Appendix 6 - Bldg 7020 Specifications.pdf

PDF 97 KB Posted

Attached to
MBMV222321 Repair Emergency Power
Solicitation number
W50S84-22-B-0008
Issued by

About this file

This document contains a solicitation for emergency power repair services and specifications for required equipment. The solicitation seeks bids for a project at the Battle Creek, Michigan National Guard facility to repair the emergency power system for $500,000 to $1,000,000. Interested parties are encouraged to attend an in-person pre-bid conference on August 17, 2022. The award will be made based on price to the responsible bidder that conforms to the solicitation requirements. The equipment specifications include a 40kW diesel generator set that meets EPA Tier 3 emissions standards, along with an automatic transfer switch, fuel tank, and other accessories. Funding may become available by September 30, 2022, at which time the government intends to make an award if prices are within an awardable range.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Appendix 6

Diesel Genset, 60Hz, 40kW

U.S. EPA, Stationary Emergency Application 40kW, 60Hz, Standby, Diesel Genset Duty Rating-Standby Power (ESP) Emission Certification, EPA, Tier 3, NSPS CI Stationary Emergency Fuel Tank-Regional, Dual Wall, Sub Base, 24 Hour Minimum Listing-UL 2200 NFPA 110 Type 10 Level 1 Capable High Fuel Level Alarm Panel High Fuel Level Switch, 90% Low Fuel Level Switch, 40% Mechanical Fuel Gauge 5 Gallon Lockable Spill Containment Fuel Fill Box Fuel Tank, Over Fill Protection Valve, 95% Riser-Fuel Tank, 2 inch Switch-Fuel Tank, Rupture Basin Control Mounting-Right Facing PowerCommand1.1 Controller Gauge-Oil Pressure Stop Switch-Emergency Relays-Auxiliary, Qty 2, 25A-15V DC/10A-30V DC Control Display Language-English Load Connections-Dual Circuit Breaker, Location A, 80A, 3P, 600 Volts AC, 80%, UL Circuit Breaker, Location B, 80A, 3P, 600 Volts AC, 80%, UL Engine Governor-Electronic, Isochronous Engine Starter-12 Volt DC Motor Engine Air Cleaner-Normal Duty Battery Charging Alternator Battery Charger-6 Amp, Regulated Engine Cooling-Radiator, High Ambient Air Temperature, Ship Fitted Shutdown-Low Coolant Level Extension-Coolant Drain Engine Coolant-50% Antifreeze, 50% Water Mixture Exciter/Reg-Torque Match Coolant Heater Voltage-277/480, 3 Phase, Wye, 4 Wire Extension-Oil Drain Engine Oil Genset Warranty-2 Years Base Alternator-60Hz, 12L, 480/277V, 105C, 40C Ambient, Increased Motor Starting (IMS) Alternator Heater, 120 Volt AC

Aluminum Sound Attenuated Level 1 Enclosure, with Exhaust System Enclosure Color-Green, Aluminum Enclosure-Wind Load 180 MPH, ASCE7-10 Larger Battery Rack

Skidbase-Housing Ready

ATS: Transfer Switch-Electronic Control: 600A

Transfer Switch, 600 Amp Interface-Communications Network, MODBUS RTU Module Listing-UL 1008/CSA Certification Application-Utility to Genset Transfer Switch Warranty-2 Year Comprehensive Cabinet-Type 1 Poles-3 (Solid Neutral) Frequency-60 Hz System-3 Phase, 3 or 4 Wire Voltage-480 Volts AC Genset Starting Battery-12V DC Aux Relay-Emergency Position-12 Volts DC

Oil and Antifreeze Installed, Plus One (1) Set of O & M Manuals unless noted otherwise.

12VDC Engine Starting Battery - 700CCA

Delivery of Equipment to Jobsite

Service - start up & testing

Manual - Operator/Maintenance, Parts and Service

Remote Emergency Stop Station in a NEMA 4X Enclosure

Fuel Tank Riser 2"

File details come from the government source that posted it. Updated .