283111 Digital Addressable Fire Alarm System.DOC
DOC document 33 KB Posted
- Attached to
- RECOVERY Replace Annex Building HVAC, Beneficial Insects Introduction Research Unit (BIIRU), Newark, DE
- Solicitation number
- AG-3615-S-10-0001
About this file
J.1 -02 SPECIFICATIONS - FILE 26
View the file
Other files
Show all 44
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. System smoke detectors.
1.3 DEFINITIONS
A. NICET: National Institute for Certification in Engineering Technologies.
1.4 SYSTEM DESCRIPTION
A. UL-certified addressable system, with multiplexed signal transmission, dedicated to fire-alarm service only.
B. Existing Fire Alarm System: NFPA 72, manual and automatic local fire alarm system with connections to central station. All programming and equipment modifications must be compatible with the existing central campus monitoring control panel and network/remote fire alarm systems:
1. Manufacturer: Simplex, Model # 4010 C. Work includes; Cleaning and reinstallation of stored smoke detectors and reprogramming fire alarm system.
1. Pretesting and Post testing are included as part of this work.
D. Existing fire alarm sequence of operation shall remain unchanged.
1.5 SUBMITTALS
A. General Submittal Requirements:
1. Shop Drawings shall be prepared by persons with the following qualifications:
a. Trained and certified by manufacturer in fire-alarm system design.
b. NICET-certified fire-alarm technician, Level III minimum.
c. Licensed or certified by authorities having jurisdiction.
B. Product Data: For each type of product indicated.
C. Qualification Data: For qualified Installer.
D. Field quality-control reports.
1.6 QUALITY ASSURANCE
A. Installer Qualifications: Installation shall be by personnel certified by NICET as fire-alarm Level III technician.
B. NFPA Certification: Obtain certification according to NFPA 72 by a UL-listed alarm company.
1.7 PROJECT CONDITIONS
A. Interruption of Existing Fire-Alarm Service: Do not interrupt fire-alarm service to facilities occupied by Owner or others unless permitted under the following conditions and then only after arranging to provide temporary guard service according to requirements indicated:
1. Notify Owner no fewer than 2 days in advance of proposed interruption of fire-alarm service.
2. Do not proceed with interruption of fire-alarm service without Owner’s written permission.
PART 2 - PRODUCTS
Not Used.
PART 3 - EXECUTION
3.1 EQUIPMENT INSTALLATION
A. Comply with NFPA 72 for installation of fire-alarm equipment.
B. Connecting to Existing Equipment: Verify that existing fire-alarm system is operational before making changes or connections.
1. Re-connect existing equipment to existing control panel in the building. Existing devices shall be removed, relocated, and reinstalled in ceilings as required for removal and reinstallation of ceilings and HVAC ductwork.
2. Expand, modify, and supplement existing control, monitoring equipment as necessary to extend existing functions to the new points. New components shall be capable of merging with existing configuration without degrading the performance of either system.
3.2 IDENTIFICATION
A. Identify system components, wiring, cabling, and terminals. Comply with requirements for identification specified in Division 26 Section "Identification for Electrical Systems."
3.3 FIELD QUALITY CONTROL
A. Field tests shall be witnessed by authorities having jurisdiction.
B. Conduct Pretest and Post test to confirm system functionality.
C. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect, test, and adjust components, assemblies, and equipment installations, including connections.
D. Tests and Inspections of provided components:
1. Visual Inspection: Conduct visual inspection prior to testing.
a. Inspection shall be based on completed Record Drawings and system documentation that is required by NFPA 72 in its "Completion Documents, Preparation" Table in the "Documentation" Section of the "Fundamentals of Fire Alarm Systems" Chapter.
b. Comply with "Visual Inspection Frequencies" Table in the "Inspection" Section of the "Inspection, Testing and Maintenance" Chapter in NFPA 72; retain the "Initial/Reacceptance" column and list only the installed components.
2. System Testing: Comply with "Test Methods" Table in the "Testing" Section of the "Inspection, Testing and Maintenance" Chapter in NFPA 72.
3. Factory-authorized service representative shall prepare the "Fire Alarm System Record of Completion" in the "Documentation" Section of the "Fundamentals of Fire Alarm Systems" Chapter in NFPA 72 and the "Inspection and Testing Form" in the "Records" Section of the "Inspection, Testing and Maintenance" Chapter in NFPA 72.
E. Reacceptance Testing: Perform reacceptance testing to verify the proper operation of added or replaced devices and appliances.
F. Fire-alarm system will be considered defective if it does not pass tests and inspections.
G. Prepare test and inspection reports.
END OF SECTION
Upgrade The Annex Building HVAC
Digital, Addressable, Fire-Alarm System
BIIRU, Newark DE 283111-1
File details come from the government source that posted it. Updated .