This document contains a federal contract solicitation and related specifications. The solicitation is for emergency power repair services at a National Guard facility in Battle Creek, Michigan. Services include installation of a 25kW diesel generator set and transfer switch, with an estimated value between $500,000 and $1 million. The NAICS code is 238210 and the period of performance is 120 calendar days. The solicitation is set aside for small businesses with a size standard of $16.5 million. A pre-bid conference will be held on August 17th and award will be to the responsible bidder providing the most advantageous price. Funding is not presently available but is expected by September 30th. The generator specifications include a Tier 3 engine, sound attenuated enclosure, dual fuel tank, automatic transfer switch, and spare parts.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Appendix 2

Diesel Genset, 60Hz, 25kW

U.S. EPA, Stationary Emergency Application Duty Rating-Standby Power (ESP) Emission Certification, EPA, Tier 3, NSPS CI Stationary Emergency Fuel Tank-Regional, Dual Wall, Sub Base, 24 Hour Minimum Listing-UL 2200 NFPA 110 Type 10 Level 1 Capable High Fuel Level Alarm Panel High Fuel Level Switch, 90% Low Fuel Level Switch, 40% Mechanical Fuel Gauge 5 Gallon Lockable Spill Containment Fuel Fill Box Fuel Tank, Over Fill Protection Valve, 95% Riser-Fuel Tank, 2 inch Switch-Fuel Tank, Rupture Basin Control Mounting-Right Facing Controller Gauge-Oil Pressure Stop Switch-Emergency Relays-Auxiliary, Qty 2, 25A-15V DC/10A-30V DC Control Display Language-English Load Connections-Dual Circuit Breaker, Location A, 100A, 3P, 600 Volts AC, 80%, UL Circuit Breaker, Location B, 100A, 3P, 600 Volts AC, 80%, UL Engine Governor-Electronic, Isochronous Engine Starter-12 Volt DC Motor Engine Air Cleaner-Normal Duty Battery Charging Alternator Battery Charger-6 Amp, Regulated Engine Cooling-Radiator, High Ambient Air Temperature, Ship Fitted Shutdown-Low Coolant Level Extension-Coolant Drain Engine Coolant-50% Antifreeze, 50% Water Mixture Exciter/Reg-Torque Match Coolant Heater Voltage-120/240, 3 Phase, Delta, 4 Wire Extension-Oil Drain Engine Oil Genset Warranty-2 Years Base Alternator-60Hz, 12L, 240/120V, 105C, 40C Ambient, Increased Motor Starting (IMS) Literature-English Packing-Skid, Poly Bag

Ship Loose-Tank Riser B Alternator Heater, 120 Volt AC Aluminum Sound Attenuated Level 1 Enclosure, with Exhaust System Enclosure Color-Green, Aluminum Enclosure-Wind Load 180 MPH, ASCE7-10 Larger Battery Rack Skidbase-Housing Ready

ATS: 225A

TransferSwitch, 225 Amp Interface-Communications Network, MODBUS RTU Module Listing-UL 1008/CSA Certification Application-Utility to Genset Transfer Switch Warranty-2 Year Comprehensive Cabinet-Type 1 Poles-4 (Switched Neutral) Frequency-60 Hz System-3 Phase, 3 or 4 Wire Voltage-208 Volts AC Genset Starting Battery-12V DC PC40 Control Aux Relay-Emergency Position-12 Volts DC

Oil and Antifreeze Installed, Plus One (1) Set of O & M Manuals unless noted otherwise.

12VDC Engine Starting Battery - 700CCA Delivery of Equipment to Jobsite Service - start up & testing Manual - Operator/Maintenance, Parts and Service Remote Emergency Stop Station in a NEMA 4X Enclosure Fuel Tank Riser 2" Interface-Communications Network, MODBUS RTU Module