Appendix D - MIL-STD-188-124B.pdf
PDF 2 MB Posted
- Attached to
- MEC Raised Floor Federal contract opportunity
- Solicitation number
- HC102821R0024
- Issued by
- Defense Information Systems Agency
About this file
This solicitation is for a raised floor replacement project at a Defense Information Systems Agency facility. The contractor will be required to provide and install a concrete core access flooring system with a structural load rating of 2500 pounds. The new flooring system will replace the existing panels and pedestals. The period of performance is 365 days after award. A pre-proposal site visit is scheduled for March 17th and all questions are due by March 24th.
View the file
Other files for this federal contract opportunity
Show all 32
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMSC N/A
DISTRIBUTION STATEMENT A - Approved for public release distribution is unlimited.
MIL-S
NOTIC
18 Dec
DEPARTMENT OF DEFENSE
INTERFACE STANDARD
GROUNDING, BONDING AND SHIELDING
TO ALL HOLDERS OF MIL-STD-188-124B
1. THE FOLLOWING PAGES OF MIL-STD-188-124B HAVE BEEN REVISED
THE PAGES LISTED:
NEW PAGE DATE SUPERSEDED PAGE
i 1 February 1992 i Reprint ii 18 December 2000 ii 1 Febru v 18 December 2000 v 1 Febru vi 1 February 1992 vi Reprint 1 18 December 2000 1 1 Febru 2 1 February 1992 2 Reprint 3 1 February 1992 3 Reprint 4 18 December 2000 4 1 Febru
15 18 December 2000 15 1 Febru 16 18 December 2000 16 1 Febru 17 18 December 2000 17 1 Febru 18 18 December 2000 18 1 Febru 31 18 December 2000 31 1 Febru 32 1 February 1992 32 Reprint
DD Form 1426 18 December 2000 DD Form 1426 1 Febru
2. RETAIN THIS NOTICE AND INSERT BEFORE TABLE OF CONTENTS.
3. Holders of MIL-STD-188-124B will verify that page changes and additions indicated entered. This notice and page will be retained as a check sheet. This issuance, together pages, is a separate publication. Each notice is to be retained by stocking points until th is completely revised or canceled.
CUSTODIANS: Preparing Activity:
ARMY: AC DISA: DC1
AIR FORCE:02 (Project TCSS-0059)
NAVY: EC
DIA: DI
NSA: NS
USMC: MC
METRIC
NOTICE OF
CHANGE
AREA TCSS
TD-188-124B
E 3 ember 2000
AND SUPERSEDE
DATE
ed without change ary 1992 ary 1992 ed without change ary 1992 ed without change ed without change ary 1992 ary 1992 ary 1992 ary 1992 ary 1992 ary 1992 ed without change ary 1992 above have been with appended e military standards
MIL-STD-188-124B
1 Feb 92
SUPERSEDING
MIL-STD-188-124A
2 FEBRUARY 1984
DEPARTMENT OF DEFENSE
INTERFACE STANDARD
GROUNDING, BONDING AND SHIELDING
for
Common Long Haul/Tactical Communication Systems
Including Ground Based Communications-
Electronics Facilities and Equipments
AMSC N/A AREA TCSS
DISTRIBUTION STATEMENT A. Approved for public release; distribution is unlimited.
METRIC
SUPERSEDES PAGE ii OF MIL-STD-188-124B ii
FOREWORD
1. This Military Standard is approved and mandatory for use by all Departments and Agencies of the Department of Defense in accordance with Department of Defense Instruction 5000.2, dated 23 February 1991.
2. Beneficial comments (recommendations, additions, deletions) and any pertinent data which may be of use in improving this document should be addressed to:DISA/JIEO Center For Standards, ATTN: JEBB, Fort Monmouth, NJ, 07703-5613, by using the self-addressed Standardization Document Improvement Proposal (DD Form 1426) appearing at the end of this document or by letter.
3. Standards for all military communications are published as part of a MIL-STD-188 series of documents: Military Communications System Technical Standards are subdivided into Common Long Haul/Tactical Standards (MIL- STD-188-100 series), Tactical Standards (MIL-STD-188-200 series) and Long Haul Standards (MIL-STD-188-300 series).
4. This document contains technical standards and design objectives to ensure the optimum performance of ground-based telecommunications C-E equipment installations. This is accomplished by reducing noise and by providing adequate protection against power system faults and lightning strikes. Thorough consideration must be given to the grounding of equipment and facility installations, the bonding required, and the methods of shielding and implementation needed for personnel safety and equipment control.
5. This standard is also recommended for applicable use on any ground facility or equipment where grounding, bonding, shielding, personnel safety, lightning and EMC are required. Examples of such facilities are aircraft simulators, computer centers, laboratory buildings, weapons checkout and assembly, etc.
6. Paragraph 5.1, Grounding, for this standard is divided as follows:
I. Detailed requirements for facilities, including buildings and associated structures used principally for C-E equipment.
II. Detailed requirements for C-E equipment which address grounding, bonding, and shielding for tactical/long haul fixed ground transportables and military communications electronics equipment installations and associated subsystems.
7. Detailed requirements for Bonding and Shielding are contained in 5.2 and 5.3.
8. This standard is further implemented by MIL-HDBK-419; Grounding, Bonding, and Shielding for Electronic Facilities and Equipments.
9. Notations are not used in this revision to identify changes with respect to the previous issue due to the extensiveness of the changes.
SUPERSEDES PAGE v OF MIL-STD-188-124B v
CONTENTS (Con't)
Paragraph Page
5.1.2.1.1.2 Equipment Signal Ground Terminations
5.1.2.1.1.3 Shield Terminations of Coaxial and Other Higher Frequency Cable
5.1.2.1.1.4 Overall Shields
5.1.2.2 Fault Protection Subsystem
5.1.2.2.1 General
5.1.2.2.2 Personnel Protection
5.1.2.2.3 AC Power Neutral
5.1.2.2.4 Individual Power Line Filters
5.1.2.2.5 Convenience Outlets
5.1.2.2.6 Portable Equipment
5.2 Bonding
5.2.1 General
5.2.2 Surface Platings or Treatments
5.2.3 Bond Protection
5.2.3.1 Corrosion Protection
5.2.3.2 Compression Bonds in Protected Areas
5.2.3.3 Vibration
5.2.3.3.1 Bonding Straps
5.2.4 Bond Resistance
5.2.5 Materials
5.2.5.1 Sweat Solder
5.2.5.2 Brazing Solder
5.2.5.3 Clamps
5.2.5.4 Nuts, Bolts and Washers
5.2.6 Direct Bonds
5.2.6.1 Welding
5.2.6.2 Brazing and Silver Soldering
5.2.6.3 Bonding of Copper to Steel
5.2.6.4 Soft Soldering
5.2.6.4.1 Sweat Soldering
5.2.6.4.2 Sheet Metal or Duct Work
5.2.6.5 Bolting
5.2.6.6 C-Clamps and Spring Clamps
5.2.7 Indirect Bonds
5.2.8 Surface Preparation
5.2.8.1 Area to be Cleaned
5.2.8.2 Paint Removal
5.2.8.3 Inorganic Film Removal
5.2.8.4 Final Cleaning
5.2.8.4.1 Clad Metals
5.2.8.4.2 Aluminum Alloy
5.2.8.5 Completion of the Bond
5.2.9 Dissimilar Metals
5.2.9.1 Corrosion Prevention
CONTENTS (Con’t) Paragraph Page
REPRINTED WITHOUT CHANGE
vi
5.2.10 Enclosure Bonding
5.2.10.1 Subassemblies
5.2.10.2 Equipments
5.2.11 Connector Mounting
5.2.12 Shield Terminations
5.2.13 RF Gaskets
5.3 Shielding
5.3.1 General
5.3.1.1 Basic Shielding Requirements
5.3.1.2 Shielded Enclosures
5.3.2 Electromagnetic Interference (EMI) Control
5.3.2.1 Materials
5.3.2.2 Gaskets
5.3.2.3 Filter Integration
5.3.2.4 Control of Apertures
5.3.2.5 Wire and Cable Routing
5.3.2.6 Telephone Cable Shields
APPENDIX - Discussion of Signal Ground Systems
FIGURES
Figure Page
1 Example of Equipotential or Multipoint Grounding to Earth Electrode Subsystem for Overhead Plane
2 Example of Equipotential Plane to Earth Electrode Subsystem (New Construction)
3 Typical Single Point Entry for Exterior Penetrations (Top View) 4 Typical Entry Plate Showing Rigid Cable, Conduit and Pipe Penetrations 5 Radius and Angle of Down Conductor Bends 6 Typical Equipotential Ground Plane for Higher
Frequency Installation (New Construction)
SUPERSEDES PAGE 1 OF MIL-STD-188-124B
1. SCOPE
1.1 Purpose. This standard establishes the minimum basic requirements and goals for grounding, bonding, and shielding of ground-based telecommunications C-E equipment installations, subsystems, and facilities including buildings and structures supporting tactical and long haul military communication systems.
1.2 Content. This standard addresses the facilities ground systems, as well as grounding, bonding, and shielding and lightning protection for telecommunications C-E facilities and equipment. Grounding for building and structures is listed under the headings of Earth Electrode Subsystem, Fault Protection Subsystem, Lightning Protection Subsystem and Signal Reference Subsystem.
1.3 Applications. This standard shall be used in the design and engineering of new ground-based military communication systems, subsystems, and equipment installations as well as those C-E facilities undergoing major retrofit requiring Military Construction (MILCON) Funding. This includes air traffic control and navigational aid facilities, radio, radar, satellite ground terminals, telephone central offices, microwave and data communications systems, as well as C-E transportables, aircraft simulators, computer centers, and weapon assembly facilities. When upgrading existing facilities for installation of minor C-E equipment, the requirements of this standard shall be established on a case-by-case basis by the cognizant engineering agency. Use of this standard for other ground C-E facilities or equipment is also encouraged. It is not to be used solely as the basis for retrofit of existing C-E facilities.
It does not apply to general construction such as barracks, administration buildings, dining facilities, warehouses, and non-communications facilities, nor does it apply to mobile units such as tanks, trucks, jeeps, etc. When MILCON Funding improvements are made to any structure housing a communications, computer, or electronic facility this standard does apply.
1.4 Objectives. The objectives of this standard are to provide for the protection of personnel, equipment, buildings and structures against the hazards posed by electrical power faults and lightning strikes. It also provides for the reduction of noise and electromagnetic interference caused by inadequate grounding, bonding and shielding of ground based military communications installations to acceptable performance levels. It shall be required that the grounding, bonding, and shielding system be engineered to be compatible with the supplemental requirements of the specific equipment or facility supporting these communications.
1.5 System Standards and Design Objectives. The parameters and other requirements specified in this document are mandatory system standards if the word “shall” is used in connection with the parameter value or requirement under consideration. Non-mandatory design objectives are indicated by parentheses after a standardized parameter value or by the word “should” in connection with the parameter value or requirement under consideration. For a definition of the terms “system standard” and “design objective” (DO), see FED-STD-1037.
REPRINTED WITHOUT CHANGE
2. REFERENCED DOCUMENTS
2.1 Government Documents.
2.1.1 Specifications, Standards, and Handbooks. Unless otherwise specified, the following specifications, standards, and handbooks of the issue listed in that issue of the Department of Defense Index of Specifications and Standards (DODISS) specified in a solicitation form a part of this standard to the extent specified herein.
SPECIFICATIONS
FEDERAL
P-D-680 - Dry Cleaning and Degreasing Solvent
TT-P-1757 - Primer Coating, Zinc Chromate, Low Moisture Sensitivity
STANDARDS
FEDERAL
FED-STD-1037 - Glossary of Telecommunication Terms
FIPS PUB 94 - Guideline on Electrical Power for ADP Installations
MILITARY
AN-735 - Clamp, Loop Type Bonding
AN-742 - Clamp, Loop, Plain, Support, Aircraft
MIL-E-6051D - Electromagnetic Compatibility System Requirements
MIL-STD-285 - Attenuation Measurement for Enclosures, Electromagnetic Shielding, for Electronic Test Purposes, Method of
MIL-STD-454 - Standard General Requirements for Electronic Equipment
MIL-STD-461 - Electromagnetic Emission and Susceptibility Requirements for the Control of Electromagnetic Interference
MIL-STD-462 - Electromagnetic Interference Characteristics, Measurement of
MIL-STD-463 - Definitions and Systems of Units, Electromagnetic Interference and Electromagnetic Compatibility Technology
MIL-STD-1857 - Grounding, Bonding and Shielding Design Practices
REPRINTED WITHOUT CHANGE
MIL-C-83413 - Connectors and Assemblies, Electrical Aircraft Grounding: Type IV Jumper Cable Assembly, Lead, Electrical
MIL-STD-188-125 - High Altitude Electromagnetic Pulse (HEMP) Protection for Ground-Based C4I Facilities
HANDBOOKS
MILITARY
MIL-HDBK-232 - Red/Black Engineering Installation Guidelines
MIL-HDBK-419 - Grounding, Bonding, and Shielding for Electronic Equipments and Facilities
MIL-HDBK-1195 - Radio Frequency Shielded Enclosures
FM-1 1-487-4/ - Installation Practices: Communications TO 31-1024 Systems Grounding, Bonding, and Shielding
2.1.2 Other Government Documents, Drawings, and Publications. The following other Government documents, drawings, and publications form a part of this standard to the extent specified herein.
DOD Directive 1000.3 - Safety and Occupational Health Policy for the Department of Defense
DOD Directive 3222.3 - Department of Defense Electromagnetic Compatibility Program
(Copies of specifications, standards, handbooks, drawings, and publications required by contractors in connection with specific acquisition functions should be obtained from the contracting activity or as directed by the contracting officer.)
2.2 Other Publications. The following document(s) form a part of this standard to the extent specified herein.
The issues of the documents which are indicated as DOD adopted shall be the issue listed in the current DODISS and the supplement thereto, if applicable.
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
AISC S326 - Specification for the Design, Fabrication and Erection of Structural Steel for Buildings
(Application for copies of the AISC specification should be addressed to the American Institute of Steel Construction, 400 North Michigan Avenue, Chicago IL 60611.)
AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM)
ASTM B 32 - Standard Specification for Solder Metal (DOD Adopted)
(Application for the ASTM document should be addressed to the American Society for Testing and Materials, 1916 Race Street, Philadelphia, PA 19103.)
SUPERSEDES PAGE 4 of MIL-STD-188-124B
AMERICAN WELDING SOCIETY (AWS)
AWS A 5.8 - Specification for Brazing Filler Metal (DOD Adopted, ANSI Approved)
(Application for the AWS specification should be addressed to the American Welding Society, 550 Northwest Lejeune Road, P.O. Box 351040, Miami, Florida 33135.)
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA No. 70 - National Electrical Code
NFPA No. 780 - Lightning Protection Code (ANSI Approved)
(Application for NFPA-70 or 780 should be addressed to the National Fire Protection Association, Batterymarch Park, Quincy MA 02269.)
(Industry association specifications and standards are generally available for reference from libraries. They are also distributed among technical groups and using Federal agencies.)
2.3 Source of Documents. Copies of Federal and military standards, specifications, and associated documents listed in the Department of Defense Index of Specifications and Standards (DODISS), should be obtained from the Standardization Order Desk, Bldg. 4D, 700 Robbins Avenue, Philadelphia PA 19111-5094. To expedite a customer's ability to obtain a document, a computerized Telephone Order Entry System (TOES) has been implemented which provides the capability to place an order directly into the computer via a touch-tone telephone.
This system may also be used to receive immediate status or follow-up on a previously submitted order. In order to use TOES you must obtain your customer number from previously ordered material. If a customer number has not been assigned, one can be obtained by calling AC (215) 697-2179 or DSN 442-2179. TOES can then be accessed by dialing AC (215) 679- 1187 or DSN 442-1187. It is important to replace the letter “Q” with the number “7” and the letter “Z” with the number “9” since the telephone dial does not include these letters.
Copies of industry association documents should be obtained from the sponsor. Copies of all other listed documents should be obtained from the contracting activity or as directed by the contracting officer.
2.4 Order of Precedence. In the event of a conflict between the text of this standard and the references cited herein, the text of this standard shall take precedence.
SUPERSEDES PAGE 15 of MIL-STD-188-124B
5.1.1.2.4.2 Cable Trays or Raceways. The individual sections of all metallic cable tray systems shall be bonded to each other and to the raceways which they support. All electrically continuous bonds shall be in accordance with the procedures and requirements specified in 5.2 through 5.2.8. Direct bonding methods of 5.2.6 are preferred. All metallic cable tray assemblies shall be connected to ground within 0.6m (2 feet of each end of the run and at intervals not exceeding 15m (50 feet) along each run).
5.1.1.2.4.3 Wiring System Enclosures. All electrical and electronic wiring and distribution equipment enclosures, not otherwise specifically covered herein, shall be grounded. The grounding conductor shall not penetrate equipment cabinets or cases but rather shall be terminated on a ground stud peripherally welded to the metal barrier.
5.1.1.2.4.4 Metallic Power Cable Sheaths. Metallic cable sheaths on electrical power cables shall be connected to ground at both ends.
5.1.1.2.5 Electrical Power Systems. All electrical power distribution systems shall be grounded in accordance with the following:
5.1.1.2.5.1 AC Distribution Systems. AC power distribution systems shall have the neutral conductor grounded at the distribution transformer and to the earth electrode subsystem of the facility. The size of the ground conductor from the first service disconnect means to the earth electrode subsystem shall be as specified in Table 1-20 of MIL- HDBK-419 or Table 250-66 of the National Electrical Code. In each facility served by a common distribution transformer, the neutral shall be directly connected to the nearest point of the earth electrode subsystem. Where delta-wye system conversion is employed, the service entrance shall be a five-wire system consisting of three phase conductors, a grounded (neutral) conductor, and a grounding (green) conductor. In each facility, all power distribution neutrals shall be isolated from the C-E equipment case and the structure elements so that no ac return current flows through the equipment and fault protection subsystem or the signal reference network. The fault protection subsystem grounding (green) conductor shall be installed in accordance with the National Electrical Code for all C-E equipment. Conduit shall not be used in lieu of the separate grounding (green) wire.
5.1.1.2.5.1.1 Single Building with Multiple Power Sources. All grounded (neutral) conductors shall be grounded at the first service disconnect means of each source. For delta-wye conversions, a five- wire system shall be utilized from each source. Delta systems shall employ four-wires from the source, consisting of three phase conductors and a grounded conductor for grounding purposes.
5.1.1.2.5.1.2 Multiple Buildings with Single Power Source. Neutral conductors from multiple buildings being serviced from a single commercial power source shall be grounded at the source only. The neutral shall be isolated at the first disconnect means. A five-wire system shall be utilized from the source.
5.1.1.2.5.2 Standby AC Generators. Motor and generator frames and housings shall be grounded in accordance with Article 250 of the National Electrical Code. The generator neutral shall be grounded directly to the earth electrode subsystem.
When generators are connected in parallel, the neutrals shall be interconnected and grounded with a single ground conductor.
5.1.1.2.5.3 AC Outlets. Grounding of receptacles and associated grounding terminals shall meet the requirements of Articles 250-146 and 250-66 of the National Electrical Code (1999 or later). However, aluminum and copper clad aluminum conductors permitted by Article 410-56 shall not be used. When necessary to control noise problems, grounding of grounding terminals may be accomplished IAW Article 250-146 (d). Grounding of metallic outlet boxes shall not be dependent upon serrated strips or clips.
SUPERSEDES PAGE 16 of MIL-STD-188-124B
5.1.1.2.5.4 Electrical Motors and Generators. The frames of motors, generators, and other types of electrical rotating machinery shall be grounded to the fault protection subsystem, according to Article 430 of the National Electrical Code.
5.1.1.2.5.5 DC Power Sources. One leg of each dc power system shall be grounded with a single connection directly to the earth electrode subsystem. The size of the grounding conductor shall be as specified by Article 250 of the National Electrical Code. Whether grounded at the source or at a load, a separate current return from load to the source shall be used to assure that no dc current flows in the fault protection or the signal reference subsystem.
5.1.1.2.5.6 Metallic Battery Racks. Metallic battery racks shall also be grounded to the facility ground system at the nearest point.
5.1.1.2.5.7 Ground Fault Circuit Interrupters. All 120 volt single phase 15 and 20 ampere receptacle outlets located in bathrooms or on rooftops shall use ground fault circuit interrupters (GFCI) for personnel protection (See NEC Article 210 and 215).
5.1.1.2.6 Secure Facilities. All areas required to maintain communications security equipment and associated power systems shall be grounded in accordance with MIL-HDBK-419.
5.1.1.3 Lightning Protection Subsystem.
5.1.1.3.1 General. Lightning protection shall be provided as required for buildings and structures in accordance with the National Fire Protection Association (NFPA) No. 780, and the following:
5.1.1.3.2 Buildings and Structures. Lightning protection shall be provided as required for buildings and structures in accordance with the additions and modifications specified herein and the applicable paragraphs of NFPA No.
780. This protection shall be extended to all electrical, electronic, or other elements which are a part of, or are in support of all C-E facilities. Such elements shall include, but shall not be limited to, substations (to the extent that additional protection beyond that provided by the electric utility is necessary), power poles, towers, antennas, masts, etc.
SUPERSEDES PAGE 17 of MIL-STD-188-124B
5.1.1.3.3 Down Conductors. Where copper-clad steel down conductors are used on structures not greater than 23m (75 feet) in height, the dc resistance of solid wires or stranded cables shall not be greater than 0.176 ohms per 305m (1000 feet). On structures greater than 23m (75 feet) in height, the dc resistance of the wire or cable shall not be greater than 0.088 ohms per 305m (1000 feet). The size of wires in copper-clad stranded cable shall not be less than No. 14 AWG. (In cases where mechanical and installation situations warrant, a larger (preferably No. 6 AWG copper) wire may be utilized.) The copper covering of all copper-clad steel down conductors shall be permanently and effectively welded to the steel core. The conductivity of copper- clad conductors shall not be less than 30% of a solid copper conductor of equivalent cross-sectional area. Down conductors bends shall be gradual and not have a radius less than 20cm (8 in). The angle of any bend shall not be less than 90 degrees (see Figure 5). Any metal object within 1.8m (6 feet) of the lightning download shall be bonded to the down conductor (see NEC Article 250). Where practicable, a separation of at least 1.8m (6 feet) shall be maintained between open conductors of power and communications systems and lightning down conductors (see NEC Article 800). On structures higher than 18m (60 feet) there shall be at least one additional down conductor for each additional 18m (60 feet) of height fractions thereof, except that the interval between down conductors around the perimeters shall not be less than 15m (50 feet) nor greater than 30m (100 feet). Down conductors shall be continuous and shall be bonded in accordance with
5.1.1.1.5 and 5.2.3 to an earth electrode subsystem or to a ground rod bonded to this subsystem installed as near as practicable and within 1.8m (6 feet) from the structure.
Figure 5. Radius and Angle of Down Conductor Bends
5.1.1.3.4 Bonding. All bonds between elements of the lightning protection subsystems shall be made by welding or brazing or UL approved high compression clamping devices. Welding or brazing shall be used for all bonds not readily accessible for inspection and maintenance. Soft solder shall not be used for bonding any conductor in the lightning protection subsystem.
5.1.1.3.5 Structural Steel. Substantial metal structural elements of buildings and towers (including overall building shield where it exists) shall be acceptable substitutes, for lightning down conductors provided they are permanently bonded in accordance with 5.2 and bonded to the earth electrode subsystem. Bonding straps across all structural joints shall be IAW 5.2.3.3.1.
5.1.1.3.6 Air Terminals (Lightning Rods). Non-metallic objects, extensions, or protrusions requiring protection shall have the air terminals designed and installed in accordance with requirements of NFPA No. 780, chapters 3-7 and 3-8.
SUPERSEDES PAGE 18 OF MIL-STD-188-124B
5.1.1.3.7 Guards. Where conductive guards must be used, the guards shall be electrically bonded at each end of the enclosed lightning conductor. Each isolated section of conductive guards shall also be bonded to the lightning conductor.
5.1.1.3.8 Supporting Structures. Lightning protection shall be provided for radar, communications or navigational aid antenna towers, and similar supporting structures in accordance with the following:
5.1.1.3.8.1 Earth Electrode Subsystem. An earth electrode subsystem conforming to requirements 5.1.1 through 5.1.1.1.7 shall be provided for all supporting structures. If a tower is adjacent to another structure such that the minimum distance between the tower and the structure is 6m (20 feet) or less, one earth electrode subsystem encompassing both the tower and the other structure shall be provided.
For distances greater than 6m (20 feet), separate earth electrode subsystems shall be installed. These subsystems shall be interconnected for separations up to 200 feet. Two bare 1/0 AWG copper cables shall be used by independent routes to bond the earth electrode subsystem of the tower to the earth electrode subsystem of buildings and structures that have signal, control, or power line interfaces with the tower and are separated less than 60m (200 feet). (See Figures 1 and 2).
5.1.1.3.8.2 Air Terminals. An air terminal shall be installed on the tower as specified in 5.1.1.3.6. A minimum of two conductive paths shall exist between any two air terminals and between any air terminal and the earth electrode subsystem (except for dead ends less than 5m (16 feet)).
5.1.1.3.8.3 Antennas. Antennas installed on towers or platforms shall be within a 1:1 zone of protection of an air terminal. Large array type antennas such as rhombics, yagis, etc. shall be protected by 0.6m (2 feet) air terminals installed on the top of the mast or structure supporting the antenna. For additional information see MIL-
HDBK-419.
5.1.1.3.8.4 Down Conductors. As a minimum, down conductors shall meet the requirements of 5.1.1.3.3.
Each down conductor shall be continuous and shall be bonded to the earth electrode subsystem for the tower in accordance with 5.2. For metal towers, where the structural elements are not used as down conductors, the down conductors shall be bonded to the tower legs at the base. Down conductors connecting cables to the earth electrode subsystem shall be protected against mechanical damage. Connecting cables passing through foundations or footings shall be installed in plastic or non-metallic conduit.
5.1.1.3.8.5 Waveguide Grounding. As a minimum, all waveguides shall be grounded as follows:
a. All waveguides to the antennas shall be grounded at three points: near the antenna, at the vertical-to-horizontal transition near the base of the tower, and at the waveguide entry port.
b. Metallic supporting structures for waveguides shall be electrically continuous and shall be connected to the exterior earth electrode subsystem at the first and last support columns as a minimum. The wire leads shall be as direct as possible.
c. Waveguides shall be grounded with solid copper strap or copper wire at least equal to No. 6 AWG.
The size of wires in this cable shall not be less than No. 14 AWG. Braid or finer-stranded wire than No. 14 AWG shall not be used. All bends of ground conductors shall have a radius of 20 cm (8 in) or greater and the angle of any bend shall not be less than 90 degrees.
SUPERSEDES PAGE 31 OF MIL-STD-188-124B
CUSTODIANS: Preparing Activity:
ARMY: AC DISA: DC1
AIR FORCE: 02 (Project TCSS-0059)
NAVY: EC
DIA: DI
NSA: NS
USMC: MC
OTHER:
USSPACECOM:US
Reviewing Activities:
ARMY: CR, MI
NAVY: CG, NC, OM, TD,
AIR FORCE: 11, 13, 93
NIMA: MP
DOT: OST
OUSD(AT&L): SE
OASD: IR
STRICOM: PT
DCMA: CM
DISA: DC5
APPENDIX - Discussion of Signal Ground Systems
REPRINTED WITHOUT CHANGE
10 General. The following methods can be used to ground signal reference subsystems within a piece of electronic equipment, or within a facility containing several pieces of equipment: floating point, single point, and multiple-point (also known as multipoint or equipotential plane). However, due to personnel hazards, the floating point method is not generally utilized.
20 Single Point Ground System. In the single point ground system (for use at lower frequencies)1, all signal circuit grounds are referenced to a single point; this reference ground is then connected to the facility ground or a special ground connection provided for this purpose. In a cabinet, all electronic circuits (including the chassis) are bonded to a ground which is isolated from the cabinet and are then bonded to the one reference point. This isolates the cabinet and prevents any conducted, circulating currents in the facility ground from producing potential (noise) drops within the equipment. Conversely, no conducted circulating currents are introduced into the facility ground from the cabinets. Ground currents can produce voltage drops within the facility ground, and this can be a source of interference. However, the magnitude is generally small enough that it doesn't cause the signal-to-noise ratio to become intolerable.
While the cable or bus to the single point ground offers the most effective low impedance path for lower frequency signals, its impedance at higher frequencies prevents it from being an effective ground at frequencies above 300 Khz. In some instances, it may even be an ineffective ground at frequencies above 30 Khz. A single wire ground bus, even though terminated in zero impedance, assumes the characteristics of a single wire unbalanced transmission line. The impedance of such a line can be calculated by taking into account such parameters as length, height above ground (radiation effects) and finite earth conductivity. Since one end of the ground bus is not terminated, it can be accurately represented as an open-ended transmission line.
From this, it can be assumed the impedance of the grounding system is very high throughout the frequency spectrum, except in very narrow frequency ranges where the impedance changes signs. Consequently, a ground distribution system which performs adequately for dc or lower frequencies presents an entirely different characteristic at higher frequencies.
1Lower frequencies - includes all voltages and currents whether signal, control, or power from dc to 30 Khz and may extend up to 300 Khz depending on the electromagnetic and physical aspects of the equipment, subsystem, and/or facility involved. (Audio and tone signaling devices operate in the lower frequency ranges).
The paths of copper that connect the single reference point become longer as the systems become larger and begin to generate appreciable unavoidable ground loops which, in turn, increase the magnitude of the noise. The effectiveness of this type of system must then be weighed against other possible solutions.
SUPERSEDES DD FORM 1426 OF MIL-STD-188-124B
STANDARDIZATION DOCUMENT IMPROVEMENT PROPOSAL
INSTRUCTIONS
1. The preparing activity must complete blocks 1, 2, 3, and 8. In block 1, both the document number and revision letter should be given.
2. The submitter of this form must complete blocks 4, 5, 6, and 7, and send to preparing activity.
3. The preparing activity must provide a reply within 30 days from receipt of the form.
NOTE: This form may not be used to request copies of documents, nor to request waivers, or clarification of requirements on current contracts. Comments submitted on this form do not constitute or imply authorization to waive any portion of the referenced document(s) or to amend contractual requirements.
I RECOMMEND A CHANGE:
1. DOCUMENT NUMBER:
MIL-STD-188-124B
2. DOCUMENT DATE (YYMMDD)
920201
3. DOCUMENT TITLE: Grounding, Bonding, and Shielding
4. NATURE OF CHANGE (Identify paragraph number and include proposed rewrite, if possible. Attach extra sheets as needed.)
5. REASON FOR RECOMMENDATION
6. SUBMITTER
a. NAME (Last, First, Middle Initial) b. ORGANIZATION
c. ADDRESS (Include Zip Code) d. TELEPHONE (Include Area Code)
(1) Commercial
(2) AUTOVON
(If applicable)
7. DATE SUBMITTED
8. PREPARING ACTIVITY
a. NAME
DISA/JIEO/JEBB
b. TELEPHONE (Include Area Code)
(1) Commercial
(732) 427-6868
(2) DSN
987-6868
c. ADDRESS (Include Zip Code)
JIEO/CFS/JEBB
BLDG 283, Squier Hall Fort Monmouth, NJ 07703-5613
IF YOU DO NOT RECEIVE A REPLY WITHIN 45 DAYS, CONTACT:
Defense Standardization Program Office (DLSC-LM) 8725 John J. Kingman Rd, Suite 2533, Ft Belvoir, VA 22060-6221 Telephone (703) 767-6888 AUTOVON 427-6888
DD Form 1426, FEB 1999 (EG) PREVIOUS EDITIONS ARE OBSOLETE WHS/DIOR, Feb 99
NOTICE OF INCH-POUND
REINSTATEMENT
MIL-STD-188/124B
Notice 2 1-May-1998
MILITARY STANDARD
GROUNDING, BONDING AND SHIELDING FOR COMMON LONG
HAUL/TACTICAL COMMUNICATIONS SYSTEMS INCLUDING GROUND
BASED COMMUNICATIONS-ELECTRONICS FACLITIES AND EQUIPMENT
Mil-Std-188/124B, dated 1 Feb. 1992, is hereby reinstated and may be used for acquisition.
Custodians: Preparing Activity:
Army - CR DISA – DC1 Navy - EC Air Force – 02
Review Activities:
Army – AC Navy – CG, NC, OM, TD Air Force – 01, 02, 11, 13, 50, 80, 84, 93
AMSC N/A FSC TCSS
DISTRIBUTION STATEMENT A: Approved for public release; distribution is unlimited
NOTICE 1
30 January 1998
SUPERSEDING
MIL-STD-188-124B
1 February 1992
MILITARY STANDARD
GROUNDING, BONDING, AND SHIELDING
for Common Long Haul/Tactical Communication Systems Including Ground Based Communications-
Electronics Facilities and Equipments
MIL-STD-188-124B dated 1 February 1992, is hereby canceled without replacement. Guidance on the subject matter of this standard is available in MIL-HDBK-419A.
Custodians: Preparing Activity:
Air Force - 90 Air Force - 90 Army - SC (Project SLHC-1242)
Navy - EC
AREA TCSS/EMCS
NOTICE OF
CANCELLATION
o METRIC
MILITARY STANDARD
for Common Long Haul/Tactical Communication Systems
Including Ground Based Communications- Electronics Facilities and Equipments o
GROUNDING, BONDING AND SHIELDING
MlL-STD-l 88-124B 1 Feb 92
SUPERSEDING
MlL-STO-l 88-1 24A
2 FEBRUARY 1984
0 AMSC WA AREA SLHC/TCTS/EMCS
DISTRIBUTION STATEMENT A. Approved for public release; distribution is unlimited.
FOREWORD
1. This Military Standard is approved and mandatory for use by all Departments and Agencies of the Department of Defense in accordance with Department of Defense Instruction 5000.2, dated 23 February 1991.
2. Beneficial comments (recommendations, additions, deletions) and any pertinent data which may be of use in improving this document should be addressed to: TIC/TIS, Scott AFB IL 62225-6343, by using the self-addressed Standardization Document Improvement Proposal (DD Form 1426) appearing at the end of this document or by letter.
3. Standards for all military communications are published as part of a MIL-STD-188 series of documents:
Military Communications System Technical Standards are subdivided into Common Long Haul/Tactical Standards (MIL-STD-I88-1OO series), Tactical Standards (MIL-STD-188-200 series) and Long Haul Standards (MIL-STD-188-300 series).
4. This document contains technical standards and design objectives to ensure the optimum performance of ground-based telecommunications C-E equipment installations. This is accomplished by reducing noise and by providing adequate protection against power system faults and lightning strikes. Thorough consideration must be given to the grounding of equipment and facility installations, the bonding required, and the methods of shielding and implementation needed for personnel safety and equipment control.
5. This standard is also recommended for applicable use on any ground facility or equipment where grounding, .
bonding, shielding, personnel safety, lightning and EMC are required. Examples of such facilities are aircraft simulators, computer centers, laboratory buildings, weapons checkout and assembly, etc.
6. Paragraph 5.1, Grounding, for this standard is divided as follows: o I. Detailed requirements for facilities, including buildings and associated structures used principally for
C-E equipment.
11. Detailed requirements for C-E equipment which address grounding, bonding, and shielding for tacticaUlong haul fixed ground transportable and military communications electronics equipment installations and associated subsystems.
7. Detailed requirements for Bonding and Shielding are contained in !5.2 and 5.3.
8. This standard is further implemented by MIL-HDBK-419; Grounding, Bonding, and Shielding for Electronic Facilities and Equipments.
9. Notations are not psed in this revision to identify changes with respect to the previous issue due to the extensiveness of the changes.
ii o MIL-S’TD-188-124B
CONTENTS
I Parammh ! 1.
1.1 I 1.2
I 1.3 I 1.4
1.5 i I 2.
I * ;:l I 2:1:2
. 2.2 2.3
I 2.4
3.
4.
I
4.1 4.2 4.2.1
,0 4.2.2 4.2.3 4.3 4.4
5.
5.1 5.1.1 5.1.1.1 5.1.1.1.1 5.1.1.1.2 5.1.1.1.3.
5.1.1 .1.3.1
5.1.1 .1.3.2 5.1.1.1.4 5.1.1.1.5 5.1.1.1.6 5.1.1.1.7 5.1.1.2 5.1.1.2.1 5.1.1.2.2 5.1.1.2.3 5.1.1.2.4
SCOPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I
Purpose Conterlt Applications Objectives System Standards and Design Objectives
REFERENCEDDOCUMENTS
GovemmentDocuments Specifications, Standards, and Handbooks Other GovernmentDocuments, Drawings,and Publications Other Publications Source ofDocuments Order ofPrecedence
DEFINITIONS
GENERALREQUIREMENTS
General Grounding General T*tid Equipma@md Fmilitim Grounding inArcticRegions Bonding Shielding
DETAILEDREQUXREMENTS
Grounding 13uildingand Structure Earth Electrode Subsystem General Earth ResistivitySurvey Minimum Configuration Resistance to Earth Additional Considerations Ground Rods cOMdIlgRiSWS Other Underground Metals Resistance Checks FaultProtection Subsystem General BuildingStxuctural Steel PipeSand Tubes, Ek@-iealSuppotingStructures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1,4
0 ...
CONTENTS (Con’t)
Paragraph
5.1.1 .2.4.1
5.1.1 .2.4.2
5.1.1 .2.4.3
5.1.1 .2.4.4 5.1.1.2.5
5.1.1 .2.5.1
5.1.1 .2.5.1.1 ‘5.1.1 .2.5.1.2
5.1.1 .2.5.2
5.1.1 .2.5.3
5.1.1 .2.5.4
5.1.1 .2.5.5
5.1.1 .2.5.6
5.1.1 .2.5.7 5.1.1.2.6 5.1.1.3 5.1.1.3.1 5.1.1.3.2 5.1.1.3.3 5.1.1.3.4 5.1.1.3.5 5.1.1.3.6 5.1.1.3.7 5.1.1.3.8 5,1.1 .3.8.1
5.1.1 .3.8.2
5.1.1 .3.8.3
5.1.1 .3.8.4
5.1.1 .3.8.5
5.1.1 .3.8.6 5.1.1.3.9 5.1.1.3.10
5.1.1 +3.10.1
5.1.1 .3.10.2 5.1.1.3.11 5.1.1.3.12 5.1.1.3.13 5.1.1.4 5.1.1.4.1 5.1.1.4.2 5.1.1.4.3 5.1”2 5.1.2.1 5.1.2.1.1
5.1.2 .1.1.1
PaJT_e Conduit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..-...14 Cable Trays or Raceways Wiring System Enclosures . . . . . . . . . . . . .’
MetallicPower Cable Sheaths ElectricalPowerS ystems AC Distribution Systems SingleBuildingwithMuMplePower Sources . . . . . . ~ MultipleBuildingswith Single Power Source Standby ACGenerators AC Outlets Elech-icalMotorsandGenerators DC Power Sources MetallicBattery Racks GroundFault Circuit Interrupters Secure Facilities LightningProtection Subsystem General Buildingsand Structures Down Conductors Bonding Structural Steel Air Terminals (Lightning Rods) Guards Supporting Structures EarthElectrodeSubsystem Air Terminals Antennas Down Conductors Waveguide Grounding Coaxial Cable Grounding Exterior Nonstructural Metal Elements Exterior Wires and Cables Conduit Overhwd Guard Wires Underground Guard Wires LightningArrestors Security/PerimeterFences Signal Reference Subsystem General HigherFrequency Netxvork Lower Frequency Network Communications-Electronics(C-E) Equipment SignalReference Subsystem . . . . . . . . . . . . . . . . . . ...1 HigherFrequency Network Signal Isolation iv
Parawimh 5.1.2.1.1.2 5.1.2.1.1.3
5.1.2 .1.1.4 5.1.2.2 5.1.2.2.1 5.1.2.2.2 5.1.2.2.3 5.1.2.2.4 5.1.2.2.5 5.1.2.2.6 5.2 5.2.1 5.2.2 5.2.3 5.2.3.1 5.2.3.2 5.2.3.3 5.2.3.3.1 5.2.4 5.2.5 5.2.5.1 5.2.5.2 5.2.5.3 5.2.5.4 5.2.6 5.2.6.1 5.2.6.2 5.2.6.3 5.2.6.4 5.2.6.4.1 5.2.6.4.2 5.2.6.5 5.2.6.6 5.2.7 5.2.8 5.2.8.1 5.2.8.2 5.2.8.3 5.2.8.4 5.2.8.4.1 5.2.8.4.2 5.2.8.5 5.2.9 5.2.9.1 o I
I
MIL-STD-188-124B
CONTENTS (Con’t)
Equipment Signal Gmmd Tetinatiom ShieId Terminations of Coaxial and Other Higher Frequency Cables Overall Shields Fault Protection Subsystem General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..”. ”.. -””. .”. ~ Personnel Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..”. ”.”.23 ACPowerNeutnd individualPowerLimeFilters.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..”23 Convenience Outlets . . . . . . . . . . . - . . . . . . . . . ..+...... . ..-. ”...23 Portable Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . ...?
Bonding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...-.” ““G..*.U General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..”. .”.24 SurfacePlatingsorTreatm@s. . . . . . . . . . . . . . . . . . . . . . . . . - Bond Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0....”..”.24 Corrosion Protection . . . . . . . . . . . . . . . . . . . . . ...”... ...- CompressionBonds inProtwtiM= Vibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .........-.:
BondmgStraps . . . . . . . . . . . . . . . . . . . . . . . . . ..”...... .......”.
Bond Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..........M Materials . . . . . . . . . . . . . . . .~........,.........”
Swwt Solder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .........fi Brazing Solder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .........M Clmnps . . . . . . . . . . . . . . . . . . . . . . ................”
Nuts, Bolts andWashera . . . . . . . . . . . . . . . . . . . . . . . . . . . ......”...~ Direct Bonds . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..”...... ........= Welding Bmzingand SilverSoldetig . . . . . . . . . . . . . . . . . . . . . . . . . . . ...-...26 BondingofCopperto Steel tifiSoldtig . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..”.”.... .....= Sw-t Soldtig . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...-..*”.Z Sheet Metalor Ductwork . . . . . . . . . . . . . . . . . . . . . . . ...”.. ....””.26 Bolting. . . . . . . . . . . . . . . . . . . . . . . . . . . ...””.”....”.”.” . ..”.26 C-Clamps andSpringClmqx Indirect Bonds . . . . . . . . . . . . . . . . . . . . . . . . . . ...”...- . . -..-...27 surface Preparation . . . . . . . . ....-...............’ . . . . . ..”” ””27 Area to bechxl?le d . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..”.27 PaintRemoval lhorgauic FilmRemoval Finai Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..”
Clad Metals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..”- .”27 Alurninuml%llo y . . . . . . . . . . . ....................”
Completionofthe Bond DissimilarMetal s Corrosion Prevention v
‘1 d o r.
m o o m w w m m m cN tw N c.lelc-4 elN m
2.
o
“L
E l n MIL-STD-188-124B
1. SCOPE
1.1 Purwse. This standard establishes the minimum basic requirements and goals for grounding, bonding, and shielding of ground-basd telecommunications C-E equipment installations, subsystems, and facilities including buildings and structures supporting tactical and long haul military communication systems.
1.2 Content. This standard addresses the facilities ground systems, as well as grounding, bonding, and shielding and lightning protection for telecommunications C-E facilitim and equipments. Grounding for building and structures is listed under the headings of IMh Electrode Subsystem, Fmdt Protection Subsystem, Lightning Protection Subsystem and Signal Reference Subsystem.
. 1.3 Armlications. This standard shall be used in the design and engineering of new ground-based military communication systems, subsystems, and equipment installations as well as those C-E facilities undergoing major retrofit. This includes air traffic control and navigational aid facilities, radio, radar, satellite ground
. terminals, telephone centraloffices, microwave and data communications systems, as well as C-E transportable, aircmfi simulators, computer centers, and weapon assembly facilities. When upgrading existing facilities for installation of minor C-E equipments, the requirements of thk standard shall be established on a case-by-case basis by the cognimnt engineering agency. Use of this standard for other ground C-E facilities or equipment is also encouraged. It is not to be used solely m the basis for retrofit of existing C-E facilities. lt does not apply to general construction such m barracks, administration buildings, dining facilities, warehouses, andnonummumications facilities, nor does it apply to mobile units such as tanks, trucks, jeeps, etc.
1.4 Objectives. The objectives of this standard are to provide for the protection of personnel, equipments, buiidings and structures against the hamrds posed by electrical power faults and lightning strikes. It also o provides for the reduction of noise and electromagnetic interftmnce caused by inadequate grounding, bonding ad shieiding of ground W military communications installations to acceptable performance levels. It shall be required that the grounding, bonding, and shielding system be engineered to be compatible with the supplemental requirements of the specific equipment or facility supporting these communications.
1.5 Svstem Standards and Desi m Objectives The parameters and other requirements specified in this” document are mandatory system standards if the word “shall’ is used in comection with the parameter wdue or requirement under consideration. Non-mandatory design objectives are indicated by parentheses afk a standardize parameter value or by the word *shoulda in connection with the parameter value or requirement under consideration. For a definition of the terms “system standard” and “design objective” (DO), see
FED-STD-1037.
o
MIL-STD-188-12413
2. REFERENCED DOCUMENTS
2.1 Government Documents.
2.1.1 Smcifications, Standards, and Handbooks. Urdess otherwise specified, the following specifications, standards, and handbooks of the issue listed in that issue of the Department of Defense Index of Specifications and Standards (DODISS) specified in a solicitation form a part of this standard to the extent specified herein.
SPECIFICATIONS
FEDERAL
P-D-680
TT-P-1757 -
STANDARDS
FEDERAL
FED-STD-1037 -
FIPS PUB 94 -
MILITARY
AN-735
AN-742
MIL-E-6051D -
MIL-STD-285 -
MIL-STD-454 -
MIL-STD-461 -
MIL-STD-462 -
MIL-STD-463 -
MIL-STD-1857 -
Dry Cleaning and Decreasing Solvent
Primer Coating, Zinc Chromate, Low Moisture Sensitivity
Glossary of Telecommunication Terms
Guideline on Electrical Power for ADP Installations
Clamp, Loop Type Bonding
Clamp, Loop, Plain, Support, Aircraft
Electromagnetic Compatibility System Requirements
Attenuation Measurement for Enclosures, Electromagnetic Shielding, for Electronic Test Purposes, Method of
Standard General Requirements for Electronic Equipment
Electromagnetic Emission and Susceptibility Requirements for the Control of Electromagnetic Interference
Electromagnetic Interference Characteristics, Measurement of
Definitions and Systems of Units, Electromagnetic Interference and Electromagnetic Compatibility Technology
Grounding, Bonding and Shielding Design Practices
O
0,,,!
o.,!
MIL-C-83413 -
MDA’I’D-188-125 -
HANDBOOKS
MILITARY
MIL-HDBK-232 -
MrL-HDBK-419 -
MUA3DBK-1 195 -
FM-1 14874/ -
TO 31-1024
MIL-STD-188-124B
Connectorsand Assemblies, Electrical Aircraft Grounding: Type IV Jumper Cable Assembly, Lead, Electrical
High Altitude Electromagnetic Pulse (HEMP) Protection for Ground-Based C41 Facilities
Red/Black Engineering Installation Guidelines
Grounding, Bonding, and Shielding for Electronic Equipments and Facilities
Radio Frequency Shielded Enclosures
Installation Practices: Communications Systems Grounding, Bonding, and Wielding
2.1.2 Other Government Documents. Drawirws. and Publications. The fotlowing other Government documents, - drawings, and publications form a part of this standard to the extent specified herein.
DOD Directive 1000.3 - Safety and Occupational Health Policy for the Depmtment of Defense
DOD Directive 3222.3 - Department of Defense Electromagnetic Compatibility Program
(Copies of specifications, standards, handbooks, drawings, and publications required by contractors in comection with specific acquisition functions should be obtained from the contracting activity or as directed by the contracting officer.)
2.2 Other Publications. The following document(s) form a part of this standard to the extentspecifiedherein.
The issues of the documents which are indicated as DOD adopted shall be the issue listed in the cument DODEW and the supplement thereto, if applicable.
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (A.ISC)
ABC!S326 Specifica~ion for the Design, Fabrication and Erection of Structural Steel for Buildings
(Application for copies of the AISC specification should be addressed to the American Institute of Steel Cmstmction, 400 North Michigan Avenue, Chicago IL 6061 1.)
AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM)
ASTM B 32 Standard Specification for Solder Metal (DOD Adopted)
(Application for the ASTM document should be addressed to the American Society for Testing and Materials, 1916 Race Street, Philadelphia, PA 19103.)
IWL-STD-188-124B
AMERICAN WELDING SOCIETY (AWS)
AWS A 5.8 Specification for Brazing Filler Metall (DOD Adopted, ANSI APProved)
(Application for the AWS specification should be addressed to the American Welding Society, 550 Northwest Lejeune Road, P.O. Box 351040, Miami, Florida 33135.)
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA No. 70 - National Electrical Code
NFPA No.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .