Specification 34 73 16 Airfield Grounding.pdf
PDF 12 KB Posted
- Solicitation number
- 80GSFC22B0004
About this file
This solicitation is for a firm fixed price construction contract to perform repairs at Wallops Airfield in Virginia. Work includes Portland cement concrete spall repairs, full depth repairs, slab replacements, crack sealing, joint sealing, and asphalt concrete seal coating. The scope of work focuses on routine maintenance recommendations from a 2018 pavement condition report. Repairs are needed for the Runway 28 approach, taxiways supporting Runway 10-28, and an east ramp area.
A site visit is scheduled for August 11, 2022 where attendees will meet for badge access. Questions are due by August 12 and electronic bids are due by August 30, 2022. The bid opening will be that day at 2:00 pm Eastern via Microsoft Teams. The contractor must furnish all equipment, labor, materials, and services to complete the project. This competitive procurement is expected to result in a firm fixed price construction contract awarded under full and open competition.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FCLP Phase 9 - Wallops Flight Facility 1696789
SECTION 34 73 16
AIRFIELD GROUNDING
11/19
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM B8 (2011; R 2017) Standard Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 407 (2022) Standard for Aircraft Fuel Servicing
UNDERWRITERS LABORATORIES (UL)
UL 467 (2013; Reprint Jun 2017) UL Standard for Safety Grounding and Bonding Equipment
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
As-Built Drawings; G
SD-06 Test Reports
Tests
SD-07 Certificates
Grounding Rods
Copper Conductors
Grounding Connectors
1.3 AS-BUILT DRAWINGS
Submit as-built drawngs that provide current factual information, including deviations from and amendments to the drawings and changes in the work, concealed and visible.
SECTION 34 73 16 Page 1
PART 2 PRODUCTS
2.1 METALS
Do not use a combination of materials that forms an electrolytic couple, which accelerates corrosion in the presence of moisture, unless moisture is permanently excluded from the junction of such metals.
2.2 GROUNDING RODS
Use grounding rods, unless otherwise indicated, in accordance with UL 467 and made of copper. Use rods not less than 3/4 in in diameter and not less than 10 ft long. Submit certificates of compliance stating that the grounding rods meet the specified requirements. Provide rods with a closed eye or shepherd's hook bend having an inside diameter of not less than 1-1/2 in.
2.3 COPPER CONDUCTORS
Use copper conductors that bare number 4 AWG copper wire in accordance with ASTM B8. Submit certificates of compliance stating that the copper conductors meet the specified requirements.
2.4 GROUNDING CONNECTORS
Use grounding connectors that comply with UL 467 for the required application. Submit certificates of compliance stating that the grounding connectors meet the specified requirements.
PART 3 EXECUTION
Prior to installing grounding rods, obtain approved digging permits in accordance with Section 01 11 00 SUMMARY OF WORK.
3.1 GROUNDING POINTS
Locate the grounding points to within plus or minus 2 in of location in existing slab.
3.1.1 Pavement Recess
Set the top of the grounding rod at or not more than 1/4 in below the pavement surface grade. Provide a recess 3 in wide, and not more than 6 in long, with a smooth rounded edge in the pavement around the grounding point anchor eye to permit the entrance of lines into the eye and to allow for attachment of the grounding cable. Do not allow the depth of the recess to be deeper than the bottom of the opening of the grounding point eye.
3.1.2 Installation
3.1.2.1 New Rigid Pavement
Install the grounding rod by pushing or driving the rod through the pavement base courses and subgrade prior to concrete placement. Do not allow the installation technique chosen to damage the grounding rod. Keep hand finishing around the rod to a minimum.
SECTION 34 73 16 Page 2
3.2 TESTS
Submit an independent testing agency's certified reports of inspections and tests, including analysis and interpretation of test results. Properly identify each report. Describe test methods and standards used. Measure resistance to ground tests as specified in NFPA 407. Submit test results to the Contracting Officer. Report immediately to the Contracting Officer ground rods that have more than 10,000 ohms of resistance.
-- End of Section --
SECTION 34 73 16 Page 3
File details come from the government source that posted it. Updated .