About this file

J.1 -02 SPECIFICATIONS - FILE 15

View the file

Other files

File Type Posted
SF-30 Amendment 03.pdf PDF
BiddersSign-InSheet.pdf PDF
sf-30 amend 02.pdf PDF
of 17.pdf PDF
SF-30 AMEND NO 01.pdf PDF
SF 30 AMEND NO 02.pdf PDF
AG-3615-S-10-0001 newark replace annex hvac IFB amend 02 COVERLETTER.docx DOCX document
260502_Minor Electrical Demolition.DOC DOC document
013300 Submittal Procedures.doc DOC document
230593_Testing Adjusting and Balancing for HVAC Systems.doc DOC document
260526_Grounding Bonding for Electrical Systems.DOC DOC document
230553_Identification for HVAC Piping and Equipment.DOC DOC document
2003.162.031-USDA-TS-22x34-Model.PDF PDF
DE6.dvb DVB file
095100_Acoustical Ceilings.DOC DOC document
SF-LLL FORM.pdf PDF
238113_Packaged Terminal Air Conditioners.DOC DOC document
230513_Common Motor Requirements For HVAC Equipment.DOC DOC document
2003.162.031-M101-USDA 22x34.PDF PDF
260529_Hangers Supports for Electrical Systems.DOC DOC document
022250-Minor Demolition for Remodeling.doc DOC document
230500_Common Work Results For HVAC.doc DOC document
260519_Low-Voltage Electrical Power Conductors Cables.DOC DOC document
099000-Paints and Coatings.doc DOC document
2003.162.031-A101-USDA 22x34.PDF PDF
260553_Identification for Electrical Systems.DOC DOC document
NEWARK RECOVERY - UPGRADE ANNEX BUILDING HVAC FAC 2005-37.DOCX DOCX document
AG-3615-S-10-0001 newark replace annex hvac IFB COVERLETTER.docx DOCX document
013000 Administrative Requirements.doc DOC document
233300_Air Duct Accessories.DOC DOC document
283111 Digital Addressable Fire Alarm System.DOC DOC document
017000 Execution and Closeout Requirements.doc DOC document
014000 Quality Requirements.doc DOC document
233713_Diffusers Registers Grilles and Louvers.DOC DOC document
260533_Raceway Boxes for Electrical Systems.DOC DOC document
2003.162.031-Specification Cover.pdf PDF
2003.162.031-M201-USDA 22x34.PDF PDF
233113_Metal Ducts.DOC DOC document
2003.162.031-E101-USDA 22x34.PDF PDF
016000 Product Requirements.doc DOC document
2003.162.031-M001-Layout.PDF PDF
2003.162.031-M102-USDA 22x34.PDF PDF
2003.162.031-M202-USDA 22x34.PDF PDF
000110ST - Table of Contents.doc DOC document
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECTION 230700 - HVAC INSULATION

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Insulation Materials:

a. Glass Fiber

2. Insulating cements.

3. Adhesives.

4. Mastics.

5. Lagging adhesives.

6. Sealants.

7. Factory-applied jackets.

8. Tapes.

9. Securements.

B. Codes and Regulations

1. International Mechanical Code – 2006 Edition with amendments.

2. International Plumbing Code - 2006 Edition with amendments.

3. International Building Code - 2006 Edition with amendments.

1.3 SUBMITTALS

A. Product Data: For each type of product indicated. Include thermal conductivity, thickness, and jackets (both factory and field applied, if any).

B. Shop Drawings:

1. Detail application at linkages of control devices.

2. Detail field application for each equipment type.

C. Qualification Data: For qualified Installer.

D. Material Test Reports: From a qualified testing agency acceptable to authorities having jurisdiction indicating, interpreting, and certifying test results for compliance of insulation materials, sealers, attachments, cements, and jackets, with requirements indicated. Include dates of tests and test methods employed.

E. Field quality-control reports.

1.4 QUALITY ASSURANCE

A. Installer Qualifications: Skilled mechanics who have successfully completed an apprenticeship program or another craft training program certified by the Department of Labor, Bureau of Apprenticeship and Training.

B. Fire-Test-Response Characteristics: Insulation and related materials shall have fire-test-response characteristics indicated, as determined by testing identical products per ASTM E 84, by a testing and inspecting agency acceptable to authorities having jurisdiction. Factory label insulation and jacket materials and adhesive, mastic, tapes, and cement material containers, with appropriate markings of applicable testing and inspecting agency.

1. Insulation Installed Indoors: Flame-spread index of 25 or less, and smoke-developed index of 50 or less.

1.5 DELIVERY, STORAGE, AND HANDLING

A. Packaging: Insulation material containers shall be marked by manufacturer with appropriate ASTM standard designation, type and grade, and maximum use temperature.

1.6 SCHEDULING

A. Schedule insulation application after pressure testing systems and, where required, after installing and testing heat tracing. Insulation application may begin on segments that have satisfactory test results.

B. Complete installation and concealment of plastic materials as rapidly as possible in each area of construction.

PART 2 - PRODUCTS

2.1 DUCTWORK INSULATION

A. Manufacturers:

1. Knauf Fiber Glass

2. Johns Manville

3. Owens Corning

B. Insulation (Type A) - Flexible Fiber Glass Blanket:

1. ASTM C 553 Types II and ASTM C 1290; flexible, limited combustible.

2. ‘K’ Value: ASTM C 177, 0.23 at 75oF, Density 3.0 PCF

3. Maximum Service Temperature

a. Faced: 250 oF

b. Unfaced: 350 oF

4. Maximum allowable compression: 25%

5. Vapor Retarder Jacket: FSK conforming to ASTM C 1136 Type II.

6. Securement: Outward cinching staples in combination with appropriate pressure-sensitive aluminum foil tape, or in combination with glass fabric and vapor retarder mastic.

7. Design Basis: Johns Manville Microlite

C. Insulation (Type B1) – Rigid Fiber Glass Board:

1. ASTM C 612 Type IB; rigid

2. ‘K’ Value: ASTM C 177, 0.23 at 75 oF, Density 3.0 PCF

3. Maximum Service Temperature: 450 oF

4. Vapor Retarder Jacket: ASJ conforming to ASTM C 1136 Type I or FSK conforming to ASTM C 1136 Type II.

5. Securement: Adhesive and mechanical fasteners spaced a minimum of 12” on center with a minimum of 2 rows per side of duct. Secure with speed washers and all joints, breaks and punctures shall be sealed with appropriate pressure-sensitive foil tape, or glass fabric and vapor retarder mastic.

6. Design Basis: Johns Manville 814 Series

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates and conditions for compliance with requirements for installation and other conditions affecting performance of insulation application.

1. Verify that systems and equipment to be insulated have been tested and are free of defects.

2. Verify that surfaces to be insulated are clean and dry.

3. Proceed with installation only after unsatisfactory conditions have been corrected.

B. Mix insulating cements with clean potable water; if insulating cements are to be in contact with stainless-steel surfaces, use demineralized water.

3.2 INSTALLATION

A. Furnish factory-applied or field-applied vapor retarder jackets.

B. Secure factory-applied jackets with pressure sensitive adhesive self-sealing longitudinal laps and butt strips.

C. Secure field-applied jackets with outward clinch expanding staples and seal staple penetrations with vapor retarder mastic.

D. Insulate fittings, joints, and valves with molded insulation of like material and thickness as adjacent pipe.

E. Continue insulation through penetrations of building assemblies or portions of assemblies having fire resistance rating of two hour or less. Provide intumescent firestopping when continuing insulation through assembly. Finish at supports, protrusions, and interruptions.

F. Continuous insulation through hangers and supports.

G. Insulated ductwork conveying air below ambient temperature:

1. Provide insulation with vapor retarder jackets.

2. Finish with tape and vapor retarder jacket.

3. Continue insulation through walls, sleeves, hangers, and other duct penetrations.

4. Insulate entire system including fittings, joints, flanges, fire dampers, flexible connections, and expansion joints.

H. Insulated ductwork conveying air above ambient temperature:

1. Provide with or without standard vapor retarder jacket.

2. Insulate fittings and joints. Where service access is required, bevel and seal ends of insulation.

I. External Duct Insulation Application:

1. Secure insulation with vapor retarder with wires and seal jacket joints with vapor retarder adhesive or tape to match jacket.

2. Secure insulation without vapor retarder with staples, tape, or wires.

3. Install without sag on underside of ductwork. Use adhesive or mechanical fasteners where necessary to prevent sagging. Lift ductwork off trapeze hangers and insert spacers.

4. Seal vapor retarder penetrations by mechanical fasteners with vapor retarder adhesive.

5. Stop and point insulation around access doors and damper operators to allow operation without disturbing wrapping.

J. Additional duct insulation requirements

1. All cooling supply ducts shall be insulated in unconditioned spaces

2. Insulate all heating ducts in non-heated spaces

3.3 SCHEDULES

A. Ductwork Systems:

1. Plenums, conditioned space within the building:

a. Energy Conservation Construction Code Minimum R-5.0

b. Concealed Space:

1) (Type A) Provide 2” of Knauf Duct Wrap with an installed R-6.0, for ductwork less than 18” wide.

2. Unconditioned space within the building:

a. Energy Conservation Construction Code Minimum R-8.

b. Concealed Space:

1) (Type B1) Provide 2-1/2” Knauf Insulation Board with an installed R-10.9.

3. Duct Systems to be insulated: (2)

Fluid
Exterior of Building
Interior of Building
Insulation Type
Insulation Jacket
Insulation Type
Insulation Jacket (1)
Supply Air System
N/A
N/A
A / B1
Al
Return Air System
N/A
N/A
A / B1
Al

(1) Concealed spaces Aluminum foil jacket

(2) Refer to 3.2 of this section for insulation requirements of specific applications in addition to those requirements listed in the table above.

END OF SECTION

Upgrade The Annex Building HVAC

HVAC Insulation