US Forest Service
Rincon Fire Station and Barracks
RFIs / Questions August 15, 2010
1. Please provide direction regarding plans and specifications to be used for bidding. The ZIP file issued on August 10, 2010 includes duplicate copies of specifications, and plans that appear to apply to other projects. Can one set of plans and one set of specifications for this project (or for each building) be provided? No, all plans are on-line
2. Please confirm that a Bid Bond is required. Per the Site Visit Questions, a Bid Bond is required, but per the Solicitation, an Offer Guarantee is not..Bid Bond is required
3. Please clarify the A/E components required for this project. Will the Construction Documents be completed by either the Contractor or the US Forest Service after award? Does the Contractor need to include an allowance for completion of the Construction Documents or to cover incomplete design components? How much should be included in this allowance? There are no A&E requirements for this award. As per the Forest Service, all drawings and specs are posted. No allowance shall be required to cover incomplete design.
4. Please clarify Alternates that will be required with the Proposal. There are Alternates shown on several of the drawings, but are not itemized on the Schedule of Items. Is the intent of the Schedule of Items to provide a complete breakdown of the entire cost include in the Proposal, or is the Schedule of Items meant to create a Unit Cost Sheet for future reference? Both
5. Will the Fire Protection scope of work for the barracks be considered using an NFPA 13 or an NFPA 13R (Residential) system? 13R will be used for the Barracks.
6. Please confirm that a Fire Protection (Sprinkler) system is only indicated in the Barracks, and is not indicated in the Fire Station. Correct, only the Barracks require sprinklers.
7. Will any of the Kitchen Equipment / Appliances require a Wet Chemical Fire Protection system (such as an Ansul System)? No, this is all residential kitchen equipment.