This document contains specifications for a 200kW diesel generator set and related equipment as well as details of a federal contract opportunity for emergency power repairs at a National Guard facility in Battle Creek, Michigan. The generator set specifications include an EPA Tier 3-compliant diesel engine, 200kW standby rating, UL2200 and NFPA110 Level 1 compliance, dual wall fuel tank, generator and alternator specifications, sound attenuated enclosure, automatic transfer switch, and other accessories. The solicitation seeks bids for emergency power repairs between $500,000 to $1 million to be completed within 120 calendar days and follows a small business set-aside. A pre-bid conference will be held on August 17th and award is anticipated by September 30th contingent on available funding.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Appendix 5
Diesel Genset, 60Hz, 200kW
U.S. EPA, Stationary Emergency Application Diesel Genset, 60Hz, 200kW Duty Rating-Standby Power (ESP) Emission Certification, EPA, Tier 3, NSPS CI Stationary Emergency Fuel Tank-Regional, Dual Wall, Sub Base, 24 Hour Minimum Listing-UL 2200 NFPA 110 Type 10 Level 1 Capable High Fuel Level Alarm Panel Fuel Water Separator High Fuel Level Switch, 90% Low Fuel Level Switch, 40% Mechanical Fuel Gauge 5 Gallon Lockable Spill Containment Fuel Fill Box Fuel Tank, Over Fill Protection Valve, 95% Riser-Fuel Tank, 2 inch Switch-Fuel Tank, Rupture Basin Control Mounting-Left Facing Controller Gauge-Oil Pressure Stop Switch-Emergency Relays-Auxiliary, Qty 2, 25A-15V DC/10A-30V DC Control Display Language-English Load Connections-Dual Circuit Breaker, Location A, 125A-400A, 3P, LSI, 600 Volts AC, 100%, UL Circuit Breaker, Location B, 125A-400A, 3P, LSI, 600 Volts AC, 80%, UL Circuit Breaker or Terminal Box (Position C)-None Bottom Entry, Right Engine Governor-Electronic, Isochronous Engine Starter-12 Volt DC Motor Engine Air Cleaner-Normal Duty Battery Charging Alternator Battery Charger-6 Amp, Regulated Engine Cooling-Radiator, High Ambient Air Temperature, Ship Fitted Shutdown-Low Coolant Level Extension-Coolant Drain Engine Coolant-50% Antifreeze, 50% Water Mixture Exciter/Regulator-Permanent Magnet Generator, 3 Phase Sensor Coolant Heater, Extreme Cold Ambient Voltage-277/480, 3 Phase, Wye, 4 Wire Engine Oil Heater-120 Volts AC, Single Phase Engine Oil Genset Warranty-2 Years Base
Alternator-60Hz, 12L, 480/277V, 105C, 40C Ambient, Increased Motor Starting (IMS) Literature-English Packing-Skid, Poly Bag
Battery Rack Extension-Oil Drain Tank Riser A Alternator Heater, 120 Volt AC
Aluminum Sound Attenuated Level 1 Enclosure, with Exhaust System Enclosure Color-Green, Aluminum Enclosure-Wind Load 180 MPH, ASCE7-10 Skidbase-Housing Ready
ATS: Transfer Switch-Electronic Control: 600A
OTEC600, Transfer Switch, 600 Amp Interface-Communications Network, MODBUS RTU Module Listing-UL 1008/CSA Certification Application-Utility to Genset Transfer Switch Warranty-2 Year Comprehensive Cabinet-Type 1 Poles-3 (Solid Neutral) Frequency-60 Hz System-3 Phase, 3 or 4 Wire Voltage-480 Volts AC Genset Starting Battery-12V DC Aux Relay-Emergency Position-12 Volts DC
Oil and Antifreeze Installed, Plus One (1) Set of O & M Manuals unless noted otherwise.
Service - start up & testing
Manual - Operator/Maintenance, Parts and Service
Remote Emergency Stop Station in a NEMA 4X Enclosure
Generator connection panel
12VDC Engine Starting Battery - 700CCA
Kit, FUEL SYSTEM