This file is an appendix containing as-built drawings for a clean room renovation project. The related federal contract opportunity is solicitation number W912DS23B0008 from the Department of the Army Corps of Engineers Engineering District New York for renovations to Building 125 at an undisclosed West Virginia location. The solicitation seeks contractors to perform renovations and upgrades to convert the existing space into a clean room according to the specifications and drawings provided in Appendix B. The response deadline and award date are not stated.
View the file
Other files for this federal contract opportunity
Show all 24
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DAHSP
DPS-1
CLEANROOM RECIRCULATING AIR HANDLING UNITS
CONTROL DRAWING
(TYPICAL FOR RAH-1 – RAH-10)
ZN-T
TE-2
TCHWR
TCHWS
SF
VSD
C
C
N O
CC-O
VLV-1
RA
LOCAL
GUAGE
DA
7051-0036
Drawing Title
GBBGDR
Johnson Controls, Inc.
4 Pine West Plaza
Suite 405
Albany, NY 12205
(518) 869-9595
GB 7/27/2007
REFERENCE DRAWING
RAH- Flow Schematic
Typical for RAH-1 – RAH-10
Systems & Services Division
ATC-6
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Vistec
Building 125 -Watervliet Arsenal
Watervliet, NY
SFx-C
R-1
SFx-O
SFx-S
CT-1
SFxVSD-FB
(Software)
Note: Duct Smoke Tied into Life Safety
System
ZN-SP
DPT-1
H L
Corrridor
@ 0.4"wc
BILL OF MATERIALS
Designation Qty Part Number Description
Field Devices:
CB-1 10 10250T53 NO CONTACT BLOCKS, CUTLER HAMMER
CT-1 10 H904 CURRENT SWITCH
CT-2 10 H930 CURRENT SWITCH,CMD RELAY
DA-1 10 M9210-BAC-3 DAMPER ACTUATOR 10 NM SR W/ 2 AUX SW
DPT-1 10 DPT2640-001B-A XMTR,DIFF PR,AIR,-1 TO 1"WC,0-5VDC,0.25%
DPS-1 10 AFS-460 SWTICH,DIFF PR,CLEVELAND
10 FTG18A-600R STATIC PROBE
EN-1 10 PADA00011BC1 PANEL DX W/TB 24X36 ENC FACE
R-1- R-4 40 RH2B-UAC24-L RELAY 24VAC SPDT, IDEC
40 SH2B-05 RELAY BASE
TE-1 10 TE-6315P-1 SENSOR,T-PT-EQV,8FT AVG,1K
20 TE-6001-8 CLIP F/AVG ELEMENT,10-PACK
TE-2 10 TE-6314P-1 SENSOR,T-NI,1K, 0.1%
VLV-1 4 VALVE SEE VALVE SCHEDULESFx-FLT
(Software)
SFHOA-S
(Software)
RA-SD
(By Others)
LO HI
DA-T
TE-1
RAH-P
PxHOA-S
CB-1
RAHPx-C\
RAHPx-S
CT-2
Cleanroom
Bay
CLEANROOM RECIRCULATION AIR HANDLING UNITS (RAH-1 THROUGH RAH-10)
The Cleanroom recirculation air system provides conditioned air to the Cleanroom for temperature and particle control.
Each recirculation air unit consists of the following functional components:
1. Return air intake
2. Prefilter bank
3. Sensible chilled water cooling coil (40% Propylene Glycol) with dedicated coil pump
4. Direct drive centrifugal plug fan(s) with unit mounted variable-frequency-drive(s) (VFD)
Sequence of operations:
The process exhaust fans system is enabled through a master enable point in the facility management system. When the fan is called to come on the discharge air damper shall open via the VFD and the fan shall start when the damper is open as proven by the damper end switch. When enabled the coil pump shall start and with the hand-off-auto switch in the auto position the VFD shall be energized and the fan shall start and run continuously. The VFD shall be manually set to achieve the required airflow velocity in the cleanroom. The velocity required shall be established by the air balancing contractor.
The desired fan speed output to derive the required air shall be programmed into and controlled from the facility management system. The speed setting shall be adjustable.
Temperature control shall be obtained via modulating the coil leaving water control valve to achieve the unit leaving air temperature. The control valve shall open to 30% (adj) prior to the pump starting. The pump shall continue to run until the valve is less than
5 %The unit leaving air temperature shall be compared continuously to the cleanroom temperature and shall be re-set automatically as required to maintain the cleanroom temperature set-point of 70 F (adjustable). The reset schedule shall be as follows:
Cleanroom Temp Discharge Air Temp
68 (adj) 85 (adj)
72 (adj) 65 (adj)
When the system is disabled the supply fan is off, the coil pump is off, and all coil hydronic control valves are closed.
Safety/Shutdowns:
Upon detection of smoke as sensed by the duct smoke detector, the supply fans will shutdown via a fire alarm shutdown relay at the VFD, the coil pump shall stop and the control valves shall close. Additionally, an alarm shall be generated through the facility management system.
NOTE: Wiring Terminations For Drives Need To Be Field Verified By Drive
Rep Before Running Drives. Field Verified Actual Wiring Terminations.
RAH SUPPLY FAN VSD WIRING DETAIL
AHU(N) VSD
See Current Switch
Wiring Detail
BICOMBI1
SF-S
Drive Status From
Current Switch
R-1
L1 L2 VAC From Motor Starter
Transformer
RAHP-x
RAH PUMP-x STARTER
(Typical)
O
AH
H-930 N.O. Status
Output Status Set
24 VAC/VDC
Coil
Relay Contact
RAHPx-S RAHPx-C
RAHP-x
EN-x
RAH Control Panel
(One Panel for two RAH’s)
Locate panel between RAH’s
DX-9100
in
24 in.
in
22 1/ 2 in.
S u b -P a n e l
E n c lo s u re O u tl in e
TX-1
RC-1
TB-1
CIRCUIT BREAKER
N
G
H
1-1/2 " WIRE DUCT ( LOW VOLTAGE)
-1 /2 W
IR
E D U C T (L O W V O L T A G E
-1 /2 W
IR
E D U C T (L O W V O L T A G E
1-1/2 " WIRE DUCT ( LOW VOLTAGE)
Note: Fault to be mapped via communication protocol
Note: Feedback to be mapped via communication protocol
Fire Alarm
Shutdown
(By others)
Supply Air
High Static
DPS-1
VSD Safety
Circuit
1TB
SFVSD-O
0-10VDC
VSD
Speed Feedback Hand
Mode
Selected
Auto
Mode
Selected
VSD
Speed Control
VSD
Enable
VSD
Fault
R-1-1
R-1 Located in VFD
Note: Modes to be mapped via communication protocol
10 16X1 2 3 10 13
ABB 550CH-PD-031A-4
N2
Communication
Trunk
N O
DA-DPR
DA-1
ES-1
DAMPER
FBO
Wire directly to VSD. See detail below.
x x x
N2
Communication Bus
ABB 550CH-PD-031A-4
X x
24VAC
24VAC
Com Damper Actuator
COM
CW
CCW
Add contact blocks to the HOA switch for
Hand Status Indication
Discharge
Dmpr End Switch
ES-1
Add contact blocks to the HOA switch for Hand
Status Indication
7051-0036
Drawing Title
GBBGDR
Johnson Controls, Inc.
4 Pine West Plaza
Suite 405
Albany, NY 12205
(518) 869-9595
GB 7/27/2007
REFERENCE DRAWING
RAH Panel Wiring Details &
Points Lists
Typical for RAH’s
Systems & Services Division
ATC-6A
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Vistec
Building 125 -Watervliet Arsenal
Watervliet, NY
2/14
VIO
SF-C \ DO-3
SUPPLY FAN COMMAND
4-7-DO-3
2/14
VIO
RAHP-C \ DO-4
HOT WATER PUMP COMMAND
4-7-DO-4
MOTOR
LEAD
ORG
SF-S \ DI-1
SUPPLY FAN STATUS
4-7-DI-1
2/14
ORG4-7-DI-2
2/22
ORG
DAHSP-A \ DI-3
SUPPLY PRESSURE ALARM
4-7-DI-3
2/14
ORG
RAHP-S \ DI-4
HOT WATER PUMP STATUS
4-7-DI-4
2/22
YEL
DA-T \ AI-1
DISCHARGE AIR TEMP
4-7-AI-1
2/22
YEL
ZN-T \ AI-2
ZONE TEMP
4-7-AI-2
3/22
YEL
ZN-SP \ AI-3
ZONE STATIC PRESSURE
4-7-AI-3
2/22
YEL
SFVSD-FB \ AI-4
SUPPLY FAN SPEED FEEDBACK
4-7-AI-4
2/22
TAN
SFVSD-O \ AO-1
SUPPLY FAN OUTPUT
4-7-AO-1
3/18
TAN
CC-O \ AO-2
COOLING COIL 1 OUTPUT
4-7-AO-2
3/18
BLUTO NEXT N2 DEVICE N2
3/18
BLUFROM LAST N2 DEVICE N2
VAC
Power
DX-10-X
SERVICING RAH-A & B
ADDRESS: X
EN-X
2/14
VIO4-7-DO-5
2/14
VIO4-7-DO-6
MOTOR
LEAD
ORG
4-7-DI-5
2/14
ORG4-7-DI-6
2/22
ORG4-7-DI-7
2/14
ORG4-7-DI-8
2/22
YEL4-7-AI-5
2/22
YEL4-7-AI-6
3/22
YEL4-7-AI-7
2/22
TAN4-7-AO-9
3/18
TAN4-7-AO-10
SF-C \ DO-5
SUPPLY FAN COMMAND
RAHP-C \ DO-6
HOT WATER PUMP COMMAND
SF-S \ DI-5
SUPPLY FAN STATUS
DAHSP-A \ DI-7
SUPPLY PRESSURE ALARM
RAHP-S \ DI-8
HOT WATER PUMP STATUS
SFVSD-O \ AO-9
SUPPLY FAN OUTPUT
CC-O \ AO-10
COOLING COIL 1 OUTPUT
DA-T \ AI-5
DISCHARGE AIR TEMP
ZN-T \ AI-6
ZONE TEMP
ZN-SP \ AI-7
ZONE STATIC PRESSURE
1 4 : 2 8
RAH-(A) Points
RAH-1
RAH-3
RAH-5
RAH-7
RAH-9
RAH-(B) Points
RAH-2
RAH-4
RAH-6
RAH-8
RAH-10
Enclosure/Address Schedule
Enclosure Systems DX Add XT Add
EN-4 RAH-1/RAH-2 9 10
EN-5 RAH-3/RAH-4 11 12
EN-6 RAH-5/RAH-6 13 14
EN-7 RAH-7/RAH-8 15 16
EN-8 RAH-9/RAH-10 17 18
RECIRC AIR HANDLING UNITS Wiring Details
RAH-(A) & RAH-(B) Points List
RAHPHOAS \ DI-2
PUMP HOA STATUS
RAHPHOAS \ DI-6
PUMP HOA STATUS
| A_Architectural |
| A-001 |
| A-201 |
| A-202 |
| A-601 |
| D_Process |
| D-001 |
| D-002 |
| D-201A |
| D-202A |
| D-601 |
| D-602 |
| D-603 |
| D-604 |
| D-605 |
| D-606 |
| D-607 |
| D-608 |
| D-609 |
| D-901 |
| E_Electrical |
| E-001 |
| E-200 |
| E-301A |
| E-301B |
| E-301D |
| E-302A |
| E-401A |
| E-401B |
| E-401D |
| E-402A |
| E-403A |
| E-403B |
| E-403D |
| E-501A |
| E-701A |
| E-701B |
| E-801 |
| E-802 |
| E-901 |
| E-902 |
| E-903 |
| H_Fire Alarm |
| H-301A |
| H-301B |
| H-301C |
| H-301D |
| H-301E |
| H-303A |
| H-304A |
| H-801 |
| H-901 |
| H-902 |
| J_Instrumentation & Controls |
| J-001 |
| J-201 |
| J-301A |
| J-301B |
| J-303A |
| J-304A |
| M_Mechanical |
| M-001 |
| M-002 |
| M-201A |
| M-201B |
| M-201D |
| M-202A |
| M-203A |
| M-204A |
| M-204D |
| M-301A |
| M-301B |
| M-301D |
| M-303A |
| M-304A |
| M-304D |
| M-401 |
| M-501 |
| M-601 |
| M-602 |
| M-603 |
| M-604 |
| M-605 |
| M-606 |
| M-607 |
| M-608 |
| M-609 |
| M-610 |
| M-611 |
| M-801 |
| M-802 |
| M-803 |
| M-901 |
| M-902 |
| M-903 |
| M-904 |
| P_Plumbing |
| P-001 |
| P-201A |
| P-201D |
| P-203A |
| P-601 |
| P-602 |
| P-801 |
| P-901 |
| S_Structural |
| S-000 |
| S-001 |
| S-002 |
| S-200A |
| S-200B |
| S-200C |
| S-200D |
| S-200E |
| S-201A |
| S-201B |
| S-202A |
| S-202B |
| S-202C |
| S-202D |
| S-202E |
| S-203A |
| S-203B |
| S-203D |
| S-301 |
| FP_Fire Protection |
| As-Built - Detail |
| As-Built Dwg |
ATC_Building Automation System