAD INDEX 76-200; SMOKE DEVELOPED INDEX 0-450
FIRE RESISTANCE RATING (HOURS):
PRIMARY STRUCTURAL FRAME: 0
EXTERIOR BEARING WALLS: 0
INTERIOR BEARING WALLS: 0
INTERIOR NON BEARING WALLS: 0
FLOOR CONSTRUCTION AND
SECONDARY MEMBERS: 0
ROOF CONSTRUCTION AND
SECONDARY MEMBERS: 0
CODE REQUIREMENTS
PARTITION TYPES
12. DURING AND AT THE COMPLETION OF THE CONTRACTORS
DAILY WORK, CONTRACTORS ARE RESPONSIBLE FOR THE
CLEANING UP AND REMOVAL OF ALL RUBBISH AND DEBRIS
BEFORE LEAVING THE JOBSITE.
13. THE FOLLOWING ARE STRICTLY PROHIBITED WORK AND
PRACTICES:
A. ANY COMBUSTIBLE MATERIALS ABOVE FINISHED
CEILING
B. IMPOSING ANY STRUCTURAL LOAD, TEMPORARY OR
PERMANANT, ON ANY PART OF THE BUILDING
STRUCTURE WITHOUT PRIOR WRITTEN APPROVAL
C. CUTTING ANY HOLES IN FLOOR SLABS, WALLS OR ROOF
WITHOUT PROPER APPROVAL.
14. CONTRACTORS SHALL CARRY ADEQUATE LIABILITY INSURANCE
AS SET FORTH BY OWNER'S REQUIREMENTS.
15. A CERTIFICATE OF OCCUPANCY MUST BE OBTAINED UPON
COMPLETION OF ALL WORK AND FINAL INSPECTIONS. THE ORIGINAL
C.O. TO BE SUBMITTED TO OWNER
16. IN EVENT OF CONFLICT, DISCREPENCY, OBLIGATION, ETC.
CONTRACTOR TO CONTACT ARCHITECT AND OWNER
FOR CLARIFICATION PRIOR TO PROCEEDING.
17. PROVIDE ALL INSURANCE, LICENSES, BONDING AND RELEASE
OF LIENS REQUIRED BY OWNER. PROVIDE COPIES
OF ALL DOCUMENTATION UPON REQUEST.
18. PROVIDE COMPLETE OPERATING MAINTENANCE AND
SPECIFICATION MANUALS TO STAGE FOR ALL EQUIPMENT WITHIN
(15) DAYS OF FINAL COMPLETION OF JOB.
19. PROVIDE A WRITTEN LIST OF SERVICE SUB-CONTRACTORS TO
OWNER INCLUDING NAMES, ADDRESSES, PHONE NUMBERS AND
CONTACT PERSONS FOR FUTURE SERVICE NEEDS WITHIN (15) DAYS
OF COMPLETION OF JOB.
20. CONTRACTORS SHALL NOT BE ALLOWED TO USE, STORE OR
DISPOSE OF ANY HAZARDOUS, FLAMMABLE, EXPLOSIVE,
RADIOACTIVE TOXIC, CONTAMINATING, POLLUTING MATERIALS
OR SUBSTANCES RELATED TO INJUROUS OR CHEMICALLY
REGULATED MATERIALS ON THE JOB SITE.
21. ALL INTERIOR WALLS SHALL HAVE A MINIMUM OF ONE COAT OF
WHITE PRIMER INSTALLED AND TWO FINISH COATS.
22. GENERAL CONTRACTOR IS TO CONSTRUCT INTERIOR WALLS
FROM STEEL STUDS. GENERAL CONTRACTOR MUST USE FIRE
RETARDANT TREATED WOOD BLOCKING AT CRITICAL LOCATIONS
FOR THE MOUNTING OF MILLWORK, OR ACCESSORIES
23. ARCHITECTURAL SIGNAGE FOR TOILETS, EXITS, OTHER CODE
RELATED SIGNS NECESSARY SHALL BE FURNISHED AND INSTALLED
BY THE CONTRACTOR.
24. GENERAL CONTRACTOR SHLL PROVIDE ADEQUATE PROTECTION
OF ANY TENANT SUPPLIED MATERIALS, FIXTURES, ETC. ON JOB SITE.
25.GENERAL CONTRACTOR IS TO VERIFY ALL EXISTING CONDITIONS.
ANY DIMENSIONS SHOWN WHICH INDICATE AN EXISTING CONDITION
ARE APPROXIMATE AND SHOULD BE VERIFIED ON SITE.
26. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO DETERMINE
THE EXISTING CONDITIONS WHICH MAY AFFECT THE COMPLETION OF
THE PROJECT IN ACCORDANCE WITH THE CONSTRUCTION
DOCUMENTS. NOTIFY THE ARCHITECT IF EXISTING CONDITIONS VARY
SUCH THAT IMPLEMENTATION OF THE DOCUMENTS WILL ADVERSLY
AFFECT THE PROJECT COST OR PROJECT SCHEDULE.
27. IT IS NOT WITHIN THE SCOPE OF WORK OF THE ARCHITECT TO
DISCOVER, LOCATE, HANDLE, REMOVE OR DISPOSE OF ANY
HAZARDOUS MATERIALS INCLUDING, BIT NOT LIMITED TO: ASBESTOS,
ASBESTOS PRODUCTS, POLYCHLORINATED BIPHENYL (PCB),
HYDROCARBONS OR ANY OTHER TOXIC SUBSTANCES. SHOULD THE
G.C. OR ANY OTHER ENTITY WORKING ON BEHALF OF THE G.C. OR
THE OWNER DISCOVER OR ENCOUNTER ANY HAZARDOUS
MATERIALS, THE G.C. SHALL NOTIFY THE APPROPRIATE AUTHORITIES
IMMEDIATELY AND PROCEED IN ACCORDANCE WITH ALL APPLICABLE
LAWS AND REGULATIONS.
34. ARCHITECT AND OWNER SHALL INSPECT THE PROJECT TO
VERIFY STATUS OF COMPLETION WITH REASONABLE PROMPTNESS
AFTER NOTIFICATION BY CONTRACTOR.
35. CONTRACTOR TO PROVIDE ALL CIVIL, ELECTRICAL, AND
MECHANICAL ASSOCIATED WITH THE DESIGN INTENT SHOWN
ON THE ARCHITECTURAL AND ENGINEERING DRAWINGS
36. SHOULD CONTRACTOR, IN PREPARING HIS BID OR AT ANY TIME
THEREAFTER, FIND ANY DISCREPANCY, INCONSISTENCY, CONFLICT
OR OMISSION IN, OR BE IN DOUBT AS TO THE EXACT MEANING
OF THE DRAWINGS OR SPECIFICATIONS HE SHALL IMMEDIATELY
AND BEFORE PROCEEDING FURTHER NOTIFY OWNER IN WRITING.
OWNER WILL IMMEDIATELY RESOLVE SUCH DISCREPANCY AND
FURNISH CONTRACTOR WITH WRITTEN INSTRUCTIONS WITH
RESPECT THERETO. IT WILL NOT BE A DISCREPANCY IF THESE SPECS
DO NOT MENTION PORTIONS OF THE WORK WHICH THE DRAWINGS
COMPETENTLY EXPLAIN.
1. ALL NEW CONSTRUCTION SHALL BE IN STRICT COMPLIANCE
WITH NATIONAL, STATE, COUNTY AND CITY BUILDING CODES AND
THE AMERICANS WITH DISABILIITIES ACT (A.D.A) REGULATIONS.
2. ALL WORK SHALL BE DONE IN COMPLIANCE WITH THE
OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA)
3. DIMENSIONS GIVEN IN FIGURES ON THE PLANS SHALL TAKE
PRECEDENCE OVER SCALED DIMENSIONS. ALL DIMENSIONS
SHALL BE VERIFIED IN FIELD. DIMENSIONS ARE NOT
ADJUSTABLE UNLESS NOTED OTHERWISE.
4. ALL DIMENSIONS ARE GIVEN FROM FACE OF DRYWALL
TO FACE OF DRYWALL UNLESS NOTED OTHERWISE.
5. "EQUAL" WHEN USED SHALL MEAN AN EQUIVALENT PRODUCT
OR MATERIAL AS APPROVED BY THE TENANT.
6. ALL HEIGHTS ARE DIMENSIONED FROM FINISHED FLOOR
UNLESS NOTED OTHERWISE.
7. THE CONTRACTOR SHALL VERIFY THAT NO CONFLICTS
EXIST IN LOCATIONS OF ANY AND ALL MECHANICAL,
TELEPHONE/DATA, ELECTRICAL, LIGHTING, PLUMBING AND
SPRINKLER EQUIPMENT (TO INCLUDE ALL PIPING, DUCTWORK
AND CONDUIT) AND THAT ALL REQUIRED CLEARANCES FOR
INSTALLATION OR MAINTENANCE OF THE ABOVE EQUIPMENT
IS PROVIDED.
8. ALL GYPSIUM BOARD PARTITIONS SHALL BE TAPED, BEDDED
AND SANDED SMOOTH WITH NO VISIBLE JOINTS. ALL CORNERS
SHALL RECEIVE METAL CORNER BEAD UNLESS OTHERWISE
NOTED
9. ALL RATED WALLS SHALL HAVE THEIR RATING MAINTAINED
AND ALL NEW PENETRATIONS SEALED TO MEET CURRENT
CODE REQUIREMENTS.
10. ALL MATERIALS FURNISHED AND INSTALLED SHALL BE FREE
FROM DEFECTS. ALL MATERIALS AND WORKMANSHIP SHALL
BE GUARANTEED FOR A PERIOD OF ONE YEAR FROM THE DATE
OF ACCEPTANCE. DURING THIS PERIOD, PROBLEMS DUE TO
DEFECTIVE MATERIALS OR FAULTY WORKMANSHIP SHALL BE
CORRECTED AT NO COST TO THE TENANT. ANY PROBLEMS
THAT OCCUR DURING CONSTRUCTION SHALL BE CORRECTED
IMMEDIATELY TO THE SATISFACTION OF THE TENANT.
11. GENERAL CONTRACTOR SHALL PROVIDE ADEQUATE BRACIING
AS REQUIRED TO SECURE WORK TO STRUCTURE ABOVE CEILING
WHERE REQUIRED AND SHALL BE TOTALLY RESPONSIBLE FOR
HIS WORK. ARCHITECTURAL DRAWINGS:
SHEET # NAME
G-001 COVER SHEET
G-002 PROJECT NOTES
G-003 PLUMBING CALCULATIONS
G-004 BASEMENT CODE STUDY PLAN
G-005 1ST FLOOR CODE STUDY PLAN
G-006 2ND FLOOR CODE STUDY PLAN
AS-001 VICINITY MAP
AS-002 BUILDING LOCATION PLAN
AS-003 SURVEY/PLAT PLAN
A-101 1ST FLOOR DEMO PLAN
A-102 2ND FLOOR DEMO PLAN
A-103 3RD FLOOR DEMO PLAN
A-104 1ST FLOOR PLAN
A-105 2ND FLOOR PLAN
A-106 3RD FLOOR PLAN
A-107 3RD FLOOR POTENTIAL FURNITURE PLAN
A-108 1ST FLOOR REFLECTED CEILING DEMO PLAN
A-109 2ND FLOOR REFLECTED CEILING DEMO PLAN
A-110 3RD FLOOR REFLECTED CEILING DEMO PLAN
A-111 1ST FLOOR REFLECTED CEILING PLAN
A-112 2ND FLOOR REFLECTED CEILING PLAN
A-113 3RD FLOOR REFLECTED CEILING PLAN
A-201 INTERIOR ELEVATIONS
A-202 INTERIOR ELEVATIONS
A-401 ENLARGED PLANS & ELEVATIONS
A-501 SPECS/DETAILS
A-502 SPECS/DETAILS
A-503 SPECS
A-504 PHOTOS
A-505 PHOTOS AND ADA SIGN MOUNTING
A-506 SPRINKLER SYSTEM DEFICIENCIES & EDF SPEC
A-507 FIRE STOP DETAILS
A-601 DOOR SCHEDULE
A-602 DOOR SCHEDULE
A-603 DOOR SCHEDULE
A-604 DOOR SCHEDULE
A-701 1ST FLOOR FINISH PLAN
A-702 2ND FLOOR FINISH PLAN
A-703 3RD FLOOR FINISH PLAN
A-704 FINISH SPECS/LEGEND
A-705 FINISH SPECS
A-706 FINISH SPECS
GENERAL NOTES
30. CONTRACTOR SHALL MAINTAIN REQUIRED DOCUMENTS AND UP
TO DATE CONSTRUCTION PLANS ON THE JOB SITE.
31. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR FINAL
CLEANING PRIOR TO TURNING THE SPACE OVER TO THE OWNER.
CLEANING SHALL INCLUDE, BIT NOT BE LIMITED TO: REMOVAL OF
GREASE MASTIC ADHESIVES, DUST, DIRT, STAINS, FINGERPRINTS,
LABELS AND OTHER FOREIGN MATERIALS FROM EXPOSED
INTERIOR AND EXTERIOR SURFACES. PRESSURE WASH EXTERIOR
PAVED SURFACES.
28. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ANY
DAMAGE TO THE FACILITY DURING CONSTRUCTION.
29. CONTRACTOR SHALL PROPERLY DISPOSE OF ALL DEMOLISHED
MATERIALS IN ACCORDANCE WITH ALL APPLICABLE REGULATIONS.
32. PROVIDE OWNER WITH A MINIMUM OF ONE (1) SET OF "AS-BUILT"
DRAWINGS INDICATING ALL VARIANCES BETWEEN ORIGINAL
APPROVED CONSTRUCTION DOCUMENTS AND ACTUAL COMPLETED
CONSTRUCTION.
33. IN THE EVENT THAT CERTAIN FEATURES OF THE CONSTRUCTION
ARE NOT FULLY SHOWN ON THE DRAWINGS OR CALLED FOR IN
GENERAL NOTES, THEN THERE CONSTRUCTION SHALL BE OF THE
SAME CHARACTER AS FOR SIMILAR CONDITIONS.
GENERAL NOTES
GENERAL NOTES
PLUMBING FIIXTURES, CONT'D
3. ALL NEW RESTROOM FIXTURES INCLUDING:
A. STANDARD TOILET
B. ADA TOILET
C. STANDARD LAVATORY
D. ADA LAVATORY
E. TOILET PARTITIONS/URINAL SCREEN
F. STANDARD URINAL
G. ADA URINAL
H. SHOWER UNIT
4. GREASE INTERCEPTOR
D. ALL SIGNAGE
E. EXHAUST FAN
F. ALL DOORS AND HARDWARE INCLUDING:
1. ALL NEW DOORS INCLUDING
A. HOLLOW METAL DOORS
B. SOLID CORE WOOD DOORS
2. LEVER LOCKSET
3. LEVER PRIVACY SET
4. LEVER PASSAGE SET
5. PANIC HARDWARE
6. AUTOMATIC CLOSER
7. HINGES
8. DOOR FRAME
G. PORTABLE FIRE EXTINGUISHER
THE FOLLOWING MATERIALS REQUIRE SUBMITTALS PRIOR TO
PROCUREMENT OR INSTALLATION:
A. ALL FINISH MATERIALS INCLUDING:
1. WALL FINISHES INCLUDING:
A. PRIMER PAINT
B. FINISH PAINT
C. CERAMIC WALL TILE
D. VINYL WALL COVERING
2. FLOOR COVERINGS INCLUDING
A. CERAMIC FLOOR TILE
B. CARPET
C. SHEET VINYL
D. VINYL TILE
3. ALL CEILING TILE INCLUDING
A. 2 X 4 TILE
B. 2 X 2 TILE
B. ALL ELECTRCAL ITEMS INCLUDING:
1. 2 X 4 LIGHT FIXTURES
2. 1 X 4 LIGHT FIXTURES
3. EMERGENCY EXIT/LIGHT COMBO UNIT
4. CEILING MOUNTED FIRE ANNUNCIATOR
5. WALL MOUNTED FIRE ANNUNCIATOR
6. ILLUMINATED EXIT SIGNAGE
7. ALL CEILING TILE INCLUDING
A. 2 X 4 TILE
B. 2 X 2 TILE
8. SMOKE DETECTOR
9. CEILING MOUNTED EXIT DIRECTIONAL SIGN
10. WALL MOUNTED EXIT DIRECTIONAL SIGN
11. WALL MOUNTED EMERGENCY LIGHT
C. ALL PLUMBING FIXTURES INCLUDING:
1. RESTROOM ACCESSORIES INCLUDING
A. MIRROR
B. GRAB BARS
C. TOILET TISSUE DISPENSER
D. TOILET SEAT COVER DISPENSER
E. BABY CHANGING STATION
F. SOAP DISPENSER
G. WASTE RECEPTACLE/PAPER TOWEL
DISPENSER
2. DRINKING FOUNTAINS
SUBMITTAL REQUIREMENTS
Partition Type 1: 3 5/8" metal stud (Clark Dietrich ProStud 20) @ 24" O.C. from floor to underside of structure; provide 5/8" type X gyp board at both sides. Total wall thickness = 4 7/8" (1) hour rated - UL Des U419 Partition Type 2: 3 5/8" metal stud (Clark Dietrich ProStud 20) @ 24" O.C. from floor to top of opening with 5/8" type X gyp board at hall side and 5/8" type X USG Durock Brand Glass-Mat Tile Backerboard at restroom side. Total wall thickness = 4 7/8"; Provide batt insulation from floor to top of wall.
Partition Type 3: 3 5/8" metal stud (Clark Dietrich ProStud 20) @ 24" O.C. from floor to underside of structure; with 5/8" type X gyp board at each side. Total wall thickness = 4 7/8". (1) hour rated - UL Des U419
Partition Type 4: 3 5/8" metal stud (Clark Dietrich ProStud 20) @ 24" O.C. from floor to underside of structure; provide (2) layers of 5/8" type X gyp board at both sides. Total wall thickness = 6 1/8"; install 3 1/2" batt insulation from floor to top of wall; (2) hour rated - UL Des U419
Partition Type 5: 3 5/8" metal stud (Clark Dietrich ProStud 20) @ 24" O.C. from floor to top of opening; provide 5/8" type X gyp board at both sides. Total wall thickness = 4 7/8"; install 3 1/2" batt insulation from floor to top of wall
6 NOT USED
Partition Type 7: 3 5/8" metal stud (Clark Dietrich ProStud 20) @ 24" O.C. from floor to underside of structure; provide (1) layer 5/8" type X gyp board at hall side and (1) layer of 5/8" Sheetrock Brand Mold Tough Firecode X Panel at rm side. Total wall thickness = 4 7/8".
Partition Type 11: 3 5/8" metal stud (Clark Dietrich ProStud 20) @ 24" O.C. from floor to underside of structure; provide 5/8" type X gyp board at one side. Provide 5/8" type X USG Durock Brand Glass-Mat Tile Backerboard at restroom side; Total wall thickness = 4 7/8"; (1) hour rated - UL Des U419
Partition Type 12: 3 5/8" metal stud (Clark Dietrich ProStud 20) @ 24" O.C. from floor to underside of structure; Provide 5/8" type X USG Durock Brand Glass-Mat Tile Backerboard at exposed side; Total wall thickness = 4 1/4"
Partition Type 13: 4" metal stud (Clark Dietrich ProStud 20) @ 24" O.C. from floor to underside of structure; provide (1) layer of 5/8" type X gyp board at one side and (1) layer of 5/8" type X USG Durock Brand Glass-Mat Tile Backerboard at restrm side; Total wall thickness = 5 1/4"; install 3 1/2" batt insulation from floor to top of wall. exceeds (1) hour rated - UL Des U419
Partition Type 14: 6" metal stud (Clark Dietrich ProStud 20) @ 24" O.C. from floor to underside of structure; provide (1) layer of 5/8" type X gyp board at hall side and (1) layer of 5/8" type X USG Durock Brand Glass-Mat Tile Backerboard at restrm side. Total wall thickness = 7 1/4"; install 5 1/2" batt insulation from floor to top of wall. (1) hour rated - UL Des U419
Partition Type 16: 6" metal stud (Clark Dietrich ProStud 20) @ 24" O.C. from floor to underside of structure; provide (1) layer of 5/8" type X gyp board at each side. Total wall thickness = 7 1/4"; install 5 1/2" batt insulation from floor to top of wall. (1) hour rated - UL Des U419
Partition Type 2: 4" metal stud (Clark Dietrich ProStud 20) @ 24" O.C. from floor to underside of structure; provide 5/8" type X gyp board at both sides. Total wall thickness = 5 1/4"; install 3 1/2" batt insulation from floor to top of wall; (1) hour rated - UL Des U419
Partition Type 15: 4" metal stud (Clark Dietrich ProStud 20) @ 24" O.C. from floor to top of opening or adjacent wall; provide 5/8" type X gyp board at both sides. Total wall thickness = 5 1/4"; install 3 1/2" batt insulation from floor to top of wall
Partition Type 17: 4" metal stud (Clark Dietrich ProStud 20) @ 24" O.C. from floor to underside of structure; provide 5/8" type X gyp board at both sides. Total wall thickness = 5 1/4"; install 3 1/2" batt insulation from floor to top of wall; (1) hour rated - UL Des U419
MEP DRAWINGS:
M0.1 MECHANICAL NOTE SHEET
M1.1 2ND FLOOR MECHANICAL PLAN
P0.1 PLUMBING NOTES & SCHEDULES
P1.1 BASEMENT FLOOR PLUMBING PLAN
P1.2 FIRST FLOOR PLUMBING PLAN
P1.3 SECOND FLOOR PLUMBING PLAN
E0.1 ELECTRICAL NOTE SHEET
E1.1 BASEMENT ELECTRICAL PLAN
E2.1 1ST FLOOR ELECTRICAL PLAN
E3.1 2ND FLOOR ELECTRICAL PLAN
DRAWING LISTING
NOT USED
NOT USED
SUBMITTAL REQUIREMENTS
37. ALL PIPING PENETRATIONS THROUGH FLOORS SHALL BE
SEALED WATER TIGHT BY GROUTING PERIMETER GAP BETWEEN
PIPE AND FLOOR STRUCTURE OR BY USING APPROVED UL SLEEVE
AND SEALER SYSTEM. PENETRATIONS OF RATED WALLS SHALL
USE SLEEVE WITH UL APPROVED FIRE SEALANT PER SECTION
714.4.1.1 OF THE 2021 IBC. PENETRATIONS THROUGH FLOORS
SHALL COMPLY WITH SECTION 714.5.1.1 OR 714.5.1.2” .
38. FLOOR PENETRATIONS CONTAINED AND LOCATED WITHIN THE
CAVITY OF A WALL ABOVE OR BELOW THE FLOOR DO NOT REQUIRE
A T RATING PER SECTION 714.5.1.2 EXCEPTION 1. FLOOR
PENETRATIONS BY FLOOR DRAINS, TUB DRAINS OR SHOWER
DRAINS CONTAINED AND LOCATED WITHIN THE CONCEALED SPACE
OF A HORIZONTAL ASSSEMBLY DO NOT REQUIRE A T RATING PER
SECTION 714.5.1.2 EXCEPTION 2
CONSULTANTS
PROJECT NO: FORT LYON LS-6-2021
MODEL FILE:
Fort Lyon Bldg 6 Final final LS version 24.pln
DRAWN BY: TAD
ISSUE DATE:
G-003
12/9/2022
/U se rs /ta du ke
/D oc um en ts /A rc hi ca d
Fi le s/ Fo rt Ly on B ld g
Fi na l f in al
L S v er si on
4.
pl n
OCCUPANCY/PLUMBING
CALCULATIONS & ACM
REPORT
Fort Lyon Life Safety Corrections -
Building 6
T.A. DUKE & ASSOCIATES, Inc.
4220 Brigadoon Lane
Colorado Springs, CO 80906 719 648 7722 taduke@earthlink.net
McShea Consulting LLC 4445 Northpark Dr., Suite 200 Colorado Springs, CO 80907
719 358 8208
12/9/22 ISSUED FOR PRICING AND
PERMIT
3/31/23 CODE COMMENT REVISIONS
4/13/23 ISSUED FOR STATE REVIEW
5/18/23 ISSUED FOR STATE REVIEW
5/25/23
ISSUED FOR CODE
CONSULTANT REVIEW
9/21/2023
5/31/23 ISSUED FOR STATE REVIEW
7/19/23
ISSUED FOR CODE
CONSULTANT REVIEW
8/23/23
ISSUED FOR CODE
CONSULTANT REVIEW
9/12/23
ISSUED FOR CODE
CONSULTANT REVIEW
9/21/23
ISSUED FOR PERMIT
PROJECT NUMBER: 2021-035M21/HB 1408
10/3/23
ISSUED FOR PRICING
Asbestos Inspection Report Page 15 obscured by carpet (was possible in three separate areas) in the First Floor Clinic. Rooms affected by this work, were 109, 111 (a-c and halls), 114, 117, 119, 119a, 120,121, 125, 126, and west end of east/west halls. AC also removed all floor coverings, (carpets, sheet vinyl flooring, floor tiles, and all flooring adhesives) in Building Five’s South Wing, 3rd Floor Special Medical Needs Unit, (approximately 5,900 sq. ft.). Rooms/corridors affected by this work, included all 3rd floor space located south of the elevator lobby.
See GHP report 06505.27-Building 5 Partial Abatement (2nd Floor Inmate Housing and Medical Area). This abatement project was done by HWT during the time of August 27th, 2009 through October 3rd, 2009. Abatement Project included Building 5, 2nd Floor Inmate Housing Unit and Medical Area; Abatement Contractor (AC) removed all floor tiles, floor tile adhesives, and cove base throughout the 2nd Floor of Building 5 (approximately 6,600 sq. ft. of floor surface).
NOTES:_________________________________________________________________
Building 6
Approximately 1,200 sq. ft. of various colored/patterned ACM sheet vinyl floor coverings exist throughout various locations of the building, (see drawings for locations), (25% Chrysotile). This material was in good condition at the time of this inspection exhibiting only minor marks and wearing.
Approximately 10,250 sq. ft. of various colored/patterned, 9” x 9” and 12” x 12” ACM floor tiles and associated adhesives exist throughout various locations of the building, (see drawings for locations), (see drawings for locations), (5-30% Chrysotile). This material was in good condition at the time of this inspection exhibiting only minor breakage and wearing.
Floor tiles and sheet vinyl are normally considered non-friable if the material is in good condition and repair could be performed during routine operations and maintenance activities assuring that the material is not cut, abraded, or in any other way damaged causing release of asbestos fibers or the material must be properly abated prior to renovation/demolition activities.
Approximately 3,000 l.f. of ACM baseboard adhesives exist throughout the building, (see drawings for locations), (2% Chrysotile). This material was in good condition at the time of this inspection. This material should be managed following the facilities Operation & Maintenance Program. The material should be properly abated by a State of Colorado
Asbestos Inspection Report Page 16 licensed General Abatement Contractor prior to renovation or if the material becomes damaged.
Approximately 22,000 sq. ft. of ACM wall plaster exists throughout the facility, (see drawings for locations), (Trace % Chrysotile). The material was in good condition at the time of this inspection. This material remains regulated by the EPA and State of Colorado until determined otherwise by point count analysis. This material should be managed following the facilities Operations & Maintenance Program. The material should be properly abated by a State of Colorado licensed General Abatement Contractor prior to renovation/demolition or if the material becomes damaged. If the material is determined to be less than 1% asbestos by point count at a later time. The material shall be managed by properly trained (OSHA training) personnel.
Approximately 2,500 sq. ft. of gypsum board with asbestos containing joint compounds exists throughout the building, (see drawings for locations), (1% Chrysotile). The material was in good condition at the time of this inspection. This material should be managed following the facilities Operations & Maintenance Program. The material should be properly abated by a State of Colorado licensed General Abatement Contractor prior to renovation/demolition or if the material becomes damaged.
Approximately 2,000 l.f. of ACM Thermal Systems Pipe Insulation exists throughout the building and basement/crawlspace, (see drawings for locations), (8-70% Chrysotile).
This material was in good to poor condition at the time of this inspection. GHP inspected/assessed only those materials that were accessible. Access panels were not available for performing a thorough survey of pipe insulation inside wall cavities and/or pipe chases. Pipe insulation inside walls/pipe chases should be assumed to be asbestos containing until determined otherwise. GHP determined that fiberglass insulation is obscuring remnant TSI on pipes. All fiberglass insulation should be assumed to be covering ACM material. Personal protective equipment should be worn by those entering wall cavities/pipe chases. Isolate the areas surrounding pipe chases when performing routine maintenance in these areas. The material in the crawlspace exhibited significant damage including dislodged material. The crawlspace soils are considered contaminated. Damaged material should be repaired immediately.
Sample Number Material and Location Asbestos Content B-06505.01-62 Brown marbled 12”X 12” floor tile - Sample acquired from Building
6 from dining room at north side stairwell door threshold at east side.
5% Chrysotile in tile
B-06505.01-63 Tan colored 12”X12” floor tile – Sample acquired from Building 6 in dining room at north side stairwell door threshold at east side.
None Detected
B-06505.01-64 Plaster with lathe – Sample acquired from Building 6 walls above ceiling grid at west wall, 3ft down from deck, 12ft in from north wall.
Trace Chrysotile
B-06505.01-65 Acoustic tile – Sample acquired from Building 6 above grid adjacent to room 223 on second floor in middle of hallway.
None Detected
B-06505.01-66 Fibrous flooring material–Sample acquired from Building 6 from room 223, 2ft in from wall under tile.
None Detected
B-06505.01-67 Gypsum board with joint compounds – Sample acquired from Building 6 across from 228 4ft up from floor on the southwest corner of wall.
None Detected
Asbestos Inspection Report Page 17
B-06505.01-68 Hard pack mudded material – Sample acquired from Building 6 over chicken wire that is insulating a hot water exchange in mechanical room in basement, room 10A at north wall.
None Detected
B-06505.01-130 Fireproofing material – Sample acquired from Building 6, taken from inside fire door of room 214 at closet door knob.
None Detected
B-06505.01-575 White insulating panels - Sample acquired from Building 6, east side of level above kitchen fan room, adjacent to elevator equipment room.
None Detected
See GHP report 06505.06- Building 6 Partial Abatement (Mechanical Room).
Abate Building 6 Mechanical Room (Room #10). Abatement Contractor (AC) abated all ACM TSI from all pipes and pipe fittings, (approximately 750 l.f. of 4”-12” OD TSI).
AC also removed/disposed of loose LCP where this condition existed within their immediate work areas and were impacted by asbestos abatement activities.
NOTES:_________________________________________________________________
Building 7
Approximately 600 sq. ft. of various colored/patterned, 9” x 9” and 12” x 12” ACM floor tiles and associated adhesives exist throughout various locations of the building, (see drawings for locations), (5% Chrysotile). This material was in good condition at the time of this inspection exhibiting only minor breakage and wearing.
Floor tiles are normally considered non-friable if the material is in good condition and repair could be performed during routine operations and maintenance activities assuring that the material is not cut, abraded, or in any other way damaged causing release of asbestos fibers or the material must be properly abated prior to renovation/demolition activities.
Approximately 1,800 l.f. of ACM baseboard adhesives exist throughout the building, (see drawings for locations), (2% Chrysotile). This material was in good condition at the time of this inspection. This material should be managed following the facilities Operation & Maintenance Program. The material should be properly abated by a State of Colorado licensed General Abatement Contractor prior to renovation or if the material becomes damaged.
Approximately 14,000 sq. ft. of ACM wall plaster exists throughout the facility, (see drawings for locations), (Trace % Chrysotile). The material was in good condition at the time of this inspection. This material remains regulated by the EPA and State of Colorado until determined otherwise by point count analysis. This material should be
GOBBELL HAYES ACM REPORT GOBBELL HAYES ACM REPORT
GOBBELL HAYES ACM REPORT
PLUMBING FIXTURES REQUIRED:
OCCUPANT LOAD CALCULATION:
1ST FLOOR:
A-2 (KITCHEN) OCCUPANCY: 2,237 NSF/200 NSF = 11.19 OCCUPANTS
11.19 OCCUPANTS / 2 = 5.60 OCCUPANT LOAD PER SEX
PER IBC TABLE 2902.1: ASSEMBLY OCCUPANCY (ASSUME RESTAURANT,
BANQUET HALLS AND FOOD COURTS):
MINIMUM REQUIRED PLUMBING FIXTURES:
MALE WC FEMALE WC LAVS
1/75 1/75 1/200
A-2 (KITCHEN) MINIMUM REQUIRED FIXTURES:
5.60 OCCUPANT LOAD/75 OCCUPANTS PER WC = .075 MALE
5.60 OCCUPANT LOAD/75 OCCUPANTS PER WC = .075 FEMALE
5.60 OCCUPANT LOAD/200 OCCUPANTS PER LAV = .028 MALE
5.60 OCCUPANT LOAD/200 OCCUPANTS PER LAV = .028 FEMALE
S-1 OCCUPANCY: 3,573 SF/300 = 11.91 OCCUPANTS
11.91 OCCUPANTS / 2 = 5.96 OCCUPANT LOAD PER SEX
PER IBC TABLE 2902.1: STORAGE/UTILITY OCCUPANCY:
MINIMUM REQUIRED PLUMBING FIXTURES:
MALE WC FEMALE WC LAVS
1/100 1/100 1/100
S-1 MINIMUM REQUIRED FIXTURES:
5.96 OCCUPANT LOAD/100 OCCUPANTS PER WC = .060 MALE
5.96 OCCUPANT LOAD/100 OCCUPANTS PER WC = .060 FEMALE
5.96 OCCUPANT LOAD/100 OCCUPANTS PER LAV = .060 MALE
5.96 OCCUPANT LOAD/100 OCCUPANTS PER LAV = .060 FEMALE
S-2 OCCUPANCY: 2,083 GSF/300 GSF = 6.94 OCCUPANTS
U OCCUPANCY: 1,073 GSF/300 GSF = 3.58 OCCUPANTS
(6.94 OCCUPANTS + 3.58 OCCUPANTS) / 2 = 5.26 OCCUPANT LOAD PER SEX
PER IBC TABLE 2902.1: STORAGE OCCUPANCY:
MINIMUM REQUIRED PLUMBING FIXTURES:
MALE WC FEMALE WC LAVS
1/100 1/100 1/100
S-2/U MINIMUM REQUIRED FIXTURES:
5.26 OCCUPANT LOAD/100 OCCUPANTS PER WC = .053 MALE
5.26 OCCUPANT LOAD/100 OCCUPANTS PER WC = .053 FEMALE
5.26 OCCUPANT LOAD/100 OCCUPANTS PER LAV = .053 MALE
5.26 OCCUPANT LOAD/100 OCCUPANTS PER LAV = .053 FEMALE
NOTE:
PER 2902.1.1: TO DETERMINE OCCUPANT LOAD OF EACH SEX, THE TOTAL
OCCUPANT LOAD SHALL BE DIVIDED IN HALF. …. FOR CALCULATIONS
INVOLVING MULTIPLE OCCUPANCIES, SUCH FRACTIONAL NUMBERS FOR
EACH OCCUPANCY SHALL BE FIRST SUMMED AND THEN ROUNDED UP TO
THE NEXT WHOLE NUMBER
TOTAL NUMBER OF MALE WC REQUIRED:
A-2 .075 S-1 .060 S-2/U .053
TOTAL: .188 = 1 WC
TOTAL NUMBER OF FEMALE WC REQUIRED:
A-2 .075 S-1 .060 S-2/U .053
TOTAL: .188 = 1 WC
TOTAL NUMBER OF MALE LAVS REQUIRED:
A-2 .028 S-1 .060 S-2/U .053
TOTAL: .141 = 1 LAV
TOTAL NUMBER OF FEMALE LAVS REQUIRED:
A-2 .028 S-1 .060 S-2/U .053
TOTAL: .141 = 1 LAV
WC'S PROVIDED
WOMEN: 2
MEN: 1 + 1 URINAL
UNISEX: 1
LAV'S PROVIDED
WOMEN: 1
MEN: 1
UNISEX" 1
PLUMBING FIXTURES REQUIRED:
OCCUPANT LOAD CALCULATION:
2ND FLOOR:
A-2 (KITCHEN) OCCUPANCY: 4,184 GSF/200 GSF = 20.92 OCCUPANTS
20.92 OCCUPANTS / 2 = 10.46 OCCUPANT LOAD PER SEX
PER IBC TABLE 2902.1: ASSEMBLY OCCUPANCY (ASSUME KITCHENS,
RESTAURANT, BANQUET HALLS AND FOOD COURTS):
MINIMUM REQUIRED PLUMBING FIXTURES:
MALE WC FEMALE WC LAVS
1/75 1/75 1/200
A-2 (KITCHEN) MINIMUM REQUIRED FIXTURES:
10.46 OCCUPANT LOAD/75 OCCUPANTS PER WC = .140 MALE
10.46 OCCUPANT LOAD/75 OCCUPANTS PER WC = .140 FEMALE
10.46 OCCUPANT LOAD/200 OCCUPANTS PER LAV = .052 MALE
10.46 OCCUPANT LOAD/200 OCCUPANTS PER LAV = .052 FEMALE
A-2 (DINING) OCCUPANCY: 3,832 NSF/15 NSF = 255.47 OCCUPANTS
255.47 OCCUPANTS / 2 = 127.74 OCCUPANT LOAD PER SEX
A-2 (KITCHEN) MINIMUM REQUIRED FIXTURES:
127.74 OCCUPANT LOAD/75 OCCUPANTS PER WC = 1.70 MALE
127.74 OCCUPANT LOAD/75 OCCUPANTS PER WC = 1.70 FEMALE
127.74 OCCUPANT LOAD/200 OCCUPANTS PER LAV = .64 MALE
127.74 OCCUPANT LOAD/200 OCCUPANTS PER LAV = .64 FEMALE
B OCCUPANCY: 549 GSF/150 GSF = 3.66 OCCUPANTS
3.66 OCCUPANTS / 2 = 1.83 OCCUPANT LOAD PER SEX
PER IBC TABLE 2902.1: BUSINESS OCCUPANCY:
MINIMUM REQUIRED PLUMBING FIXTURES:
MALE WC FEMALE WC LAVS
1/25 FOR 1ST 50 1/25 FOR 1ST 50 1/40 FOR 1ST 80
AND 1 PER 50 FOR AND 1 PER 50 FOR AND 1 PER 80 FOR
THE REMAINDER THE REMAINDER THE REMAINDER
EXCEEDING 50 EXCEEDING 50 EXCEEDING 80
B MINIMUM REQUIRED FIXTURES:
1.83 OCCUPANT LOAD/25 OCCUPANTS PER WC = .07 MALE
1.83 OCCUPANT LOAD/25 OCCUPANTS PER WC = .07 FEMALE
1.83 OCCUPANT LOAD/40 OCCUPANTS PER LAV = .06 MALE
1.83 OCCUPANT LOAD/40 OCCUPANTS PER LAV = .06 FEMALE
S-2 OCCUPANCY: 148 GSF/300 GSF = .49 OCCUPANTS
U OCCUPANCY: 197 GSF/300 GSF = .66 OCCUPANTS
(.49 OCCUPANTS + .66 OCCUPANTS) / 2 = .56 OCCUPANT LOAD PER SEX
PER IBC TABLE 2902.1: STORAGE OCCUPANCY:
MINIMUM REQUIRED PLUMBING FIXTURES:
MALE WC FEMALE WC LAVS
1/100 1/100 1/100
S-2/U MINIMUM REQUIRED FIXTURES:
.56 OCCUPANT LOAD/100 OCCUPANTS PER WC = .01 MALE
.56 OCCUPANT LOAD/100 OCCUPANTS PER WC = .01 FEMALE
.56 OCCUPANT LOAD/100 OCCUPANTS PER LAV = .01 MALE
.56 OCCUPANT LOAD/100 OCCUPANTS PER LAV = .01 FEMALE
NOTE:
PER 2902.1.1: TO DETERMINE OCCUPANT LOAD OF EACH SEX, THE TOTAL
OCCUPANT LOAD SHALL BE DIVIDED IN HALF. …. FOR CALCULATIONS
INVOLVING MULTIPLE OCCUPANCIES, SUCH FRACTIONAL NUMBERS FOR
EACH OCCUPANCY SHALL BE FIRST SUMMED AND THEN ROUNDED UP TO
THE NEXT WHOLE NUMBER
TOTAL NUMBER OF MALE WC REQUIRED:
A-2 (KITCHEN) .140
A-2 (DINING) 1.700
B .070 S-2/U .010
TOTAL: 1.92 = 2 WC
TOTAL NUMBER OF FEMALE WC REQUIRED:
A-2 (KITCHEN) .140
A-2 (DINING) 1.700
B .070 S-2/U .010
TOTAL: 1.92 = 2 WC
TOTAL NUMBER OF MALE LAVS REQUIRED:
A-2 (KITCHEN) .052
A-2 (DINING) .640
B .060 S-2/U .010
TOTAL: .762 = 1 LAV
TOTAL NUMBER OF FEMALE LAVS REQUIRED:
A-2 (KITCHEN) .052
A-2 (DINING) .640
B .060 S-2/U .010
TOTAL: .762 = 1 LAV
WC'S PROVIDED
WOMEN: 0
MEN: 0
UNISEX: 1
LAV'S PROVIDED
WOMEN: 0
MEN: 0
UNISEX" 1
NOTE:
WC'S PROVIDED - MEN AND WOMEN RESTROOMS ARE PROVIDED IN
BUILDING 5, 1ST FLOOR VIA THE CONNECTING CORRIDOR; 155' AWAY, AS
WELL AS ON THE 3RD FLOOR
THE MAXIMUM POPULATION OF RESIDENTS IS CURRENTLY
CONTRACTUALLY LIMITED TO LESS THAN 245.
PLUMBING CALCULATIONS PLUMBING CALCULATIONS PLUMBING CALCULATIONS
PLUMBING FIXTURES REQUIRED:
OCCUPANT LOAD CALCULATION:
3RD FLOOR:
B OCCUPANCY: 1,925 GSF/150 GSF = 12.83 OCCUPANTS
12.83 OCCUPANTS / 2 = 6.42 OCCUPANT LOAD PER SEX
PER IBC TABLE 2902.1: BUSINESS OCCUPANCY:
MINIMUM REQUIRED PLUMBING FIXTURES:
MALE WC FEMALE WC LAVS
1/25 FOR 1ST 50 1/25 FOR 1ST 50 1/40 FOR 1ST 80
AND 1 PER 50 FOR AND 1 PER 50 FOR AND 1 PER 80 FOR
THE REMAINDER THE REMAINDER THE REMAINDER
EXCEEDING 50 EXCEEDING 50 EXCEEDING 80
B MINIMUM REQUIRED FIXTURES:
6.42 OCCUPANT LOAD/25 OCCUPANTS PER WC = .26 MALE
6.42 OCCUPANT LOAD/25 OCCUPANTS PER WC = .26 FEMALE
6.42 OCCUPANT LOAD/40 OCCUPANTS PER LAV = .16 MALE
6.42 OCCUPANT LOAD/40 OCCUPANTS PER LAV = .16 FEMALE
B OCCUPANCY (A-2 CLASSROOM): 3,972 NSF/ 15 NSF = 264.8 OCCUPANTS
264.8 OCCUPANTS / 2 = 132.4 OCCUPANT LOAD PER SEX
PER IBC TABLE 2902.1: BUSINESS ASSEMBLY OCCUPANCY (ASSUME
LECTURE HALLS):
MINIMUM REQUIRED PLUMBING FIXTURES:
MALE WC FEMALE WC LAVS
1/125 1/65 1/200
B OCCUPANCY (A-2 CLASSROOM) MINIMUM REQUIRED FIXTURES:
132.4 OCCUPANT LOAD/125 OCCUPANTS PER WC = 1.06 MALE
132.4 OCCUPANT LOAD/65 OCCUPANTS PER WC = 2.04 FEMALE
132.4OCCUPANT LOAD/200 OCCUPANTS PER LAV = .662 MALE
132.4 OCCUPANT LOAD/200 OCCUPANTS PER LAV = .662 MALE
S-1 OCCUPANCY: 319 GSF/300 GSF = 1.06 OCCUPANTS
U OCCUPANCY: 65 GSF/300 GSF = .22 OCCUPANTS
(1.06 OCCUPANTS + .22 OCCUPANTS) / 2 = 1.28 OCCUPANT LOAD PER SEX
PER IBC TABLE 2902.1: STORAGE OCCUPANCY:
MINIMUM REQUIRED PLUMBING FIXTURES:
MALE WC FEMALE WC LAVS
1/100 1/100 1/100
S-1/U MINIMUM REQUIRED FIXTURES:
1.28 OCCUPANT LOAD/100 OCCUPANTS PER WC = .013 MALE
1.28 OCCUPANT LOAD/100 OCCUPANTS PER WC = .013 FEMALE
1.28 OCCUPANT LOAD/100 OCCUPANTS PER LAV = .013 MALE
1.28 OCCUPANT LOAD/100 OCCUPANTS PER LAV = .013 FEMALE
NOTE:
PER 2902.1.1: TO DETERMINE OCCUPANT LOAD OF EACH SEX, THE TOTAL
OCCUPANT LOAD SHALL BE DIVIDED IN HALF. …. FOR CALCULATIONS
INVOLVING MULTIPLE OCCUPANCIES, SUCH FRACTIONAL NUMBERS FOR
EACH OCCUPANCY SHALL BE FIRST SUMMED AND THEN ROUNDED UP TO
THE NEXT WHOLE NUMBER
TOTAL NUMBER OF MALE WC REQUIRED:
B .26
B (A-2 CLASSROOM) 1.06
S-1/U .013
TOTAL: 1.333 = 2 WC
TOTAL NUMBER OF FEMALE WC REQUIRED:
B .26
B (A-2 CLASSROOM) 2.04
S-1/U .013
TOTAL: 2.313 = 3 WC
TOTAL NUMBER OF MALE LAVS REQUIRED:
B .16
B (A-2 CLASSROOM) .662
S-1/U .013
TOTAL: 1.333 = 2 WC
TOTAL NUMBER OF FEMALE LAVS REQUIRED:
B .16
B (A-2 CLASSROOM) .662
S-1/U .013
TOTAL: 1.333 = 2 WC
WC'S PROVIDED
WOMEN: 3
MEN: 2 + 1 URINAL
LAV'S PROVIDED
WOMEN: 2
MEN: 2
NOTE:
THE MAXIMUM POPULATION OF RESIDENTS IS CURRENTLY
CONTRACTUALLY LIMITED TO LESS THAN 245.
ACM NOTES
1. IT IS NOT WITHIN THE SCOPE OF WORK OF THE ARCHITECT TO
DISCOVER, LOCATE, HANDLE, REMOVE OR DISPOSE OF ANY
HAZARDOUS MATERIALS INCLUDING, BUT NOT LIMITED TO: ASBESTOS,
ASBESTOS PRODUCTS, POLYCHLORINATED BIPHENYL (PCB),
HYDROCARBONS OR ANY OTHER TOXIC SUBSTANCES. SHOULD THE
G.C. OR ANY OTHER ENTITY WORKING ON BEHALF OF THE G.C. OR
THE OWNER DISCOVER OR ENCOUNTER ANY HAZARDOUS
MATERIALS, THE G.C. SHALL NOTIFY THE APPROPRIATE AUTHORITIES
IMMEDIATELY AND PROCEED IN ACCORDANCE WITH ALL APPLICABLE
LAWS AND REGULATIONS.
2. ALL MATERIALS BEING REMOVED FROM THE SITE SHALL BE
TESTED FOR ACM PRIOR TO ANY DEMOLITION WORK. IF MATERIAL
TESTS POSITIVE FOR ACM (ASBESTOS CONTAINING MATERIALS),
AREA MUST BE CLEARED OF ALL ACM CONTAINING MATERIALS
AFFECTED BY CONSTRUCTION PRIOR TO DEMOLITION
OR CONSTRUCTION
3. ANY ABATEMENT OF ACM SHALL BE ACCOMPLISHED BY A
CONTRACTOR LICENSED BY THE STATE OF COLORADO
FOR ACM REMOVAL.
4. ALL ACM SHALL BE PROPERLY DISPOSED OF ACCORDING
TO REGULATIONS DEFINED BY THE STATE OF COLORADO
5. ALL MATERIAL BEING INSTALLED IN THE PROJECT,
INCLUDING GYP BOARD, JOINT COMPOUND, VINYL TILE,
SHEET VINYL, CEILING TILE, PLASTER, CARPET, BASE
ADHESIVE OR ANY OTHER MATERIAL BEING PROPOSED
SHALL BE TESTED FOR ACM. A REPORT SHALL BE GIVEN
TO THE OWNER INDICATING RESULTS OF ACM TESTING
CONSULTANTS
PROJECT NO: FORT LYON LS-6-2021
MODEL FILE:
Fort Lyon Bldg 6 Final final LS version 24.pln
DRAWN BY: TAD
ISSUE DATE:
G-004
12/9/2022
/U se rs /ta du ke
/D oc um en ts /A rc hi ca d
Fi le s/ Fo rt Ly on B ld g
Fi na l f in al
L S v er si on
4.
pl n
1ST FLOOR CODE STUDY
PLAN
Fort Lyon Life Safety Corrections -
Building 6
T.A. DUKE & ASSOCIATES, Inc.
4220 Brigadoon Lane
Colorado Springs, CO 80906 719 648 7722 taduke@earthlink.net
McShea Consulting LLC 4445 Northpark Dr., Suite 200 Colorado Springs, CO 80907
719 358 8208
12/9/22 ISSUED FOR PRICING AND
PERMIT
3/31/23 CODE COMMENT REVISIONS
4/13/23 ISSUED FOR STATE REVIEW
5/18/23 ISSUED FOR STATE REVIEW
5/25/23
ISSUED FOR CODE
CONSULTANT REVIEW
9/21/2023
5/31/23 ISSUED FOR STATE REVIEW
7/19/23
ISSUED FOR CODE
CONSULTANT REVIEW
8/23/23
ISSUED FOR CODE
CONSULTANT REVIEW
9/12/23
ISSUED FOR CODE
CONSULTANT REVIEW
9/21/23
ISSUED FOR PERMIT
PROJECT NUMBER: 2021-035M21/HB 1408
10/3/23
ISSUED FOR PRICING
117B
117C
117A
119A
109B 109A
108A
108B
107 106 105
107A
104A
101B
121A
102B
102A
101AB
123A
101AA
122A 122B
104B
101A
119C
128A 128B
119B
EGRESS
E G
R E
S S
EGRESS
EGRESS
E G
R E
S S
EGRESS
E G
R E
S S
E G
R E
S S
EGRESS
E
G R
E S
S
E G
R E
S S
E G
R E
S S
E G
R E
S S
EGRESS
Restroom
A: 117 sq ft
Storage
A: 1,056 sq ft
Storage 119A
A: 94 sq ft
Kitchen
A: 234 sq ft
Cooler 117B
A: 172 sq ft
Freezer 117C
A: 209 sq ft Kitchen
117A A: 451 sq ft
Kitchen
A: 269 sq ft
Storage
A: 26 sq ft
Storage
A: 126 sq ft
Cooler
A: 136 sq ft
Mechanical
A: 627 sq ft
Storage
A: 274 sq ft
Cooler
A: 272 sq ft Cooler
A: 176 sq ft
Cooler
A: 199 sq ft
Freezer 107A
A: 493 sq ft
Restroom 102B
A: 88 sq ft
Laundry
A: 88 sq ft
Chase 102A
A: 35 sq ft
Corridor
A: 258 sq ft
Restroom
A: 151 sq ft
Utility
A: 40 sq ft
Storage
A: 222 sq ft
Lobby
A: 287 sq ft
Comm
A: 50 sq ft
Stairwell 101A
A: 248 sq ft
Storage 123A
A: 92 sq ft
Storage
A: 579 sq ft
Storage
A: 357 sq ft
Stairwell 119B
A: 231 sq ft
Utility 104A
A: 71 sq ft
Corridor
A: 521 sq ft
Receiving
A: 182 sq ft
Mechanical
A: 105 sq ft
Corridor
A: 822 sq ft
Corridor 118A
A: 141 sq ft
Corridor
A: 628 sq ft
LOBBY
A: 55 sq ft
FLOOR AREA
A: 10,735 sq ft
N
SCALE: 1/8" = 1'-0"1 1st Floor Code Study Plan 0 4' 8' 16'
COMMENTS FROM THE 2021 EXISTING BUILDING CODE:
LEVEL 2 ALTERATIONS:
EXISTING BUILDING CODE COMMENTS
GROUP S-2 OCCUPANCY - LOW
HAZARD STORAGE
UNASSIGNED OCCUPANCY - MECHANICAL/
ELECTRICAL/UTILITY
GROUP S-1 OCCUPANCY - MODERATE
STORAGE
PROJECT NAME: FORT LYON LIFE SAFETY IMPROVEMENTS - BUILDING 6
STATE PROJECT NUMBER: 2021-035M21/HB 1408
LOCATION: FORT LYON, COLORADO
FLOOR AREA: 1ST FLOOR - 10,735 GSF
CCONSTRUCTION TYPE: NON CONFORMING TYPE IIB (SPRINKLERED)
NOTE: ALL NEW INTERIOR CONSTRUCTION WILL MEET OR EXCEED
FIRE RESISTIVE MATERIALS REQUIRED BY TYPE IIB CONSTRUCTION
ALLOWABLE HEIGHT: A-2 OCCUPANCY: 75'
S-1 OCCUPANCY: 75'
S-2 OCCUPANCY: 75'
ACTUAL HEIGHT: 52'-9" (AT EAST ELEVATION - TO TOP OF ROOF)
ALLOWABLE STORIES: A-2 OCCUPANCY: 4
(ABOVE GRADE) S-1 OCCUPANCY: 3
S-2 OCCUPANCY: 4
ACTUAL STORIES: 3 STORIES ABOVE GRADE
ALLOWABLE FLOOR AREA
PER TABLE 506.2: A-2 OCCUPANCY: 28,500 SF
S-1 OCCUPANCY: 52,500 SF
S-2 OCCUPANCY: 78,000 SF
FRONTAGE INCREASE: 50-57% OF BUILDING PERIMETER AND
30' OR GREATER OPEN SPACE = .50
ALLOWABLE AREA THIS STORY: A-2 OCCUPANCY: Aa = 28,500 SF + (9,500 SF X .5) = 33,250 SF S-1 OCCUPANCY: Aa = 52,500 SF + (17,500 SF X .5) = 61,250 SF S-2 OCCUPANCY: Aa = 78,000 SF + (26,000 SF X .5) = 91,000 SF
MIXED OCCUPANCY FACTOR: 2,199 SF/ 33,250 SF = .07
1,763 SF/ 61,250 SF = .03
9,190 SF/ 91,000 SF = .10
TOTAL = .20 = LESS THAN 1
ACTUAL BUILDING AREA: 30,472 GSF
OCCUPANCY CALCS: 1ST FLOOR:
A-2 (KITCHEN) OCCUPANCY: 2,237 SF/200 = 11.19
S-1 OCCUPANCY: 3,573 SF/300 = 11.91
S-2 PCCUPANCY: 2,083 SF/300 = 6.94
UTILITY RM. OCCUPANCY: 1,073 SF/300 = 3.58
TOTAL FLOOR OCCUPANCY: 33.62 = 34
EXITING CALCS : 1ST FLOOR:
(EXIT CORIDOR WIDTH) 34 * .15 = 5.1"
REQUIRED EGRESS CORRIDOR WIDTH: 44"
ACTUAL EGRESS CORRIDOR WIDTH: 5'-9" (MINIMUM CORRDIOR WIDTH)
REQUIRED EXIT STAIR WIDTH: 34 * .20 = 6.8" -
ACTUAL EXIT STAIR WIDTH ((3RD FLOOR) + (2ND FLOOR) + 34) * .20 = "
(2) STAIRS PROVIDED : (1) @ 60" WIDTH AND @ (1) @ 48" WIDTH
GROUP A-2 OCCUPANCY - ASSEMBLY/
KITCHEN
CODE NOTES
LEGEND
6" CLAY TILE CONSTRUCTION WITH FINSH
ON ONE SIDE (UP TO 1 HOUR FIRE RATING) -
PENETRATIONS HAVE NOT BEEN VERIFIED
FOR (1) HOUR COMPLIANCE
8" DOUBLE WYTHE BRICK CONSTRUCTION
WITH FINSH ON ONE SIDE (UP TO 6 HOUR
FIRE RATING) - PENETRATIONS HAVE NOT
BEEN VERIFIED FOR (1) HOUR COMPLIANCE
12 1/2" CLAY TILE CONSTRUCTION WITH
BRICK AT EXTERIOR AND PLASTER AT
INTERIOR (UP TO 6 HOUR FIRE RATING) -
PENETRATIONS HAVE NOT BEEN VERIFIED
FOR (1) HOUR COMPLIANCE
(1) HOUR WALL CONSTRUCTION (NEW WALL
CONSTRUCTION)
2 x 4 WOOD STUD AT 16" OC WITH 5/8"
PLASTER ON METAL LATHE EACH SIDE- (1)
HOUR FIRE RATING - PENETRATIONS HAVE
NOT BEEN VERIFIED FOR (1) HOUR
COMPLIANCE
4" CLAY TILE CONSTRUCTION WITH FINSH
BOTH SIDES (UP TO 1 HOUR 34 MINUTES
FIRE RATING) - PENETRATIONS HAVE NOT
BEEN VERIFIED FOR (1) HOUR COMPLIANCE
SHOWN AS (2) HR RATED CONSTRUCTION
ON PREVIOUS CONSTRUCTION
DOCUMENTS) - PENETRATIONS HAVE NOT
BEEN VERIFIED FOR (2) HOUR COMPLIANCE
SHOWN AS (1) HR RATED CONSTRUCTION
ON PREVIOUS CONSTRUCTION
DOCUMENTS) - PENETRATIONS HAVE NOT
BEEN VERIFIED FOR (1) HOUR COMPLIANCE
CONSULTANTS
PROJECT NO: FORT LYON LS-6-2021
MODEL FILE:
Fort Lyon Bldg 6 Final final LS version 24.pln
DRAWN BY: TAD
ISSUE DATE:
G-005
12/9/2022
/U se rs /ta du ke
/D oc um en ts /A rc hi ca d
Fi le s/ Fo rt Ly on B ld g
Fi na l f in al
L S v er si on
4.
pl n
2ND FLOOR CODE STUDY
PLAN
Fort Lyon Life Safety Corrections -
Building 6
T.A. DUKE & ASSOCIATES, Inc.
4220 Brigadoon Lane
Colorado Springs, CO 80906 719 648 7722 taduke@earthlink.net
McShea Consulting LLC 4445 Northpark Dr., Suite 200 Colorado Springs, CO 80907
719 358 8208
12/9/22 ISSUED FOR PRICING AND
PERMIT
3/31/23 CODE COMMENT REVISIONS
4/13/23 ISSUED FOR STATE REVIEW
5/18/23 ISSUED FOR STATE REVIEW
5/25/23
ISSUED FOR CODE
CONSULTANT REVIEW
9/21/2023
5/31/23 ISSUED FOR STATE REVIEW
7/19/23
ISSUED FOR CODE
CONSULTANT REVIEW
8/23/23
ISSUED FOR CODE
CONSULTANT REVIEW
9/12/23
ISSUED FOR CODE
CONSULTANT REVIEW
9/21/23
ISSUED FOR PERMIT
PROJECT NUMBER: 2021-035M21/HB 1408
10/3/23
ISSUED FOR PRICING
201A
217A
210A
205A
205D
205D-A
202A
206A
201B
205C
E G
R E
S S
EGRESS
E G
R E
S S
EGRESS
EGRESS
E G
R E
S S
E G
R E
S S
EGRESS
EGRESS
E G
R E
S S
Dining
A: 1,895 sq ft
Lobby
A: 204 sq ft
Dining
A: 1,937 sq ft
Serving
A: 334 sq ft
Stairwell
A: 354 sq ft
Kitchen
A: 3,142 sq ft
Prep
A: 244 sq ft
Chase 202A
A: 36 sq ft
Cooler
A: 88 sq ft
Cooler
A: 60 sq ft
Stair 205D
A: 94 sq ft
Utility 205C
A: 42 sq ft
Corridor
A: 62 sq ft
Restroom 205A
A: 109 sq ft
Cooler
A: 204 sq ft
Office
A: 408 sq ft
Utility
A: 40 sq ft
Utility
A: 42 sq ft
Serving
A: 293 sq ft
Warewashing
A: 660 sq ft
Office
A: 141 sq ft
Utility
A: 52 sq ft
Comm
A: 47 sq ft
Comm 215A
A: 16 sq ft
FLOOR AREA
A: 10,710 sq ft
STAIR
A: 232 sq ft
N
SCALE: 1/8" = 1'-0"1 2nd Floor Code Study Plan 0 4' 8' 16'
COMMENTS FROM THE 2021 EXISTING BUILDING CODE:
LEVEL 2 ALTERATIONS:
EXISTING BUILDING CODE COMMENTS
CODE NOTES
LEGEND
PROJECT NAME: FORT LYON LIFE SAFETY IMPROVEMENTS - BUILDING 5
STATE PROJECT NUMBER: 2021-035M21/HB 1408
LOCATION: FORT LYON, COLORADO
FLOOR AREA: 2ND FLOOR -10,710 GSF
CONSTRUCTION TYPE: NON CONFORMING TYPE IIB (SPRINKLERED)
NOTE: ALL NEW INTERIOR CONSTRUCTION WILL MEET OR EXCEED
FIRE RESISTIVE MATERIALS REQUIRED BY TYPE IIB CONSTRUCTION
ALLOWABLE HEIGHT: A-2 OCCUPANCY: 75'
B OCCUPANCY: 75'
S-1 OCCUPANCY: 75'
S-2 OCCUPANCY: 75'
ACTUAL HEIGHT: 52'-9" (AT EAST ELEVATION - TO TOP OF ROOF)
ALLOWABLE STORIES: A-2 OCCUPANCY: 3
(ABOVE GRADE) B OCCUPANCY: 4
S-1 OCCUPANCY: 3
S-2 OCCUPANCY: 4
ACTUAL STORIES: 3 STORIES ABOVE GRADE
ALLOWABLE FLOOR AREA
PER TABLE 506.2: A-2 OCCUPANCY: 28,500 SF
B OCCUPANCY: 69,000 SF
S-1 OCCUPANCY: 52,500 SF
S-2 OCCUPANCY: 78,000 SF
FRONTAGE INCREASE: 50-75% OF BUILDING PERIMETER AND
30' OR GREATER OPEN SPACE = .50
ALLOWABLE AREA THIS STORY: A-2 OCCUPANCY: Aa = 28,500 SF + (9,500 SF X .5) = 33,250 SF B OCCUPANCY: Aa = 69,000 SF + (23,000 SF X .5) = 80,500 SF S-1 OCCUPANCY: Aa = 52,500 SF + (17,500 SF X .5) = 61,250 SF S-2 OCCUPANCY: Aa = 78,000 SF + (26,000 SF X .5) = 91,000 SF
MIXED OCCUPANCY FACTOR: 2,199 SF/ 33,250 SF = .07
549 SF/ 80,500 SF = .01
1,763 SF/ 61,250 SF = .03
9,190 SF/ 91,000 SF = .10
TOTAL = .21 = LESS THAN 1
ACTUAL BUILDING AREA: 30,472 GSF
OCCUPANCY CALCS: 2ND FLOOR:
A-2 OCCUPANCY (KITCHEN): 4,184 SF/200 = 20.92
A-2 OCCUPANCY (DINING): 3,832 SF/15 = 255.46
B OCCUPANCY: 549 SF/150 = 3.66
S-2 OCCUPANCY: 148 SF/300 = .49
UTILITY RM. OCCUPANCY: 197 SF/300 = .66
TOTAL FLOOR OCCUPANCY: 281.19 = 282
NOTE: THE TOTAL NUMBER OF RESIDENTS IS CONTRACTUALLY LIMITED TO 245 AT THIS TIME
EXITING CALCS : 2ND FLOOR:
(EXITING WIDTH) 282 * .15 = 42.3"
REQUIRED EGRESS CORRIDOR WIDTH: 44"
ACTUAL EGRESS CORRIDOR WIDTH: 5'-0" (AT NARROWEST POINT)
(STAIR WIDTH) 2ND FLOOR: 282 * .20 = 56.4" -
( 42" (2ND FLOOR) + 46.20") = 88.2"
(2) STAIRS PROVIDED : (1) @ 60" WIDTH
(1) @ 48" WIDTH
GROUP B OCCUPANCY - BUSINESS
GROUP A-3 OCCUPANCY - ASSEMBLY
GROUP S-1 OCCUPANCY - MODERATE
STORAGE
GROUP A-2 OCCUPANCY - ASSEMBLY/
KITCHEN
UNASSIGNED OCCUPANCY - MECHANICAL/
ELECTRICAL/UTILITY
LEGEND
6" CLAY TILE CONSTRUCTION WITH FINSH
ON ONE SIDE (UP TO 1 HOUR FIRE RATING) -
PENETRATIONS HAVE NOT BEEN VERIFIED
FOR (1) HOUR COMPLIANCE
8" DOUBLE WYTHE BRICK CONSTRUCTION
WITH FINSH ON ONE SIDE (UP TO 6 HOUR
FIRE RATING) - PENETRATIONS HAVE NOT
BEEN VERIFIED FOR (1) HOUR COMPLIANCE
12 1/2" CLAY TILE CONSTRUCTION WITH
BRICK AT EXTERIOR AND PLASTER AT
INTERIOR (UP TO 6 HOUR FIRE RATING) -
PENETRATIONS HAVE NOT BEEN VERIFIED
FOR (1) HOUR COMPLIANCE
(1) HOUR WALL CONSTRUCTION (NEW WALL
CONSTRUCTION)
2 x 4 WOOD STUD AT 16" OC WITH 5/8"
PLASTER ON METAL LATHE EACH SIDE- (1)
HOUR FIRE RATING - PENETRATIONS HAVE
NOT BEEN VERIFIED FOR (1) HOUR
COMPLIANCE
4" CLAY TILE CONSTRUCTION WITH FINSH
BOTH SIDES (UP TO 1 HOUR 34 MINUTES
FIRE RATING) - PENETRATIONS HAVE NOT
BEEN VERIFIED FOR (1) HOUR COMPLIANCE
SHOWN AS (2) HR RATED CONSTRUCTION
ON PREVIOUS CONSTRUCTION
DOCUMENTS) - PENETRATIONS HAVE NOT
BEEN VERIFIED FOR (2) HOUR COMPLIANCE
SHOWN AS (1) HR RATED CONSTRUCTION
ON PREVIOUS CONSTRUCTION
CONSULTANTS
PROJECT NO: FORT LYON LS-6-2021
MODEL FILE:
Fort Lyon Bldg 6 Final final LS version 24.pln
DRAWN BY: TAD
ISSUE DATE:
G-006
12/9/2022
/U se rs /ta du ke
/D oc um en ts /A rc hi ca d
Fi le s/ Fo rt Ly on B ld g
Fi na l f in al
L S v er si on
4.
pl n
3RD FLOOR CODE STUDY
PLAN
Fort Lyon Life Safety Corrections -
Building 6
T.A. DUKE & ASSOCIATES, Inc.
4220 Brigadoon Lane
Colorado Springs, CO 80906 719 648 7722 taduke@earthlink.net
McShea Consulting LLC 4445 Northpark Dr., Suite 200 Colorado Springs, CO 80907
719 358 8208
12/9/22 ISSUED FOR PRICING AND
PERMIT
3/31/23 CODE COMMENT REVISIONS
4/13/23 ISSUED FOR STATE REVIEW
5/18/23 ISSUED FOR STATE REVIEW
5/25/23
ISSUED FOR CODE
CONSULTANT REVIEW
9/21/2023
5/31/23 ISSUED FOR STATE REVIEW
7/19/23
ISSUED FOR CODE
CONSULTANT REVIEW
8/23/23
ISSUED FOR CODE
CONSULTANT REVIEW
9/12/23
ISSUED FOR CODE
CONSULTANT REVIEW
9/21/23
ISSUED FOR PERMIT
PROJECT NUMBER: 2021-035M21/HB 1408
10/3/23
ISSUED FOR PRICING
317A 316 317
315A
313 312
318B
318C
321A
322A
323A
324A
325A
305A
304B
329330
304A
318A
326A
326B
E G
R E
S S
E G
R E
S S
EGRESS
EGRESS
Restroom
A: 167 sq ft
Restroom
A: 192 sq ft
STAIR
A: 232 sq ft
CORRIDOR
A: 364 sq ft
Conference
A: 393 sq ft
Meeting
A: 173 sq ft
Training
A: 649 sq ft
Meeting
A: 182 sq ft
Meeting
A: 184 sq ft
Meeting
A: 184 sq ft
Meeting
A: 184 sq ft
Office
A: 181 sq ft
Training
A: 596 sq ft
Office
A: 118 sq ft
Conference
A: 315 sq ft
Stairwell
A: 198 sq ft
Meeting
A: 216 sq ft
Meeting
A: 334 sq ft
Storage 304A
A: 14 sq ft Office
A: 129 sq ft
STORAGE
305A
A: 13 sq ft
Utility
A: 12 sq ft
Office
A: 109 sq ft
Storage
A: 113 sq ft
Storage
A: 60 sq ft
Conference
A: 381 sq ft
Utility 315A
A: 53 sq ft
FLOOR AREA
A: 1,078 sq ft
FLOOR AREA
A: 7,949 sq ft
CORRIDOR
303A
A: 938 sq ft
CORRIDOR
303B
A: 200 sq ft
N
SCALE: 1/8" = 1'-0"1 3rd Floor Code Study Plan 0 4' 8' 16'
COMMENTS FROM THE 2021 EXISTING BUILDING CODE:
LEVEL 2 ALTERATIONS:
EXISTING BUILDING CODE COMMENTS
CODE NOTES
LEGEND
GROUP B OCCUPANCY - BUSINESS
GROUP S-1 OCCUPANCY - MODERATE
STORAGE
PROJECT NAME: FORT LYON LIFE SAFETY IMPROVEMENTS - BUILDING 5
STATE PROJECT NUMBER: 2021-035M21/HB 1408
LOCATION: FORT LYON, COLORADO
FLOOR AREA: 3RD FLOOR -10,735 GSF
CONSTRUCTION TYPE: NON CONFORMING TYPE IIB (SPRINKLERED)
NOTE: ALL NEW INTERIOR CONSTRUCTION WILL MEET OR EXCEED
FIRE RESISTIVE MATERIALS REQUIRED BY TYPE IIB CONSTRUCTION
ALLOWABLE HEIGHT: B OCCUPANCY: 75'
A-3 OCCUPANCY: 75'
S-1 OCCUPANCY: 75'
ACTUAL HEIGHT: 52'-9" (AT EAST ELEVATION - TO TOP OF ROOF)
ALLOWABLE STORIES: B OCCUPANCY: 4
(ABOVE GRADE) S-1 OCCUPANCY: 3
ACTUAL STORIES: 3 STORIES ABOVE GRADE
ALLOWABLE FLOOR AREA
PER TABLE 506.2: B OCCUPANCY: 69,000 SF
S-1 OCCUPANCY: 52,500 SF
FRONTAGE INCREASE FACTOR: 50-75% OF BUILDING PERIMETER AND
30' OR GREATER OPEN SPACE = .50
ALLOWABLE AREA THIS STORY: B OCCUPANCY: Aa = 69,000 SF + (23,000 SF X .5) = 80,500 SF S-1 OCCUPANCY: Aa = 52,500 SF + (17,500 SF x .5) = 61,250 SF
MIXED OCCUPANCY FACTOR: N/A; S-1 OCCUPANCY IS ANCILLARY TO THE B OCCUPANCY
ACTUAL BUILDING AREA: 30,472 GSF
OCCUPANCY CALCS: 3RD FLOOR:
B OCCUPANCY: 1,925 SF/150 = 12.83
B OCCUPANCY (CLASSROOM ) 3,972 SF/15 = 264.8
S-1 OCCUPANCY: 319 SF/300 = 1.06
UTILITY RM. OCCUPANCY: 65 SF/300 = .22
TOTAL FLOOR OCCUPANCY: 278.91 = 279
NOTE: THE TOTAL NUMBER OF RESIDENTS IS CONTRACTUALLY LIMITED TO 245 AT THIS TIME
EXITING CALCS : 3RD FLOOR:
(EXITING WIDTH) 279 * .15 = 41.85"
REQUIRED EGRESS CORRIDOR WIDTH: 44"
ACTUAL EGRESS CORRIDOR WIDTH: 7'-4" (AT NARROWEST POINT)
(STAIR WIDTH) 3RD FLOOR: 157 * .20 = 55.8"
(2) STAIRS PROVIDED : (1) @ 60" WIDTH
(1) @ 48" WIDTH
GROUP B OCCUPANCY - RESIDENT
TRAINING/TEACHING
UNASSIGNED OCCUPANCY - MECHANICAL/
ELECTRICAL/UTILITY
6" CLAY TILE CONSTRUCTION WITH FINSH
ON ONE SIDE (UP TO 1 HOUR FIRE RATING) -
PENETRATIONS HAVE NOT BEEN VERIFIED
FOR (1) HOUR COMPLIANCE
8" DOUBLE WYTHE BRICK CONSTRUCTION
WITH FINSH ON ONE SIDE (UP TO 6 HOUR
FIRE RATING) - PENETRATIONS HAVE NOT
BEEN VERIFIED FOR (1) HOUR COMPLIANCE
12 1/2" CLAY TILE CONSTRUCTION WITH
BRICK AT…