Appendix 4 - Bldg 6923 Specifications.pdf
PDF 96 KB Posted
- Attached to
- MBMV222321 Repair Emergency Power
- Solicitation number
- W50S84-22-B-0008
- Issued by
-
Department of the Army National Guard
About this file
This document contains a federal contract solicitation and related specifications for emergency power repair services. The solicitation seeks bids for repairing emergency power at a National Guard facility in Battle Creek, Michigan with a project value between $500,000 to $1 million. Services include installation of a 250kW diesel generator set and 500 gallon fuel tank in compliance with EPA Tier 3 emissions standards, along with transfer switches, controls, enclosure, and start-up testing. The period of performance is 120 calendar days. The solicitation is unrestricted and set aside for small businesses with a $16.5 million size standard. A pre-bid conference will be held on August 17th and bids are due by September 30th or when funds become available. The award will be made based on price to the responsible bidder providing the most advantageous offering to the government.
The specifications appendix provides additional details on the required 250kW diesel generator set and accessories, including an EPA compliant engine and fuel system, controls, circuit breakers, enclosure, automatic transfer switch, and start-up services. Documentation and warranty requirements are also outlined.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Appendix 4
Diesel Genset, 60Hz, 250kW
U.S. EPA, Stationary Emergency Application Diesel Genset, 60Hz, 250kW Duty Rating-Standby Power (ESP) Emission Certification, EPA, Tier 3, NSPS CI Stationary Emergency Fuel Tank-Sub Base, 500 Gallon, UL142 Compliant Compliance-Fuel Tank, Michigan Listing, ULC-S601-07 Fuel Tank-Dual Wall Sub-Base, 24 Hour Minimum Capacity Listing-UL 2200 Alarm-High Fuel Level, External with OFPV Override Fuel Water Separator Spill/Fill Box-Fuel with OFPV Vent Extensions-Fuel Tank, 5 Inch Diameter Control Mounting-Left Facing Generator Controller Control Cabinet Heater, 120 Volt AC Switch-Key, Control Operation Mode Backlit Digital Control Display Relays-Genset Status, User Configured Stop Switch-Emergency Alarm-Audible, Engine Shutdown Control Display Language-English Circuit Breaker or Entrance Box or Terminal Box-Right And Left Circuit Breaker-400A, Left Circuit Breaker on Right side, 3-Pole, UL 600, IEC 690 100% Circuit Breaker-400A, Right Circuit Breaker on Right side, 3-Pole, UL 600, IEC 690 100% Bottom Entry, Left Bottom Entry, Right Shunt Trip-24 Volts DC, Dual Breakers Engine Governor-Electronic, Isochronous Engine Starter-24 Volt DC Motor Engine Air Cleaner-Normal Duty Battery Charging Alternator External Battery Charger-12 Amp, Regulated Engine Cooling-Radiator, High Ambient Air Temperature, Ship Fitted Shutdown-Low Coolant Level Engine Coolant-50% Antifreeze, 50% Water Mixture Coolant Heater-240V, Single Phase Voltage-277/480, 3 Phase, Wye, 4 Wire Engine Oil Genset Warranty-2 Years Base Alternator-60Hz, 12 Lead, Extended Range, 105/80C Literature-English Packing-None, Base Mounted Housing Exciter/Regulator-Permanent Magnet Generator, 3 Phase Sensor Alternator Heater, 120 Volt AC
Steel Sound Attenuated Level 1 Enclosure, with Exhaust System Enclosure Color-Green, Steel
ATS: Service Entrance Transfer Switch-Electronic Control: 1000A
Interface-Communications Network, MODBUS RTU Module Listing-UL 1008 Application-Utility to Genset Transfer Switch Warranty-2 Year Comprehensive Cabinet-Type 3R Poles-3 (Solid Neutral) Frequency-60 Hz System-3 Phase, 3 or 4 Wire Voltage-480 Volts AC Genset Starting Battery-24V DC PC40 Control Auxiliary Relay-Switch in Emergency Position-24 Volts DC
Oil and Antifreeze Installed, Plus One (1) Set of O & M Manuals unless noted otherwise.
24VDC Engine Starting Batteries - 1000CCA
72/hr Sub-Base Diesel Tank
Generator connection panel
Service - start up & testing
Manual - Operator/Maintenance, Parts and Service
Remote Emergency Stop Station in a NEMA 4X Enclosure
File details come from the government source that posted it. Updated .