657-23-113JB - Construction Drawings - 13 of 14 - TG.pdf

PDF 564 KB Posted

Attached to
Z1DA--Create Code Compliant Research Laboratory Space in Building 1, 657-23-113JB Federal contract opportunity
Solicitation number
36C25524R0053
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15

About this file

This document appears to be a set of construction drawings and specifications for the renovation of research laboratory space at the St. Louis VA Health Care System. The project, identified as 657-23-113JB, involves creating code-compliant research laboratory space in Building 1. The drawings provide detailed technical information on electrical, security, and technology requirements, including specifications for cabling, conduits, floor boxes, access points, security cameras, and other system components. Key details include requirements for staggering receptacles, coordinating device locations, and providing fire-rated conduit sleeves. The project is being solicited under Solicitation Number 36C25524R0053, issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--Create Code Compliant Research Laboratory Space in Building 1, 657-23-113JB, newest first.
File Type Posted
S02-657-23-113JB - Create Code Compliant Research Laboratory Space Prebid Questions 20240422.pdf PDF
Pre-Bid Conference Sign-in Sheet 657-23-113 --- Scan04-09-2024-102719.pdf PDF
S02-3- As Built from-657-10-104JB_1C-A1.pdf PDF
36C25524R0053 0001.docx DOCX document
657-23-113JB - Construction Drawings - 14 of 14 - TT.pdf PDF
657-23-113JB - Construction Drawings - 12 of 14 - EP.pdf PDF
657-23-113JB - Construction Drawings - 9 of 14 - MG.pdf PDF
657-23-113JB - Construction Drawings - 8 of 14 - FP.pdf PDF
657-23-113JB - Construction Drawings - 1 of 14 - GI.pdf PDF
657-23-113JB - Construction Drawings - 7 of 14 - PM.pdf PDF
657-23-113JB - Construction Drawings - 6 of 14 - PL.pdf PDF
657-23-113JB - Construction Drawings - 5 of 14 - PG.pdf PDF
657-23-113JB - Construction Drawings - 4 of 14 - AE.pdf PDF
657-23-113JB - Construction Drawings - 3 of 14 - HA.pdf PDF
36C25524R0053_1.docx DOCX document
657-23-113JB - Construction Drawings - 10 of 14 - MH.pdf PDF
657-23-113JB - Construction Drawings - 11 of 14 - EG.pdf PDF
657-23-113JB - Construction Drawings - 2 of 14 - GJ.pdf PDF
657-23-113JB Specifications - Reduced File Size.pdf PDF
Show all 19

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

T2

B

T2

DETAIL: B = DETAIL DESIGNATION

T2 = SHEET WHERE DETAIL IS LOCATED

SECTION: 1 = SECTION DESIGNATION

T2 = SHEET WHERE SECTION IS LOCATED

PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN.

DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.

GENERAL FLOOR PLAN NOTES

CONDUIT RUN IN WALL OR ABOVE CEILING PER DIV 26.

CONDUIT RUN IN SLAB OR UNDERGROUND PER DIV 26.

CABLE MANAGEMENT SYSTEM PATHWAY PER DIV 27 / DIV 28.

LADDER TRAY PER DIV 26, 12" x 4" DEEP UNLESS NOTED OTHERWISE.

CM

A. ALL CONDUITS SHALL BE SIZED FOR 1.25” MINIMUM.

B. ALL JUNCTION BOXES ARE TO BE FLUSH MOUNTED UNLESS OTHERWISE NOTED.

C. FIRESTOP ALL PENETRATIONS THRU WALLS.

D. VERIFY EXACT LOCATION OF ALL CEILING MOUNTED DEVICES WITH REFLECTED CEILING PLAN AND/OR ARCHITECT PRIOR TO ROUGH-IN.

COORDINATE LOCATIONS OF CEILING MOUNTED DEVICES WITH LIGHT FIXTURES, MECHANICAL DUCTS, AND SPRINKLER PIPES AND

HEADS BEFORE ROUGH-IN TO PREVENT CONFLICTS.

E. REMOVE EXISTING CEILING TILES AS REQUIRED FOR INSTALLATION OF NEW TECHNOLOGY ITEMS AND REINSTALL TILES IN A SIMILAR

MANNER AS NOW EXISTS.

F. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATIONS AND MOUNTING HEIGHTS OF OUTLETS AND DEVICES.

G. COORDINATE EXACT LOCATION OF ALL SWITCHES, RECEPTACLES, DATA OUTLETS, VOLUME CONTROLLERS, AV SYSTEM CONTROLLERS, THERMOSTATS, ETC. WITH RESPECTIVE CONTRACTORS PRIOR TO ROUGH-INS. ALL MOUNTING HEIGHTS OF DEVICES WHICH ARE MOUNTED ADJACENT TO EACH OTHER SHALL BE AT THE SAME DISTANCE MEASURED ABOVE THE FINISHED FLOOR.

H. STAGGER RECEPTACLES AND OTHER RECESSED OUTLETS WHEN LOCATED ON OPPOSITE SIDES OF PARTITION / WALL TO ELIMINATE

SOUND TRANSMISSION FROM ONE SPACE TO THE OTHER.

I. WHERE DEVICES ARE MOUNTED IN AREAS WHERE THERE ARE EXSPOSED CEILINGS, COORDINATE THE EXACT MOUNTING / LOCATION WITH THE STRUCTURAL SUPPORT MEMBERS AND WORK OF OTHER TRADES. PROVIDE ALL NECESSARY LABOR AND MATERIALS TO

ACHIEVE MOUNTING HEIGHTS AND LOCATIONS AS INDICATED ON THE PLANS.

J. ANY EXPOSED CONDUITS WITHIN THE FINISHED PORTIONS OF THE BUILDING SHALL BE PRIME AND FINISH PAINTED.

K. ALL EMPTY CONDUITS SHALL BE INSTALLED WITH PULL STRING.

L. DEMO, PATCH AND REPAIR EXISTING WALLS AS REQUIRED FOR INSTALLATION OF BOXES, CONDUIT, AND WALL PENETRATIONS.

M. WHERE EXISTING WALLS ARE FURRED ON ONE SIDE, ALL NEW SERVICES SHALL BE INSTALLED IN THE WALL FROM THE FURRED OUT

SIDE OF THE WALL.

N. ALL CONDUIT SLEEVES AND PATHWAYS SHOWN ON BID DOCUMENTS SHALL BE PROVIDED. ALL CONDUIT SLEEVES THRU WALLS AND FLOORS, NOT SPECIFICALLY SHOWN ON DRAWINGS BUT REQUIRED FOR COMPLIANT INSTALLATION OF CABLING SHALL BE PROVIDED AS

PART OF THE SCOPE OF WORK.

O. COMPLETELY AND THOROUGHLY COORDINATE ALL PATHWAYS BEING PROVIDED. ANY PATHWAYS THAT ARE PROVIDED THAT CAUSE CABLING INSTALLATION TO BE NON-COMPLIANT SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER PRIOR TO THE INSTALLATION

OF CABLING.

P. A 3.5" DEEP MASONRY BOX SHALL BE USED IN CMU WALLS.

Q. BOND ALL CABLE NEW AND/OR EXISTING RUNWAY SPLICES AND BUTT JOINTS WITH #6 AWG BOLTED TO CABLE RUNWAY. REMOVE PAINT OFF OF CABLE RUNWAY FOR METAL TO METAL CONNECTION AND APPLY ANTI-OXIDANT JOINT COMPOUND OVER ANY REMAINING AREAS

WITH BARE METAL EXPOSED.

R. ALL CONDUITS SHALL HAVE NYLON BUSHINGS INSTALLED.

S. PULL BOXES SHALL NOT BE USED TO CHANGE DIRECTION AND SHALL BE INSTALLED IN LINE WITH CONDUIT.

T. ALL TECHNOLOGY CONDUITS SHALL UTILIZE TELECOM SYSTEM GROUND FROM CONDUIT TO CABLE TRAY THEN BACK TO TGBB.

GENERAL NOTES

SECURITY SYMBOLS

CC

1 CCTV SYSTEM CEILING MOUNTED CAMERA. REFER TO CAMERA SCHEDULE FOR MOUNTING HEIGHT AND CAMERA

SPECIFICATIONS. SUBSCRIPT "X" INDICATES ENTRY IN CAMERA SCHEDULE.

MD CEILING MOUNTED MOTION DETECTOR.

X

SECURITY SYMBOLS WITH ELECTRICAL REQUIREMENTS

CC

CCTV SYSTEM WALL MOUNTED CAMERA (REFER TO CAMERA SCHEDULE FOR MOUNTING HEIGHT AND CAMERA SPECIFICATIONS). SUBSCRIPT "X" INDICATES ENTRY IN CAMERA SCHEDULE. 1-GANG BOX WITH 1.25" CONDUIT TO ABOVE

ACCESSIBLE CEILING PER DIV 26. CAMERA AND CABLING PER DIV 28.

DM

DOOR POSITION SWITCH WITH WIRING PER DIV 28. CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. PROVIDE ONE CONTACT FOR EACH LEAF IN MULTI-DOOR

OPENINGS. REFER TO SECURITY ROUGH-IN DETAILS.

RX

REQUEST TO EXIT SWITCH IN DOOR HARDWARE BY OTHERS. LOW VOLTAGE WIRING PER DIV 28. CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO SECURITY

ROUGH-IN DETAILS.

CR

WALL MOUNTED PROXIMITY CARD READER (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. CARD READER AND CABLING PER DIV 28. REFER

TO SECURITY ROUGH-IN DETAILS.

KC

WALL MOUNTED COMBINATION KEYPAD/CARD READER (46" MH UNLESS NOTED OTHERWISE). 2-GANG BOX WITH 1.25" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. DEVICE AND CABLING PER DIV 28.

K WALL MOUNTED SECURITY KEYPAD ENTRY STATION (55" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 1.25" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. KEYPAD AND CABLING PER DIV 28.

X

MD

CEILING MOUNTED MOTION DETECTOR. 1-GANG BOX MOUNTED IN CEILING PER DIV 26. DETECTOR AND CABLING PER

DIV 28.

TECHNOLOGY SYMBOLS

AP CEILING MOUNTED WIRELESS ACCESS POINT WITH DATA DROP ABOVE CEILING. PROVIDE 20' COIL IN DATA CABLE TO

FACILITATE RELOCATION OF WAP. WAP PROVIDED BY OWNER.

AV SYMBOLS

TECHNOLOGY SYMBOLS WITH ELEC. REQUIREMENTS

CONDUIT SLEEVE / FIRE RATED SLEEVE ASSEMBLY THRU WALL (1-2" SLEEVE UNLESS NOTED OTHERWISE) PER DIV 26.

AV SYMBOLS WITH ELECTRICAL REQUIREMENTS

SP

SELF CONTAINED INTRUSION DETECTION SIREN. (96" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 1.25" CONDUIT TO

ABOVE ACCESSIBLE CEILING.

4"

4"

CABLE TRAY PER DIV 26, 12" x 4" DEEP UNLESS NOTED OTHERWISE.

NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT

TO MODIFICATIONS ON OTHER DRAWINGS.

ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT

NECESSARILY BE USED ON THIS PROJECT.

T2 1 ELEVATION: 1 = ELEVATION DESIGNATION

T2 = SHEET WHERE ELEVATION IS LOCATED

FLOOR BOX PER DIV 26. # INDICATES TYPE, REFER TO FLOOR BOX (FB) SCHEDULE. SUBSCRIPT "X" INDICATES TECHNOLOGY

DEVICE(S), REFER TO TECHNOLOGY DETAILS.

X

POKE-THRU PER DIV 26. # INDICATES TYPE, REFER TO POKE-THRU (PT) SCHEDULE. SUBSCRIPT "X" INDICATES TECHNOLOGY

DEVICE(S), REFER TO TECHNOLOGY DETAILS.

X

EDC

X ELECTRONIC DOOR CONTROL. SUBSCRIPT "X" INDICATES SPECIFIC DOOR. REFER TO ELECTRONIC DOOR CONTROL

SCHEDULE FOR REQUIREMENTS.

SP CEILING MOUNTED STANDARD ROUND PAGING/INTERCOM SYSTEM SPEAKER.

WALL MOUNTED DATA OUTLET (18" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUIT(S) TO ABOVE CORRIDOR CEILING PER DIV 26. JACKS, FACEPLATE AND CABLING PER DIV 27. SUBSCRIPT "X" DESIGNATES QUANTITY OF DATA

CABLES. REFER TO FACEPLATE DETAILS.

X

ABBREVIATIONS

AAP - AREA ALARM PANEL - MEDICAL GAS

ACC - ACCESS

ADJ - ADJUSTABLE

AF - ARC FAULT CIRCUIT INTERRUPTER

AFCI - ARC FAULT CIRCUIT INTERRUPTER

AFF - ABOVE FINISHED FLOOR TO BOTTOM OF ITEM

AFG - ABOVE FINISHED GRADE TO BOTTOM OF ITEM

ALT - ALTERNATE

AP - ACCESS PANEL

APPROX - APPROXIMATE

ARCH - ARCHITECT OR ARCHITECTURAL

ASSY - ASSEMBLY

ATS - AUTOMATIC TRANSFER SWITCH

BLDG - BUILDING

BOE - BOTTOM OF EQUIPMENT

BOT - BOTTOM

BTWN - BETWEEN

CKT - CIRCUIT

CLG - CEILING

CMU - CONCRETE MASONRY UNIT

CONN - CONNECT OR CONNECTION

CORR - CORRIDOR

CTR - CENTER

D - DEPTH

DET - DETAIL

DIA - DIAMETER

DIM - DIMENSION

DIV - DIVISION

DN - DOWN

DWG - DRAWING

EA - EACH

EC - ELECTRICAL (DIVISION 26)

EJ - EXPANSION JOINT

ELEC - ELECTRICAL

ELEV - ELEVATION OR ELEVATOR

EM - EMERGENCY

EQ - EQUAL

EQS - EQUIPMENT SUPPLIER

EQUIP - EQUIPMENT

ETR - EXISTING TO REMAIN

EX - EXISTING

EXP - EXPANSION

EXT - EXTERIOR

FCE - FIRE CONTROL EQUIPMENT

FF - FINISHED FLOOR ELEVATION

FLR - FLOOR

FSC - FIRE SUPPRESSION (DIVISION 21)

FT - FEET

FTG - FOOTING

GC - GENERAL CONSTRUCTION TRADES (DIVISION 01)

GF - GROUND FAULT CIRCUIT INTERRUPTER

GFCI - GROUND FAULT CIRCUIT INTERRUPTER OR GOVERNMENT

FURNISHED CONTRACTOR INSTALLED

GFFT - GROUND FAULT FEED THRU

HC - HVAC (DIVISION 23)

HP - HORSE POWER OR HIGH POINT

HVAC - HEATING, VENTILATING, AND AIR CONDITIONING

ID - INSIDE DIAMETER

IN - INCHES

KEC - KITCHEN EQUIPMENT

L - LENGTH

LBS - POUNDS

MAP - MASTER ALARM PANEL (MEDICAL GAS)

MAX - MAXIMUM

MEZZ - MEZZANINE

MFR - MANUFACTURER

MH - MANHOLE OR MOUNTING HEIGHT TO CENTER LINE OF ITEM

MIN - MINIMUM OR MINUTE

MISC - MISCELLANEOUS

MTD - MOUNTED

MTG - MOUNTING

NIC - NOT IN CONTRACT

NOM - NOMINAL

NTS - NOT TO SCALE

OD - OUTSIDE DIAMETER

OFCI - OWNER FURNISHED GC INSTALLED

OFOI - OWNER FURNISHED OWNER INSTALLED

PC - PLUMBING (DIVISION 22)

PLBG - PLUMBING

RAD - RADIUS

REC - RECESSED

REQD - REQUIRED

RI - ROUGH-IN

S - SURFACE MOUNTED

SC - SECURITY (DIVISION 28)

SCH - SCHEDULE

SHT - SHEET

SMS - SECURITY MANAGEMENT SYSTEM

SPEC - SPECIFICATIONS

SQ - SQUARE

SS - STAINLESS STEEL

STD - STANDARD

STRUC - STRUCTURAL OR STRUCTURE

SUC - SITE UTILITY CONTRACTOR

TC - TECHNOLOGY (DIVISION 27)

TEMP - TEMPERATURE

TOE - TOP OF EQUIPMENT

TYP - TYPICAL

UNO - UNLESS NOTED OTHERWISE

VFD - VARIABLE FREQUENCY DRIVE

VOL - VOLUME

W/ - WITH

W/O - WITHOUT

WP - WEATHERPROOF

ZVC - ZONE VALVE CABINET

CABLE JACKET JACK USAGE

YELLOW YELLOW WIFI - VA

RED RED SECURITY

BLUE BLUE GENERAL DATA

DATA CABLING COLOR CODE

DESIGN-AIRE ENGINEERING, INC.

www.daengineering.comwww.daengineering.com voice (317) 464-9090

2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

FCA - Create Code Compliant Research Laboratory Space in Building 1

657-23-113JB

Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM

08-6231 1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

CONSTRUCTION DOCUMENTS

12-22-2023Project Number: 2023-05162.00

JCM JWE

1-TG-001

LEGEND, GENERAL NOTES, INDEX

TECHNOLOGY SHEET LIST

SHEET NUMBER SHEET NAME

1-TG-001 LEGEND, GENERAL NOTES, INDEX

1-TT-100 PARTIAL SECOND FLOOR PLANS - TECHNOLOGY

1-TT-101 PARTIAL THIRD FLOOR PLANS - TECHNOLOGY

1-TT-501 DETAILS

1-TT-502 SECURITY DETAILS & SCHEDULES

40 44