657-23-113JB - Construction Drawings - 11 of 14 - EG.pdf

PDF 683 KB Posted

Attached to
Z1DA--Create Code Compliant Research Laboratory Space in Building 1, 657-23-113JB Federal contract opportunity
Solicitation number
36C25524R0053
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15

About this file

This document contains construction drawings and a related federal contract opportunity announcement for a project to create code compliant research laboratory space in Building 1 at the Saint Louis VA Health Care System.

The drawings provide electrical specifications, symbols, and legend for the project, including details on electrical panels, receptacles, lighting, and other electrical systems. The related federal contract opportunity is Solicitation Number 36C25524R0053, issued by the Department of Veterans Affairs Veterans Health Administration, for the project titled "Z1DA--Create Code Compliant Research Laboratory Space in Building 1, 657-23-113JB". The solicitation requests proposals to perform this construction work, with an unspecified award date. No additional details on pricing, set asides, or incumbent contractors are provided in the materials.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--Create Code Compliant Research Laboratory Space in Building 1, 657-23-113JB, newest first.
File Type Posted
S02-3- As Built from-657-10-104JB_1C-A1.pdf PDF
36C25524R0053 0001.docx DOCX document
S02-657-23-113JB - Create Code Compliant Research Laboratory Space Prebid Questions 20240422.pdf PDF
Pre-Bid Conference Sign-in Sheet 657-23-113 --- Scan04-09-2024-102719.pdf PDF
657-23-113JB - Construction Drawings - 2 of 14 - GJ.pdf PDF
657-23-113JB Specifications - Reduced File Size.pdf PDF
657-23-113JB - Construction Drawings - 10 of 14 - MH.pdf PDF
657-23-113JB - Construction Drawings - 14 of 14 - TT.pdf PDF
657-23-113JB - Construction Drawings - 12 of 14 - EP.pdf PDF
657-23-113JB - Construction Drawings - 9 of 14 - MG.pdf PDF
657-23-113JB - Construction Drawings - 8 of 14 - FP.pdf PDF
657-23-113JB - Construction Drawings - 1 of 14 - GI.pdf PDF
657-23-113JB - Construction Drawings - 13 of 14 - TG.pdf PDF
657-23-113JB - Construction Drawings - 7 of 14 - PM.pdf PDF
657-23-113JB - Construction Drawings - 6 of 14 - PL.pdf PDF
657-23-113JB - Construction Drawings - 5 of 14 - PG.pdf PDF
657-23-113JB - Construction Drawings - 4 of 14 - AE.pdf PDF
657-23-113JB - Construction Drawings - 3 of 14 - HA.pdf PDF
36C25524R0053_1.docx DOCX document
Show all 19

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELECTRICAL SYMBOLS

EXISTING OUTLET OR DEVICE TO REMAIN. MAINTAIN EXISTING CIRCUITING.

DASH SYMBOL INDICATES PARTICULAR OUTLET OR DEVICE TO BE REMOVED AND CIRCUITRY MADE CONTINUOUS WHERE

REQUIRED.

ELECTRICAL CONNECTION.

20A-125V SINGLE RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERWISE).

SPECIAL PURPOSE RECEPTACLE. REFER TO NOTE ON PLAN.

20A-125V DOUBLE DUPLEX RECEPTACLE. NEMA 5-20R, (18" MH UNLESS NOTED OTHERWISE) TWO GANG ASSEMBLY.

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R WITH BOTTOM OUTLET CONTROLLED BY WALL SWITCH. (18" MH UNLESS

NOTED OTHERWISE).

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, WITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED

OTHERWISE).

20A-125V WEATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R (HORIZONTAL 18" MH UNLESS NOTED OTHERWISE) WITH

TAYMAC #MM420G EXTRA DUTY GRAY COVER, VERTICAL MOUNT.

20A-125V WEATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R WITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED OTHERWISE), WITH TAYMAC #MM420G EXTRA DUTY GRAY COVER, VERTICAL MOUNT.

20A-125V POWERLOCK GROUNDING TYPE RECEPTACLE, HOSPITAL USE (66" MH UNLESS NOTED OTHERWISE).

20A-125V DUPLEX PEDESTAL TYPE FLOOR RECEPTACLE, NEMA 5-20R, IN HUBBELL BA-2527 FLOOR BOX WITH SA-2525

COVERPLATE AND SC-3091 HOUSING. PROVIDE CARPET FLANGE WHERE REQUIRED.

20-125V DUPLEX RECEPTACLE, NEMA 5-20R, WITH ISOLATED GROUND (18" MH UNLESS NOTED OTHERWISE).

20A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-20R (18" MH UNLESS NOTED OTHERWISE).

30A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-30R (18" MH UNLESS NOTED OTHERWISE).

50A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-50R (18" MH UNLESS NOTED OTHERWISE).

20A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-20R (18" MH UNLESS NOTED OTHERWISE).

30A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-30R (18" MH UNLESS NOTED OTHERWISE).

50A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-50R (18" MH UNLESS NOTED OTHERWISE).

JUNCTION BOX. SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POWER.

MULTI-OUTLET RECEPTACLES ASSEMBLY, NEMA 5-15R (SINGLE OUTLETS ON 18" CENTERS) (46" MH UNLESS NOTED

OTHERWISE).

CLOCK HANGER OUTLET, SINGLE NEMA 5-15R RECESSED IN COVER PLATE (84" MH UNLESS NOTED OTHERWISE).

SINGLE POLE SWITCH (46" MH UNLESS NOTED OTHERWISE).

TWO POLE WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).

MULTI-WAY WALL SWITCH, # INDICATES NUMBER OF WAYS (46" MH UNLESS NOTED OTHERWISE).

SWITCH WITH NEON PILOT LIGHT. ONE-GANG ASSEMBLY (46" MH UNLESS NOTED OTHERWISE).

KEY OPERATED WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).

LIGHTING DIMMER SWITCH (46" MH UNLESS NOTED OTHERWISE) 1000 WATTS UNLESS OTHERWISE INDICATED.

SWITCH WITH RECEPTACLE (46" MH UNLESS NOTED OTHERWISE) STANDARD TWO-GANG ASSEMBLY OF SWITCH AND

RECEPTACLE.

FLUSH FRACTIONAL HORSEPOWER MOTOR STARTER WITH NEON PILOT LIGHT. ONE-GANG ASSEMBLY (46" MH UNLESS

NOTED OTHERWISE).

HP RATED WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).

DISCONNECT SWITCH.

MOTOR STARTER.

COMBINATION MOTOR STARTER AND DISCONNECT SWITCH.

ELECTRIC MOTOR.

ELECTRICAL PANEL OR SWITCHBOARD PER DRAWINGS.

PULL BOX.

LINE VOLTAGE THERMOSTAT.

UNIT HEATER.

FAN COIL.

ELECTRIC BASEBOARD HEATER.

AIR CONDITIONER.

CONDENSING UNIT.

UNIT VENTILATOR.

CORD REEL.

POWER POLE.

PHOTOELECTRIC SENSOR.

LIGHTING CONTACTOR.

CEILING MOUNTED OCCUPANCY SENSOR.

WALL MOUNTED OCCUPANCY SENSOR.

CEILING MOUNTED DAYLIGHT SENSOR.

OCCUPANCY SENSOR POWER PACK.

PUSHBUTTON (46" MH UNLESS NOTED OTHERWISE) EDWARDS 852 (120 VOLT).

BUZZER (90" MH UNLESS NOTED OTHERWISE) EDWARDS 340-A (120 VOLT).

4" DIAMETER (90" MH UNLESS NOTED OTHERWISE) EDWARDS "ADAPTABEL" (120 VOLT).

GF

WP

WP/GF

T

IG

20A

30A

50A

20A

50A

30A

J

P

K

DM

R

H

UH

FC

AC

CU

UV

PP

OS

M

OS

M

DS

OP

PC

T

B

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (44" MH UNLESS NOTED OTHERWISE).

C

M

CR

LC

P/B

ELAPSED TIME INDICATOR CLOCK (90" MH UNLESS NOTED OTHERWISE) WITH RESET SWITCH (46" MH UNLESS NOTED

OTHERWISE).

INTERCOM SYSTEM DESK MOUNTED MASTER CONTROL STATION. SUBSCRIPT "W" INDICATES WALL MOUNT (46" MH

UNLESS NOTED OTHERWISE).

INTERCOM STAFF STATION (46" MH UNLESS NOTED OTHERWISE).

INTERCOM HORN TYPE SPEAKER (84" MH UNLESS NOTED OTHERWISE).

INTERCOM SPEAKER FLUSH MOUNT IN CEILING.

I

M

H

S

DUCT HEATER.H

DH

H

EB

LOW-VOLTAGE MOMENTARY WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).L

ABBREVIATIONS

AAP - AREA ALARM PANEL - MEDICAL GAS

ACC - ACCESS

ADJ - ADJUSTABLE

AF - ARC FAULT CIRCUIT INTERRUPTER

AFCI - ARC FAULT CIRCUIT INTERRUPTER

AFF - ABOVE FINISHED FLOOR TO BOTTOM OF ITEM

AFG - ABOVE FINISHED GRADE TO BOTTOM OF ITEM

ALT - ALTERNATE

AP - ACCESS PANEL

APPROX - APPROXIMATE

ARCH - ARCHITECT OR ARCHITECTURAL

ASSY - ASSEMBLY

ATS - AUTOMATIC TRANSFER SWITCH

BLDG - BUILDING

BOE - BOTTOM OF EQUIPMENT

BOT - BOTTOM

BTWN - BETWEEN

CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED

CKT - CIRCUIT

CLG - CEILING

CMU - CONCRETE MASONRY UNIT

CONN - CONNECT OR CONNECTION

CONTR - CONTRACTOR

CORR - CORRIDOR

CTR - CENTER

D - DEPTH

DET - DETAIL

DIA - DIAMETER

DIM - DIMENSION

DIV - DIVISION

DN - DOWN

DW - DISHWASHER

DWG - DRAWING

EA - EACH

EC - ELECTRICAL (DIVISION 26)

EJ - EXPANSION JOINT

ELEC - ELECTRICAL

ELEV - ELEVATION OR ELEVATOR

EM - EMERGENCY

EQ - EQUAL

EQS - EQUIPMENT SUPPLIER

EQUIP - EQUIPMENT

E/R - EXISTING TO BE RELOCATED

EX - EXISTING TO REMAIN

EXP - EXPANSION

EXT - EXTERIOR

FCE - FIRE CONTROL EQUIPMENT

FF - FINISHED FLOOR ELEVATION

FLR - FLOOR

FSC - FIRE SUPPRESSION (DIVISION 21)

FT - FEET

FTG - FOOTING

GC - GENERAL CONTRACTOR

GF - GROUND FAULT CIRCUIT INTERRUPTER

GFB - GROUND FAULT BREAKER

GFCI - GROUND FAULT CIRCUIT INTERRUPTER OR GOVERNMENT

FURNISHED CONTRACTOR INSTALLED

GFFT - GROUND FAULT FEED THRU

HC - HVAC (DIVISION 23)

HP - HORSE POWER OR HIGH POINT

HVAC - HEATING, VENTILATING, AND AIR CONDITIONING

ID - INSIDE DIAMETER

IN - INCHES

KEC - KITCHEN EQUIPMENT

L - LENGTH

LBS - POUNDS

MAP - MASTER ALARM PANEL (MEDICAL GAS)

MAX - MAXIMUM

MEZZ - MEZZANINE

MFR - MANUFACTURER

MH - MANHOLE OR MOUNTING HEIGHT TO CENTER LINE OF ITEM

MIN - MINIMUM OR MINUTE

MISC - MISCELLANEOUS

MTD - MOUNTED

MTG - MOUNTING

NIC - NOT IN CONTRACT

NOM - NOMINAL

NTS - NOT TO SCALE

OD - OUTSIDE DIAMETER

OFCI - OWNER FURNISHED CONTRACTOR INSTALLED

OFOI - OWNER FURNISHED OWNER INSTALLED

PC - PLUMBING (DIVISION 22)

PLBG - PLUMBING

RAD - RADIUS

REC - RECESSED

REQD - REQUIRED

RF - REFRIGERATOR

RI - ROUGH-IN

S - SURFACE MOUNTED

SC - SECURITY CONTRACTOR

SCH - SCHEDULE

SHT - SHEET

SMS - SECURITY MANAGEMENT SYSTEM

SPEC - SPECIFICATIONS

SQ - SQUARE

SS - STAINLESS STEEL

STD - STANDARD

STRUC - STRUCTURAL OR STRUCTURE

SUC - SITE UTILITY

TC - TECHNOLOGY (DIV 27)

TEMP - TEMPERATURE

TOE - TOP OF EQUIPMENT

TYP - TYPICAL

UNO - UNLESS NOTED OTHERWISE

VFD - VARIABLE FREQUENCY DRIVE

VOL - VOLUME

W/ - WITH

W/O - WITHOUT

WP - WEATHERPROOF

ZVC - ZONE VALVE CABINET

WIREMOLD RACEWAY, AS NOTED ON PLANS.

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R WITH 2 INTEGRAL USB CHARGERS (18" MH UNLESS NOTED OTHERWISE).

NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT

TO MODIFICATIONS ON OTHER DRAWINGS.

ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT

NECESSARILY BE USED ON THIS PROJECT.

SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POWER. SPECIFICATION IS SAME AS RESPECTIVE ROUND DEVICE.

J

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, IN HUBBELL BA-2527 FLUSH FLOOR BOX WITH ROUND SA-3925 COVERPLATE.

PROVIDE CARPET FLANGE WHERE REQUIRED.

E2

B

E2

DETAIL: B = DETAIL DESIGNATION

E2 = SHEET WHERE DETAIL IS LOCATED

SECTION: 1 = SECTION DESIGNATION

E2 = SHEET WHERE SECTION IS LOCATED

PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN.

DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.

GENERAL FLOOR PLAN NOTES

WIRE & CONDUIT IN WALL OR ABOVE CEILING.

WIRE & CONDUIT IN OR BELOW SLAB OR GRADE.

EACH ARROWHEAD REPRESENTS ONE COMPLETE CIRCUIT; "X" DENOTES PANEL NAME; NUMBER(S)

DENOTES CIRCUIT(S).

LADDER TRAY, 12" x 4" DEEP UNLESS NOTED OTHERWISE.

CONDUIT FOR DATA CIRCUITRY.DAT

WIRE & CONDUIT FOR FIRE ALARM CIRCUITRY.FA

WIRE & CONDUIT FOR NURSE CALL CIRCUITRY.NC

EXISTING WIRE & CONDUIT TO REMAIN.EX

CONDUIT TO BE REMOVED.

WIRE & CONDUIT FOR NIGHT LIGHT CIRCUITRY.NL

CONDUIT FOR PHONE CIRCUITRY.PHO

WIRE & CONDUIT FOR SECURITY SYSTEM CIRCUITRY.SEC

WIRE RUN IN SURFACE WIREWAY.W

CABLE MANAGEMENT SYSTEM PATHWAY.CM

X - 1,2

WIRE & CONDUIT FOR EMERGENCY CIRCUITRY.EM

WIRE & CONDUIT FOR SOUND SYSTEM CIRCUITRY.S

WIRE & CONDUIT FOR INTERCOM SYSTEM CIRCUITRY.I

WIRE & CONDUIT FOR TELEVISION SYSTEM CIRCUITRY.TV

CABLE TRAY, 12" x 4" DEEP UNLESS NOTED OTHERWISE.

4"

4"

4"

T2 1 ELEVATION: 1 = ELEVATION DESIGNATION

T2 = SHEET WHERE ELEVATION IS LOCATED

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERWISE). WHEN SHOWN, RECEPTACLE TO HAVE

"CONTROLLED" MARKINGS.

LIGHTING CONTROL DETAIL NOTE. APPLIES TO THE LIGHTING CONTROL SEQUENCE OF OPERATIONS

SCHEDULE FOR ROOM CONTROL.

3 DEVICE QUANTITY - POWER NOTE. REFER TO DEVICE QUANTITIES - POWER SCHEDULE.

GENERAL NOTES

A. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE

OBTAINED FROM THE ARCHITECTURAL REFLECTED CEILING PLAN.

B. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF

EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS

BETWEEN DEVICES.

C. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE

CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN

INSULATED EQUIPMENT GROUNDING CONDUCTOR.

GENERAL NOTES - DEMOLITION

A. FOR EXISTING EQUIPMENT, SUCH AS LIGHTING FIXTURES, WIRING DEVICES,

CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP

CONDUITS AT THE AREA OF WORK PERIMETER AND REMOVE CONDUIT WITHIN

THE WORK AREA, DISCONNECT WIRING AT THE OVERCURRENT PROTECTIVE

DEVICE AND REMOVE WIRING COMPLETELY FROM THE ABANDONED CONDUITS.

B. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE OVERCURRENT

PROTECTIVE DEVICE. COMPLETELY REMOVE ALL ABANDONED WIRING.

C. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS

PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.

GENERAL NOTES

A. THESE NOTES APPLY EQUALLY TO THE FULL SET OF DOCUMENTS.

B. ACOUSTICAL CEILING ACCESS IDENTIFICATION MARKERS: COLORED MARKERS WITH

PRESSURE SENSITIVE ADHESIVE ON ONE SIDE, PAPER OR PLASTIC, 6 TO 9 MM (1/4 TO 3/8

INCH) DIAMETER. REFER TO SPECIFICATION 09 51 00 SECTION 2.6.C.

1. COLOR CODE: PROVIDE THE FOLLOWING COLOR MARKERS FOR SERVICE IDENTIFICATION:

• RED - SPRINKLER SYSTEM: VALVES AND CONTROLS.

• GREEN - DOMESTIC WATER: VALVES AND CONTROLS.

• YELLOW - CHILLED WATER AND HEATING WATER.

• ORANGE - DUCTWORK: FIRE DAMPERS.

• BLUE - DUCTWORK: DAMPERS AND CONTROLS.

• BLACK - GAS: LABORATORY, MEDICAL, AIR AND VACUUM.

C. INCLUDE ALL WORK NECESSARY TO ACCOMMODATE PHASING. REFER TO

ARCHITECTURAL DRAWINGS AND GENERAL REQUIREMENTS SECTION 01 00 00.

D. CONTRACTOR SHALL REFER TO ALL SPECIFICATION SECTIONS AND THE

DRAWINGS FOR DETAILS OF BUILDING CONSTRUCTION TO ENSURE SPACE AND

SATISFACTORY ARRANGEMENT FOR THEIR WORK. THE VARIOUS DRAWINGS

COMPRISING THE SET ARE INTERDEPENDENT AND MUST BE USED JOINTLY AT

ALL TIMES. THE CONTRACTOR SHALL REFER TO THE GENERAL REQUIREMENTS

OF THE CONTRACT. THE NOTES AND SYMBOLS INDICATED ON THE DRAWINGS

ARE FOR THE GUIDANCE OF ALL TRADES INVOLVED IN THE PROJECT AND MUST

BE FOLLOWED TO EXECUTE THE WORK AS INTENDED. IF DISCREPANCIES OCCUR,

CONTACT THE COR THROUGH THE CONTRACTING OFFICER FOR CLARIFICATION

BEFORE PROCEEDING.

E. ALL WORK MUST BE COORDINATED WITH THE CONTRACTING OFFICER AND (FOR

ALL OTHERS) TO MAINTAIN OPERATION OF THE EXISTING FACILITY.

F. ALL WORK SHALL BE PERFORMED IN COMPLETE COMPLIANCE WITH ALL CURRENT

OVERNING CODES AND STANDARDS.

G. EXISTING CONDITIONS SHOWN HAVE BEEN BASED UPON AVAILABLE DRAWING

INFORMATION, AND MAY BE AT VARIANCE WITH ACTUAL WORK IN PLACE. THE

CONTRACTOR SHALL TAKE ALL NECESSARY FIELD MEASUREMENTS AND FIELD

VERIFY ALL CONDITIONS AFFECTING THE EXECUTION OF THE WORK. ANY

DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THE WORK SHOWN ON THE

CONTACT DOCUMENTS WHICH MAY IMPACT THE PROGRESS OF THE WORK SHALL

BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER IN WRITING

FOR RESOLUTION BEFORE PROCEEDING WITH THE WORK.

H. REFER TO ARCHITECTURAL FIRE-RATED PARTITION PLAN(S) FOR LOCATIONS AND

FIRE-RATING OF NEW AND EXISTING WALL ASSEMBLIES. ALL PENETRATIONS

THROUGH FIRE-RATED ASSEMBLIES SHALL BE PROJECTED AND/OR FIRE-STOPPED

AS REQUIRED TO MAINTAIN FIRE-RATINGS INDICATED. COORDINATE WITH ALL

TRADES TO ENSURE FIRE-RATED PENETRATION REQUIREMENTS AND DETAILS

ARE MET.

I. ANNULAR SPACE OF ALL PIPE, CONDUIT, DUCT AND OTHER SIMILAR PENETRATIONS

OF FIRE RATED ASSEMBLIES SHALL BE FIRESTOPPED. IN ADDITION, PENETRATIONS

THROUGH 0-HOUR RATED WALLS AND FLOORS SHALL BE FIRESTOPPED TO RETARD

PASSAGE OF FIRE AND SMOKE.

J. ALL CONDUITS IN FINISHED ROOMS AND CORRIDORS SHALL BE CONCEALED IN A

WALL OR ABOVE CEILING.

K. ACCESS PANELS IN NON ACCESSIBLE CEILINGS SHALL BE PROVIDED FOR ALL

ELECTRICAL ITEMS REQUIRING ACCESS.

L. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF

LIGHTS, SPEAKERS, NURSE CALL DEVICES, ETC.

M. ALL CUTTING AND PATCHING REQUIRED FOR THIS PROJECT SHALL BE INCLUDED IN

THE CONTRACT. REFINISH ANY SURFACE DISTURBED UNDER THIS WORK TO MATCH

EXISTING.

N. ANY REMOVED EQUIPMENT SHALL BE TURNED OVER TO THE VA. ITEMS NOT DESIRED

BY THE VA SHALL BE REMOVED FROM THE PREMISES AND DISPOSED OF PROPERLY

BY THE CONTRACTOR.

O. THE CONTRACT DRAWINGS ARE NOT INTENDED TO SHOW EVERY VERTICAL OR HORIZONTAL

OFFSET WHICH MAY BE NECESSARY TO COMPLETE THE SYSTEMS. COORDINATE WORK IN

ADVANCE WITH ALL OTHER TRADES AND REPORT IMMEDIATELY AND DIFFICULTIES

WHICH CAN BE ANTICIPATED.

P. ALL ABANDONED EXTRANEOUS CONDUITS, WIRING, DEVICES, ETC. SHALL BE REMOVED.

Q. REFER TO MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION CONCERNING

MECHANICAL EQUIPMENT THAT REQUIRES ELECTRICAL CONNECTIONS.

• R.

DESIGN-AIRE ENGINEERING, INC.

www.daengineering.comwww.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

FCA - Create Code Compliant Research Laboratory Space in Building 1

657-23-113JB

Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM

08-6231 1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

CONSTRUCTION DOCUMENTS

12-22-2023Project Number: 2023-05162.00

JSF PJM

1-EG-001

LEGEND, GENERAL NOTES, INDEX

ELECTRICAL SHEET LIST

SHEET NUMBER SHEET NAME

1-EG-001 LEGEND, GENERAL NOTES, INDEX

1-EG-002 SCHEDULES

1-EP-100 PARTIAL SECOND FLOOR PLANS - ELECTRICAL

1-EP-101 PARTIAL THIRD FLOOR PLANS - ELECTRICAL

1-EP-102 PARTIAL ROOF PLAN

35 44

DESIGN-AIRE ENGINEERING, INC.

www.daengineering.comwww.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

FCA - Create Code Compliant Research Laboratory Space in Building 1

657-23-113JB

Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM

08-6231 1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

CONSTRUCTION DOCUMENTS

01-18-2024Project Number: 2023-05162.00

JSF PJM

1-EG-002

SCHEDULES

3.76 kVA 3.76 kVA (10 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes: EXISTING PANEL. NORMAL POWER.

$ = GFCI BREAKER

Total Est. Demand: 10 A

Total Conn.: 10 A

Total Est. Demand: 3.76 kVA

Total Conn. Load: 3.76 kVA

Receptacle 3760 VA 100.00% 3760 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 1.44 kVA 0.54 kVA 1.78 kVA

41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42

39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40

37 Spare 20 A 1 0 VA 0 VA 1 20 A SPARE 38

35 Spare 20 A 1 0 VA 0 VA 1 20 A SPARE 36

33 Spare 20 A 1 0 VA 0 VA 1 20 A SPARE 34

31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 32

29 $REC 2C19 20 A 1 1600... 0 VA 1 20 A Spare 30

27 Spare 20 A 1 0 VA 360 VA 1 20 A REC 2C19 28

25 REC 2C19 20 A 1 360 VA 900 VA 1 20 A REC 2C19 26

23 Spare 20 A 1 0 VA 180 VA 1 20 A REC 2C19 24

21 Spare 20 A 1 0 VA 180 VA 1 20 A REC 2C19 22

19 Spare 20 A 1 0 VA 180 VA 1 20 A REC 2C19 20

17 LIGHTS RMS... 20 A 1 0 VA 0 VA 1 20 A RECPT RMS 2C11,12 18

15 RECEPT RM... 20 A 1 0 VA 0 VA 1 20 A REC LTS 2C12, 13 16

13 COMPUTER LTS... 20 A 1 0 VA 0 VA 1 20 A LTS 2C5, 6 7, COMP... 14

11 CORRIDOR LTS 20 A 1 0 VA 0 VA 1 20 A LTS RM 2C5,6,7 12

9 -- -- -- 0 VA 0 VA 1 20 A RECEPT LTS 2C3 10

7 AC ROOM 2C3 20 A 2 0 VA 0 VA 1 20 A RECEPT RM 2C3 8

5 RECEPT SW WALL 2C4 20 A 1 0 VA 0 VA 1 20 A LTS, REC, FCU 2C29 6

3 RECEPT NE WALL... 20 A 1 0 VA 0 VA 1 20 A LTS 2C27,28 RCPT... 4

1 RECEPT NW WALL... 20 A 1 0 VA 0 VA 1 20 A LIGHTS RMS 2C25-26 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 208Y/120V-3PH-4W-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type:

Location: CORRIDOR H205 Mounting: Surface A.I.C. Rating:

Panel: 1-L22L

1.72 kVA 1.97 kVA (5 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes: EXISTING PANEL. NORMAL POWER.

Total Est. Demand: 5 A

Total Conn.: 5 A

Total Est. Demand: 1.97 kVA

Receptacle 720 VA 100.00% 720 VA Total Conn. Load: 1.72 kVA

Lighting 1000 VA 125.00% 1250 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 0.18 kVA 0.00 kVA 1.54 kVA

41 -- -- -- 0 VA 360 VA 1 20 A REC 2C19 42

39 USED 20 A 2 0 VA 0 VA -- -- -- 40

37 Receptacle 20 A 1 180 VA 0 VA 2 30 A SPARE 38

35 Lighting 2C19 20 A 1 1000... 0 VA -- -- -- 36

33 RM 2C2 AC 20 A 1 0 VA 0 VA 2 20 A 2C10 UPS 34

31 RECPT RM2C203 20 A 1 0 VA 0 VA 1 20 A SPARE 32

29 RECPT RM2C20 20 A 1 0 VA 0 VA 1 20 A RECPT 210 RM 220 30

27 RECPT RM 2C20/30 4W 20 A 1 0 VA 0 VA 1 20 A RECPT 2C7 28

25 -- -- -- 0 VA 0 VA 1 20 A RECPT 2C7 26

23 RECPT RM 2C19 30 A 2 0 VA 0 VA 1 20 A LTS RC RM 2C9 24

21 -- -- -- 0 VA 0 VA 1 20 A RECPT ROOM 2C3 22

19 2C16 USED 30 A 2 0 VA 0 VA -- -- -- 20

17 REC 2C13,2C14 20 A 1 0 VA 0 VA 2 40 A FCU RM C219 18

15 USED 20 A 1 0 VA 0 VA 1 30 A RECP RMC219 16

13 USED 30 A 1 0 VA 0 VA 1 30 A 208V REC KITCHEN 14

11 RECPT RM 2C13,14,15 30 A 1 0 VA 0 VA 1 20 A 208V REC KITCHEN 12

9 RECEPT RM 2C15 20 A 1 0 VA 0 VA 1 20 A FLOOR CLEANER 10

7 FLOOR CLEANER 20 A 1 0 VA 0 VA 1 20 A FLOOR CLEANER 8

5 REC 2C19 20 A 1 180 VA 0 VA -- -- -- 6

3 -- -- -- 0 VA 0 VA -- -- -- 4

1 2C10 UPS 20 A 2 0 VA 0 VA 3 15 A FCU 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 208Y/120V-3PH-4W-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type:

Location: CORRIDOR H205 Mounting: Surface A.I.C. Rating:

Panel: 1-L22R

3.4 kVA 3.4 kVA (9 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes: EXISTING PANEL. NORMAL POWER.

$ = GFCI BREAKER

Total Est. Demand: 9 A

Total Conn.: 9 A

Total Est. Demand: 3.4 kVA

Total Conn. Load: 3.4 kVA

Receptacle 3400 VA 100.00% 3400 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 1.60 kVA 1.26 kVA 0.54 kVA

41 FUME HOOD 3C13 20 A 1 0 VA 0 VA -- -- -- 42

39 CORR EAST END... 20 A 1 0 VA 0 VA -- -- -- 40

37 CORR E END CENTER 20 A 1 0 VA 0 VA 3 20 A AC 3C09 38

35 REC N WALL 3C26 20 A 1 0 VA 0 VA 1 20 A PLUGMOLD C7,C9 36

33 REC W WALL 3C26 20 A 1 0 VA 0 VA 1 20 A SHORTED 34

31 CEILING LTS AND... 20 A 1 0 VA 0 VA 1 20 A REC RM 3C18 N & S 32

29 ISLAND TABLE REC 20 A 1 0 VA 0 VA 1 20 A LTS 3C20,21,22,23 30

27 PLUGMOLD WALL 20 A 1 0 VA 0 VA 1 20 A LTS 3C18,19 28

25 CLNG LTS RM 3C17 20 A 1 0 VA 0 VA 1 20 A AUTOCLAVE 3C15,16 26

23 RECEPTS N WALL,... 20 A 1 0 VA 0 VA 1 20 A E WALL 3C26 24

21 Receptacle LAB 3C17 20 A 1 720 VA 0 VA 1 20 A 3C14 RECPT 22

19 CEILING LTS 3C13-14 20 A 1 0 VA 1600... 1 20 A $ REC 3C17 20

17 REC 3C17 20 A 1 360 VA 180 VA 1 20 A REC 3C17 18

15 Receptacle Room 3C17 20 A 1 540 VA 0 VA 1 20 A CEILING LTS 3C12 16

13 CEILING LITS 3C11 20 A 1 0 VA 0 VA 1 20 A CEILING LTS C7, 3C9 14

11 3C4 RECPT WEST... 20 A 1 0 VA 0 VA 1 20 A Spare 12

9 3C4 RECEPT E WALL 20 A 1 0 VA 0 VA 1 20 A Spare 10

7 CEILING LITES 3C4 20 A 1 0 VA 0 VA 1 20 A 3C6 CEILING LITES &... 8

5 WIREMOLD ROOM 301 20 A 1 0 VA 0 VA 1 20 A RECPT C304, 305 6

3 LITES 3C30-C 20 A 1 0 VA 0 VA 1 20 A WIREMOLD RM 301 4

1 ICE MACHINE 3C29 20 A 1 0 VA 0 VA 1 20 A LITES RC301,2,3,4 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 208Y/120V-3PH-4W-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type:

Location: CORRIDOR H304 Mounting: Surface A.I.C. Rating:

Panel: 1-L32L

1.17 kVA 1.33 kVA (4 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes: EXISTING PANEL. NORMAL POWER.

Total Est. Demand: 4 A

Total Conn.: 3 A

Total Est. Demand: 1.33 kVA

Receptacle 540 VA 100.00% 540 VA Total Conn. Load: 1.17 kVA

Lighting 629 VA 125.00% 786 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 0.87 kVA 0.18 kVA 0.12 kVA

47 -- -- -- 0 VA 0 VA 1 20 A USED 48

45 Spare 20 A 2 0 VA 0 VA 1 20 A USED 46

43 Spare 20 A 1 0 VA 0 VA 1 20 A USED 44

41 Spare 20 A 1 0 VA 0 VA 1 20 A PLUG MOLD RM 3C27 42

39 3C26 20 A 1 0 VA 0 VA 1 20 A WEST RECEPT 3C17 40

37 3C26 20 A 1 0 VA 0 VA 1 20 A FC 3C26,27 38

35 Spare 20 A 1 0 VA 0 VA 1 20 A FC... 36

33 Receptacle 20 A 1 180 VA 0 VA 1 20 A FC 3C12, 3C4,8 34

31 3C23 RECEPT 20 A 1 0 VA 0 VA -- -- -- 32

29 3C23 RECEPT 20 A 1 0 VA 0 VA 2 20 A Spare 30

27 3C6 CENTER FUSE 20 A 1 0 VA 0 VA -- -- -- 28

25 3C6 CENTER FUSE 20 A 1 0 VA 0 VA 2 20 A Spare 26

23 -- -- -- 0 VA 0 VA -- -- -- 24

21 SPARE 20 A 2 0 VA 0 VA 2 20 A TWIST LOCK RM C11 22

19 -- -- -- 0 VA 360 VA 1 20 A REC 3C17 20

17 SPARE 20 A 2 0 VA 117 VA 1 20 A Lighting LAB 3C17 18

15 CENTER FUSE 3C26 20 A 1 0 VA 0 VA 1 20 A Spare 16

13 CENTER FUSE 3C26 20 A 1 0 VA 512 VA 1 20 A Lighting LAB 3C17 14

11 -- -- -- 0 VA 0 VA -- -- -- 12

9 -- -- -- 0 VA 0 VA -- -- -- 10

7 SUBFEED PNL SP1L43 20 A 3 0 VA 0 VA 3 20 A Spare 8

5 -- -- -- 0 VA 0 VA -- -- -- 6

3 -- -- -- 0 VA 0 VA -- -- -- 4

1 PENTHOUSE PNL 20 A 3 0 VA 0 VA 3 20 A FUME HOOD 3C18 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 208Y/120V-3PH-4W-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type:

Location: CORRIDOR H304 Mounting: Surface A.I.C. Rating:

Panel: 1-L32R

NOTES:

LUMINAIRES

MARK

LAMPS

VA VOLTAGE MANUFACTURER CATALOG NO. DESCRIPTION

OTHER ACCEPTABLE

MANUFACTURERS DIFFUSING MEDIA

MOUNTING SIZE

S E

E N

O T

E

LUMENS COLOR

S-SURFACE

R-RECESSED

SM-STEM MTD

WM-WALL MTD

C-CHAIN MTD

UC-UNDER CAB

CS-CEIL SURFACE D

IA

M

E T

E R

W

ID

T H

L E

N G

T H

D E

P T

H

FP24 6000 4000K 128 120 ACUITY EPANL-2X4-4800LM-80CRI-40K-MIN10-ZT-MVOLT LED FLAT PANEL WITH WHITE TRIM, 2'X4' 4000K COLOR OR APPROVED EQUAL R 24" 48" 6"

UC1 550/FT 4000K 13 120 AIREY THOMPSON 13HC-H-40K-24-2-0-AMS UNDER CABINET LUMINAIRE ANTI-MICROBIAL FINISH HOPSITAL GRADE, 24" OR APPROVED EQUAL S 2.5" 24" 1"

0.00 kVA

TOTAL CONNECTED ESTIMATED DEMAND

Notes: EXISTING PANEL

EMERGENCY POWER

Total Est. Demand: 0 A

Total Conn.: 0 A

Total Est. Demand: 0 kVA

Total Conn. Load: 0 kVA

Motor 0 VA 0.00% 0 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 0.00 kVA 0.00 kVA 0.00 kVA

29 AIR COND. 20 A 1 0 VA 0 VA 1 20 A 3C21 PLUGMOLD 30

27 PENTHOUSE 20 A 1 0 VA 0 VA 1 20 A 3C21 PLUGMOLD 28

25 PENTHOUSE MW 20 A 1 0 VA 0 VA 1 20 A 3C28 PLUGMOLD 26

23 3C26 RECPT 20 A 1 0 VA 0 VA 1 20 A MICROWAVE 24

21 3C13 20 A 1 0 VA 0 VA 1 20 A 3C18 PLUGMOLD 22

19 Motor LAB 3C17 20 A 1 0 VA 0 VA 1 20 A 3C18 20

17 -- -- -- 0 VA 0 VA 1 20 A 3C26 WIREMOLD 18

15 BC-2 3C17 20 A 2 0 VA 0 VA 1 20 A 3C26 REF 16

13 3C15 PLUGMOLD 20 A 1 0 VA 0 VA 1 20 A 3C13 LGHTS 14

11 3C15 PLUGMOLD 20 A 1 0 VA 0 VA -- -- -- 12

9 3C18 N PLUGMOLD 20 A 1 0 VA 0 VA 2 20 A CENTRIFUGE 10

7 3C13 20 A 1 0 VA 0 VA -- -- -- 8

5 -- -- -- 0 VA 0 VA 2 20 A 3C15 30A RECPT 6

3 -- -- -- 0 VA 0 VA -- -- -- 4

1 EXHAUST FAN ROOF 20 A 3 0 VA 0 VA 2 20 A 3C18 REC 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 208Y/120V-3PH-4W-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type:

Location: CORRIDOR H304 Mounting: Surface A.I.C. Rating:

Panel: 3CEC

9.02 kVA 9.08 kVA (25 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes: EXISTING PANEL

EMERGENCY POWER.

Total Est. Demand: 25 A

Total Conn.: 25 A

Receptacle 8760 VA 100.00% 8760 VA Total Est. Demand: 9.08 kVA

Motor 0 VA 0.00% 0 VA Total Conn. Load: 9.02 kVA

Lighting 256 VA 125.00% 320 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

D Total Load: 3.54 kVA 2.17 kVA 3.31 kVA

41 Lighting 2C19 20 A 1 128 VA 0 VA 1 20 A BLANK 42

39 NOT USED 20 A 1 0 VA 128 VA 1 20 A Lighting LAB 3C17 40

37 -- -- -- 0 VA 0 VA 1 20 A 2C10 RECPT 38

35 -- -- -- 0 VA 0 VA 1 20 A SPARE 36

33 DATA RM 2C10 20 A 3 0 VA 360 VA 1 20 A Receptacle 34

31 Motor 20 A 1 0 VA 360 VA 1 20 A Receptacle 32

29 REC 2C18 20 A 1 0 VA 0 VA 1 20 A GFCI MENS RM 2C08 30

27 NOT USED 20 A 1 0 VA 0 VA 1 20 A RE 2C08 +LTS 28

25 NOT USED 20 A 1 0 VA 0 VA 1 20 A REC 2C08, 07 26

23 REC 3C17 20 A 1 1500... 0 VA 1 20 A REC 2C13 24

21 LTS 2C10 20 A 1 0 VA 0 VA 1 20 A REC 2C01 22

19 REC 3C17 20 A 1 1500... 0 VA 1 20 A REC 2C01, 2C23 20

17 Receptacle 20 A 1 180 VA 0 VA 1 20 A REC 2C19 18

15 Receptacle 20 A 1 180 VA 0 VA 1 20 A FA 2C18 16

13 Receptacle LAB 3C17 20 A 1 180 VA 1500... 1 20 A REC 2C19 14

11 -- -- -- 0 VA 1500... 1 20 A REC 2C19 12

9 BC-1 2C19 20 A 2 0 VA 1500... 1 20 A REC 2C19 10

7 NOT USED 20 A 1 0 VA 0 VA 1 20 A REC 2C10 8

5 REC RM 2C119 20 A 1 0 VA 0 VA 1 20 A REC 2C10 SWALL 6

3 NOT USED 20 A 1 0 VA 0 VA 1 20 A NOT USED 4

1 RACK RM 2C10 20 A 1 0 VA 0 VA 1 20 A NOT USED 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 208Y/120V-3PH-4W-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type:

Location: Mounting: Surface A.I.C. Rating:

Panel: 2CEC

NOTES

1. PROVIDE NEW CIRCUIT BREAKER. MATCH

MANUFACTURER TO OTHER EXISTING CIRCUIT BREAKERS

WITHIN PANEL.

36 44