SECTION 095100 - ACOUSTICAL CEILINGS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes suspended metal grid ceiling system and acoustical units.
1. Base Proposal: Work includes removal of existing acoustical units and suspended grid in limited areas to permit HVAC unit replacement and duct modifications as indicated on drawings.
2. Bid Option No. 1: Work includes the complete removal and the installation of new acoustical units; the removal of existing suspended metal grid ceiling system and reinstallation to permit HVAC ductwork replacement and modifications throughout the entire building. The reinstallation of existing suspended metal grid ceiling systems will match existing layouts, any damaged materials shall be replaced with new materials conforming to the requirements below.
1.3 DEFINITIONS
A. AC: Articulation Class.
B. CAC: Ceiling Attenuation Class.
C. LR: Light Reflectance coefficient.
D. NRC: Noise Reduction Coefficient.
1.4 SUBMITTALS
A. Product Data: For each type of product indicated.
B. Samples for Initial Selection: For components with factory-applied color finishes.
C. Samples for Verification: For each component indicated and for each exposed finish required, prepared on Samples of size indicated below.
1. Acoustical Unit: Set of 6-inch square samples of each type, color, pattern, and texture.
2. Exposed Suspension System Members, Moldings, and Trim: Set of 12-inch- (300-mm-) long Samples of each type, finish, and color.
D. Qualification Data: For testing agency.
E. Field quality-control test reports.
F. Product Test Reports: Based on evaluation of comprehensive tests performed by a qualified testing agency, for each acoustical unit ceiling.
G. Research/Evaluation Reports: For each acoustical unit ceiling and components and anchor and fastener type.
H. Maintenance Data: For finishes to include in maintenance manuals.
1.5 QUALITY ASSURANCE
A. Acoustical Testing Agency Qualifications: An independent testing laboratory, or an NVLAP-accredited laboratory, with the experience and capability to conduct the testing indicated. NVLAP-accredited laboratories must document accreditation, based on a "Certificate of Accreditation" and a "Scope of Accreditation" listing the test methods specified.
B. Source Limitations:
1. Acoustical Ceiling Panel: Obtain each type through one source from a single manufacturer.
2. Suspension System: Obtain each type through one source from a single manufacturer.
C. Source Limitations: Obtain each type of acoustical ceiling panel and supporting suspension system through one source from a single manufacturer.
D. Fire-Test-Response Characteristics: Provide acoustical unit ceilings that comply with the following requirements:
1. Fire-Resistance Characteristics: Where indicated, provide acoustical unit ceilings identical to those of assemblies tested for fire resistance per ASTM E 119 by UL or another testing and inspecting agency acceptable to authorities having jurisdiction.
a. Fire-Resistance Ratings: Indicated by design designations from UL's "Fire Resistance Directory" or from the listings of another testing and inspecting agency.
b. Identify materials with appropriate markings of applicable testing and inspecting agency.
2. Surface-Burning Characteristics: Provide acoustical units with the following surface-burning characteristics complying with ASTM E 1264 for Class A materials as determined by testing identical products per ASTM E 84:
a. Smoke-Developed Index: 450 or less.
1.6 DELIVERY, STORAGE, AND HANDLING
A. Deliver acoustical units, suspension system components, and accessories to Project site in original, unopened packages and store them in a fully enclosed, conditioned space where they will be protected against damage from moisture, humidity, temperature extremes, direct sunlight, surface contamination, and other causes.
B. Before installing acoustical units, permit them to reach room temperature and a stabilized moisture content.
C. Handle acoustical units carefully to avoid chipping edges or damaging units in any way.
1.7 PROJECT CONDITIONS
A. Environmental Limitations: Do not install acoustical unit ceilings until work above ceilings is complete, and ambient temperature and humidity conditions are maintained at the levels indicated for Project when occupied for its intended use.
1. Pressurized Plenums: Operate ventilation system for not less than 48 hours before beginning acoustical unit ceiling installation.
1.8 COORDINATION
A. Coordinate layout and installation of acoustical units and suspension system with other construction that penetrates ceilings or is supported by them, including light fixtures, HVAC equipment, fire-suppression system, and partition assemblies.
1.9 EXTRA MATERIALS
A. Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Acoustical Ceiling Units: Full-size panels equal to 2.0 percent of quantity installed.
PART 2 - PRODUCTS
2.1 ACOUSTICAL UNITS, GENERAL
A. Manufacturers:
1. Armstrong World Industries, Inc.: www.armstrong.com
2. USG: www.usg.com
3. Certain Teed Corporation: www.certainteed.com B. Acoustical Panels:
1. Surface Texture: Medium
2. Composition: Mineral Fiber
3. Color: White
4. Size: 24in x 48in x 5/8in
5. Edge Profile: Square Lay-in
6. Noise Reduction Coefficient(NRC): ASTM C 423; Classified with UL label n product carton, 0.50
7. Ceiling Attenuation Class (CAC): ASTM C 1414; Classified with UL label on product carton, 35.
8. Flame Spread: ASTM E 1264; Class A (UL)
9. Light Reflectance (LR): ASTM E 1477; White Panel: Light Reflectance: 0.87
10. Dimensional Stability: HumiGard Plus – temperatures up to 120 degrees F and high humidity excluding exterior use, use over standing water, and direct contact with moisture.
11. Mold/Mildew Inhibitor: The front and back of the product have been treated with BioBlock, a paint that contains a special biocide that inhibits or retards the growth of mold or mildew.
12. Acceptable Product: Tundra, 302 as manufactured by Armstrong World Industries.
2.2 METAL SUSPENSION SYSTEMS, GENERAL
A. Metal Suspension System Standard: Clean and reinstall existing metal ceiling grid system runners and main tees.
B. Wire Hangers, Braces, and Ties: Provide wires complying with the following requirements:
1. Zinc-Coated, Carbon-Steel Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper.
2. Nickel-Copper-Alloy Wire: ASTM B 164, nickel-copper-alloy UNS No. N04400.
3. Size: Select wire diameter so its stress at 3 times hanger design load (ASTM C 635, Table 1, "Direct Hung") will be less than yield stress of wire.
4. Coordinate final locations with new ductwork installation. Relocate existing wire hangers, braces and ties as required to accommodate new ductwork. Where required by final ductwork locations, provide additional wire hangers, braces and ties as specified to hang ceiling according to Manufacturer’s recommendations.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates, areas, and conditions, including structural framing to which acoustical unit ceilings attach or abut, with Installer present, for compliance with requirements specified in this and other Sections that affect ceiling installation and anchorage and with requirements for installation tolerances and other conditions affecting performance of acoustical unit ceilings.
1. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Measure each ceiling area and establish layout of acoustical units to balance border widths at opposite edges of each ceiling. Avoid using less-than-half-width panels at borders, and comply with layout shown on reflected ceiling plans.
3.3 INSTALLATION
A. General: Install acoustical unit ceilings to comply with ASTM C 636 per manufacturer's written instructions and CISCA's "Ceiling Systems Handbook."
B. Suspend ceiling hangers from building's structural members and as follows:
1. Install hangers plumb and free from contact with insulation or other objects within ceiling plenum that are not part of supporting structure or of ceiling suspension system.
2. Splay hangers only where required to miss obstructions; offset resulting horizontal forces by bracing, countersplaying, or other equally effective means.
3. Where width of ducts and other construction within ceiling plenum produces hanger spacings that interfere with location of hangers at spacings required to support standard suspension system members, install supplemental suspension members and hangers in form of trapezes or equivalent devices.
4. Secure wire hangers to ceiling suspension members and to supports above with a minimum of three tight turns. Connect hangers directly either to structures or to inserts, eye screws, or other devices that are secure and appropriate for substrate and that will not deteriorate or otherwise fail due to age, corrosion, or elevated temperatures.
5. Secure flat, angle, channel, and rod hangers to structure, including intermediate framing members, by attaching to inserts, eye screws, or other devices that are secure and appropriate for both structure to which hangers are attached and type of hanger involved. Install hangers in a manner that will not cause them to deteriorate or fail due to age, corrosion, or elevated temperatures.
6. When steel framing does not permit installation of hanger wires at spacing required, install carrying channels or other supplemental support for attachment of hanger wires.
7. Space hangers not more than 48 inches (1200 mm) o.c. along each member supported directly from hangers, unless otherwise indicated; provide hangers not more than 8 inches (200 mm) from ends of each member.
8. Size supplemental suspension members and hangers to support ceiling loads within performance limits established by referenced standards and publications.
C. Install edge moldings and trim of type indicated at perimeter of acoustical ceiling area and where necessary to conceal edges of acoustical units.
1. Apply acoustical sealant in a continuous ribbon concealed on back of vertical legs of moldings before they are installed.
2. Screw attach moldings to substrate at intervals not more than 16 inches (400 mm) o.c. and not more than 3 inches (75 mm) from ends, leveling with ceiling suspension system to a tolerance of 1/8 inch in 12 feet (3.2 mm in 3.6 m). Miter corners accurately and connect securely.
3. Do not use exposed fasteners, including pop rivets, on moldings and trim.
D. Install suspension system runners so they are square and securely interlocked with one another. Remove and replace dented, bent, or kinked members.
E. Install acoustical units with undamaged edges and fit accurately into suspension system runners and edge moldings. Scribe and cut panels at borders and penetrations to provide a neat, precise fit.
1. Arrange directionally patterned acoustical units as follows:
a. As indicated on reflected ceiling plans.
b. Install panels with pattern running in one direction parallel to long axis of space.
c. Install panels in a basket-weave pattern.
2. For square-edged panels, install panels with edges fully hidden from view by flanges of suspension system runners and moldings.
3.4 FIELD QUALITY CONTROL
A. Tests and Inspections: Testing and inspecting of completed installations of acoustical unit ceiling hangers and anchors and fasteners shall take place in successive stages, in areas of extent and using methods as follows. Do not proceed with installations of acoustical unit ceiling hangers for the next area until test results for previously completed installations of acoustical unit ceiling hangers show compliance with requirements.
1. Extent of Each Test Area: When installation of ceiling suspension systems has reached 20 percent completion but no panels have been installed.
Verify loadings in two subparagraphs below with structural engineer based on ceiling loadings and seismic zone where Project is located. CISCA's "Guidelines for Seismic Restraint of Direct-Hung Suspended Ceiling Assemblies--Seismic Zones 3 & 4" requires hanger wire attachment devices to be "capable of supporting 100 lbf (445 N)."
a. Within each test area, testing agency will select 1 of every 10 power-actuated fasteners and postinstalled anchors used to attach hangers to concrete and will test them for 200 lbf (890 N) of tension; it will also select one of every 2 postinstalled anchors used to attach bracing wires to concrete and will test them for 440 lbf (1957 N) of tension.
b. When testing discovers fasteners and anchors that do not comply with requirements, testing agency will test those anchors not previously tested until 20 pass consecutively and then will resume initial testing frequency.
B. Remove and replace acoustical unit ceiling hangers and anchors and fasteners that do not pass tests and inspections and retest as specified above.
3.5 CLEANING
A. Clean exposed surfaces of acoustical unit ceilings, including trim, edge moldings, and suspension system members. Comply with manufacturer's written instructions for cleaning and touchup of minor finish damage. Remove and replace ceiling components that cannot be successfully cleaned and repaired to permanently eliminate evidence of damage.
END OF SECTION