657-23-113JB - Construction Drawings - 14 of 14 - TT.pdf

PDF 849 KB Posted

Attached to
Z1DA--Create Code Compliant Research Laboratory Space in Building 1, 657-23-113JB Federal contract opportunity
Solicitation number
36C25524R0053
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15

About this file

This document contains construction drawings for a project titled "FCA - Create Code Compliant Research Laboratory Space in Building 1" with the solicitation number 36C25524R0053. The project is for the Department of Veterans Affairs (VA) at the Saint Louis VA Health Care System located at Jefferson Barracks in Saint Louis, Missouri.

The drawings provide details for the technology infrastructure upgrades required, including second and third floor plans showing the locations of data cabling, wireless access points, CCTV cameras, and other technology equipment. Detailed drawings are provided for technology outlet types, speaker installation, cable tray routing, and security system components such as door contacts and credential readers. The project also requires monitoring of LPG gas, refrigerators, and freezers. The project is a construction effort to create code compliant research laboratory space in the existing Building 1 facility.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--Create Code Compliant Research Laboratory Space in Building 1, 657-23-113JB, newest first.
File Type Posted
S02-657-23-113JB - Create Code Compliant Research Laboratory Space Prebid Questions 20240422.pdf PDF
Pre-Bid Conference Sign-in Sheet 657-23-113 --- Scan04-09-2024-102719.pdf PDF
S02-3- As Built from-657-10-104JB_1C-A1.pdf PDF
36C25524R0053 0001.docx DOCX document
657-23-113JB - Construction Drawings - 11 of 14 - EG.pdf PDF
657-23-113JB - Construction Drawings - 2 of 14 - GJ.pdf PDF
657-23-113JB Specifications - Reduced File Size.pdf PDF
657-23-113JB - Construction Drawings - 12 of 14 - EP.pdf PDF
657-23-113JB - Construction Drawings - 9 of 14 - MG.pdf PDF
657-23-113JB - Construction Drawings - 8 of 14 - FP.pdf PDF
657-23-113JB - Construction Drawings - 1 of 14 - GI.pdf PDF
657-23-113JB - Construction Drawings - 13 of 14 - TG.pdf PDF
657-23-113JB - Construction Drawings - 7 of 14 - PM.pdf PDF
657-23-113JB - Construction Drawings - 6 of 14 - PL.pdf PDF
657-23-113JB - Construction Drawings - 5 of 14 - PG.pdf PDF
657-23-113JB - Construction Drawings - 4 of 14 - AE.pdf PDF
657-23-113JB - Construction Drawings - 3 of 14 - HA.pdf PDF
36C25524R0053_1.docx DOCX document
657-23-113JB - Construction Drawings - 10 of 14 - MH.pdf PDF
Show all 19

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

42" MH

4D

42" MH

4D

AP

SP

SP

MD

0"

M H

SP

KC

EDC

CC

44" MH

4D

44" MH

4D

K

44" MH

4D

44" MH4D

CC

2C19

LAB

2C20

2C23

12"x4"

H210

PAC

TYP.

2C10

OIT

2C18 2C17

2C16

2C15 2C14 2C13 2C12 2C11

2W22A

2W22B

2W22C

H205

2C01

2C292W23

2W22

2W21

H208 2W01

2C09

2C03

2C02

1 1/2"ø

"ø

2"ø

"ø

1 1/2"ø

/2 "ø

1 1/2"ø

1 1/2"ø

/2 "ø

"ø

"ø

1"ø

1"ø

2C19

LAB

2C20

2C23

H210

PAC

5 6

2C10

OIT

2C18 2C17

2C16

2C15 2C14 2C13 2C12 2C11

2W22A

2W22B

2W22C

H205

2C01

2C292W23

2W22

2W21

H208 2W01

2C09

2C03

2C02

DESIGN-AIRE ENGINEERING, INC.

www.daengineering.comwww.daengineering.com voice (317) 464-9090

2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

FCA - Create Code Compliant Research Laboratory Space in Building 1

657-23-113JB

Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM

08-6231 1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

CONSTRUCTION DOCUMENTS

12-22-2023Project Number: 2023-05162.00

JCM JWE

1-TT-100

PARTIAL SECOND FLOOR PLANS -

TECHNOLOGY

TRUE

NORTH

SCALE: 1/8" = 1'-0"1-TT-100

TECHNOLOGY SECOND FLOOR PATHWAY

PLAN

TRUE

NORTH

SCALE: 1/8" = 1'-0"1-TT-100

PARTIAL SECOND FLOOR PLAN -

TECHONLOGY

1. 4C/22AWG FROM DEVICE TO 2H10 SIGNALS CLOSET. FOR TEMPERATURE

MONITORING.

2. (2) 4C/22AWG FROM DEVICE TO 2H10 SIGNALS CLOSET. FOR LPG

MONITORING. (1) SET FOR CONNECTIVITY TO ALTOS 2 AND (1) SET FOR

EMERGENCY STOP BUTTON IF EQUIPPED WITH (2) OUTPUTS (1) FOR STOP

OPERATION (1) FOR ALARM MONITORING.

3. APROXIMATE LOCATION OF NURSE CALL EQUIPMENT CABINET.

4. APROXIMATE LOCATION OF PHYSICAL ACCESS CONTROL SYSTEMS

CABINET.

5. APROXIMATE LOCATION OF NOTIFICATION APPLIANCE CIRCUIT CABINET.

6. APROXIMATE LOCATION OF PAGING AMPLIFIER CABINET.

7. APROXIMATE LOCATION OF SURVEILLANCE SYSTEMS CABINET.

8. APROXIMATE LOCATION OF EXISTING CABLE ROUTE, TO REMAIN.

9. PROVIDE J-HOOKS AS NEEDED FOR NEW DATA CABLING ATTACHED TO

CABLE TRAY.

10. PROVIDE 2" CONDUIT FROM SECOND FLOOR TO THIRD FLOOR UTILIZING

CHASE AS SHOWN.

11. PROVIDE 2" CONDUIT.

12. PROVIDE 8"L X 8"W X 6"D JUNCTION BOX.

13. FURNITURE MOUNTED DATA JACK. CABLING SHALL BE CONCEALED IN

FURNITURE CHASE.

14. UTILIZE PERMANENT GROUNDING BAR LOCATION. (PER VA STANDARDS)

15. TEMPORARY GROUNDING BAR LOCATION. REFER TO NOTE 14.

16. ENSURE COMMON GROUND CONNECTIVITY WITH NOTE 14 LOCATION.

PLAN NOTES

A. GAS, FREEZER, PAGING, PACS, INTRUSION DEVICE CABLING SHALL ROUTE

BACK TO SIGNAL CLOSET H210.

B. DATA CABLING SHALL ROUTE TO OIT 2C10.

GENERAL NOTES

41 44

42" MH

4D

42" MH

4D

AP

SP

SP

MD

96" M H

SP

KC

EDC

CC

CC

42" MH

4D

44" MH4D

K

44" MH

4D

44" MH4D

3C21

G2165YY

3C18

3C29

3C15

3C27

3C13

OIT

12"x4"

3C17

LAB

3C23

3C26

C307 C305

C306 C304

C303

3C14

H304

1 1/2"ø

"ø

2"ø

1 1/2"ø

"ø

1 1/2"ø

1 1/2"ø

1"ø

3C21

G2165YY

3C18

3C29

3C15

3C27

3C23

3C26

C307 C305

C306 C304

H304

LAB

3C17

DESIGN-AIRE ENGINEERING, INC.

www.daengineering.comwww.daengineering.com voice (317) 464-9090

2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

FCA - Create Code Compliant Research Laboratory Space in Building 1

657-23-113JB

Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM

08-6231 1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

CONSTRUCTION DOCUMENTS

12-22-2023Project Number: 2023-05162.00

JCM JWE

1-TT-101

PARTIAL THIRD FLOOR PLANS -

TECHNOLOGY

TRUE

NORTH

SCALE: 1/8" = 1'-0"1-TT-101

1 TECHNOLOGY THIRD FLOOR

TRUE

NORTH

SCALE: 1/8" = 1'-0"1-TT-101

PARTIAL THIRD FLOOR PLAN -

TECHNOLOGY

1. 4C/22AWG FROM DEVICE TO 2H10 SIGNALS CLOSET. FOR TEMPERATURE

MONITORING.

2. (2) 4C/22AWG FROM DEVICE TO 2H10 SIGNALS CLOSET. FOR LPG

MONITORING. (1) SET FOR CONNECTIVITY TO ALTOS 2 AND (1) SET FOR

EMERGENCY STOP BUTTON IF EQUIPPED WITH (2) OUTPUTS (1) FOR STOP

OPERATION (1) FOR ALARM MONITORING.

3. APROXIMATE LOCATION OF EXISTING CABLE ROUTE, TO REMAIN.

4. PROVIDE J-HOOKS AS NEEDED FOR NEW DATA CABLING ATTACHED TO

CABLE TRAY.

5. PROVIDE 2" CONDUIT FROM SECOND FLOOR TO THIRD FLOOR UTILIZING

CHASE AS SHOWN.

6. PROVIDE 2" CONDUIT.

7. PROVIDE 8"L X 8"W X 6"D JUNCTION BOX.

8. FURNITURE MOUNTED DATA JACK. CABLING SHALL BE CONCEALED IN

FURNITURE CHASE.

PLAN NOTES

A. GAS, FREEZER, PAGING, PACS, INTRUSION DEVICE CABLING SHALL ROUTE

BACK TO SIGNAL CLOSET H210.

B. DATA CABLING SHALL ROUTE TO OIT 3C13.

GENERAL NOTES

42 44

CEILING LINE

2-POSITION SURFACE BOX "BISCUIT":

• TWO (2) MODULAR 8-POSITION JACK "YELLOW"

• TWO (2) CATEGORY UTP CABLES "YELLOW"

FURNISH AND TERMINATE CABLES WITH A 25 FT. SLACK COIL AT EACH

LOCATION.

WIRELESS DEVICE

ACCESS POINT (AP)

AP

CEILING LINE

2-POSITION SURFACE BOX "BISCUIT":

• TWO (2) MODULAR 8-POSITION JACK "RED"

• TWO (2) CATEGORY 6A UTP CABLES "RED"

FURNISH AND TERMINATE CABLES WITH A 15 FT. SLACK COIL AT EACH

LOCATION.

CCTV CAMERA (CC)

CC

1.25" CONDUIT HOMERUN STUBBED

TO ACCESSIBLE CEILING SPACE PER

DIVISION 26

AIR-AP-BRACKET

PER DIV. 27

INTERIOR - ACCESSIBLE CEILING ARRANGEMENTS

WIRELESS ACCESS POINT

(2) X CATEGORY 6A 4-PAIR UTP

HOMERUN TO TELECOM ROOM

PER DIVISION 27

RACO #260H LARGE

CAPACITY BOX

PER DIV. 26

2-PORT

HOUSING

W/ CAT 6A

JACKS

12 INCH PATCH CORD

PER DIVISION 27

15 FT. SLACK COIL

21 2

15 FT. SLACK COIL

4-11/16" BOX

1.25" BUSHED

CONDUIT

DATA DATA

DATA DATA

OUTLET TYPE

QUADPLEX (DATA)

4D

4-POSITION SINGLE GANG FACEPLATE

WITH CLEAR LABEL WINDOWS:

• FOUR (4) MODULAR 8-POSITION JACKS "BLUE"

• FOUR (4) 4-PAIR CATEGORY 6A UTP CABLES "BLUE"

MOUNTING HEIGHT = 18" AFF UNLESS NOTED

OTHERWISE.

ROUTING = 1.25" CONDUIT AND BACKBOX WITH BUSHING

TO CORRIDOR CABLE TRAY.

AP CC

SPEAKER SUPPORT/TILE BRIDGE

ACUSTIC CEILING TILE

SPEAKER

SPEAKER COVER

SPEAKER BACK BOX

FLEX CONDUIT WHIP

NOTE:

CABLING WILL NEED TO BE FED

INTO THE SPEAKER THEN OUT TO

THE NEXT SPEAKER IN LINE.

SP

9/16" D

6/32" D (TYP. OF 6)

1-1/8" O.C.

9/32" D (TYP. OF 12)

1-1/8" O.C.

NOTE: ASSEMBLY AS MADE BY NEWTON

INSTRUMENT COMPANY BUTNER, NC. OR EQUIVILANT

DETAIL NOTES

1. 4"x1/4"x12" MIN. LENGTH GROUNDING BAR #A-6163

ACTUAL LENGTH REQUIRED BY QUANTITY OF GROUND

CONNECTIONS.

2. WALL MOUNTING BRACKET #A-6056.

3. INSULATORS #3061-4.

4. 5/8-11X1 H.H.C.S. #3012-1.

5. 5/8" LOCKWASHER.

BASKET TYPE CABLE TRAY ADAPTER

NTS

DETAIL SHEET NOTES:

CONDUIT ADAPTER (TYP)

RIGID STEEL

CONDUIT

-MOUNTS CONDUIT DIRECTLY TO

SIDE OR BOTTOM OF CABLE TRAY

-FOLD OVER TABS SECURES

DEVICE TO CABLE TRAY

-ADAPTER MAY BE DIFFERENT

FROM THAT SHOWN

1. DETAILS SHOWN IS FOR GUIDANCE ONLY. BRACING

SHALL BE IN ACCORDANCE WITH MANUFACTURER'S

RECOMMENDATION AND ANCHORS TO BE SEISMICALLY

PRE-QUALIFIED PER ACI 355.2.

2. INSTALL CABLE TRAY AND FITTINGS STRICTLY IN

ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.

CABLE TRAY

GROUND CLAMP

-UTILIZE A GROUNDING BUSHING TO CONNECT

CONDUIT TO BASKET CABLE TRAY ADAPTER.

CONNECT GROUNDING BUSHING TO CABLE TRAY

GROUND CLAMP.

BASKET TRAY

GROUNDING BUSHING

#6 AWG GROUND WIRE

CONDUIT CONNECTOR

BASKET TYPE

CABLE TRAY

ADAPTER

GROUNDING

BUSHING

EXPLODED VIEW

BASKET TYPE

CABLE TRAY

FIRE SEAL WITH APPROVED

CAULK OR PUTTY BY CABLE

INSTALLER

6"

2"

1' -3

FIRE SEAL BY CONDUIT INSTALLER

EMT CONDUIT WITH

BUSHED ENDS

APPROVED

CATEGORY-RATED

CABLE

THE CONDUIT METHOD SHALL ONLY BE USED FOR

INSTANCES IN WHICH THE EZ-PATH LENGTH EXTENSION

METHOD IS NOT SUFFICIENT

12" MIN. BOTH ENDS

FIRE SEAL WITH APPROVED

CAULK OR PUTTY BY CABLE

INSTALLER

FIRE SEAL BY CONDUIT INSTALLER

EMT CONDUIT WITH BUSHED ENDS

APPROVED CATEGORY-RATED

CABLE

THE CONDUIT METHOD SHALL ONLY BE USED FOR

INSTANCES IN WHICH THE EZ-PATH LENGTH EXTENSION

METHOD IS NOT SUFFICIENT

DESIGN-AIRE ENGINEERING, INC.

www.daengineering.comwww.daengineering.com voice (317) 464-9090

2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

FCA - Create Code Compliant Research Laboratory Space in Building 1

657-23-113JB

Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM

08-6231 1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

CONSTRUCTION DOCUMENTS

12-22-2023Project Number: 2023-05162.00

JCM JWE

1-TT-501

DETAILS

NOT TO SCALE1-TT-501

1 TECHNOLOGY OUTLET DETAILS

NOT TO SCALE1-TT-501

6 SPEAKER DETAIL

NOT TO SCALE1-TT-501

2 GROUND BAR DETAIL

NOT TO SCALE1-TT-501

TELECOMM SYSTEM GROUND FROM

CONDUIT TO CABLE TRAY

NOT TO SCALE1-TT-501

4 CONDUIT WITH FIRESTOP THRU FLOOR

NOT TO SCALE1-TT-501

5 CONDUIT WITH FIRESTOP THRU WALL

43 44

CEILING CEILING

DETAIL NOTES

1. NEW SECURITY WIRING JUNCTION BOX ABOVE CEILING.

2. PROVIDE WALL BOX ABOVE CEILING AT LOCATION OF PENETRATION INTO WALL CAVITY.

3. FISH CABLING DOWN INTERIOR WALL CAVITY.

4. RECESS CREDENTIAL READER INTO EXISTING WALL.

5. NEW/REPLACED ELECTRIC STRIKE.

6. EXTEND CABLING THROUGH FRAME INTO NEW STRIKE.

7. FIELD VERIFY STRIKE MOUNTING HEIGHT.

8. DPDT DOOR CONTACT. (1) SET OF CONTACTS FOR PACS, (1) SET OF CONTACTS FOR IDS.

9. DOOR MAGNET.

4 5 5

46" MH

FINISH

FLOOR

UNSECURE SIDE SECURE SIDE

FINISH

FLOOR

RXRX

46" MH

CAMERA MOUNTING DETAIL NOTES

INTERIOR - CEILING RECESSED

1. CAMERA AS SHOWN ON THE PLANS.

2. 1.25" CONDUIT TO BE ROUTED TO ACCESSIBLE INTERIOR JUNCTION

BOX.

3. JUNCTION BOX ABOVE ACCESSIBLE CEILING.

4. 2-DATA OUTLETS UTILIZING SURFACE MOUNT "BISCUIT" FOR

TERMINATION OF DATA DROP INTO RJ-45 OUTLET.

5. PROVIDE PATCH CABLE WITH CONNECTIONS.

6. 15' COIL OF CABLE MANAGED ABOVE CEILING.

5 4 6

K

DM

MD

H210 2C19

3C17

K DMMD

SP

SP

4C/22AWG

4C/22AWG

4C/22AWG

4C/22AWG

4C/22AWG

4C/22AWG

4C/22AWG

4C/22AWG

LEVEL 3

LEVEL 2

GENERAL NOTES

1. PROGRAMING AND FINAL TERMINATIONS BY PASS

SECURITY. PHONE: 618-394-1144 x7036.

CEILING

DETAIL NOTES

1. NEW SECURITY WIRING JUNCTION BOX ABOVE CEILING.

2. PROVIDE WALL BOX ABOVE CEILING AT LOCATION OF PENETRATION INTO WALL CAVITY.

3. FISH CABLING DOWN INTERIOR WALL CAVITY.

4. RECESS IDS KEYPAD INTO EXISTING WALL.

5. DPDT DOOR CONTACT. (1) SET OF CONTACTS FOR PACS, (1) SET OF CONTACTS FOR IDS.

6. DOOR MAGNET.

55" MH

FINISH

FLOOR

UNSECURE SIDE SECURE SIDE

FINISH

FLOOR

MD

96" MH

SP

CEILING

55" MH

MD

96" MH

SP

1 1

2 2

H210 2C19

3C17

4C/22AWG

4C/22AWG

(2) 4C/22AWG

4C/22AWG

4C/22AWG

(2) 4C/22AWG

LEVEL 3

LEVEL 2

DETAIL NOTES

1. LPG GAS CABINET.

2. REFRIGERATOR.

3. FREEZER.

GENERAL NOTES

1. PROGRAMING AND FINAL TERMINATIONS BY PASS

SECURITY. PHONE: 618-394-1144 x7036.

DESIGN-AIRE ENGINEERING, INC.

www.daengineering.comwww.daengineering.com voice (317) 464-9090

2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

FCA - Create Code Compliant Research Laboratory Space in Building 1

657-23-113JB

Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM

08-6231 1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

CONSTRUCTION DOCUMENTS

12-22-2023Project Number: 2023-05162.00

JCM JWE

1-TT-502

SECURITY DETAILS & SCHEDULES

NOT TO SCALE1-TT-502

1 SINGLE DOOR ROUGH-IN ELEVATIONS

NOT TO SCALE1-TT-502

CCTV SYSTEM - CAMERA MOUNTING

DETAILS-NEW

NOT TO SCALE1-TT-502

3 INTRUSION RISER DIAGRAM

44 44

NOT TO SCALE1-TT-502

4 IDS ELEVATIONS

NOT TO SCALE1-TT-502

LPG, REFRIGERATOR, FREEZER

MONITORING