J-6_PWM HVAC ADENDUM NOTES LIST.pdf

PDF 95 KB Posted

Attached to
Upgraded HVAC and Fire Life Safety Project at the Air Traffic Control Tower (ATCT) in Portland, ME
Solicitation number
697DCK-24-R-00596
Issued by

About this file

This document contains drawing clarifications and notes for an HVAC upgrade project (Project #1302899) at a FAA facility, providing specific technical modifications and requirements across multiple drawing sheets. The notes cover both mechanical and control system modifications.

Key technical requirements include: flushing and refilling chilled/hot water systems before equipment startup, reusing control wire where specifications allow, renaming VAV-3 to VAV-T3, maintaining specific pipe spacing requirements, changing nomenclature from CWR/CWS to CHWR/CHWS throughout drawings, installing a circuit setter in the CHWS bypass while eliminating HWR bypass and CHWR solenoid valve, adding a new DDC gas meter, correcting VFD point labels, verifying boiler control temp sensor location, modifying MERV filter configurations to Analog Input points, relocating the freezestat, updating sensor specifications, and maintaining OA damper at required minimum without economizing. These modifications span multiple drawing sheets (G020, D300-D304, M100-M810) and address various aspects of the HVAC system upgrade.

View the file

Other files

File Type Posted
697DCK-24-R-00596_Amendment 07.pdf PDF
697DCK-24-R-00596_Amendment 06.pdf PDF
J-8_UPDATED QA for PWM HVAC and Fire Alarm_12_16_2024.pdf PDF
J-13_20241213_102801.jpg JPG image
J-14_20241213_102844.jpg JPG image
J-9_20241213_101951.jpg JPG image
J-11_20241213_102043.jpg JPG image
J-17_20241213_103520.jpg JPG image
697DCK-24-R-00596_Amendment 05.pdf PDF
J-18_20241213_104733.jpg JPG image
J-10_20241213_102014.jpg JPG image
J-19_PWM Plot layout with staging area and offices shown.pdf PDF
J-20_Utility Site Plan pwm-d-atct-c110-bl.pdf PDF
J-12_20241213_102514.jpg JPG image
J-16_20241213_103308.jpg JPG image
J-15_20241213_103246.jpg JPG image
J-5_Mobile_Office_PS1.pdf PDF
697DCK-24-R-00596_Amendment 04.pdf PDF
J-8_QA for PWM HVAC and Fire Alarm December 02 2024.pdf PDF
J-7_Restroom Trailer Spec Sheet.pdf PDF
697DCK-24-R-00596_Amendment 03.pdf PDF
PWM PreBid Walkthru 2024-10-29.pdf PDF
697DCK-24-R-00596_Amendment 02.pdf PDF
697DCK-24-R-00596_Amendment 01.pdf PDF
J-1_PWM HVAC FINAL SPECIFICATIONS 9.25.2024.pdf PDF
J-1 FINAL SPECIFICATIONS PWM HVAC 1302899.pdf PDF
J-1aFAA PWM HVAC REHAB FINAL DRAWINGS SIGNED.pdf PDF
J-1b Bid Alternate PWM ATCT FLS Upgrade F101 JLSB Signed.pdf PDF
697DCK-24-R-00596.pdf PDF
J-4_BLANK BID FORM E25_IGCE_ATCT_PWM_PWM-HVAC_1302899_001_638555123691731894.pdf PDF
J-2 Wage Determination.pdf PDF
J-3_Past Performance Questionnaire.pdf PDF
J-4a_ALTERNATE 1 BLANK BID FORM E25_IGCE_ATCT_PWM_PWM-HVAC_1302899_001_638555123691731894.pdf PDF
Show all 33

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1302899 PWM HVAC UPGRADE PROJECT

FAA DRAWING CLARIFICATIONS AND NOTES:

1. G020 - Contractor shall flush out both chilled and hot water systems and refill with appropriate composi on prior to temporary equipment start up.

2. D300-D304 – Contractor to reuse control wire to maximum extent assuming exis ng wire mee ngs specifica on. If not, all wire is to be demolished along with all devices.

3. M100 – Rename VAV-3 located in tower to VAV-T3. Update all system labels accordingly.

4. M400 – Please refer to page M803 for pipe spacing note “DISTANCE NOT TO EXCEED 4 PIPE

DIAMETERS”.

5. M607 – Change all CWR and CWS to CHWR and CHWS throughout drawing package.

6. M607 – Install circuit se er in bypass for CHWS. Eliminate HWR bypass. Eliminate solenoid valve on CHWR.

7. M6XX – Tie in new DDC gas meter in 2” pipe a er exis ng meter before take off. Coordinate with plumber. Detail for clarity on M813.

8. M802 – There should only be on point CHWP-1-VFD-P. The second point with label shall be

CHWP-2-VFD-P.

9. M803 – Verify loca on of Hardwired Boiler Control Temp sensor via manufacturer’s recommenda on.

10. M803 – 20% system flow is not necessary. Maintain differen al pressure, at minimum VFD speed. Bypass shall open to maintain VFD speed.

11. M805 – Change MERV 8 and MERV 15 filters to Analog Input (AI) points.

12. M805 – Freezestat shall be located on downstream face of hea ng coil for AHU-1.

13. M807 – Sensor shall be UNIT DISCHARGE TEMP SENSOR

14. M810 – Add mixed air temperature sensors. Add to sequence note 65.

15. M810 – Do not economize. Keep OA damper at required minimum.