This document appears to be construction drawings related to a federal contract opportunity for the Department of Veterans Affairs to create code compliant research laboratory space in Building 1 at the Saint Louis VA Health Care System. The drawings provide details on the mechanical systems, including air handling units, exhaust fans, ductwork, controls, and piping. Key details include the equipment schedules, duct leakage classifications, control schematics, and points lists for the Engineering Control Center. The contract opportunity, Solicitation Number 36C25524R0053, is for the construction work to renovate and upgrade the research laboratory space in Building 1.
View the file
Other files for this federal contract opportunity
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OVERALL GENERAL NOTES:
INFORMATION CONCERNING THE LOCATION(S) AND SIZES OF EXISTING
EQUIPMENT AND PIPING WAS OBTAINED FROM EXISTING DRAWINGS AND
CURSORY FIELD OBSERVATION, HOWEVER, ACTUAL "ASBUILT" DRAWINGS
WERE NOT AVAILABLE, CERTAIN INFORMATION CONCERNING THE
LOCATION OF THE EXISTING CONDITIONS HAS BEEN ASSUMED IN THIS
DRAWING. THE EXACT LOCATION(S) AND DIRECTION OF FLOW OF ALL
EXISTING EQUIPMENT, ETC., IS UNKNOWN. REASONABLE EFFORT HAS BEEN
MADE TO ACCURATELY DEPICT THE EXISTING CONDITIONS, HOWEVER, ALL
EXISTING WORK MUST BE VERIFIED IN THE FIELD TO DETERMINE THE EXACT
LOCATIONS, DIRECTIONS OF PIPE RUNS, SIZE, ETC.. PRIOR TO STARTING
CONSTRUCTION. ANY CONFLICT BETWEEN THESE PLANS AND ACTUAL FIELD
CONDITIONS SHALL BE REPORTED IMMEDIATELY TO THE ENGINEER FOR
VERIFICATION AND/OR CORRECTION.
PIPING FIELD VERIFY:
MECHANICAL FIELD VERIFY:
INFORMATION CONCERNING THE LOCATION(S) AND SIZES OF EXISTING
DUCTWORK AND DIFFUSERS WAS OBTAINED FROM EXISTING DRAWINGS
AND CURSORY FIELD OBSERVATION, HOWEVER, ACTUAL "ASBUILT"
DRAWINGS WERE NOT AVAILABLE, CERTAIN INFORMATION CONCERNING
THE LOCATION OF THE EXISTING CONDITIONS HAS BEEN ASSUMED IN THIS
DRAWING. THE EXACT LOCATION(S) AND DIRECTION OF FLOW OF ALL
EXISTING EQUIPMENT, ETC., IS UNKNOWN. REASONABLE EFFORT HAS BEEN
MADE TO ACCURATELY DEPICT THE EXISTING CONDITIONS, HOWEVER,
ALL EXISTING WORK MUST BE VERIFIED IN THE FIELD TO DETERMINE THE
EXACT LOCATIONS, DIRECTIONS OF DUCT RUNS, SIZE, ETC.. PRIOR TO
STARTING CONSTRUCTION. ANY CONFLICT BETWEEN THESE PLANS AND
ACTUAL FIELD CONDITIONS SHALL BE REPORTED IMMEDIATELY TO THE
ENGINEER FOR VERIFICATION AND/OR CORRECTION.
MECHANICAL GENERAL NOTES:
A. FOR GENERAL DUCT CONSTRUCTION AND PIPING CONNECTIONS SEE
DETAILS ON MECHANICAL DETAILS SHEET.
B. ALL WORK SHALL BE IN ACCORDANCE WITH THE BEST QUALITY
STANDARDS OF THE TRADE, AND SHALL CONFORM WITH ALL FEDERAL,
STATE, AND LOCAL CODES AND STANDARDS.
C. CONSTRUCTION DOCUMENTS SHALL BE FOLLOWED AS CLOSELY AS
POSSIBLE, HOWEVER, SYSTEMS HAVE BEEN SHOWN DIAGRAMMATICALLY
AND IN SOME CASES, ENLARGED FOR CLARITY. ANY OFFSETS,
ADDITIONAL FITTINGS, AND/OR APPURTENANCES REQUIRED TO PROVIDE
A COMPLETE AND COORDINATED SYSTEM SHALL BE BORNE BY THE
CONTRACTOR.
D. BALANCE DAMPERS SHALL BE LOCATED AT BRANCH CONNECTION TO THE
MAIN.
E. ALL EQUIPMENT INCLUDING BUT NOT LIMITED TO DUCTWORK, PIPING,
UNIT HEATERS, ETC. SHALL BE HUNG FROM THE TOP CHORD OF THE
STRUCTURAL STEEL OR BY HANGERS CONNECTED TO CONCRETE SLAB
ABOVE AS REQUIRED.
F. EACH MAIN DUCT PASSING THROUGH FLOOR SPACES SHALL BE FIRE
DAMPERED WITH ACCESS DOOR.
G. ALL EXTERIOR PENETRATIONS SHALL BE WEATHER AND WATER TIGHT.
H. CONTRACTORS ARE TO REVIEW EXISTING STRUCTURAL AND PLANS, WITH
ACTUAL LAYOUT OF BEAMS, JOISTS, ETC. TO AVOID CONFLICT BETWEEN
DUCT. ADJUST DUCT ROUTING TO ACCEPT STRUCTURAL CONDITIONS.
I. ALL EXHAUST DISCHARGES AND GAS FLUES WHERE INDICATED SHALL BE
LOCATED A MINIMUM OF 25'-0" AWAY FROM OUTSIDE AND COMBUSTION
AIR INTAKES UNLESS LOCAL AND STATE CODES MANDATE ADDITIONAL
DISTANCE.
J. CONTRACTOR SHALL VERIFY ELECTRICAL CHARACTERISTICS OF ALL
MECHANICAL EQUIPMENT WITH THE ELECTRICAL CONTRACTOR PRIOR TO
PLACING EQUIPMENT ON ORDER.
K. CONTRACTOR SHALL PROVIDE AN INFECTION CONTROL RISK ASSESSMENT
BARRIER AROUND THE PROJECT AREA CONSISTENT WITH THE
CONTRACTOR'S PHASING PLAN AS APPROVED BY THE VHA AND VA COR.
1. ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE
CONCEALED IN FURRED CHASE OR SUSPENDED CEILING.
2. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN
OR INDICATED. DUCT SIZES ARE NET INSIDE DIMENSIONS.
3. ACCESS PANELS IN SUSPENDED CEILINGS ARE REQUIRED FOR ALL VALVES,
TRAPS, DAMPERS, CLEANOUTS, CONTROLS, ETC., AND SHALL BE FURNISHED
AND INSTALLED UNDER ARCHITECTURAL SPECIFICATIONS UNLESS NOTED
OTHERWISE.
4. TOTAL STATIC PRESSURE NOTED IN SCHEDULES INCLUDES DUCT SYSTEM,
TERMINAL UNITS, FILTERS, COILS, ETC.
5. FOR TYPICAL STEAM, WATER & PIPING CONNECTIONS TO EQUIPMENT SEE
STANDARD DETAILS.
6. CEILING DIFFUSER SIZES SHOWN ON FLOOR PLANS ARE NECK SIZES.
7. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE
MADE SO THERE WILL BE COUNTER FLOW BETWEEN WATER AND AIR.
8. ALL PRESSURES LISTED ARE GAGE PRESSURE UNLESS NOTED OTHERWISE.
9. ALL NEW CONTROLS SHALL BE COMPATIBLE WITH AND CONNECT INTO THE
EXISTING JOHNSON CONTROLS HEAD END.
10. PROVIDE ACOUSTICAL SEALANT PER SPECIFICATION SECTION 07 92 00 AT
ALL DUCT AND PIPE PENETRATIONS THROUGH SOUND RATED PARTITIONS.
EXIST..
ELEC.
EF
EP
ECC
DWG
DPT
DN
Db
DCP
CR
dB
CW
CP
CONN
COND
CHWR
CHWS
CFM
CC
BLDG
AHU
AFMS
ABV
AC
EXISTING
ELECTRICAL
EXHAUST FAN
ELECTRICAL/PNEUMATIC
ENGINEERING CONTROL CENTER
DRAWINGS
DIFFERENTIAL PRESSURE TRANSMITTER
DOWN
DECIBELS
DRY BULB TEMPERATURE, (DEGREES)
DISTRIBUTED CONTROL PANEL
CONDENSATE RETURN
COLD WATER
CONDENSATE PUMP
CONNECT
CONDENSATE
CHILLED WATER RETURN (PIPING)
CHILLED WATER SUPPLY (PIPING)
CUBIC FEET PER MINUTE
COOLING COIL
BUILDING
AIR HANDLING UNIT
AIR FLOW MEASURING STATION
ABOVE
AIR CONDITIONING UNIT
WFMD
WF
WC
Wb
VAV
VTR
VSMC
TYP
TEMP
T'STAT
SYS
SQ/FT
SPT
SPS
SPEC.
SP
SHT
RV
RM
RET
REQ'D
PRV
PSI
PL
PHC
PD
O.C.
N.O.
NO
O.L.
NC
WATER FLOW MEASURING DEVICE
WATER FILTER
WATER COLUMN
WET BULB
VARIABLE AIR VOLUME
VENT THROUGH ROOF
VARIABLE SPEED MOTOR CONTROLLER
TYPICAL
TEMPERATURE
THERMOSTAT
SYSTEM
SQUARE FEET
STATIC PRESSURE SENSOR
SPECIFICATION
STATIC PRESSURE (INCHES OF WATER)
STATIC PRESSURE TRANSMITTER
SHEET
RELIEF VENT
ROOM
RETURN
REQUIRED
PRESSURE REDUCING VALVE
POUNDS PER SQUARE INCH
PLACES
PREHEAT COIL
OVER LOAD
ON CENTERS
NORMALLY OPEN
PRESSURE DROP (FEETWATER)
NUMBER
NOISE CRITERIA
MT'D
MFG
MIN.
MECH
MAX.
MVD
LBS/HOUR
LTCP
LPS
LPR
KWH
IN
HWP
MOUNTED
KW
MANUFACTURER
MINIMUM
MECHANICAL
MAXIMUM
MANUAL VOLUME DAMPER
POUNDS PER HOUR
LOCAL TEMPERATURE CONTROL PANEL
LOW PRESSURE STEAM SUPPLY
LOW PRESSURE STEAM RETURN
KILOWATT HOUR
KILOWATT
INCHES
HOT WATER PUMP
HAND-OFF-AUTOHOA
O.A./OSA
SF
E
RAG
CD
R
S
HWR
HWS
HPR
HPS
HP
HORIZ.
HC
G.P.M.
FEET PER MINUTE
FLANGED (SEE DWG'S)
FLEXIBLE CONNECTOR
FD FLOOR DRAIN
FPM
FLNG'D
FLEX. CONN.
FLEX
FLR.
FF
EXH
FLEXIBLE
FLOOR
FINAL FILTER
EXHAUST AIR
GA.
F&T
FT
OUTDOOR AIR
SUPPLY FAN
EXHAUST CFM
RETURN AIR GRILLE
CEILING DIFFUSER
RETURN CFM
SUPPLY CFM
HEATING WATER RETURN
HEATING WATER SUPPLY
HIGH PRESSURE RETURN
HIGH PRESSURE STEAM
HORSEPOWER
HORIZONTAL
HEATING COIL
GALLONS PER MINUTE
GAGE
FLOAT AND THERMOSTATIC
FEET
VALVES
BALL VALVE
P/T TEST PLUG (PRESSURE/TEMPERATURE)
MANUAL AIR VENT
PRESSURE REDUCING VALVE
SAFETY OR PRESSURE RELIEF VALVE
THREE-WAY MODULATING CONTROL VALVE
STRAIGHT-THRU TWO POSITION CONTROL VALVE
STRAIGHT-THRU MODULATING CONTROL VALVE
CIRCUIT SETTER
BALANCING VALVE
BUTTERFLY-VALVE
CHECK VALVE
GATE VALVE WITH 3/4" HOSE ADAPTER
GLOBE VALVE
ANGLE GLOBE VALVE
GATE VALVE
ABBREVIATION LEGEND
ECCENTRIC REDUCER
CONCENTRIC REDUCER
UNION
FINISHED FLOORFIN.
NEGATIVE PRESSURE RELIEF VENTNPR
FIRE SMOKE DAMPERFSD
NORMALLY CLOSEDN.C.
RTU ROOF TOP UNIT
SS STAINLESS STEEL
CEILING SUPPLY DIFFUSER W/ CFM INDICATED (FOUR WAY THROW)
LD LINEAR DIFFUSER
WITH CFM INDICATED
V.D.
MANUAL VOLUME DAMPER
LOUVER
SPIN-N-TAP WITH MVD DAMPER
DOUBLE WALL SOUND
12X10
6"0 M.V.D.
RECTANGULAR DUCT (WXH)
RND DUCT TAKE OFF WITH SPIN-IN EXTRACTOR
MANUAL VOLUME DAMPER
FLEXIBLE DUCT (MAXIMUM 5'-0" IN LENGTH)
MOTORIZED DAMPER (OPPOSED BLADE) W/INTERLOCK
100S
MOTORIZED DAMPER (PARALLEL BLADE) W/INTERLOCK
NEGATIVE PRESSURE RELIEF VENT
NPR
100S
10 X 8 NEW DUCT-WIDTH X DEPTH
ATTENUATING DUCT
FC
D
R
FLEXIBLE CONNECTION
INCLINED DROP, IN DIRECTION OF AIR FLOW
INCLINED RISE, IN DIRECTION OF AIR FLOW
STANDARD RADIUS ELBOW
VANED ELBOW (SHORT RADIUS)
ELBOWS WITH VANES EVEN IF SYMBOL IS MISSING)
VANED ELBOW (PROVIDE ALL SQUARE OR RECTANGULAR
DUCTWORK ELBOW UNLESS NOTED OTHERWISE.
THICKNESS VANES. VANES REQUIRED IN ALL
SQUARE TYPE ELBOW WITH DOUBLE
7:1 RATIO FOR HIGH PRESSURE.
TRANSITION. 4:1 RATIO FOR LOW PRESSURE,
ELBOW TURNED DOWN WITH TURNING VANES
ELBOW TURNED UP WITH TURNING VANES
R
DN.
DIRECTION OF AIR FLOW
INCLINED RISE IN RESPECT TO
DIRECTION OF AIR FLOW
INCLINED DROP IN RESPECT TO
DUCTWORK LEGEND
CEILING DIFFUSER
6"
EXHAUST CEILING REGISTER OR GRILLE
EXHAUST OR RETURN TOP REGISTER OR GRILLE (WALL TYPE)
SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)
VANE TURN ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF
FLEXIBLE DUCT
F.S.D. FIRE/SMOKE DAMPER
F.S.D.
F.D.
F.D. FIRE DAMPER
FLAT OVAL DUCT DOWN
FLAT OVAL DUCT UP
UP
UP RETURN AIR DUCT
EXHAUST AIR DUCT
DOWN
OUTSIDE AIR DUCT
SUPPLY AIR DUCT
DOWN
ROOM CONTROL: THERMOSTAT, HUMIDISTATT H
T REMOTE BULB THERMOSTAT
DUCT OR PIPE THERMOSTAT (NOTE: PROVIDE 12" MINT
LENGTH IN DUCT WHEN SPACE PERMITS)
DUCT OR PIPE TEMP. SENSOR SEE NOTE ABOVE.T
H
DUCT STATIC PRESSURE SENSOR
DUCT HUMIDITY SENSOR
SP
F SMOKE DETECTOR (SEE ELECTRICAL DWGS)
SD
C HOLDING COIL IN MOTOR STARTER
CONTACT, NORMALLY OPEN (N.O.)
CONTACT, NORMALLY CLOSED (N.C.)
SWITCH
SIGNAL FROM ECC OR DCP
SIGNAL TO ECC OR DCP
SIGNAL TO FIRE ALARM SYSTEM
PRESSURE TRANSMITTERP
HIGH PRESSURE STEAM (60 PSIG & ABOVE)
HIGH PRESSURE STEAM CONDENSATE RETURN
MEDIUM PRESSURE STEAM (16 PSIG THRU 59 PSIG)
MEDIUM PRESSURE STEAM CONDENSATE RETURN
LOW PRESSURE STEAM (15 PSIG & BELOW)
LOW PRESSURE STEAM CONDENSATE RETURN
CONDENSATE PUMP DISCHARGE
HOT WATER HEATING SUPPLY
HOT WATER HEATING SUPPLY
VENT LINE
HWH
HWHR
V V
PIPING SYMBOLS
CONTROLS
ANCHORX
CHR
CH
CHILLED WATER RETURN
CHILLED WATER SUPPLY
GENERAL
EX. PIPE TO BE REMOVED
WATER FLOW MEASURING DEVICE
THERMOMETER
STRAINER
THERMOSTATIC TRAP
FLOAT & THERMOSTATIC TRAP SET INCLUDING PIPING
ACCESSORIES (SEE STD. DETAIL)
ACCESSORIES (SEE STD. DETAIL)
INVERTED BUCKET TRAP SET INCLUDING PIPING
NEW AND EXISTING WORK ON REVISED SHEETS
POINT OF CONNECTION BETWEEN NEW
UNION
RISE OR DROP IN PIPE
SIDE CONNECTION
BOTTOM CONNECTION, 45° OR 90°
TOP CONNECTION, 45° OR 90°
ECCENTRIC REDUCER
REDUCER OR INCREASER
ANCHOR (ALSO SEE "D" DWGS)
DIRECTION OF FLOW
DIRECTION OF PIPE PITCH (DOWN)
OR
POINT OF WHERE DEMOLITION STOPS AND
EXISTING IS TO REMAIN ON DEMO SHEETS
OR
1-XX-000
1-XX-000
A
E.T.R.
E.T.R.
DETAIL NUMBER
DRAWING NUMBER WHERE SHOWN
SECTION LETTER
DRAWING NUMBER WHERE DRAWN
CROSS HATCHED AREAS ARE NOT
IN CONTRACT AND ARE EXISTING
TO REMAIN, UNLESS
SPECIFICALLY NOTED OR SHOWN
OTHERWISE.
THIS SYMBOL SHOWS THE APPROXIMATE
POINT
WHERE NEW WORK STARTS AND EXISTING IS
TO REMAIN.
FOR DEMOLITION THIS SYMBOL SHOW THE
APPROXIMATE POINT WHERE DEMOLITION
STOPS AND EXISTING IS TO REMAIN FOR
REVISED WORK.
EXISTING TO REMAIN
DRAWING SYMBOLS
DIFFERENTIAL PRESSURE SENSORDP
PE−2021014461P
R
O F
E S S I O N A L E N G
I N E
E R
HANNAH
ROSE
KIGER
S T
A
T E
OF MI SSO
U
R I
DESIGN-AIRE ENGINEERING, INC.
www.daengineering.comwww.daengineering.com voice (317) 464-9090
2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - Create Code Compliant Research Laboratory Space in Building 1
657-23-113JB
Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM
08-6231 1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
01-18-2024
100% CONSTRUCTION DOCUMENTS
100% SPRINKLERED
DEH RE
1-MG-001
ABBREVIATIONS, LEGENDS, & NOTES
- MECHANICAL
ADAPTOR
MINUMUM SIZE 1-1/4". ABOVE
1-1/4" FULL SIZE ON UNIT
CONNECTION.
AIR HANDLING UNIT OR AIR CONDITIONING UNIT
COOLING COIL
DRAIN PAIN
SECTION
DRAIN PLUG
01-MG-002
A3 CONDENSATE DRAIN DETAIL
NO SCALE
NOTE: REFER TO
FLOOR PLANS FOR
DIFFUSER OR
GRILLE NECK SIZE
INSULATED
SHEET METAL
DUCT
THERMAL BLANKET
INSULATION
DIFFUSER OR GRILLE
01-MG-002
B9 DIFFUSER INSTALLATION DETAIL
NO SCALE
LAY-IN CEILING T-BAR
LAY-IN CEILING PAD
W x D
EQUAL SPLIT
W x D
UNEQUAL SPLIT
FLOW
AIR
X x
D
45°
X
A x
B
FLOW
AIR
W x
D
45°
X x
D
45°
Y
FLOW
AIR
45° 5 W x
D
FLOW
AIR
DOUBLE THICKNESS TURNING
VANES (TYP)
BRANCH DUCT BRANCH DUCT
MAIN DUCT
DOUBLE THICKNESS TURNING
VANES (TYP)
BRANCH DUCT
BRANCH DUCT
MAIN DUCT
01-MG-002
B1 DUCT DETAIL
NO SCALE
1-1/4"x1-1/4"x3/6"
ANGLE IRON SUPPORTS
NUTS AND WASHERS BOTH SIDES
OF ANGLE (TYP)
STRUCTURAL JOIST
1/2" BOLT AND BUT
WITH 2-1/2" WASHER
1/2" THREADED ROD (TYP)
01-MG-002
A1 DUCT HANGER DETAIL
NO SCALE
CONCRETE FLOOR
OR ROOF DECK
WEDGE ANCHOR
L 2x2x1/4 BRACE
BLOWER COIL UNIT
L 3 x 3 x 1/8 ATU SUPPORTS
NUTS & LOCKWASHERS (TYP)
3/8" THREADED
ROD, TYPICAL
UNIT
TYPICAL
BUILDING MEMBER
END VIEWSIDE VIEW
AUXILLIARY STEEL MEMBER FOR EQUIPMENT SUPPORT (ROOF)
01-MG-002
D1 HORIZONTAL BLOWER COIL UNIT MOUNTING DETAIL
NO SCALE
FLEXIBLE CONNECTOR;
TYPICAL
UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL
APPLY.
PLAN OR SIDE VIEW WITHOUT EQUIPMENT
20° MAX.
PLAN OR SIDE VIEW WITH EQUIPMENT
EQUIPMENT
30° MAX.
15° MAX.
NOTE:
20° MAX.
30° MAX.
AIR FLOW AIR FLOW
15° MAX.
01-MG-002
B7 TYPICAL DUCTWORK TRANSITIONS
NO SCALE
AIR
FLOW
12" FOR ALL BRANCH DUCTS LARGER THAN 12".
*-EQUALS WIDTH OF BRANCH DUCT UP TO 12".
*45°
MAIN L.P. AIR DUCT
L.P. BRANCH DUCT
HAND VOLUME DAMPER
01-MG-002
A7 TYPICAL LOW PRESSURE BRANCH
NO SCALE
HANDLE WITH
STIFFEN BLADE
SIDE ELEVATION
DUCT
DAMPER BLADEINSULATION
INSIDE END
BEARING
HANDLE WITH WITH
LOCKING QUADRANT
INSULATION STAND-
OFF
1/2" (15 MM)
ROUND ROD PIN
SECTION
DAMPER BLADE
1/8" (6 MM) CLEARANCE
ALL AROUND
OUTSIDE END BEARING
DUCT
INSULATION - IF APPLICABLE
LOCKING QUADRANT
AS REQUIRED
01-MG-002
A5 VOLUME DAMPER DETAIL
NO SCALE
1. DETAIL APPLIES TO ALL ELBOWS UNLESS NOTED OTHERWISE. ONLY
RADIUS ELBOWS ARE ALLOWED FOR KITCHEN EXHAUST HOOD DUCTS.
2. BRANCH DUCT TAKE-OFFS MUST BE A MINIMUM OF 4D DOWNSTREAM
OF EITHER TYPE OF ELBOW, AND NOT LESS THAN 3D UPSTREAM.
3. ALL SQUARE ELBOWS WITH D = 36" OR LESS SHELL HAVE SINGLE
THICKNESS TURNING VANES WITH 2" RADIUS AND 1-1/2" SPACING.
4. ALL SQUARE ELBOWS WITH D OVER 36" SHALL HAVE DOUBLE
THICKNESS TURNING VANES WITH 4-1/2" RADIUS AND 3-1/4" SPACING.
NOTES:
SQUARE ELBOW TURNING VANES
WFLOW
SEE NOTE 2
BRANCH DUCT.
SEE TAKE-OFF DETAIL
1.5 x W
RADIUS ELBOW
W
WxD
WxD
W x D
SINGLE THICKNESS VANES DOUBLE THICKNESS VANES
SPACING SPACING
RR
AIR
FLOW
01-MG-002
B3 DUCT ELBOW
NO SCALE
W2 X D
W2 X D VANES DO NOT HAVE "TRAILING EDGES,"
BUT SHALL BE MOVED IN THE VANE
RUNNER TO REMAIN TANGENT TO THE
AIRSTREAM.
PROPER INSTALLATION OF TURNING VANES:
1. ALL VANED ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS
DETAILS BY SMACNA.
2. WHEN W1 DOES NOT EQUAL W2 VANE SHALL BE SINGLE VANE
TYPE REGARDLESS OF D DIMENSION.
3. ALL SINGLE VANES SHALL HAVE A 2" RADIUS, 1-1/2" MAXIMUM
SPACE BETWEEN VANES AND A 3/4" TRAILING EDGE.
4. CONSTRUCT VAN EDGES TO PROJECT TANGENTS PARALLEL TO
DUCT SIDES. STANDARD VANES USED FOR NON-REDUCING ELBOWS
ARE NOT ACCEPTABLE WITHOUT MODIFICATION.
NOTES:
01-MG-002
B5 CONVERGING OR DIVERGING RECTANGULAR ELBOWS
NO SCALE
01-MG-002
D7 ROUND DUCT ON ROOF SUPPORT
NO SCALE
ROOFING
(BY G.C.)
BASE PLATE
ROOF RAIL SUPPORT CURB-SEE SPEC
WOOD NAILER
COUNTER FLASHING
ANCHOR
STRAP
M
IN
BUILT-UP ROOFING
PLYWOOD
PROVIDE JACKETING CONTINUOUSLY AROUND DUCT SIDES AND BOTTOM.
HIGH COMPRESSIVE STRENGTH RIGID INSULATION AT EACH ROOF CURB
SUPPORT PER SPECIFICATIONS. DUCT JACKETING SHALL BE CONTINUOUS
AROUND DUCT. PROVIDE METAL SADDLE AT DUCT WHERE SUPPORTED BY CURB.
STRAP DUCT AND ATTACH TO CURB WITH CADIUM PLATED SCREWS.
KEYED NOTES:
NOTES:
1. UNLESS OTHERWISE NOTED, ALL ITEMS FURNISHED AND INSTALLED BY THE M.C.
2. LENGTH OF RAIL: MINIMUM TO COVER 2 JOISTS AND/OR 12" WIDER THAN DUCT.
3. REFER TO DETAILS FOR ADDITIONAL INFORMATION.
4. ALL WOOD SHALL BE TREATED.
01-MG-002
A9 LOW PRESSURE EXTERIOR DUCT RISER SUPPORT
NO SCALE
B U
IL
D
IN
G
W A L L
4"x4" PLATE
(TYP.)
WELD
(TYP.)
WELD (TYP.)
MASONARY ANCHORS
(TYP.)
BOLT
CONNECTIONS
1-1/2"x1-1/2"x1/8"
ANGLE IRON (TYP.)
DUCT DUCT
10"
01-MG-002
D9 CURB DETAIL - ROOF RAIL CONCRETE DECK
NO SCALE
24" MIN.
NOTES:
1. UNLESS OTHERWISE NOTED, ALL ITEMS FURNISHED AND INSTALLED
BYTHE M.C. SEE SPEC 15010.
2. LEVEL TOP OF CURB(S) TO WITHIN TOLERANCES ALLOWED BY
MANUFACTURER OF SUPPORTED EQUIPMENT.
3. CONCRETE ANCHOR MINIMUM 2 PER SIDE. MAXIMUM 12" ON CENTERS.
EXISTING PLYWOOD DECK
SEE DUCT AND PIPING SUPPORT
FLASHING DETAIL FOR ROOFING DETAILS.
BASE PLATE
BASE SECTION
TREATED WOOD NAILER
COUNTER FLASHING
LEAD WASHER
LAG BOLT
DUCT ATTACHMENTCOAT BASE OF DUCT
ATTACHMENT AND LAG
BOLT WITH BITUMASTIC
ROOFING
(BY G.C.)
ANCHOR-REFER TO DETAILS
01-MG-002
F1 TYPICAL ACCESS SECTION FOR ROUND/OVAL DUCT
NO SCALE
COVER WITH HANDLE AND
CHAIN RETAINER GASKETED
AND PRESSURE SEALED.
HOUSING WELDED
TO DUCT SECTION
ROUND OR FLAT
OVAL DUCT SECTION
NOTE:
NEGATIVE PRESSURE
RELIEF VENT IS SIMILAR
1 2 3
BLOCKING BY MC
EXISTING PLYWOOD WITH BITUMINOUS ROOFING
BITUMINOUS FLASHING
SUPPORT CURB
WITH BASE
CAP
EXISTING BITUMINOUS ROOFING
NOTES:
PATE CURB PROVIDED BY MECHANICAL. ROOFING CONTRACTOR SHALL PROVIDE FLASHING. (3)
LAYERS BITUMINOUS FLASHING FROM UNDER CAP COUNTER FLASHING TO 12" BEYOND CANT WITH 6" OVERLAYS. PROVIDE ALUMINUM COATING TO MATCH EXISTING ROOF. DTL 2/THIS DRAWING.
SEE DETAILS FOR SECURING TO WOOD ROOF.
DUE TO MODULATING ROOF - PROVIDE BITUMINOUS UNDERLAY(S) FOR EVEN SUPPORT WITH
SUPPORT FLASHING.
DUCT/PIPE ATTACHMENT BY MC IS NOT SHOWN.
1.7150 0.8572 0.8572
01-MG-002
D4 DUCT AND PIPING SUPPORT FLASHING
NO SCALE
PE−2021014461P
R
O F
E S S I O N A L E N G
I N E
E R
HANNAH
ROSE
KIGER
S T
A
T E
OF MI SSO
U
R I
DESIGN-AIRE ENGINEERING, INC.
www.daengineering.comwww.daengineering.com voice (317) 464-9090
2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - Create Code Compliant Research Laboratory Space in Building 1
657-23-113JB
Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM
08-6231 1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
01-18-2024
100% CONSTRUCTION DOCUMENTS
100% SPRINKLERED
DEH RE
1-MG-002
DETAILS - MECHANICAL
HANGER ROD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
PROVIDE HIGH COM-
PRESSIVE STRENGTH
INSULATION INSERT
BLOCKS UNDER
INSULATION SHIELD
INSULATION SHIELD
AT HANGER
INSULATION
WELD
SADDLE
BAND
PROVIDE INSULATION
SHIELD & INSERT FOR
ALL PIPING (8" MIN.)
1-5/8" 12 GAGE
CHANNEL OR
2"x2"x1/4" ANGLE
ADJUSTABLE ROLLER HANGER
TYPE 43 IN SPECIFICATIONS
TRAPEZE HANGER FOR UP
TO 1000LB. UNIFORM LOAD
ADJUSTABLE CLEVIS HANGER
TYPE 1 IN SPECIFICATIONS
SIDE VIEW
MAXIMUM PIPE/TUBING SUPPORT SPACING, FEET
NOM. SIZE
PIPE
TUBING
THRU 3/4"
7 FT
5 FT 6
1-1/4
1-1/2
2-1/2
30 32
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
1" MAX.
1/2" DIA. HANGER
RODS
WITH 36" MAX. SPACING
ON EACH CHANNEL
01-MG-003
B1 TYPICAL PIPE HANGERS
NO SCALE
ELEVATION
2.
1.
CIRCULATING
WATER PIPING
REDUCER
1/2" (15 MM) x 4"
(100 MM) NIPPLE
1/2" (15 MM)
GATE VALVE
1/4" (8 MM)
COPPER TUBING
NOTES:
IF AUTOMATIC AIR VENTS ARE USED,
PIPE DISCHARGE TO DRAIN
VENT ALL HIGH POINTS INDICATED ABOVE.
01-MG-003
A1 TYPICAL AIR VENT
NO SCALE
DRAIN ALL LOW POINTS AS INDICATED ABOVE.
WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS
AND/OR PLANS LOCATE DRAIN AT BOTTOM OF SCALE POCKET.
WELDED PIPING
ELEVATION
THREADED PIPING
ELEVATION
NOTES:
ADAPTER TO 20 MM (3/4") HOSE
THREAD. PROVIDE HOSE CAP
NUT.
3/4" (20 MM) GATE VALVE
REDUCER, IF REQUIRED
TYPICAL WATER PIPING
2.
1.
01-MG-003
A2
TYPICAL CHILLED AND HOT
WATER DRAIN VALVE CONNECTIONS
NO SCALE
PROVIDE DOUBLE LOCK NUT ON THREADED ROD TO CARRY PIPE HANGERS. WHERE THREADED ROD SCREWS
INTO UPPER ATTACHMENT, PROVIDE LOCK NUT.
RETAINING CLIP REQUIRED IN SEISMIC RESTRAINED AREAS.
HANGERS THAT ARE PART OF A SEISMIC RESTRAINT SHALL BE INSTALLED IN CONTACT WITH THE PIPE; THE
INSULATION SHALL BE CARRIED OVER THE HANGER AND SEALED.
CLEVIS TYPE
HANGER
PIPE WITH INSULATION;
SUPPLEMENTAL INSULATION
SUPPORTS/INSERTS BETWEEN
PIPE AND HANGER/SHIELD
ARE REQUIRED ON PIPING
2-1/2" AND LARGER
PIPE INSULATION
SHIELD
ANGLE OR
CHANNEL
"U" BOLT OR
PIPE CLAMP
PIPE WITH INSULATION; SUPPLEMENTAL INSULATION
SUPPORTS/INSERTS BETWEEN PIPE AND
HANGER/SHIELD
ARE REQUIRED ON PIPING 2-1/2" AND LARGER
PIPE INSULATION SHIELD
TRAPEZE
HANGER
ROD
1 1 2 1
1 1
NO SCALE
CLEVIS TYPE HANGER PIPE SUPPORT
NO SCALE
TRAPEZE HANGER PIPE SUPPORT
NOTE:
01-MG-003
B4 CLEVIS AND TRAPEZE HANGER PIPE SUPPORT
NO SCALE
FLOW CONTROL VALVE (SEE SPECS) FOR PIPE SIZES
2-1/2" AND SMALLER. FOR PIPE SIZES 3" AND OVER,
SEE NOTE 2.
PIPE COILS FOR COUNTER FLOW. SEE MANUFACTURER
RECOMMENDATIONS FOR LOCATION OF SUPPLY AND
RETURN PIPING CONNECTIONS.
NOTES:
TEST PLUG
MANUAL AIR
VENT (TYP.)
CONTROL VALVE
BALL
VALVE
SUPPLY
ARRANGE PIPING TO ALLOW FOR
COIL REMOVAL WITHOUT
DISTURBING RISERS AND LOCATE
RISERS WHERE THEY WILL NOT
INTERFERE WITH OTHER
COMPONENTS OF THE AIR
HANDLING SYSTEM.
RETURN
CONTROL
VALVE
PIPE
HANGERS
TWO-WAY CONTROL
01-MG-003
B7
PIPING SCHEMATIC AT HOT AND
CHILLED WATER COIL - 2 WAY VALVE
NO SCALE
1/4" THICK
STEEL
PLATE (2 HALVES)
INSULATION
PIPE
ESCUTCHEON
PLATE
FLOOR OF AC
UNIT
SEAL/CAULK
CONTINUOUS
WELD
1. PRIME AND PAINT THE EXPOSED PORTION OF THE
ESCUTCHEON PLATE AS DESCRIBED IN SECTION
09 91 00 PAINTING. COLOR TO MATCH AS
CLOSE AS POSSIBLE TO AC UNITS.
NOTES:
PRIME AND
PAINT
PRIME AND
PAINT
01-MG-003
D4 ESCUTCHEON PLATE DETAIL
NO SCALE
01-MG-003
D2 FLEXIBLE DUCT CONNECTIONS
NO SCALE
ROUND FLEXIBLE CONNECTION
RECTANGULAR FLEXIBLE CONNECTION
FLEXIBLE MATERIAL
AS SPECIFIED
WASHER
FLANGED
CONNECTION
ON FAN SIDE
MAX. INSTALLED. 6" [150mm]
NOMINAL WITH MATERIAL TAUT 1
1/2" [40mm] MIN. TO 3" [75mm]
[40mm]
1 1/2"
[15mm]
1/2"
[15mm]
1/2"
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
DUCT
1 1/2" [40mm]
POCKET SLIP
ALTERNATE
POSITION
OF BOLT
1" [25mm] FLANGE & HEM
BOLT ON 4" [100mm] CENTERS
1"x1/8" [25x3mm] BAND IRON
SHEET METAL
AS SPECIFIED
FOR DUCTWORK.
RIVET ON 4"
[100mm] CENTERS
SHEET METAL SCREWS ON
12" [300mm] CENTERS
DUCT
5/16" [8mm] FLANGE
BOLT ON 4" [100mm] CENTERS
1"x1/8" [25x3mm] BAND IRON
1"x1/8" [25x3mm] DRAW BAND
FLEXIBLE
MATERIAL AS
SPECIFIED
1-1/2" [40mm] MIN. TO 3" [75mm] MAX. INSTALLED. 6" [150mm] NOMINAL
WITH MATERIAL TAUT
WASHER
FLANGED CONNECTION
ON FAN SIDE
01-MG-003
D1 FIRE DAMPER INSTALLATION SECTION
NO SCALE
NOTE:
1.
2.
3.
4.
5.
6.
A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION, 1S
SIMILAR. FOLLOW DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING
FASTENER OPTIONS AND GAGES FOR SLEEVE AND PERIMETERANGLES. FIRE
DAMPERS MUST BE INSTALLED IN THE PARTITION OR FLOOR AND NOT OUTSIDE
THE PENETRATION.
GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE
TO DAMPER FRAME AND TO PERIMETER ANGLES.
PERIMETER ANGELS: GALVANIZED STEEL, NOT LESS THAN 1 1/2"x1 1/2" [40x40mm], 14 GAGE, TO PROVIDE 1" [25mm] MINIMUM OVERLAP OF
OPENING ON ALL 4 SIDES.
BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES SHOWN IN
SMACNA. ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE
FUSIBLE LINK OR LINKS.
PROVIDE 1/4" TO 1/2" [6 TO 15mm] CLEARANCE ON HEIGHT AND WIDTH.
FILL OPEN SPACE WITH ROCK WOOL FIRESTOP FIBER.
ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC
FLOORS AND MECHANICAL ROOM FLOORS, SHALL BE PROVIDED WITH 3"
[75mm] HIGH CONCRETE CURB AROUND OPENING FOR DUCT.
SLEEVE, NOTE 2
DUCT
CONNECTION
NOTE 4
DAMPER,
NOTE 1
DAMPER COLLAR
EXTENSION INTEGRAL
PART OF SLEEVE
SLEEVE, NOTE 2
NOTE 6
FIRE BARRIER
PARTITION OR CHASE
TYPICAL DUCT
INSULATION
PERIMETER ANGLE, NOTE 3
(NOTE FASTENED TO PARTITION)
ACCESS
PANEL
NOTE 5
[25mm]
9" MAX
OPENING
CUT EDGE OF EXIST. SLABHAND PACK W/ 5000
PSI NON-SHRINK GROUT
PLACE TEMPORARY SHORE
TO BE REMOVED AFTER
GROUT HAS HARDENED
01-MG-003
A4 PATCH EXISTING OPENING < 9" WIDE
NO SCALE
PLACE TEMPORARY FORM TO
UNDERSIDE OF SLAB - MATCH
EXIST. THICKNESS W/ 3000PSI
CONCRETE
#4 EA. WAY @ 12" O.C. DRILL & EPOXY
INTO EXIST. W/ 12" MIN EMBED.
LAP PER GENERAL NOTES ON 1-MG-001.
NOTE: FOR RECTANGULAR
OPENINGS 9"-36" WIDE
01-MG-003
A6 TYPICAL SLAB RECTANGULAR OPENING PATCH
NO SCALE
DUCT PER MECH. DWG.
DUCT ATTACHMENT
PER MECH. DWG.
EXIST. WOOD ROOF JOISTS
EXIST. SHEATHING
(2) #10x4" LONG
SCREWS AT EA.
JOIST 1 EA. SIDE
OF PATE CURB
PATE CURB
01-MG-003
A9
TYP. ROOF DUCT SUPPORT
PERPENDICULAR TO FRAMING
NO SCALE
B7
1-MG-003
10'-0" G.C. TO VERIFY IN FIELD
DUCT PER MECH. DWG.
EXIST. WOOD
SUPPORT WALLS
EXIST. WOOD JOIST @
2'-0" O.C. (FIELD VERIFY)
(2) #10x4" LONG
SCREWS AT EA.
JOIST 1 EA. SIDE
OF PATE CURB
PATE CURB
DUCT ATTACHMENT
PER MECH. DWG.
01-MG-003
D7 SECTION AT ROOF DUCT SUPPORT
NO SCALE
10'-0" G.C. TO VERIFY IN FIELD
0.4623
EXIST. WOOD
SUPPORT WALLS
DUCT ATTACHMENT
PER MECH.
#10x4" LONG
SCREWS AT EA. JOIST
MECH. DUCT
SEE MECH.
DRAWINGS
EXIST. WOOD JOIST @
2'-0" O.C. (FIELD VERIFY)
PATE CURB
01-MG-003
B9 SECTION AT ROOF DUCT SUPPORT
NO SCALE
EXIST. SLAB
(4)-#4-DRILL & EPOXY
INTO EXIST. - 6" MIN.
EMBED (TYP.)
PLACE TEMPORARY ORM TO
UNDERSIDE OF SLAB- MATCH
EXIST. THICKNESS W/ 3000PSI
CONCRETE
NOTE: FOR 9" TO
24" ROUND SLAB
OPENINGS ONLY
01-MG-003
A8 TYPICAL ROUND SLAB OPENING PATCH
NO SCALE
0.4190
EXIST. WOOD ROOF JOISTS
EXIST. SHEATHING
DUCT ATTACHMENT
PER MECH.
MECH. DUCT
SEE MECH.
DRAWINGS
#10x4" LONG SCREWS
AT EA. JOIST
PATE CURB
01-MG-003
D5 TYP. ROOF DUCT SUPPORT PARALLEL TO FRAMING
NO SCALE
D7
1-MG-003
EXISTING EIFS
NEW EIFS FINISH COAT
AND BASE COAT WITH MESH
2" INSULATION BOARD
1" SETBACK
1/2" CDX SHEATHING
3-5/8" 20GA STUDS 16"
OC WITH R11 INSULATION
CAULK AND SEAL
JOINTS ON ALL 4 SIDES
NEW
NOTES:
NEW EIFS FACE SET BACK 1". INFILL ENTIRE OPENING. MATCH EXISTING EIFS IN TEXTURE AND COLOR.
INTERIOR OPENING SHALL BE INFILLED FLUSH WITH 1/2" CDX PLYWOOD. PROVIDE BLOCKING 16" OC AS REQUIRED. PAINT (1) PRIME COAT AND (1) FINISH COAT. COLOR TO MATCH EXISTING WALLS.
DETAIL SHALL BE ADJUSTED TO ADAPT TO
EACH INFILL.
01-MG-003
D9
EXTERIOR WALL OPENING/INFILL
(PENTHOUSE WINDOWS/OPENINGS ONLY)
NO SCALE
PE−2021014461P
R
O F
E S S I O N A L E N G
I N E
E R
HANNAH
ROSE
KIGER
S T
A
T E
OF MI SSO
U
R I
DESIGN-AIRE ENGINEERING, INC.
www.daengineering.comwww.daengineering.com voice (317) 464-9090
2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - Create Code Compliant Research Laboratory Space in Building 1
657-23-113JB
Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM
08-6231 1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
01-18-2024
100% CONSTRUCTION DOCUMENTS
100% SPRINKLERED
DEH RE
1-MG-003
DETAILS - MECHANICAL
GRILLE, REGISTER AND DIFFUSER SCHEDULE (Basis of Design)
TAG MAXIMUM CFM MAX. N.C.
NECK SIZE
INCHES
FACE SIZE
INCHES
DESCRIPTION
NECK
DAMPER
Y / N
MANUFACTURER / MODEL NO. MOUNTING NOTES
A 600 30 On Drawing 24"x 24" Supply Diffuser Yes Price PDMC-ST-AFI-BBP Ceiling 1,4
B 600 30 22"x22" 24"x 24" Return Filter Grille with Neck Plenum No Price 10FF-3P-1"-HL Ceiling 2,3
GENERAL NOTES:
A. Maximum N.C. values are based on Octave Band 1 through 8 sound power levels minus a room absorption of 10dB, re 10 to the -12 Watts.
B. Verify border requirements with all applicable architectural sheets, reflected ceiling plans, and room finish schedules.
C. Provide square to round transitions, by Manufacturer, as required. Also see Plans.
D. All grilles, registers, and diffusers shall have visible sheet metal and ductwork painted flat black behind face.
E. Provide cable operated damper for unaccessible ceiling area.
NOTES:
1 Provide baked enamel finish, Color as selected by Architect. A10 or A10x10 Tag, Neck Size (round or square)
2 Perforated Face Filter Grille, 1" filter rack, hinge tabs, 1/4 turn fasteners, for mounting in standard T-bar lay-in panel. 175 CFM CFM Value of Diffuser/Register
3 Provide two (2) 1" MERV 11 pleated air filters.
4 Perforated Face Diffuser with Rotatable Modular Cores. Provide black backpan and outer frame, foil backed fiberglass insulation on backpan.
LAB EXHAUST FAN SCHEDULE (BASIS OF DESIGN)
FAN DATA GENERAL INFORMATION
TAG MAX CFM
ESP
IN. W.C.
BYPASS AIR
FLOW CFM
TOTAL AIR
FLOW CFM
TSP
IN. W.C.
TIP
SPEED
RPM SONES VOLTAGE BHP HP DRIVE CONTROLLED BY
MANUFACTURER AND MODEL
NUMBER
FAN TYPE DISCHARGE
MIN. EFFECTIVE
PLUME HEIGHT
FEET
LOCATION WEIGHT LBS NOTES
1-EF1-LAB
1,000 1.0 0 1,000 1.2 ---- 2,463 18.4 208V/3Ph 0.53 1.0 Belt VFD Greenheck VK-H-12-7 Tubular centrifugal Upblast 16.0 Roof 834 1,2,4,5
1-EF2-LAB
1,000 1.0 0 1,000 1.2 ---- 2,463 18.4 208V/3Ph 0.53 1.0 Belt VFD Greenheck VK-H-12-7 Tubular centrifugal Upblast 16.0 Roof 834 1,2,4,5
1-EF3-LAB
550 0.5 0 550 0.5 ---- 3200 6.0 120V/1PH 0.38 0.5 Direct VFD JencoFan TD-MIXVENT TD-250 Inline - mixed flow ---- ---- 3C17 21 2,3
NOTES
1 Provide with 24" roof curb, burb seals, disconnect switch and starter, motor cover, backdraft damper, exhaust discharge nozzle, extended lube lines, protective corrosion resistant coating, inlet flexible duct connection, 125 MPH wind load rated.
2 Fan to operate continuously.
3 Provide backdraft damper, variable speed drive, disconnect switch.
4 Fans are N+1 design and share a common plenum and curb.
5 Provide with Greenheck Vektor Systems Control (VCS), control box with variable speed drives, PLC and multi-tap transfomer, tranducer and pressure probe, and static sensor and probe.
DUCT LEAKAGE CLASSIFICATION AND ALLOWABLE LEAKAGE
SEAL CLASS
C
APPLICABLE SEALINGS
SMACNA LEAKAGE CLASS
3" B TRAVERSE JOINTS AND SEAMS 12
4", 6", 10" A JOINTS, SEAMS AND ALL WALL PENETRATIONS 6 3
12TRAVERSE JOINTS ONLY
N 2"
P 4"SUPPLY
FROM ROOM OUTLETS TO EXHAUST FAN.
FROM TERMINAL BOXES TO ROOM OUTLETS.
2"N
DUCT INVOLVEDFAN TYPE
DUCT PRESSURE CLASSES
FROM FAN DISCHARGE TO TERMINAL BOXES.
P 2"
1/2", 1", 2"
N 2"FROM RA GRILLE TO AHU INLET
50693.04.096 75 5069
40703.04.05075
FAN
EXHAUST
FAN
RETURN
AIR FAN
96 75
%RH.
INSIDE
D.B.W.B.D.B.
OUTSIDE
SUMMER
D.B. W.B.
OUTSIDE
D.B.
INSIDE
WINTER
%RH.
LAB AREAS
OFFICE AREAS
AIR CONDITIONING DESIGN DATA-DESIGN ALTITUDE 909 FT.
BLOWER COIL UNIT (Basis of Design)
TAG NO. LOCATION CFM BHP OUTSIDE AIR CFM ESP/TSP DRIVE NOMINAL BTU/HR
COOLING CAPACITY HEATING CAPACITY ELECTRICAL DATA CABINET
MFG. MODEL#
TOTAL BTU/HR EDB/EWB LDB/LWB GPM EWT/LWT ROWS TOTAL BTU/HR EAT/LAT EWT/LWT GPM ROWS MCA MOCP VOLT/PH DISC. BY EM POWER WIDTH (IN) LENGTH (IN) HEIGHT (IN)
BC-1
LAB 2C19 1200 0.75 0 0.45" DIRECT 24000 19160 80/58 54.3/54.2 3.8 45/55 4 51840 50/90 140/120 1.9 2 7.3 -- 208/1 EC YES 38 47 15 PRICE BCHD-012
BC-2
LAC 3C17 1200 0.75 0 0.45" DIRECT 24000 19160 80/58 54.3/54.2 3.8 45/55 4 51840 50/90 140/120 1.9 2 7.3 -- 208/1 EC YES 38 47 15 PRICE BCHD-012
Notes:
1 Provide spring hanger and brackets, 1-inch solid metal liner, stainless steel drain pan, secondary drain connection, and 2-inch MERV 13 filters and one set of spare filters.
ROUND DUCT
FROM OUTSIDE AIR LOUVER OR RETURN SMOKE DAMPER TO COIL.
MINUMUM
PRESSURE
CLASS W.G.
POSITIVE (P) OR
NEGATIVE (N)
PRESSURE
DUCT PRESSURE
CLASS, W.G. RECTANGULAR
DUCT
DESIGN
AREA
Parapet 150' - 0"
E4
1-MG-004
1-EF1-LAB
NEW 12"Ø STAINLESS STEEL
DUCT THROUGH WALL
DUCT ROOF RAIL
SUPPORT; TYPICAL
1-EF2-LAB
Parapet 150' - 0"
E1
1-MG-004
12"⌀ EXHAUST
INTAKE
11' - 0"
2' - 3"
PE−2021014461P
R
O F
E S S I O N A L E N G
I N E
E R
HANNAH
ROSE
KIGER
S T
A
T E
OF MI SSO
U
R I
DESIGN-AIRE ENGINEERING, INC.
www.daengineering.comwww.daengineering.com voice (317) 464-9090
2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - Create Code Compliant Research Laboratory Space in Building 1
657-23-113JB
Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM
08-6231 1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
01-18-2024
100% CONSTRUCTION DOCUMENTS
100% SPRINKLERED
DEH RE
1-MG-004
SCHEDULES & DETAILS -
MECHANICAL
NOT TO SCALE1-MG-004
E1 EXHAUST FAN SECTION 1
NOT TO SCALE1-MG-004
E4 EXHAUST FAN SECTION 2
CONTROL SCHEMATIC - 1-EF1-LAB & 1-EF-2-LAB
CONTROL SCHEMATIC - 1-BC-1 & 1-BC-2
NO SCALE
NO SCALE
CONTROL SCHEMATIC - 1-EF-3 LAB & 1-EF-4-LAB
NO SCALE
RETURN AIR
T-3
C O
IL
C O
O L
IN
G
C H
R
A
V-1
C H
P
VSMC
C
T-4
SUPPLY
FAN
1 2 3 4 5
A B
INPUT
DCP
OUTPUT
(DDC)
2-WAY
P
F
IL
T E
R
H-1
SPS-1
WALL WALLSUPPLY AIR
TO LAB
T-2
3 5
H-2
EXHAUST
AIR
P
VSMC
B
EXHAUST
FAN
VPS
INLET PROBES
FAN VOLUME
SPS-4
SPS-3
HOOD B-1
ROOM 3C17
P
VSMC
A
EXHAUST
FAN
VPS
INLET PROBES
FAN VOLUME
SPS-2
1 2 3 4 5 6
A B
INPUT
DCP
OUTPUT
(DDC)
A F
M S
A F
M S
HOOD C-1
ROOM 2C19
MAKEUP AIR
VCD-2
MAKEUP AIR
VCD-1
SENSOR
ROOM 2C19
SENSOR
ROOM 3C17
D
M
C
M
7 8 9 10 11
C D
SPS-6
WALL
SPS-5
WALL
EXHAUST
AIR
P
VSMC
A
EXHAUST
FAN
VPS
INLET PROBES
FAN VOLUME
CM
SPS-4
SPS-3
GAS CABINET G10
ROOM 3C17
P
VSMC
B
EXHAUST
FAN
VPS
INLET PROBES
FAN VOLUME
1 2 3 4
A B
INPUT
DCP
OUTPUT
(DDC)
GAS CABINET G10
ROOM 2C19
C
13 14
FHC-1
FHC-2
C O
IL
H E
A T
IN
G
H W
R
B
V-2
H W
S
2-WAY
VALVE
C
CONTROLS DESCRIPTIONS
TAG DESCRIPTION NOTES
AFMS AIR FLOW MEASURING DEVICE
MONITORS AIR FLOW RATE PROVIDES VELOCITY
PRESSURE FOR TRANSMITTAL TO DCP
delta P DIFFERENTIAL PRESSURE SENSOR
TRANSMIT DIFFERENTIAL PRESSURE TO DCP TO
INDICATE FILTER CONDITIONS AND STATUS OF FANS
DCP DISTRIBUTED CONTROL PANEL
CONTROLS OPERATION OF AIR HANDLING UNIT IN
ACCORDANCE WITH THE SEQUENCE OF OPERATION
ECC ENGINEERING CONTROL CENTER
LOCATED IN BUILDING 1 FOR MONITORING OF SYSTEM
OPERATIONS
H-1 SPACE HUMIDITY SENSOR
SENSES AND TRANSMITS FLOOR HUMIDITY TO DCP FOR
CONTROL AND INDICATION
H-2 EXHAUST DUCT HUMIDIY SENSOR
SENSES AND TRANSMITS DUCT HUMIDITY TO DCP FOR
INDICATION
SPS-1 FLOOR STATIC PRESSURE SENSOR WALL MOUNTED IN CORRIDOR
SPS-2 EXHAUST DUCT STATIC PRESSURE SENSOR
SENSES AND TRANSMITS DUCT STATIC PRESSURE TO
DCP FOR CONTROL AND INDICATION
SPS-3 EXHAUST DUCT STATIC PRESSURE SENSOR
SENSES AND TRANSMITS DUCT STATIC PRESSURE TO
DCP FOR CONTROL AND INDICATION
SPS-4 EXHAUST DUCT STATIC PRESSURE SENSOR
SENSES AND TRANSMITS DUCT STATIC PRESSURE TO
DCP FOR CONTROL AND INDICATION
SPS-5 ROOM STATIC PRESSURE SENSOR
SENSES AND TRANSMITS ROOM STATIC PRESSURE TO
DCP FOR CONTROL AND INDICATION
SPS-6 ROOM STATIC PRESSURE SENSOR
SENSES AND TRANSMITS ROOM STATIC PRESSURE TO
DCP FOR CONTROL AND INDICATION
SPS-7 EXHAUST DUCT STATIC PRESSURE SENSOR
SENSES AND TRANSMITS DUCT STATIC PRESSURE TO
DCP FOR CONTROL AND INDICATION
SPS-8 EXHAUST DUCT STATIC PRESSURE SENSOR
SENSES AND TRANSMITS DUCT STATIC PRESSURE TO
DCP FOR CONTROL AND INDICATION
T-1 SUPPLY AIR TEMPERATURE SENSOR
SENSES AND TRANSMITS DRY BULB TEMPERATURE TO
DCP FOR CONTROL AND INDICATION
T-2 EXHAUST AIR TEMPERATURE SENSOR
SENSES AND TRANSMITS OFF COIL DRY BULB
TMPERAUTURE TO DCP FOR CONTROL AND INDICATION
T-3 RETURN AIR TEMPERATURE SENSOR
SENSES AND TRANSMITS DRY BULB TEMPERATURE TO
DCP FOR INDICATION ONLY
T-4 LAB SUPPLY AIR TEMPERATURE
SENSES AND TRANSMITS OFF COIL COIL DRY
TEMPERATURE TO DCP FOR CONTROL AND INDICATION
V-1
PLANT CHILLED WATER CONTROL VALVE -
TWO WAY MODULATING
PROPORTIONS FLOW OF PLANT CHILLED WATER TO
COOLING COIL IN RESPONSE TO DCP
VCD MAKE-UP AIR VOLUME CONTROL DAMPER
CONTROLS THE AMOUNT OF MAKE-UP AIR
INTRODUCED TO THE SPACE TO MAINTAIN ROOM
PRESSURE BALANCE
VPS FAN VELOCITY PRESSURE SENSOR
SENSES VELOCITY PRESSURE AT FAN INLET AND
TRANSMITS AIRFLOW ACROSS FAN
SPS-7 EXHAUST DUCT STATIC PRESSURE SENSOR
SPS-8 EXHAUST DUCT STATIC PRESSURE SENSOR
SENSES AND TRANSMITS DUCT STATIC PRESSURE TO
DCP FOR CONROL AND INDICATION
VSMC
VARIABLE SPEED MOTOR CONTROLLER WITH
MOTOR STARTER
CONTROLS SUPPLY AND RETURN FANS MOTOR SPEED
IN RESPONSE TO DCP
FHC-1/2 FUME HOOD CONTROLLER
MEASURES AND CALCULATES FUME HOOD FACE
VELOCIRY AND OUTPUTS REQUIRED AIRFLOW
SETPOINT IN CFM
Blower Coil Unit 1-BC-1 & 1-BC-2
A. General:
1. Unit is normally started and stopped by the DCP or remotely at the ECC. H-O-A switch shall be kept in the “AUTO” position. “HAND” and “OFF” shall be used only for maintenance.
2. Fan shall operate continuously during occupied mode.
B. Fan Speed Control
1. On start-up the supply fans shall be ramped up to speed to prevent over pressuring the duct.
2. The supply air flow shall be controlled by the DCP modulating supply fan variable speed motor controller (VSMC) to maintain the cooling setpoint. The maximum fan speed will be 100% of total rated air flow.
C. Cooling and Heating
1. Chilled Water Mode:
a. In cooling mode, the thermostat setpoint shall be 69 oF ± 2oF (adjustable). If the space temperature rises above the cooling setpoint, the system shall first modulate the chilled water control valve from 0% to 100% open according to the proportional-integral-derivative (PID) and the supply fan airflow shall remain at the same speed. The supply fan speed shall remain at set speed. If the space temperature drops below cooling setpoint, the system shall modulate the chilled water control valve closed according to the PID. If the control valve is less than or equal to 50% (adjustable) open, the supply fan speed shall be reset to minimum supply airflow.
3. Supply air temperature shall be monitored at the operator's terminal. Should discharge air temperature deviate from set point by 5of, an alarm shall sound at the ECC terminal.
D Safeties, Interlocks:
1. If the fire alarm panel indicates a fire or smoke the fans will be disabled and the AHU will be in its Unoccupied/ Disabled Mode.
a. Supply fan shall restart when fire alarm circuit is reset.
2. If the manual reset high- or low-pressure safeties trip the fans will be disabled and the AHU will be in its Unoccupied/ Disabled Mode.
E. Filters
1. Filter differential pressure shall be monitored at the DCP terminal in addition to local manometer, service notice shall be displayed with differential pressure exceeds 0.65” wg. (adjustable), alarm shall sound if differential pressure exceeds 1.0” wg. (adjustable).
F. Emergency Constant Speed Operation
1. On all VSMC fans in VAV systems upon failure of the VSMC the fans shall be started/stopped manually at the CDP or the ECC through the by-pass starter. Fans shall then be operated at the constant design speed.
Lab Exhaust Fans 1-EF1-LAB & 1-EF2-LAB (N+1) and Volume Control Damper VCD-1 & VCD-2
Gas Cabinet Control (Room 2C19 - #G10 and Room 3C17 - #G10) Exhaust Fan 1-EF3-Lab and 1-EF4-Lab (N+1)
A. General:
1. Unit is normally started and stopped by the DCP or remotely at the ECC. H-O-A switch shall be kept in the “AUTO” position. “HAND” and “OFF” shall be used only for maintenance.
2. Exhaust Fan shall operate continuously for cabinet ventilation.
B. Air Flow Control
1. On start-up the supply fans shall be ramped up to speed to prevent over pressuring the duct.
2. In auto position, fan speed is controlled by DCP modulating the fan variable speed motor controller (VSMC) to maintain negative static pressure as sensed by the room(s) pressure controls.
3. Fan operation shall be monitored continuously, and alarm shall sound both at the DCP and ECC terminal and in both Lab rooms should fan dp switch and/or gas cabinet Loss-of-Ventilation Detector in each cabinet indicate loss of airflow. Upon loss of air flow in one exhaust fan, the backup fan shall start automatically and operate continuously as listed herein.
C. Emergency Constant Speed Operation
1. All VSMC fans in exhaust system upon failure of the VSMC the fans shall be started/stopped manually at the CDP or the ECC through the by-pass starter. Fans shall then be operated at the constant design speed.
GENERAL INFORMATION
A. ALL VALUES SHALL BE ADJUSTABLE.
B. EXISTING FLOOR PLAN GRAPHICS AND ASSOCIATED EQUIPMENT RELATIONSHIPS SHALL BE UPDATED TO
REFLECT AS-BUILT CONDITIONS.
C. COORDINATE ALL CONTROLS, SEQUENCES, AND POINTS LIST WITH JOHNSON CONTROLS, THE LOCAL VA
FACILITY VENDOR, THE COR, AND VA MAINTENANCE PERSONNEL.
A. General:
1. Unit is normally started and stopped by the DCP or remotely at the ECC. H-O-A switch shall be kept in the
“AUTO” position. “HAND” and “OFF” shall be used only for maintenance.
2. Fan shall operate continuously during occupied mode. Fan shall operate on its own controls as required.
B. Air Flow Control
1. On start-up the supply fans shall be ramped up to speed to prevent over pressuring the duct.
2. In auto position, fan speed is controlled by DCP modulating the fan variable speed motor controller (VSMC) to maintain the total fume hood exhaust air flow set point. The total fume hood exhaust air flow setpoint will be the sum of the two infividual fume hood exhaust set points.
3. Fume hood controllers FHC-1 and FHC-2 shall calculate the total fume hood open area based on the fume hood's fixed openings, bypass opening, leakage area, ans sash position as indicatM required to maintain the average face velocity set point based on the total open area of the fume hood and the average face velocity set point. When the sash is at the minimum position, the fume hood exhaust CFM setpoint shall be set to a minimum flow. Fume hood controllers shall be capable of BACnet communicaton.
4. Fan operation shall be monitored continuously, and alarm shall sound both at the DCP and ECC terminal and in both Lab rooms should fan dp switch indicate loss of airflow. Upon loss of air flow in one exhaust fan, the backup fan shall start automatically and operate continuously as listed herein.
a. As either hood sash is opened VCD-1 or VCD-2 shall modulate open to provide makeup air to the particular hood and as the hood sash is closed then VCD-1 or VCD-2 shall modulate close. 11 C. Room Space Pressure
1. A static pressure differential shall be continuously monitored between the space and the adjacent corridor, and alarm shall sound at DCP and ECC terminal if either Lab becomes positive with respect to the corridor.
2. Maintain room pressure relationship differential with respect to reference corridor: differential pressure setpoint = -0.01”.
3. The DCP shall continuously monitor the differential pressure relative to the corridor, and shall modulate the make-up air dampers in response to changes in the differential pressure in order to maintain the differential pressure setpoint.
D. Safeties, Interlocks:
1. If the fire alarm panel indicates a fire or smoke the fans will be disabled and will be in its Unoccupied/ Disabled Mode.
a. Exhaust fan shall restart when fire alarm circuit is reset.
2. If the manual reset high- or low-pressure safeties trip the fans will be disabled and the AHU will be in its
Unoccupied/ Disabled Mode.
3. 3. Fan operation shall be monitored continuously, and alarm shall sound both at the DCP and ECC terminal and in both Lab rooms should fan dp switch indicate loss of airflow. Upon loss of air flow in one exhaust fan, the backup fan shall start automatically and operate continuously as listed herein.
E. Emergency Constant Speed Operation
1. All VSMC fans in exhaust system upon failure of the VSMC the fans shall be started/stopped manually at the CDP or the ECC through the by-pass starter. Fans shall then be operated at the constant design speed.
2. Heating Water Mode:
a. In heating mode, the thermostat setpoint shall be 69 oF ± 2oF (adjustable). If the space temperature from 0% to 100% open according to the proportional-integral-derivative (PID).
temperature drops below setpoint, the system shall modulate the heating water control valve closed according to the PID.
If the setpoint rises above setpoint, the system shall modulate the heating valve
PE−2021014461P
R
O F
E S S I O N A L E N G
I N E
E R
HANNAH
ROSE
KIGER
S T
A
T E
OF MI SSO
U
R I
DESIGN-AIRE ENGINEERING, INC.
www.daengineering.comwww.daengineering.com voice (317) 464-9090
2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - Create Code Compliant Research Laboratory Space in Building 1
657-23-113JB
Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM
08-6231 1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
01-18-2024
100% CONSTRUCTION DOCUMENTS
100% SPRINKLERED
DEH RE
1-MG-005
MECHANICAL CONTROLS
SCHEMATICS
NOTES: 1. SIGNAL VIA UNIT-MOUNTED PITOT TUBE. SEE DETAIL.
2. SEE PLANS FOR T'STAT AND TERMINAL UNIT LOCATIONS.
3. EXISTING FLOOR PLAN GRAPHICS AND ASSOCIATED
EQUIPMENT RELATIONSHIPS SHALL BE UPDATED TO
REFLECT AS BUILT CONDITIONS.
1-BC-1 AND 1-BC-2
SUPPLY FAN
SUPPLY AIR
RETURN AIR
MIXED AIR
DAMPERS (RET/MIXED AIR/RELIEF)
HUMIDITY SENSORS
M E
D
IC
A L
G A
S E
S
L E
A K
D E
T E
C T
IO
N
S M
O K
E D
E T
E C
T
IO
N /F
IR
E
A L
A R
M
P U
M P
F A
IL
U
R E
D A
M P
E R
P O
S
IT
IO
N
S U
P P
L Y
A
IR
T E
M P
E R
A T
U R
E
CONTROL POINTS
R U
N T
IM
E
M A
IN
T
E N
A N
C E
T R
E N
D
IN
G
V A
R
S P
E E
D D
R
IV
E M
O D
R E
T . A
IR
H
U M
ID
IT
Y
R H
D
IF
F . P
R E
S S
. F T
-H D
D
IF
F . P
R E
S S
IN
. W T
'R
D
IS
C H
A R
G E
A
IR
T E
M P
S T
A T
IC
P
R E
S S
. I N
. W T
'R
IN
L
E T
P R
E S
S
P S
IG
IN
L
E T
T E
M P
. D E
G . F
L O
W L
E V
E L
O N
-O F
F
D A
M P
E R
-O P
E N
/C L
O S
E D
C O
N T
R O
L V
A L
V E
C O
N T
R O
L D
A M
P E
R
W A
T E
R T
E M
P
D E
G
F
A
IR
T E
M P
. D E
G
F
O N
-O F
F
MONITORING POINTS
F R
E E
Z E
S T
A T
H
IG
H L
E V
E L
O U
T L
E T
T E
M P
. D E
G . F
O U
T L
E T
P R
E S
S
P S
IG
F L
O W
, G P
M
C F
M A
IR
F
L O
W
R E
T U
R N
A
IR
T E
M P
O U
T S
ID
E
A
IR
T E
M P
C O
O L
C
O
IL
V A
L V
E P
O S
IT
IO
N
P R
E -H
E A
T C
O
IL
V A
L V
E P
O S
O .A
. A
IR
H U
M
ID
IT
Y
R
H
D
IS
C H
A
IR
H
U M
ID
IT
Y
R H
S P
A C
E T
E M
P
D E
G
F
S P
A C
E H
U M
ID
IT
Y
R H
ECC ALARM INDICATION OUTPUTS
F R
E E
Z E
S T
A T
F A
N F
A
IL
U R
E
F
IL
T E
R H
IG
H
L
IM
IT
H
IG
H T
E M
P E
R A
T U
R E
L O
W T
E M
P E
R A
T U
R E
H
IG
H H
U M
ID
IT
Y
L O
W H
U M
ID
IT
Y
H
IG
H P
R E
S S
U R
E
L O
W P
R E
S S
U R
E
H
IG
H L
E V
E L
L O
W L
E V
E L
R U
N T
IM
E
SOFTWARE PROGRAMS
E C
O N
O M
IZ
E
R C
O N
T R
O L
T
IM
E S
C H
E D
U L
IN
G
O P
T
IM
U M
S T
A R
T /S
T O
P
E V
E N
T P
R O
G R
A M
R E
S E
T
A U
T O
M A
T
IC
R E
S T
A R
T
G R
A P
H
IC
S
S M
O K
E D
E T
E C
T
IO
N
A
IR
V O
L U
M E
C O
N T
R O
L
P R
E S
S U
R E
PRE-FILTER
PLANT COOLING COIL
STATIC PRESSURE
TEMPERATURE SENSORS
H U
M
ID
IF
IE
R V
A L
V E
P O
S
IT
IO
N
R E
-H E
A T
C O
IL
V
A L
V E
P O
S
O .A
D
A M
P E
R P
O S
IT
IO
N
DIGITAL
CONTROL
ANALOG
CONTROL DIGITAL STATUS ANALOG STATUS
POINTS LIST SCHEDULE FOR ENGINEERING CONTROL CENTER (ECC)
AIR MEASURING STATIONS
E X
H A
U S
T A
IR
H
U M
ID
IT
Y
R H
E X
H A
U S
T D
A M
P E
R P
O S
IT
IO
N
D U
C T
T E
M P
E R
A T
U R
E
1-EF1-LAB AND 1-EF2-LAB
EXHAUST FAN
EXHAUST AIR FROM 2C19
EXHAUST AIR FROM 3C17
DAMPER
AIR MEASURING STATION
TEMPERATURE SENSOR
BUILDING 1
JEFFERSON BARRACKS VAMC
1-EF3-LAB AND 1-EF4-LAB
EXHAUST FAN
AIR MEASURING STATION
PE−2021014461P
R
O F
E S S I O N A L E N G
I N E
E R
HANNAH
ROSE
KIGER
S T
A
T E
OF MI SSO
U
R I
DESIGN-AIRE ENGINEERING, INC.
www.daengineering.comwww.daengineering.com voice (317) 464-9090
2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - Create Code Compliant Research Laboratory Space in Building 1
657-23-113JB
Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM
08-6231 1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
01-18-2024
100% CONSTRUCTION DOCUMENTS
100% SPRINKLERED
DEH RE
1-MG-006
MECHANICAL CONTROLS POINTS
LIST