Appendix A - B125 Lead Paint and Asbestos Survey.pdf

PDF 6 MB Posted

Attached to
WVA Renovate Building 125 Federal contract opportunity
Solicitation number
W912DS23B0008
Issued by
Department of the Army Corps of Engineers Engineering District New York

About this file

This document is an asbestos survey report for Building 125 at Watervliet Arsenal. The report details an asbestos survey conducted by Arcadis of New York, Inc. to identify asbestos-containing materials that may be impacted by planned demolition activities. Arcadis inspected and collected samples from 50 homogeneous areas, and laboratory analysis found all samples to contain no detectable asbestos. The report provides the material description, location, quantity, condition and asbestos content for each homogeneous area. It concludes with recommendations to consider other unidentified materials as asbestos-containing until proven otherwise by inspection and analysis.

The related federal contract opportunity is a solicitation from the Department of the Army Corps of Engineers Engineering District New York to renovate Building 125 at Watervliet Arsenal. No further details are provided on required products or services, response dates, or other salient information.

View the file

Other files for this federal contract opportunity

Show all 24

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Arcadis U.S., Inc.

855 NY-146

Clifton Park, NY 12065

Tel 315.617.9165

M: 315.436.8113 www.arcadis.com

Mr. Rafal Turek

Project Manager/AF Team Leader

New York District Army Corps of Engineers

Engineering Management Section

Subject:

Supplemental Path of Construction Asbestos Survey Report

Watervliet Arsenal

Building 125

Watervliet, New York 12189

Dear Mr. Turek:

Arcadis of New York, Inc. (Arcadis) conducted a supplemental path of construction

(POC) asbestos survey of previously identified homogenous areas (HAs) at the above referenced site. The focus of the supplemental POC asbestos survey was to assess suspect asbestos-containing materials (ACM) that were not inspected or sampled during Arcadis’ 2019 survey and may be impacted during planned demolition activities. Our survey scope of work included surveying Building 125.

Arcadis’ scope of work and the findings of the asbestos POC survey are summarized below.

ASBESTOS SURVEY

On January 31, 2022, Mr. Brandon Wabble with Arcadis visited the site to conduct the supplemental asbestos POC survey. Mr. Wabble is a State of New York

Department of Labor accredited asbestos inspector. A copy of his asbestos qualification is provided in Attachment A.

Based on our understanding of the scope of work, a review of previous survey data, and our observations of the areas to be impacted by the project, the following HAs were inspected as part of this supplemental POC survey:

HA-9: Brown Grout Associated with 12” Ceramic Floor Tile

HA-10: Gray Adhesive Associated with 12” Ceramic Floor Tile

HA-11: Brown Grout Associated with 12” Ceramic Wall Cove Base

HA-12: Gray Adhesive Associated with 12” Ceramic Wall Cove Base

HA-44: Electrical Components/Wire Wrap (non-suspect, not sampled)

HA-45: Red Flange Gasket Insulation

ENVIRONMENT

Date:

April 15, 2022

Contact:

Doug Preston

Phone:

954 560 0693

Email:

Douglas.Preston@arcadis.com

Our ref:

30060446 arcadis.com

Mr. Rafal Turek

April 15, 2022

HA-46: Gray Grout Associated with 1” Ceramic Floor Tile

HA-47: Orange/Gray Adhesive Associated with 1” Ceramic Floor Tile

HA-48: 12” Brown Floor Tile

HA-49: Gray/Beige Mastic Associated with HA-48

HA-50: Blue Flange Gasket Insulation

HA-6: Electrical Components (non-suspect, not sampled)

During the survey, Arcadis assessed the HAs identified above and collected samples of suspect ACMs. Each HA observed during the survey was observed to be in good condition and non-friable. Arcadis collected twenty (20) bulk samples and submitted them for laboratory analysis. Laboratory analytical reports are provided in Attachment B. Details regarding the material location, condition, friability, analytical result, and estimated quantity of each HA assessed during the survey is presented in the updated Homogenous Application Attachment C.

FINDINGS

Based on the results of the survey, the bulk samples collected by Arcadis were reported by the laboratory as “None Detected” for asbestos.

The remaining HAs assessed during this survey, such as electrical components and wire wrap where bulk samples were not collected were determined to be “Non-

Suspect” for ACM.

RECOMMENDATIONS

Arcadis inspected a representative number of suspect materials of each HA identified in this survey. If other suspect materials that are not referenced in this report are identified during demolition activities, Arcadis recommends that these materials be considered ACM until they are inspected by an appropriately licensed asbestos inspector and proven otherwise.

CLOSING

The asbestos survey consisted solely of the activities described herein.

Thank you for your time and consideration on this project. Please do not hesitate to call if you have questions regarding the results of this asbestos survey or if you require additional information.

Mr. Rafal Turek

April 15, 2022

Sincerely, Arcadis U.S., Inc.

Brandon Wabble

State of New York Department of Labor Licensed Asbestos Inspector

Doug Preston

Senior Project Manager

Attachments:

A Inspector Qualifications

B Laboratory Analytical Reports and Chain of Custody Form

C Updated Homogenous Application Table

ATTACHMENT A

Inspector Qualifications

ATTACHMENT B

Laboratory Analytical Reports and Chain of Custody Form

EMSL Analytical, Inc.

200 Route 130 North Cinnaminson, NJ 08077

Tel/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com

042202185EMSL Order:

Customer ID: ACAD78H

Customer PO: 30060446

Project ID:

Attention: Phone:Brandon Wabble (860) 645-1084

Fax:ARCADIS U.S., Inc. (860) 645-1090

Received Date:213 Court Street, 7th Floor 02/02/2022 10:15 AM

Analysis Date:Middletown, CT 06457 02/04/2022 - 02/07/2022

Collected Date: 01/31/2022

Project: 30060446 / US Army Watervliet Arsenal / 1 Buffington St, Watervliet, NY 12189

Test Report:Asbestos Analysis of Bulk Material

Test Color

Analyzed

Date Fibrous Non-Fibrous Asbestos

Non-Asbestos

Sample ID 9A Description Men's Restroom Break Area North - Brown Grout associated w/12" Ceramic Floor Tile

042202185-0001 Homogeneity Homogeneous

PLM NYS 198.1 Friable Brown None Detected02/04/2022 100.00% Non-fibrous (other)

PLM NYS 198.6 VCM Not Analyzed

PLM NYS 198.6 NOB Not Analyzed

TEM NYS 198.4 NOB Not Analyzed

Sample ID 9B Description Men's Restroom Break Area North - Brown Grout associated w/12" Ceramic Floor Tile

042202185-0002 Homogeneity Homogeneous

PLM NYS 198.1 Friable Brown None Detected02/04/2022 100.00% Non-fibrous (other)

PLM NYS 198.6 VCM Not Analyzed

PLM NYS 198.6 NOB Not Analyzed

TEM NYS 198.4 NOB Not Analyzed

Sample ID 10A Description Men's Restroom Break Area North - Gray Adhesive associated w/12" Ceramic Floor Tile

042202185-0003 Homogeneity Homogeneous

PLM NYS 198.1 Friable Gray None Detected02/07/2022 100.00% Non-fibrous (other)

PLM NYS 198.6 VCM Not Analyzed

PLM NYS 198.6 NOB Not Analyzed

TEM NYS 198.4 NOB Not Analyzed

Sample ID 10B Description Men's Restroom Break Area North - Gray Adhesive associated w/12" Ceramic Floor Tile

042202185-0004 Homogeneity Homogeneous

PLM NYS 198.1 Friable Gray None Detected02/07/2022 100.00% Non-fibrous (other)

PLM NYS 198.6 VCM Not Analyzed

PLM NYS 198.6 NOB Not Analyzed

TEM NYS 198.4 NOB Not Analyzed

Sample ID 11A Description Men's Restroom Break Area North - Brown Grout associated w/12" Ceramic Cove Base

042202185-0005 Homogeneity Homogeneous

PLM NYS 198.1 Friable Brown None Detected02/04/2022 100.00% Non-fibrous (other)

PLM NYS 198.6 VCM Not Analyzed

PLM NYS 198.6 NOB Not Analyzed

TEM NYS 198.4 NOB Not Analyzed

Report amended: 02/07/2022 23:52:43 Replaces initial report from: 02/05/2022 11:36:55 Reason Code: NY or NJ protocol-Other (see report comment)

Page 1 of 5ASB_198x_0009 - 1.71 Printed 2/7/2022 11:54:19PM

Tel/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com

042202185EMSL Order:

Customer ID: ACAD78H

Customer PO: 30060446

Project ID:

Test Report:Asbestos Analysis of Bulk Material

Test Color

Analyzed

Date Fibrous Non-Fibrous Asbestos

Non-Asbestos

Sample ID 11B Description Men's Restroom Break Area North - Brown Grout associated w/12" Ceramic Cove Base

042202185-0006 Homogeneity Homogeneous

PLM NYS 198.1 Friable Brown None Detected02/04/2022 100.00% Non-fibrous (other)

PLM NYS 198.6 VCM Not Analyzed

PLM NYS 198.6 NOB Not Analyzed

TEM NYS 198.4 NOB Not Analyzed

Sample ID 12A Description Men's Restroom Break Area North - Gray Adhesive associated w/12" Ceramic Cove Base

042202185-0007 Homogeneity Homogeneous

PLM NYS 198.1 Friable Gray None Detected02/07/2022 100.00% Non-fibrous (other)

PLM NYS 198.6 VCM Not Analyzed

PLM NYS 198.6 NOB Not Analyzed

TEM NYS 198.4 NOB Not Analyzed

Sample ID 12B Description Men's Restroom Break Area North - Gray Adhesive associated w/12" Ceramic Cove Base

042202185-0008 Homogeneity Homogeneous

PLM NYS 198.1 Friable Gray None Detected02/07/2022 100.00% Non-fibrous (other)

PLM NYS 198.6 VCM Not Analyzed

PLM NYS 198.6 NOB Not Analyzed

TEM NYS 198.4 NOB Not Analyzed

Sample ID 45A Description - Red Flange Gasket Insulation

042202185-0009 Homogeneity Homogeneous

PLM NYS 198.1 Friable Red None Detected02/04/2022 100.00% Non-fibrous (other)

PLM NYS 198.6 VCM Not Analyzed

PLM NYS 198.6 NOB Not Analyzed

TEM NYS 198.4 NOB Not Analyzed

Sample ID 45B Description - Red Flange Gasket Insulation

042202185-0010 Homogeneity Homogeneous

PLM NYS 198.1 Friable Red None Detected02/04/2022 100.00% Non-fibrous (other)

PLM NYS 198.6 VCM Not Analyzed

PLM NYS 198.6 NOB Not Analyzed

TEM NYS 198.4 NOB Not Analyzed

Sample ID 46A Description Area Between Men's/Women's Restrooms - Gray Grout associated w/ 1" Ceramic Floor Tile

042202185-0011 Homogeneity Homogeneous

PLM NYS 198.1 Friable Gray None Detected02/04/2022 100.00% Non-fibrous (other)

PLM NYS 198.6 VCM Not Analyzed

PLM NYS 198.6 NOB Not Analyzed

TEM NYS 198.4 NOB Not Analyzed

Report amended: 02/07/2022 23:52:43 Replaces initial report from: 02/05/2022 11:36:55 Reason Code: NY or NJ protocol-Other (see report comment)

Page 2 of 5ASB_198x_0009 - 1.71 Printed 2/7/2022 11:54:19PM

Tel/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com

042202185EMSL Order:

Customer ID: ACAD78H

Customer PO: 30060446

Project ID:

Test Report:Asbestos Analysis of Bulk Material

Test Color

Analyzed

Date Fibrous Non-Fibrous Asbestos

Non-Asbestos

Sample ID 46B Description Area Between Men's/Women's Restrooms - Gray Grout associated w/ 1" Ceramic Floor Tile

042202185-0012 Homogeneity Homogeneous

PLM NYS 198.1 Friable Gray None Detected02/04/2022 100.00% Non-fibrous (other)

PLM NYS 198.6 VCM Not Analyzed

PLM NYS 198.6 NOB Not Analyzed

TEM NYS 198.4 NOB Not Analyzed

Sample ID 47A Description Area Between Men's/Women's Restrooms - Orange/Gray Adhesive associated w/1" Ceraic

Floor Tile 042202185-0013 Homogeneity Homogeneous

PLM NYS 198.1 Friable Not Analyzed

PLM NYS 198.6 VCM Not Analyzed

PLM NYS 198.6 NOB Orange Inconclusive: None Detected02/04/2022 100.00% Other

TEM NYS 198.4 NOB Orange None Detected02/05/2022 100.00% Other

Sample ID 47B Description Area Between Men's/Women's Restrooms - Orange/Gray Adhesive associated w/1" Ceraic

Floor Tile 042202185-0014 Homogeneity Homogeneous

PLM NYS 198.1 Friable Not Analyzed

PLM NYS 198.6 VCM Not Analyzed

PLM NYS 198.6 NOB Orange Inconclusive: None Detected02/04/2022 100.00% Other

TEM NYS 198.4 NOB Orange None Detected02/05/2022 100.00% Other

Sample ID 48A Description Janitors Closet Break Area - North - 12" Brown Floor Tile

042202185-0015 Homogeneity Homogeneous

PLM NYS 198.1 Friable Not Analyzed

PLM NYS 198.6 VCM Not Analyzed

PLM NYS 198.6 NOB Brown Inconclusive: None Detected02/04/2022 100.00% Other

TEM NYS 198.4 NOB Brown None Detected02/05/2022 100.00% Other

Sample ID 48B Description Janitors Closet Break Area - North - 12" Brown Floor Tile

042202185-0016 Homogeneity Homogeneous

PLM NYS 198.1 Friable Not Analyzed

PLM NYS 198.6 VCM Not Analyzed

PLM NYS 198.6 NOB Brown Inconclusive: None Detected02/04/2022 100.00% Other

TEM NYS 198.4 NOB Brown None Detected02/05/2022 100.00% Other

Sample ID 49A Description Janitors Closet Break Area - North - Gray/Beige Mastic associated w/Ha-48

042202185-0017 Homogeneity Homogeneous

PLM NYS 198.1 Friable Not Analyzed

PLM NYS 198.6 VCM Not Analyzed

PLM NYS 198.6 NOB Gray/ Beige Inconclusive: None Detected02/04/2022 100.00% Other

TEM NYS 198.4 NOB Gray/ Beige None Detected02/05/2022 100.00% Other

Report amended: 02/07/2022 23:52:43 Replaces initial report from: 02/05/2022 11:36:55 Reason Code: NY or NJ protocol-Other (see report comment)

Page 3 of 5ASB_198x_0009 - 1.71 Printed 2/7/2022 11:54:19PM

Tel/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com

042202185EMSL Order:

Customer ID: ACAD78H

Customer PO: 30060446

Project ID:

Test Report:Asbestos Analysis of Bulk Material

Test Color

Analyzed

Date Fibrous Non-Fibrous Asbestos

Non-Asbestos

Sample ID 49B Description Janitors Closet Break Area - North - Gray/Beige Mastic associated w/Ha-48

042202185-0018 Homogeneity Homogeneous

PLM NYS 198.1 Friable Not Analyzed

PLM NYS 198.6 VCM Not Analyzed

PLM NYS 198.6 NOB Gray/ Beige Inconclusive: None Detected02/04/2022 100.00% Other

TEM NYS 198.4 NOB Gray/ Beige None Detected02/05/2022 100.00% Other

Sample ID 50A Description Mechanical Room - Blue Flange Gasket Insulation

042202185-0019 Homogeneity Homogeneous

PLM NYS 198.1 Friable Blue None Detected02/04/2022 10.00%

15.00%

20.00%

Cellulose

Glass

Synthetic

55.00% Non-fibrous (other)

PLM NYS 198.6 VCM Not Analyzed

PLM NYS 198.6 NOB Not Analyzed

TEM NYS 198.4 NOB Not Analyzed

Sample ID 50B Description Mechanical Room - Blue Flange Gasket Insulation

042202185-0020 Homogeneity Homogeneous

PLM NYS 198.1 Friable Blue None Detected02/04/2022 30.00%

15.00%

Cellulose

Synthetic

55.00% Non-fibrous (other)

PLM NYS 198.6 VCM Not Analyzed

PLM NYS 198.6 NOB Not Analyzed

TEM NYS 198.4 NOB Not Analyzed

Report amended: 02/07/2022 23:52:43 Replaces initial report from: 02/05/2022 11:36:55 Reason Code: NY or NJ protocol-Other (see report comment)

Page 4 of 5ASB_198x_0009 - 1.71 Printed 2/7/2022 11:54:19PM

Tel/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com

042202185EMSL Order:

Customer ID: ACAD78H

Customer PO: 30060446

Project ID:

Test Report:Asbestos Analysis of Bulk Material

Analyst(s):

Andrew Borsos PLM NYS 198.1 Friable (5) John Witcraft PLM NYS 198.1 Friable (4)

Keishla Vazquez Caraballo PLM NYS 198.1 Friable (5) Andrew Borsos PLM NYS 198.6 NOB (3)

Keishla Vazquez Caraballo PLM NYS 198.6 NOB (3) Ted Young TEM NYS 198.4 NOB (6)

Samples reviewed and approved by:

Samantha Rundstrom, Laboratory Manager or Other Approved Signatory

EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received. Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. Estimation of uncertainty available upon request.

This report is a summary of multiple methods of analysis, fully compliant reports are available upon request. All samples examined for the presence of vermiculite when analyzed via NYS 198.1. A combination of PLM and TEM analysis may be necessary to ensure consistently reliable detection of asbestos. Polarized-light microscopy is not consistently reliable in detecting asbestos in floor coverings and similar non-friable organically bound materials. This report must not be used to claim product endorsement by

NVLAP of any agency or the U.S. Government . Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos containing. NOB= Non friable organically bound; N/A= Not applicable VCM= Vermiculite containing material.

Samples analyzed by EMSL Analytical, Inc. Cinnaminson, NJ NYS ELAP 10872, PA ID# 68-00367, NVLAP Lab Code 101048-0

Report amended: 02/07/2022 23:52:43 Replaces initial report from: 02/05/2022 11:36:55 Reason Code: NY or NJ protocol-Other (see report comment)

Page 5 of 5ASB_198x_0009 - 1.71 Printed 2/7/2022 11:54:19PM

OrderID: 042202185

ATTACHMENT C

Updated Homogenous Application Table

Table 1

Homogeneous Areas Summary

Watervliet Arsenal

Building 125

1 Buffington Street

Watervliet, New York 12189

HA No. Material Description Material Location Sample

Number Condition Friability

Asbestos

Content

Estimated

Quantity Unit Notes

1 Brick Mortar

Outer Walls (North, South, East, West), Throughout- Lower Half

Below Window and Column

Lines, Between Window Dividers, Exterior- Throughout

1-1, 1-2, 1-3 Good Non-Friable NAD 48,000 SF

Beige Mastic Associated with 8"

Cove Base

North Entrance Hallway, Break

Area (North), Long Hallway

Outside Production Room

2-1, 2-2 Good Non-Friable NAD 825 LF

3 2'x4' Pinhole Ceiling Tile

North Entrance Hallway, Break

Area (North), Restrooms Near

Break Area, Computer Room 113

3-1, 3-2 Good Friable NAD 5,745 SF

Ceiling tile appears in 2'x2' grid shape on the ground, actually 2'x4' pinhole ceiling tile.

4 Gypsum Wall Board Throughout 4-1, 4-2, 4-3 Good Friable NAD 55,000 SF

Joint Compound Associated with

HA-4

Throughout 5-1, 5-2, 5-3 Good Friable NAD 55,000 SF

6 White Wrap on Fiberglass Pipe Throughout 6-1, 6-2, 6-3 Good Friable NAD 4,150 LF

7 Silicone Window Caulking Outer Windows- Throughout 7-1, 7-2 Good Non-Friable NAD 19,865 LF

8 Mirror Mastic Restrooms- Break Area (North) Good Non-Friable 100 SF Destructive sampling required.

Gray Grout Associated with 12"

Ceramic Floor Tile Restrooms- Break Area (North) 9A, 9B Good Non-Friable NAD 1,260 SF

Supplemental POC survey on 1/31/22 revealed material to be none detected.

Adhesive Associated with 12"

Ceramic Floor Tile Restrooms- Break Area (North) 10A, 10B Good Non-Friable NAD 1,260 SF

Supplemental POC survey on 1/31/22 revealed material to be none detected.

Building 125

B0086268.1803 Arcadis U.S., Inc.

Watervliet Arsenal

Building 125

1 Buffington Street

Watervliet, New York 12189

HA No. Material Description Material Location Sample

Number Condition Friability

Asbestos

Content

Estimated

Quantity Unit Notes

Grout Associated with 12"

Ceramic Cove Base (Wall) Restrooms- Break Area (North) 11A, 11B Good Non-Friable NAD 245 SF

Supplemental POC survey on 1/31/22 revealed material to be none detected.

Glue Associated with 12" Ceramic

Cove Base (Wall) Restrooms- Break Area (North) 12A, 12B Good Non-Friable NAD 245 SF

Supplemental POC survey on 1/31/22 revealed material to be none detected.

Gray Mastic Associated with 2'x2'

Rubber Flooring

North Entrance Hallway, Break

Area/Hallway (North), Kitchen-

110, Break Room- 112

13-1, 13-2 Good Non-Friable NAD 7,415 SF

14 Gray Floor Leveling Compound

Open Space Area/Offices, North

Entrance Hallway, Break

Area/Hallway (North)

14-1, 14-2 Good Non-Friable NAD 1,440 SF

Green/Red Textured Paint on

Brick Wall North Entrance Hallway 15-1, 15-2 Good Non-Friable <1% Chrysotile 48,000 SF

16 End Cap Sealant Throughout 16-1, 16-2, 16-

Good Non-Friable NAD 640 LF Associated with fiberglass piping.

Green/Gray Carpet Mastic

Associated with 2'x2' Carpet

Squares

Reception 101, Open Space- 118, Offices 102, 103, 104, 105, 106, 107, 108, 109, 110, 111, 111A, Archive 114

17-1, 17-2 Good Non-Friable NAD 450 SF

Associated with 2'x2' carpet squares

(colors blue/green, blue, green- all same mastic).

Beige Mastic Associated with 4"

Cove Base

Reception 101, Open Space- 118, Offices 102, 103, 104, 105, 106, 107, 108, 109, 110, 111, 111A, Archive 114

18-1, 18-2 Good Non-Friable NAD 465 LF

19 2'x4' Plain Ceiling Tile Office Outside Production (100-

106) 19-1, 19-2 Good Friable NAD 1,875 SF

20 Gray Sink Undercoating Break Room-112, Kitchen-110 20-1, 20-2 Good Non-Friable NAD 10 SF

21 12" Light Green Floor Tile Engineering Test Lab- 115 21-1, 21-2 Good Non-Friable NAD 240 SF

Beige Mastic Associated with HA-

Engineering Test Lab- 115 22-1, 22-2 Good Non-Friable NAD 240 SF

Watervliet Arsenal

Building 125

1 Buffington Street

Watervliet, New York 12189

HA No. Material Description Material Location Sample

Number Condition Friability

Asbestos

Content

Estimated

Quantity Unit Notes

Beige Mastic Associated with

Stanchions/Raised Flooring

Ball Room 200, Test Labs- 211E, 212A, 212B, 213B, Build EC1-6, RA Chase, Demo 1-2, Clean

Storage 214, Wipe Down 215, Gowning/Interface, 116-120, 23-1, 23-2 Good Non-Friable NAD 265 SF Associated with stanchions below raised flooring.

Beige/White Mastic Associated with 4" Cove Base

Production Room/Offices, Open

Area/Offices, Long Hallway East of North Entrance

24-1, 24-2 Good Non-Friable NAD 855 LF

25 Gray Caulk on Concrete Floor Production Room SE 25-1, 25-2 Good Non-Friable NAD 150 SF

Beige/Gray Mastic Associated with 2'x2' Carpet Squares Open Area/Offices 26-1, 26-2 Good Non-Friable NAD 16,075 SF

27 2'x2' Plain Ceiling Tile Open Area/Offices 27-1, 27-2 Good Friable NAD 16,075 SF

28 12" Off-White Floor Tile Hallway to TFS Area 28-1, 28-2 Good Non-Friable NAD 1,960 SF

Gray Mastic Associated with HA-

Hallway to TFS Area 29-1, 29-2 Good Non-Friable NAD 1,960 SF

30 Plaster Wall Skim Coat East Add on Space 30-1, 30-2, 30-

Damaged Friable NAD 4,320 SF

31 Plaster Wall Base Coat East Add on Space 31-1, 31-2, 31-

Damaged Friable NAD 4,320 SF

32 CMU Mortar East Add on Space 32-1, 32-2 Damaged Non-Friable NAD 800 SF

Beige Glue Associated with

Ceramic Wall Tile East Add on Space 33-1, 33-2 Damaged Non-Friable NAD 150 SF

34 White Textured Paint on Brick

Outer Walls (Long Entrance

Hallway), South Walls (Below

Windows Throughout)

34-1, 34-2 Good Non-Friable NAD 150 SF

Watervliet Arsenal

Building 125

1 Buffington Street

Watervliet, New York 12189

HA No. Material Description Material Location Sample

Number Condition Friability

Asbestos

Content

Estimated

Quantity Unit Notes

35 Exterior Brick Mortar Exterior- Throughout 35-1, 35-2 Good Non-Friable NAD 100,000 SF

36 Exterior Foundation Caulk Exterior- North Entrance 36-1, 36-2 Good Non-Friable NAD 75 LF

37 Exterior Silicone Window Caulk Exterior- Windows Throughout 37-1, 37-2 Good Non-Friable NAD 19,865 LF

38 Expansion Joint Caulk Exterior- North, South 38-1, 38-2 Good Non-Friable 3.3%

Chrysotile

65 LF

39 Exterior EIFS Overhang Exterior- North Entrance

Overhang 39-1, 39-2 Good Non-Friable NAD 70 SF

White/Gray Caulk Associated with Steel Plates Above

Windows

Exterior- Throughout (At Top of

New Windows) 40-1, 40-2 Good Non-Friable

9.5%

Chrysotile

2,885 LF

Caulk Associated with Stone

Window Sills

Exterior- Bottom of Window Sills

Throughout 41-1, 41-2 Good Non-Friable NAD 4,000 LF

42 Exterior HVAC Duct Caulk Exterior- Roof Above Break Room

(North) 42-1, 42-2 Good Non-Friable NAD 700 LF

Materia also located on HVAC ducts on interior. Inaccessible on interior due to height restrictions, same material.

EPDM Rubber Roofing

Membrane Roof- Throughout 43-1, 43-2 Good Non-Friable NAD 125,000 SF

44 Electrical Components/Wire Wrap Throughout Good Non-Friable Assumed ACM 36 EA

Supplemental POC survey on 1/31/22 revealed electrical components to be none detected.

45 Flange Gasket Insulation Throughout 45A, 45B Good Non-Friable Assumed ACM 150 EA Supplemental POC survey on 1/31/22 revealed material to be none detected.

Watervliet Arsenal

Building 125

1 Buffington Street

Watervliet, New York 12189

HA No. Material Description Material Location Sample

Number Condition Friability

Asbestos

Content

Estimated

Quantity Unit Notes

Gray Grout Associated with 1"

Ceramic Floor Tile

Janitor's Closet, Area Between

Men's/Women's Restrooms 46A, 46B Good Non-Friable NAD 200 SF

Supplemental POC survey on 1/31/22 revealed material to be none detected.

Orange/Gray Adhesive

Associated with 1" Ceramic Floor

Tile

Janitor's Closet, Area Between

Men's/Women's Restrooms 47A, 47B Good Non-Friable NAD 200 SF

Supplemental POC survey on 1/31/22 revealed material to be none detected.

48 12" Brown Floor Tile Janitor's Closet, North Break

Room 48A, 48B Good Non-Friable NAD 400 SF

Supplemental POC survey on 1/31/22 revealed material to be none detected.

Gray/Beige Mastic Associated with HA-49

Janitor's Closet, Area Between

Men's/Women's Restrooms, North Break Room

49A, 49B Good Non-Friable NAD 400 SF Supplemental POC survey on 1/31/22 revealed material to be none detected.

50 Blue Flange Gasket Insulation Janitor's Closet, North Break

Room 50A, 50B Good Non-Friable NAD 50 LF

Supplemental POC survey on 1/31/22 revealed material to be none detected.

EA = Each

LF = Linear Foot

NAD = No Asbestos Detected

SF = Square Foot

Assumed ACM = Material determined by the inspector to be suspect ACM is considered asbestos-containing until laboratory analysis can prove otherwise.

ASBESTOS AND LEAD PAINT

SURVEY UPDATE – BUILDING 125

Watervliet Arsenal Watervliet, New York

Contract: W912DR-18-D-0009

WO: W912DR-19-F-0482

January 2020

ASBESTOS AND LEAD PAINT SURVEY UPDATE – BUILDING 125

ASBESTOS AND LEAD

PAINT SURVEY

UPDATE – BUILDING

Watervliet Arsenal

Watervliet, New York

Prepared for:

United States Army Corps of Engineers

Baltimore District

2 Hopkins Plaza

Room 09-F-05

Baltimore, MD

Prepared by:

Seres-Arcadis 8(a) JV, LLC

855 Route 146

Suite 210

Clifton Park, New York 12065

Tel 518.250.7300

Our Ref.:

30001988

Date:

16 January 2020

This document is intended only for the use of the individual or entity for which it was prepared and may contain information that is privileged, confidential and exempt from disclosure under applicable law. Any dissemination, distribution or copying of this document is strictly prohibited.

Report Prepared By:

Brandon Wabble

Project Task Manager

Report Reviewed By:

Gregory Donovan Certified Project Manager i

CONTENTS

Acronyms and Abbreviations ........................................................................................................................ iii

1 Introduction

2 Survey Methodology

2.1 Asbestos Survey Approach

2.2 Lead Paint Survey Approach

3 Analytical Methods

3.1 Asbestos

3.2 Lead

4 Findings

4.1 Asbestos

4.2 Lead

5 Recommendations

5.1 Asbestos

5.2 Lead

6 Additional Survey Limitations

TABLES

Table 1 Homogeneous Areas Summary

Table 2 Lead Based Paint Summary ii

FIGURES

Figure 1 Interior Sample Locations

Figure 2 Exterior Sample Locations

APPENDICES

Appendix A Limitations and Service Constraints

Appendix B Accreditations

Appendix C Laboratory Reports – Asbestos

Appendix D Laboratory Reports – Lead iii

ACRONYMS AND ABBREVIATIONS

ACMs Asbestos-containing materials

AHERA Asbestos Hazard Emergency Response Act

AIHA American Industrial Hygiene Association

CFR Code of Federal Regulations

HAs Homogeneous Areas

NESHAPs National Emissions Standards for Hazardous Air Pollutants

NVLAP National Voluntary Laboratory Accreditation Program

NYS New York State

OSHA Occupational Safety and Health Administration

PEL Permissible exposure limit

RACM Regulated asbestos-containing materials

TEM/DS Transmission Electron Microscopy with Dispersion Staining

USACE US Army Corps of Engineers

USEPA United States Environmental Protection Agency

WVA Watervliet Arsenal

1 INTRODUCTION

The Seres-Arcadis 8(a) JV, LLC (the JV) was retained by the Baltimore District of the US Army Corps of

Engineers (USACE) to update the 2017 asbestos survey for Building 125 at the Watervliet Arsenal (WVA) in Watervliet, New York (site). The work was conducted as described in the scope of work in the USACE

Baltimore District contract No. W912DR-18-D-0009, Delivery Order No. W912DR-19-F-0482.

The objective of the survey was to ascertain the general presence, quantity, and location of asbestos-containing materials (ACMs) and materials coated with lead paint at the site. The results of the survey will assist in the preparation of an abatement scope of work and subsequent abatement of identified ACMs and lead paint that may be required prior to any renovation or demolition activities. Arcadis’ survey and report are subject to the Limitations and Service Constraints provided in Appendix A.

The survey was conducted from September 23, 2019 through September 25, 2019 by Mr. Brandon

Wabble of Arcadis, accompanied by Mr. Andrew Kopchynski of Seres. A Copy of Mr. Wabble’s accreditation is provided in Appendix B. The JV staff were accompanied by personnel from the WVA

Environmental Management Office.

2 SURVEY METHODOLOGY

2.1 Asbestos Survey Approach

The JV conducted the asbestos survey of the site for compliance with the National Emissions Standards for Hazardous Air Pollutants (NESHAPs).

This was accomplished by initially conducting a visual inspection of the structure and collecting samples of suspect ACM based on these observations. The JV conducted the asbestos survey in general accordance with ASTM International (ASTM) E2356 Standard Practice for Comprehensive Building

Asbestos Surveys. ASTM E2356 meets the applicable requirements of current United States

Environmental Protection Agency (USEPA) NESHAP Standard 40 Code of Federal Regulations (CFR)

61, Subpart M (Asbestos), USEPA Asbestos Hazard Emergency Response Act (AHERA) 40 CFR 763, Subpart E, and Occupational Safety and Health Administration (OSHA) asbestos survey and/or sampling regulations.

The survey included an inspection of Building 125 providing a general sense of the overall location, type, quantity, and condition of potential ACMs present. It was thorough in that most accessible functional spaces were inspected, and bulk samples collected of suspect materials observed. The presence of asbestos in suspect materials was assumed or presumed in some cases without bulk samples being collected or analyzed. This was necessary for locations where materials were inaccessible or areas that were unsafe to access. For those areas that were not safely accessible, suspect materials observed or presumed to be present were documented and assumed as ACMs.

The survey included destructive, intrusive, and/or exploratory testing. Arcadis endeavored to observe normally inaccessible areas, such as, but not limited to, pipe chases, wall cavities, inside mechanical systems, and under primary flooring surfaces for suspect ACMs. In addition, our survey included accessing, surveying, or sampling accessible roofing systems and exterior building materials of the structure.

The asbestos survey included a visual and physical assessment of each accessible space to locate suspect ACMs. Suspect materials were divided into "Homogeneous Areas" (HAs) (i.e., building materials that were determined by the inspector to be homogeneous based on their color, texture, and assumed date of installation). The number of samples collected was conducted in general accordance with ASTM

E2356. A representative number of samples were collected from each HA.

Bulk material samples were collected in 4-mil plastic bags, and tightly sealed for transport to EMSL

Analytical, Inc. in Carle Place, New York. Each sample collected by the JV was assigned its own unique coded number. Samples were sent to EMSL for laboratory analysis under a chain-of-custody protocol.

2.2 Lead Paint Survey Approach

The JV conducted a lead paint survey of representative interior and exterior surfaces for the purpose and compliance of USEPA Resource Conservation and Recovery Act (RCRA) (Standard 40 CFR 240-280) and OSHA Lead in Construction (Standard 29 CFR 1926.62).

Suspect lead paint was identified based upon a visual inspection of painted interior and exterior building components. Samples of suspect lead paint were collected and assigned their own unique identification number, placed in 4-mil sealable plastic bags, and tightly sealed for subsequent shipment under a chain of custody protocol to EMSL Analytical, Inc. in Cinnaminson, New Jersey.

3 ANALYTICAL METHODS

3.1 Asbestos

Bulk samples were analyzed for asbestos (reported in percent of type of asbestos) using Transmission

Electron Microscopy with Dispersion Staining (TEM/DS) and Polarized Light Microscopy with Dispersion

Staining (PLM/DS) in accordance with the USEPA and New York State (NYS). Percentage estimates of each material's composition are based on the analyst's best visual judgment following TEM/DS/PLM analysis, and examination with a stereoscope.

EMSL is a member of the American Industrial Hygiene Association (AIHA), National Voluntary Laboratory

Accreditation Program (NVLAP). EMSL’s laboratory analytical reports results are provided as Appendix C.

3.2 Lead Paint

Paint chip samples were analyzed for total lead content (reported in total percent by weight) by flame atomic adsorption spectrometry (AAS) in accordance with USEPA Method 7420, SW 846-3050B/7000B.

Strict quality control/quality assurance (QA/QC) provisions were adhered to for analysis of all lead samples. EMSL conformed to its own in-house QA/QC procedures established by their accreditation manual. EMSL’s laboratory analysis results for lead are provided in Appendix D.

4 FINDINGS

4.1 Asbestos

The JV identified forty-five (45) HAs, of which, eighty-three (83) suspect ACM bulk samples were collected and submitted for laboratory analysis. A listing of the identified HAs, including each HA material description, location, condition, asbestos content, and estimated quantity, are presented in the Table 1.

Approximate sampling locations are shown on Figures 1 and 2. Representative photographs were excluded from this survey work.

Nine (9) HA’s have been confirmed or assumed to contain asbestos at concentrations above 1% (ACM is defined as a material containing more than 1% of asbestos by weight).

The following HAs have been confirmed or assumed to be ACMs:

Building 125

• HA-8: Mirror Mastic (Assumed ACM)

• HA-9: Gray Grout Associated with 12” Ceramic Floor Tile (Assumed ACM)

• HA-10: Adhesive Associated with 12” Ceramic Floor Tile (Assumed ACM)

• HA-11: Grout Associated with 12” Ceramic Cove Base on Wall (Assumed ACM)

• HA-12: Glue Associated with 12” Ceramic Wall Cove Base (Assumed ACM)

• HA-38: Exterior Expansion Joint Caulk

• HA-40: White/Gray Caulk Associated with Steel Plates Above Windows

• HA-44: Electrical Components/Wire Wrap (Assumed ACM)

• HA-45: Flange Gasket Insulation (Assumed ACM)

The remaining bulk samples collected by the JV as part of the survey were reported by the laboratory as

“None Detected” for asbestos.

4.2 Lead Paint

Five (5) paint chip samples were collected and analyzed for lead content by flame AAS. Lead in paint was detected in three (3) samples analyzed at concentrations ranging from 1.9% by weight to 2.0% by weight.

Details regarding material description, location, substrate, and reporting limit of each paint chip sampled are presented in Table 2.

The following paint chip samples were confirmed to contain detectable levels of lead:

• LP-2: White Paint on Brick

• LP-3: Green Paint on Brick

• LP-4: Red Paint on Brick

5 RECOMMENDATIONS

5.1 Asbestos

As presented in Table 1 and the laboratory data provided in Appendix C, results of the asbestos survey identified confirmed and assumed ACM’s at the site.

In accordance with current USEPA NESHAP regulations, certain types of ACM must be removed prior to being disturbed by demolition or renovation activities. Current USEPA NESHAP regulations require that all regulated ACMs (RACM) be removed prior to being disturbed. RACMs are defined as:

• Friable ACM

• Category I non-friable ACM that has become friable

• Category I non-friable ACM that has been or will be subjected to sanding, abrading, grinding, or cutting.

• Category II non-friable ACM that has a high probability of becoming friable or crumbled, pulverized, or otherwise reduced to powder by the demolition or renovation activities

ACMs identified at the site that may be disturbed during renovation activities, must be removed by a licensed asbestos abatement contractor utilizing industry standard work procedures in accordance with all federal, state, and local regulations governing asbestos.

Suspect ACMs that could not be sampled during the survey have been assumed to contain asbestos at concentrations above 1%. These materials must be managed as ACM until laboratory analysis can prove otherwise.

If other suspect materials, not referenced in this survey report, are identified during renovation activities, Arcadis recommends that these materials be considered ACM until they are inspected by an appropriately licensed asbestos inspector and proven otherwise.

Asbestos waste must be disposed at an asbestos waste receiving facility that is duly permitted by the state and/or local municipality in which it resides.

The OSHA Construction Standard for Asbestos (29 CFR 1926.1101) procedures and guidelines must be followed for personnel conducting activities that may disturb materials that contain asbestos during abatement, construction, demolition, renovation, and other similar activities, whether they are considered

ACM because they contain greater than 1% asbestos or if they contain 1% or less asbestos. Materials that are confirmed to contain trace amounts of asbestos (less than one percent) by point counting are not currently subject to the USEPA regulations. These materials, however, may still be subject to federal

OSHA regulations when their disturbance may elevate, or potentially elevate, the concentration of airborne fibers above the eight-hour time weighted average permissible exposure limit (PEL) of 0.1 fibers per cubic centimeter of air (f/cc) or the 30-minute short term excursion limit of 1.0 f/cc. It should be noted, despite these limits established by OSHA, that no "safe" level of asbestos exposure has been determined.

OSHA considers disturbance of building materials containing equal to or less than 1% asbestos as

“unclassified asbestos operations”. Unclassified asbestos operations cover employees likely to be exposed in excess of the PELs and who are performing asbestos operations that are not covered by

Class I through IV asbestos operations (e.g., renovation/restoration activities). Employees must have appropriate training meeting OSHA Standard 29 CFR 1926.1101 (k)(9)(viii). In addition, the employer still must follow the requirements in 29 CFR 1926.1101 paragraphs (g)(1) [except (g)(1)(i)], (g)(2) and (g)(3) that describe engineering and work practice controls operation.

The JV recommends that engineering controls and work practices be utilized and that personal exposure assessment (air monitoring) be conducted on contractor’s performing work in areas where materials have been identified to contain equal to or less than 1% asbestos in accordance with OSHA Standard 29 CFR

1926.1101 (f) Exposure Assessments and Monitoring. Arcadis also recommends that contractors wear applicable personal protective equipment as defined in 29 CFR 1926.1101, while performing work activities in these areas, and utilize appropriate engineering and work practice controls to minimize the potential fiber release.

5.2 Lead Paint

As presented in Table 2, and the laboratory data provided in Appendix D, detectable levels of lead in paint were identified at the site.

The JV recommends that the general contractor and any sub-trades be advised of the presence of lead-based paint/lead-containing paint and their requirements for compliance with the OSHA Lead in

Construction standard (Title 29 CFR, Part 1962.62). Compliance with OSHA is required for any detectable levels of lead in painted surfaces.

Any work that could disturb known or suspect lead-based paint should be conducted in a way to minimize and control dust, and that the contractor performs a thorough cleanup.

If other suspect lead-based paints/lead-containing paints, not referenced in this survey report, are identified during renovation activities, the JV recommends that these materials be managed as lead-containing until they are inspected and proven otherwise.

Waste characterization sampling and analysis is recommended for the representative waste stream generated by renovation activities. Waste stream analyses should include toxicity characteristic leaching procedure analysis, as required.

6 ADDITIONAL SURVEY LIMITATIONS

The JV’s survey is subject to the following limitations in addition to those presented in Appendix A:

• Photographs were excluded from survey work.

• Utilities/services, including electric, water, and heat, were active in most areas surveyed. Materials associated with electrical components and energized equipment were not safely accessible and were not sampled.

• The investigation did not include access or inspection of confined spaces, crawl spaces, underground piping, conduits, building footings, and extent of subsurface soil asbestos contamination, if any.

• The TFS area was occupied with no admittance and was therefore excluded from this survey work.

TABLES

Watervliet Arsenal

Building 125

1 Buffington Street

Watervliet, New York 12189

HA No. Material Description Material Location Sample

Number Condition Friability

Asbestos

Content

Estimated

Quantity Unit Notes

1 Brick Mortar

Outer Walls (North, South, East, West), Throughout- Lower Half

Below Window and Column Lines, Between Window Dividers, Exterior- Throughout

1-1, 1-2, 1-3 Good Non-Friable NAD 48,000 SF

Beige Mastic Associated with 8"

Cove Base

North Entrance Hallway, Break

Area (North), Long Hallway

Outside Production Room

2-1, 2-2 Good Non-Friable NAD 825 LF

3 2'x4' Pinhole Ceiling Tile

North Entrance Hallway, Break

Area (North), Restrooms Near

Break Area, Computer Room 113

3-1, 3-2 Good Friable NAD 5,745 SF

Ceiling tile appears in 2'x2' grid shape on the ground, actually 2'x4' pinhole ceiling tile.

4 Gypsum Wall Board Throughout 4-1, 4-2, 4-3 Good Friable NAD 55,000 SF

Joint Compound Associated with

HA-4

Throughout 5-1, 5-2, 5-3 Good Friable NAD 55,000 SF

6 White Wrap on Fiberglass Pipe Throughout 6-1, 6-2, 6-3 Good Friable NAD 4,150 LF

7 Silicone Window Caulking Outer Windows- Throughout 7-1, 7-2 Good Non-Friable NAD 19,865 LF

8 Mirror Mastic Restrooms- Break Area (North) Good Non-Friable 100 SF

New restroom, confirm with Doug

Baker to just assume ACM until further testing may be required.

Gray Grout Associated with 12"

Ceramic Floor Tile Restrooms- Break Area (North) Good Non-Friable NAD 1,260 SF

New restroom, confirm with Doug

Baker to just assume ACM until further testing may be required.

Adhesive Associated with 12"

Ceramic Floor Tile Restrooms- Break Area (North) Good Non-Friable NAD 1,260 SF

New restroom, confirm with Doug

Baker to just assume ACM until further testing may be required.

Building 125

B0086268.1803 Page 1 of 5

Watervliet Arsenal

Building 125

1 Buffington Street

Watervliet, New York 12189

HA No. Material Description Material Location Sample

Number Condition Friability

Asbestos

Content

Estimated

Quantity Unit Notes

Grout Associated with 12"

Ceramic Cove Base (Wall) Restrooms- Break Area (North) Good Non-Friable NAD 245 SF

New restroom, confirm with Doug

Baker to just assume ACM until further testing may be required.

Glue Associated with 12"

Ceramic Cove Base (Wall) Restrooms- Break Area (North) Good Non-Friable NAD 245 SF

New restroom, confirm with Doug

Baker to just assume ACM until further testing may be required.

Gray Mastic Associated with 2'x2'

Rubber Flooring

North Entrance Hallway, Break

Area/Hallway (North), Kitchen-

110, Break Room- 112

13-1, 13-2 Good Non-Friable NAD 7,415 SF

14 Gray Floor Leveling Compound

Open Space Area/Offices, North

Entrance Hallway, Break

Area/Hallway (North)

14-1, 14-2 Good Non-Friable NAD 1,440 SF

Green/Red Textured Paint on

Brick Wall North Entrance Hallway 15-1, 15-2 Good Non-Friable <1% Chrysotile 48,000 SF

16 End Cap Sealant Throughout 16-1, 16-2, 16-

Good Non-Friable NAD 640 LF Associated with fiberglass piping.

Green/Gray Carpet Mastic

Associated with 2'x2' Carpet

Squares

Reception 101, Open Space- 118, Offices 102, 103, 104, 105, 106, 107, 108, 109, 110, 111, 111A, Archive 114

17-1, 17-2 Good Non-Friable NAD 450 SF

Associated with 2'x2' carpet squares

(colors blue/green, blue, green- all same mastic).

Beige Mastic Associated with 4"

Cove Base

Reception 101, Open Space- 118, Offices 102, 103, 104, 105, 106, 107, 108, 109, 110, 111, 111A, Archive 114

18-1, 18-2 Good Non-Friable NAD 465 LF

19 2'x4' Plain Ceiling Tile Office Outside Production (100-

106) 19-1, 19-2 Good Friable NAD 1,875 SF

20 Gray Sink Undercoating Break Room-112, Kitchen-110 20-1, 20-2 Good Non-Friable NAD 10 SF

21 12" Light Green Floor Tile Engineering Test Lab- 115 21-1, 21-2 Good Non-Friable NAD 240 SF

Beige Mastic Associated with HA-

Engineering Test Lab- 115 22-1, 22-2 Good Non-Friable NAD 240 SF

B0086268.1803 Page 2 of 5

Watervliet Arsenal

Building 125

1 Buffington Street

Watervliet, New York 12189

HA No. Material Description Material Location Sample

Number Condition Friability

Asbestos

Content

Estimated

Quantity Unit Notes

Beige Mastic Associated with

Stanchions/Raised Flooring

Ball Room 200, Test Labs- 211E, 212A, 212B, 213B, Build EC1-6, RA Chase, Demo 1-2, Clean

Storage 214, Wipe Down 215, Gowning/Interface, 116-120, 23-1, 23-2 Good Non-Friable NAD 265 SF Associated with stanchions below raised flooring.

Beige/White Mastic Associated with 4" Cove Base

Production Room/Offices, Open

Area/Offices, Long Hallway East of North Entrance

24-1, 24-2 Good Non-Friable NAD 855 LF

25 Gray Caulk on Concrete Floor Production Room SE 25-1, 25-2 Good Non-Friable NAD 150 SF

Beige/Gray Mastic Associated with 2'x2' Carpet Squares Open Area/Offices 26-1, 26-2 Good Non-Friable NAD 16,075 SF

27 2'x2' Plain Ceiling Tile Open Area/Offices 27-1, 27-2 Good Friable NAD 16,075 SF

28 12" Off-White Floor Tile Hallway to TFS Area 28-1, 28-2 Good Non-Friable NAD 1,960 SF

Gray Mastic Associated with HA-

Hallway to TFS Area 29-1, 29-2 Good Non-Friable NAD 1,960 SF

30 Plaster Wall Skim Coat East Add on Space 30-1, 30-2, 30-

Damaged Friable NAD 4,320 SF

31 Plaster Wall Base Coat East Add on Space 31-1, 31-2, 31-

Damaged Friable NAD 4,320 SF

32 CMU Mortar East Add on Space 32-1, 32-2 Damaged Non-Friable NAD 800 SF

Beige Glue Associated with

Ceramic Wall Tile East Add on Space 33-1, 33-2 Damaged Non-Friable NAD 150 SF

B0086268.1803 Page 3 of 5

Watervliet Arsenal

Building 125

1 Buffington Street

Watervliet, New York 12189

HA No. Material Description Material Location Sample

Number Condition Friability

Asbestos

Content

Estimated

Quantity Unit Notes

34 White Textured Paint on Brick

Outer Walls (Long Entrance

Hallway), South Walls (Below

Windows Throughout)

34-1, 34-2 Good Non-Friable NAD 150 SF

35 Exterior Brick Mortar Exterior- Throughout 35-1, 35-2 Good Non-Friable NAD 100,000 SF

36 Exterior Foundation Caulk Exterior- North Entrance 36-1, 36-2 Good Non-Friable NAD 75 LF

37 Exterior Silicone Window Caulk Exterior- Windows Throughout 37-1, 37-2 Good Non-Friable NAD 19,865 LF

38 Expansion Joint Caulk Exterior- North, South 38-1, 38-2 Good Non-Friable 3.3%

Chrysotile

65 LF

39 Exterior EIFS Overhang Exterior- North Entrance

Overhang 39-1, 39-2 Good Non-Friable NAD 70 SF

White/Gray Caulk Associated with Steel Plates Above

Windows

Exterior- Throughout (At Top of

New Windows) 40-1, 40-2 Good Non-Friable

9.5%

Chrysotile

2,885 LF

Caulk Associated with Stone

Window Sills

Exterior- Bottom of Window Sills

Throughout 41-1, 41-2 Good Non-Friable NAD 4,000 LF

42 Exterior HVAC Duct Caulk Exterior- Roof Above Break Room

(North) 42-1, 42-2 Good Non-Friable NAD 700 LF

Materia also located on HVAC ducts on interior. Inaccessible on interior due to height restrictions, same material.

43 EPDM Rubber Roofing Membrane Roof- Throughout 43-1, 43-2 Good Non-Friable NAD 125,000 SF

Electrical Components/Wire

Wrap Throughout Not Sampled Good

Assumed

ACM

36 EA

Internal materials associated with safety switches, manual shut offs, breaker panels, sub stations and electrical boxes. Material is assumed asbestos-containing until laboratory analysis can confirm or deny the presence of asbestos.

B0086268.1803 Page 4 of 5

Watervliet Arsenal

Building 125

1 Buffington Street

Watervliet, New York 12189

HA No. Material Description Material Location Sample

Number Condition Friability

Asbestos

Content

Estimated

Quantity Unit Notes

45 Flange Gasket Insulation Throughout Not Sampled Good Assumed

ACM

150 EA

EA = Each

LF = Linear Foot

NAD = No Asbestos Detected

SF = Square Foot

Assumed ACM = Material determined by the inspector to be suspect ACM is considered asbestos-containing until laboratory analysis can prove otherwise.

B0086268.1803 Page 5 of 5

Table 2

Lead Paint Summary

Watervliet Arsenal

Building 125

1 Buffington Street

Watervliet, New York 12189

Sample ID Description Substrate Sample Location Material Location Condition Result (% by weight) Classification Notes

LP-1 White Paint Gypsum Board Wall Throughout Intact <0.0080 ND

LP-2 White Paint Brick Wall Long Hallway Outside

Production Room Intact 1.9% LBP

LP-3 Green Paint Brick Wall Long Hallway Outside

Production Room Intact 1.5% LBP

LP-4 Red Paint Brick Wall North Entrance Hallway Intact 2.0% LBP

LP-5 Brown Paint Gypsum Board Wall Open Office Area Intact <0.0080 ND

Notes:

LBP = Lead-Based Paint (Greater than or equal to 0.5% by weight or 5,000 mg/Kg lead)

LCP = Lead-Containing Paint (Any detectable % lead by weight)

ND = None Detected

B0086268.1803 Page 1 of 1

FIGURES

FIGURE

WATERVLIET ARSENAL

WATERVLIET, NEW YORK

ASBESTOS AND LEAD PAINT SURVEY UPDATE

BUILDING 125

INTERIOR

Legend:

103 Room Number

S4 Area Identifier

2019 Sample Location

NOT TO SCALE

FIGURE

WATERVLIET ARSENAL

WATERVLIET, NEW YORK

ASBESTOS AND LEAD PAINT SURVEY UPDATE

BUILDING 125

EXTERIOR

Legend:

103 Room Number

S4 Area Identifier

2019 Sample Location

NOT TO SCALE

APPENDIX A

Limitations and Service Constraints

Limitations and Service Constraints

The opinions, conclusions and recommendations presented in this report are limited to the information obtained during the performance of the specific scope of service identified in the report. To the extent that

SERES-ARCADIS 8(A) JV, LLC relied upon any information prepared by other parties not under direct contract to SERES-ARCADIS 8(A) JV, LLC, no representation as to the accuracy or completeness of such information is made. This report is an instrument of professional service and the services described in the report were performed in accordance with generally accepted standards and level of skill and care ordinarily exercised by members of the profession working under similar conditions including comparable budgetary and schedule constraints. No warranty, guarantee or certification express or implied, is intended or given with respect to SERES-ARCADIS 8(A) JV, LLC’s services, opinions, conclusions or recommendations. This statement is in lieu of any other statement either expressed or implied.

SERES-ARCADIS 8(A) JV, LLC’s observations, the results of testing and SERES-ARCADIS 8(A) JV, LLC’s opinions, conclusions and recommendations apply solely to conditions existing at the specific times when and specific locations where SERES-ARCADIS 8(A) JV, LLC’s investigative work was performed.

Observation and testing activities such as those conducted by SERES-ARCADIS 8(A) JV, LLC are inherently limited and do not represent a conclusive or complete characterization. Conditions in other parts of the project site, building or area may vary from conditions at the specific locations where observations were made and where testing was performed by SERES-ARCADIS 8(A) JV, LLC.

Additionally, other building material hazards which were not identified by SERES-ARCADIS 8(A) JV, LLC, such as asbestos, lead-based paint and unidentified microbial impacts, may also be present in the indoor air, un-accessed areas and in walls, ceilings, cavities and floors. Therefore, the extent of SERES-

ARCADIS 8(A) JV, LLC’s opinions, conclusions and recommendations are limited and 100% confidence in these opinions, conclusions and recommendations cannot reasonably be achieved.

This is the start of the file's text. The full file is on GovTribe.