This solicitation seeks bids for emergency power repair services at a National Guard facility in Battle Creek, Michigan. The scope of work includes repairing emergency power at the location, with a period of performance of 120 calendar days. The project magnitude is between $500,000 and $1,000,000. Bids are due from small businesses with a size standard of $16.5 million or less in average annual receipts. The NAICS code is 238210 for electrical and wiring installation. A pre-bid conference will be held on August 17th and award will be made based on price. Funds are anticipated to be available by September 30th.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Appendix 3
Diesel Genset, 60Hz, 300kW
U.S. EPA, Stationary Emergency Application Duty Rating-Standby Power (ESP) Emission Certification, EPA, Tier 3, NSPS CI Stationary Emergency Lifting Base-No Fuel Tank Listing-UL 2200 Fuel Water Separator Control Mounting-Left Facing Generator Controller Control Cabinet Heater, 240 Volt AC Switch-Key, Control Operation Mode Backlit Digital Control Display Analog Meters-AC Output Relays-Genset Status, User Configured Stop Switch-Emergency Alarm-Audible, Engine Shutdown Interface-Comms Network, FTT-10 Stop Switch-Emergency, Externally Mounted Control Display Language-English Circuit Breaker or Entrance Box or Terminal Box-Right And Left Circuit Breaker-600A, Left Circuit Breaker on Right side, 3-Pole, UL 600, IEC 690, 100% Circuit Breaker-600A, Right Circuit Breaker on Right side, 3-Pole, UL 600, IEC 690, 100% Bottom Entry, Left Bottom Entry, Right Shunt Trip-24 Volts DC, Dual Breakers Engine Governor-Electronic, Isochronous Engine Starter-24 Volt DC Motor Engine Air Cleaner-Normal Duty Battery Charging Alternator External Battery Charger-12 Amp, Regulated Engine Cooling-Radiator, High Ambient Air Temperature, Ship Fitted Shutdown-Low Coolant Level Engine Coolant-50% Antifreeze, 50% Water Mixture Coolant Heater-240V, Single Phase Voltage-277/480, 3 Phase, Wye, 4 Wire Engine Oil Genset Warranty-2 Years Base Alternator-60Hz, 12 Lead, Limited Range, 80C Standby/Increased Motor Starting (IMS) Literature-English Packing-None, Base Mounted Housing Exciter/Regulator-Permanent Magnet Generator, 3 Phase Sensor Alternator Heater, 240 Volt AC Steel Sound Attenuated Level 1 Enclosure, with Exhaust System Enclosure Color-Green, Steel Wind Rating-150 MPH, Steel Housing Alternator Heater, 240 Volt AC
Steel Sound Attenuated Level 1 Enclosure, with Exhaust System Enclosure Color-Green, Steel Wind Rating-150 MPH, Steel Housing
ATS: ATS not needing replacement at this time
Oil and Antifreeze Installed, Plus One (1) Set of O & M Manuals unless noted otherwise.
24VDC Engine Starting Batteries - 1000CCA
72/hr Sub-Base Diesel Tank
Generator connection panel
Service - start up & testing
Manual - Operator/Maintenance, Parts and Service
Remote Emergency Stop Station in a NEMA 4X Enclosure