657-23-113JB - Construction Drawings - 11 of 14 - EG.pdf
PDF 683 KB Posted
- Attached to
- Z1DA--Create Code Compliant Research Laboratory Space in Building 1, 657-23-113JB Federal contract opportunity
- Solicitation number
- 36C25524R0053
About this file
This document contains construction drawings and a related federal contract opportunity announcement for a project to create code compliant research laboratory space in Building 1 at the Saint Louis VA Health Care System.
The drawings provide electrical specifications, symbols, and legend for the project, including details on electrical panels, receptacles, lighting, and other electrical systems. The related federal contract opportunity is Solicitation Number 36C25524R0053, issued by the Department of Veterans Affairs Veterans Health Administration, for the project titled "Z1DA--Create Code Compliant Research Laboratory Space in Building 1, 657-23-113JB". The solicitation requests proposals to perform this construction work, with an unspecified award date. No additional details on pricing, set asides, or incumbent contractors are provided in the materials.
View the file
Other files for this federal contract opportunity
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL SYMBOLS
EXISTING OUTLET OR DEVICE TO REMAIN. MAINTAIN EXISTING CIRCUITING.
DASH SYMBOL INDICATES PARTICULAR OUTLET OR DEVICE TO BE REMOVED AND CIRCUITRY MADE CONTINUOUS WHERE
REQUIRED.
ELECTRICAL CONNECTION.
20A-125V SINGLE RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERWISE).
SPECIAL PURPOSE RECEPTACLE. REFER TO NOTE ON PLAN.
20A-125V DOUBLE DUPLEX RECEPTACLE. NEMA 5-20R, (18" MH UNLESS NOTED OTHERWISE) TWO GANG ASSEMBLY.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R WITH BOTTOM OUTLET CONTROLLED BY WALL SWITCH. (18" MH UNLESS
NOTED OTHERWISE).
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, WITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED
OTHERWISE).
20A-125V WEATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R (HORIZONTAL 18" MH UNLESS NOTED OTHERWISE) WITH
TAYMAC #MM420G EXTRA DUTY GRAY COVER, VERTICAL MOUNT.
20A-125V WEATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R WITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED OTHERWISE), WITH TAYMAC #MM420G EXTRA DUTY GRAY COVER, VERTICAL MOUNT.
20A-125V POWERLOCK GROUNDING TYPE RECEPTACLE, HOSPITAL USE (66" MH UNLESS NOTED OTHERWISE).
20A-125V DUPLEX PEDESTAL TYPE FLOOR RECEPTACLE, NEMA 5-20R, IN HUBBELL BA-2527 FLOOR BOX WITH SA-2525
COVERPLATE AND SC-3091 HOUSING. PROVIDE CARPET FLANGE WHERE REQUIRED.
20-125V DUPLEX RECEPTACLE, NEMA 5-20R, WITH ISOLATED GROUND (18" MH UNLESS NOTED OTHERWISE).
20A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-20R (18" MH UNLESS NOTED OTHERWISE).
30A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-30R (18" MH UNLESS NOTED OTHERWISE).
50A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-50R (18" MH UNLESS NOTED OTHERWISE).
20A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-20R (18" MH UNLESS NOTED OTHERWISE).
30A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-30R (18" MH UNLESS NOTED OTHERWISE).
50A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-50R (18" MH UNLESS NOTED OTHERWISE).
JUNCTION BOX. SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POWER.
MULTI-OUTLET RECEPTACLES ASSEMBLY, NEMA 5-15R (SINGLE OUTLETS ON 18" CENTERS) (46" MH UNLESS NOTED
OTHERWISE).
CLOCK HANGER OUTLET, SINGLE NEMA 5-15R RECESSED IN COVER PLATE (84" MH UNLESS NOTED OTHERWISE).
SINGLE POLE SWITCH (46" MH UNLESS NOTED OTHERWISE).
TWO POLE WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).
MULTI-WAY WALL SWITCH, # INDICATES NUMBER OF WAYS (46" MH UNLESS NOTED OTHERWISE).
SWITCH WITH NEON PILOT LIGHT. ONE-GANG ASSEMBLY (46" MH UNLESS NOTED OTHERWISE).
KEY OPERATED WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).
LIGHTING DIMMER SWITCH (46" MH UNLESS NOTED OTHERWISE) 1000 WATTS UNLESS OTHERWISE INDICATED.
SWITCH WITH RECEPTACLE (46" MH UNLESS NOTED OTHERWISE) STANDARD TWO-GANG ASSEMBLY OF SWITCH AND
RECEPTACLE.
FLUSH FRACTIONAL HORSEPOWER MOTOR STARTER WITH NEON PILOT LIGHT. ONE-GANG ASSEMBLY (46" MH UNLESS
NOTED OTHERWISE).
HP RATED WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).
DISCONNECT SWITCH.
MOTOR STARTER.
COMBINATION MOTOR STARTER AND DISCONNECT SWITCH.
ELECTRIC MOTOR.
ELECTRICAL PANEL OR SWITCHBOARD PER DRAWINGS.
PULL BOX.
LINE VOLTAGE THERMOSTAT.
UNIT HEATER.
FAN COIL.
ELECTRIC BASEBOARD HEATER.
AIR CONDITIONER.
CONDENSING UNIT.
UNIT VENTILATOR.
CORD REEL.
POWER POLE.
PHOTOELECTRIC SENSOR.
LIGHTING CONTACTOR.
CEILING MOUNTED OCCUPANCY SENSOR.
WALL MOUNTED OCCUPANCY SENSOR.
CEILING MOUNTED DAYLIGHT SENSOR.
OCCUPANCY SENSOR POWER PACK.
PUSHBUTTON (46" MH UNLESS NOTED OTHERWISE) EDWARDS 852 (120 VOLT).
BUZZER (90" MH UNLESS NOTED OTHERWISE) EDWARDS 340-A (120 VOLT).
4" DIAMETER (90" MH UNLESS NOTED OTHERWISE) EDWARDS "ADAPTABEL" (120 VOLT).
GF
WP
WP/GF
T
IG
20A
30A
50A
20A
50A
30A
J
P
K
DM
R
H
UH
FC
AC
CU
UV
PP
OS
M
OS
M
DS
OP
PC
T
B
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (44" MH UNLESS NOTED OTHERWISE).
C
M
CR
LC
P/B
ELAPSED TIME INDICATOR CLOCK (90" MH UNLESS NOTED OTHERWISE) WITH RESET SWITCH (46" MH UNLESS NOTED
OTHERWISE).
INTERCOM SYSTEM DESK MOUNTED MASTER CONTROL STATION. SUBSCRIPT "W" INDICATES WALL MOUNT (46" MH
UNLESS NOTED OTHERWISE).
INTERCOM STAFF STATION (46" MH UNLESS NOTED OTHERWISE).
INTERCOM HORN TYPE SPEAKER (84" MH UNLESS NOTED OTHERWISE).
INTERCOM SPEAKER FLUSH MOUNT IN CEILING.
I
M
H
S
DUCT HEATER.H
DH
H
EB
LOW-VOLTAGE MOMENTARY WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).L
ABBREVIATIONS
AAP - AREA ALARM PANEL - MEDICAL GAS
ACC - ACCESS
ADJ - ADJUSTABLE
AF - ARC FAULT CIRCUIT INTERRUPTER
AFCI - ARC FAULT CIRCUIT INTERRUPTER
AFF - ABOVE FINISHED FLOOR TO BOTTOM OF ITEM
AFG - ABOVE FINISHED GRADE TO BOTTOM OF ITEM
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
ATS - AUTOMATIC TRANSFER SWITCH
BLDG - BUILDING
BOE - BOTTOM OF EQUIPMENT
BOT - BOTTOM
BTWN - BETWEEN
CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CKT - CIRCUIT
CLG - CEILING
CMU - CONCRETE MASONRY UNIT
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
CORR - CORRIDOR
CTR - CENTER
D - DEPTH
DET - DETAIL
DIA - DIAMETER
DIM - DIMENSION
DIV - DIVISION
DN - DOWN
DW - DISHWASHER
DWG - DRAWING
EA - EACH
EC - ELECTRICAL (DIVISION 26)
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATION OR ELEVATOR
EM - EMERGENCY
EQ - EQUAL
EQS - EQUIPMENT SUPPLIER
EQUIP - EQUIPMENT
E/R - EXISTING TO BE RELOCATED
EX - EXISTING TO REMAIN
EXP - EXPANSION
EXT - EXTERIOR
FCE - FIRE CONTROL EQUIPMENT
FF - FINISHED FLOOR ELEVATION
FLR - FLOOR
FSC - FIRE SUPPRESSION (DIVISION 21)
FT - FEET
FTG - FOOTING
GC - GENERAL CONTRACTOR
GF - GROUND FAULT CIRCUIT INTERRUPTER
GFB - GROUND FAULT BREAKER
GFCI - GROUND FAULT CIRCUIT INTERRUPTER OR GOVERNMENT
FURNISHED CONTRACTOR INSTALLED
GFFT - GROUND FAULT FEED THRU
HC - HVAC (DIVISION 23)
HP - HORSE POWER OR HIGH POINT
HVAC - HEATING, VENTILATING, AND AIR CONDITIONING
ID - INSIDE DIAMETER
IN - INCHES
KEC - KITCHEN EQUIPMENT
L - LENGTH
LBS - POUNDS
MAP - MASTER ALARM PANEL (MEDICAL GAS)
MAX - MAXIMUM
MEZZ - MEZZANINE
MFR - MANUFACTURER
MH - MANHOLE OR MOUNTING HEIGHT TO CENTER LINE OF ITEM
MIN - MINIMUM OR MINUTE
MISC - MISCELLANEOUS
MTD - MOUNTED
MTG - MOUNTING
NIC - NOT IN CONTRACT
NOM - NOMINAL
NTS - NOT TO SCALE
OD - OUTSIDE DIAMETER
OFCI - OWNER FURNISHED CONTRACTOR INSTALLED
OFOI - OWNER FURNISHED OWNER INSTALLED
PC - PLUMBING (DIVISION 22)
PLBG - PLUMBING
RAD - RADIUS
REC - RECESSED
REQD - REQUIRED
RF - REFRIGERATOR
RI - ROUGH-IN
S - SURFACE MOUNTED
SC - SECURITY CONTRACTOR
SCH - SCHEDULE
SHT - SHEET
SMS - SECURITY MANAGEMENT SYSTEM
SPEC - SPECIFICATIONS
SQ - SQUARE
SS - STAINLESS STEEL
STD - STANDARD
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY
TC - TECHNOLOGY (DIV 27)
TEMP - TEMPERATURE
TOE - TOP OF EQUIPMENT
TYP - TYPICAL
UNO - UNLESS NOTED OTHERWISE
VFD - VARIABLE FREQUENCY DRIVE
VOL - VOLUME
W/ - WITH
W/O - WITHOUT
WP - WEATHERPROOF
ZVC - ZONE VALVE CABINET
WIREMOLD RACEWAY, AS NOTED ON PLANS.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R WITH 2 INTEGRAL USB CHARGERS (18" MH UNLESS NOTED OTHERWISE).
NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT
TO MODIFICATIONS ON OTHER DRAWINGS.
ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT
NECESSARILY BE USED ON THIS PROJECT.
SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POWER. SPECIFICATION IS SAME AS RESPECTIVE ROUND DEVICE.
J
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, IN HUBBELL BA-2527 FLUSH FLOOR BOX WITH ROUND SA-3925 COVERPLATE.
PROVIDE CARPET FLANGE WHERE REQUIRED.
E2
B
E2
DETAIL: B = DETAIL DESIGNATION
E2 = SHEET WHERE DETAIL IS LOCATED
SECTION: 1 = SECTION DESIGNATION
E2 = SHEET WHERE SECTION IS LOCATED
PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
GENERAL FLOOR PLAN NOTES
WIRE & CONDUIT IN WALL OR ABOVE CEILING.
WIRE & CONDUIT IN OR BELOW SLAB OR GRADE.
EACH ARROWHEAD REPRESENTS ONE COMPLETE CIRCUIT; "X" DENOTES PANEL NAME; NUMBER(S)
DENOTES CIRCUIT(S).
LADDER TRAY, 12" x 4" DEEP UNLESS NOTED OTHERWISE.
CONDUIT FOR DATA CIRCUITRY.DAT
WIRE & CONDUIT FOR FIRE ALARM CIRCUITRY.FA
WIRE & CONDUIT FOR NURSE CALL CIRCUITRY.NC
EXISTING WIRE & CONDUIT TO REMAIN.EX
CONDUIT TO BE REMOVED.
WIRE & CONDUIT FOR NIGHT LIGHT CIRCUITRY.NL
CONDUIT FOR PHONE CIRCUITRY.PHO
WIRE & CONDUIT FOR SECURITY SYSTEM CIRCUITRY.SEC
WIRE RUN IN SURFACE WIREWAY.W
CABLE MANAGEMENT SYSTEM PATHWAY.CM
X - 1,2
WIRE & CONDUIT FOR EMERGENCY CIRCUITRY.EM
WIRE & CONDUIT FOR SOUND SYSTEM CIRCUITRY.S
WIRE & CONDUIT FOR INTERCOM SYSTEM CIRCUITRY.I
WIRE & CONDUIT FOR TELEVISION SYSTEM CIRCUITRY.TV
CABLE TRAY, 12" x 4" DEEP UNLESS NOTED OTHERWISE.
4"
4"
4"
T2 1 ELEVATION: 1 = ELEVATION DESIGNATION
T2 = SHEET WHERE ELEVATION IS LOCATED
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERWISE). WHEN SHOWN, RECEPTACLE TO HAVE
"CONTROLLED" MARKINGS.
LIGHTING CONTROL DETAIL NOTE. APPLIES TO THE LIGHTING CONTROL SEQUENCE OF OPERATIONS
SCHEDULE FOR ROOM CONTROL.
3 DEVICE QUANTITY - POWER NOTE. REFER TO DEVICE QUANTITIES - POWER SCHEDULE.
GENERAL NOTES
A. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE
OBTAINED FROM THE ARCHITECTURAL REFLECTED CEILING PLAN.
B. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF
EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS
BETWEEN DEVICES.
C. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE
CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN
INSULATED EQUIPMENT GROUNDING CONDUCTOR.
GENERAL NOTES - DEMOLITION
A. FOR EXISTING EQUIPMENT, SUCH AS LIGHTING FIXTURES, WIRING DEVICES,
CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP
CONDUITS AT THE AREA OF WORK PERIMETER AND REMOVE CONDUIT WITHIN
THE WORK AREA, DISCONNECT WIRING AT THE OVERCURRENT PROTECTIVE
DEVICE AND REMOVE WIRING COMPLETELY FROM THE ABANDONED CONDUITS.
B. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE OVERCURRENT
PROTECTIVE DEVICE. COMPLETELY REMOVE ALL ABANDONED WIRING.
C. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS
PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.
GENERAL NOTES
A. THESE NOTES APPLY EQUALLY TO THE FULL SET OF DOCUMENTS.
B. ACOUSTICAL CEILING ACCESS IDENTIFICATION MARKERS: COLORED MARKERS WITH
PRESSURE SENSITIVE ADHESIVE ON ONE SIDE, PAPER OR PLASTIC, 6 TO 9 MM (1/4 TO 3/8
INCH) DIAMETER. REFER TO SPECIFICATION 09 51 00 SECTION 2.6.C.
1. COLOR CODE: PROVIDE THE FOLLOWING COLOR MARKERS FOR SERVICE IDENTIFICATION:
• RED - SPRINKLER SYSTEM: VALVES AND CONTROLS.
• GREEN - DOMESTIC WATER: VALVES AND CONTROLS.
• YELLOW - CHILLED WATER AND HEATING WATER.
• ORANGE - DUCTWORK: FIRE DAMPERS.
• BLUE - DUCTWORK: DAMPERS AND CONTROLS.
• BLACK - GAS: LABORATORY, MEDICAL, AIR AND VACUUM.
C. INCLUDE ALL WORK NECESSARY TO ACCOMMODATE PHASING. REFER TO
ARCHITECTURAL DRAWINGS AND GENERAL REQUIREMENTS SECTION 01 00 00.
D. CONTRACTOR SHALL REFER TO ALL SPECIFICATION SECTIONS AND THE
DRAWINGS FOR DETAILS OF BUILDING CONSTRUCTION TO ENSURE SPACE AND
SATISFACTORY ARRANGEMENT FOR THEIR WORK. THE VARIOUS DRAWINGS
COMPRISING THE SET ARE INTERDEPENDENT AND MUST BE USED JOINTLY AT
ALL TIMES. THE CONTRACTOR SHALL REFER TO THE GENERAL REQUIREMENTS
OF THE CONTRACT. THE NOTES AND SYMBOLS INDICATED ON THE DRAWINGS
ARE FOR THE GUIDANCE OF ALL TRADES INVOLVED IN THE PROJECT AND MUST
BE FOLLOWED TO EXECUTE THE WORK AS INTENDED. IF DISCREPANCIES OCCUR,
CONTACT THE COR THROUGH THE CONTRACTING OFFICER FOR CLARIFICATION
BEFORE PROCEEDING.
E. ALL WORK MUST BE COORDINATED WITH THE CONTRACTING OFFICER AND (FOR
ALL OTHERS) TO MAINTAIN OPERATION OF THE EXISTING FACILITY.
F. ALL WORK SHALL BE PERFORMED IN COMPLETE COMPLIANCE WITH ALL CURRENT
OVERNING CODES AND STANDARDS.
G. EXISTING CONDITIONS SHOWN HAVE BEEN BASED UPON AVAILABLE DRAWING
INFORMATION, AND MAY BE AT VARIANCE WITH ACTUAL WORK IN PLACE. THE
CONTRACTOR SHALL TAKE ALL NECESSARY FIELD MEASUREMENTS AND FIELD
VERIFY ALL CONDITIONS AFFECTING THE EXECUTION OF THE WORK. ANY
DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THE WORK SHOWN ON THE
CONTACT DOCUMENTS WHICH MAY IMPACT THE PROGRESS OF THE WORK SHALL
BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER IN WRITING
FOR RESOLUTION BEFORE PROCEEDING WITH THE WORK.
H. REFER TO ARCHITECTURAL FIRE-RATED PARTITION PLAN(S) FOR LOCATIONS AND
FIRE-RATING OF NEW AND EXISTING WALL ASSEMBLIES. ALL PENETRATIONS
THROUGH FIRE-RATED ASSEMBLIES SHALL BE PROJECTED AND/OR FIRE-STOPPED
AS REQUIRED TO MAINTAIN FIRE-RATINGS INDICATED. COORDINATE WITH ALL
TRADES TO ENSURE FIRE-RATED PENETRATION REQUIREMENTS AND DETAILS
ARE MET.
I. ANNULAR SPACE OF ALL PIPE, CONDUIT, DUCT AND OTHER SIMILAR PENETRATIONS
OF FIRE RATED ASSEMBLIES SHALL BE FIRESTOPPED. IN ADDITION, PENETRATIONS
THROUGH 0-HOUR RATED WALLS AND FLOORS SHALL BE FIRESTOPPED TO RETARD
PASSAGE OF FIRE AND SMOKE.
J. ALL CONDUITS IN FINISHED ROOMS AND CORRIDORS SHALL BE CONCEALED IN A
WALL OR ABOVE CEILING.
K. ACCESS PANELS IN NON ACCESSIBLE CEILINGS SHALL BE PROVIDED FOR ALL
ELECTRICAL ITEMS REQUIRING ACCESS.
L. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF
LIGHTS, SPEAKERS, NURSE CALL DEVICES, ETC.
M. ALL CUTTING AND PATCHING REQUIRED FOR THIS PROJECT SHALL BE INCLUDED IN
THE CONTRACT. REFINISH ANY SURFACE DISTURBED UNDER THIS WORK TO MATCH
EXISTING.
N. ANY REMOVED EQUIPMENT SHALL BE TURNED OVER TO THE VA. ITEMS NOT DESIRED
BY THE VA SHALL BE REMOVED FROM THE PREMISES AND DISPOSED OF PROPERLY
BY THE CONTRACTOR.
O. THE CONTRACT DRAWINGS ARE NOT INTENDED TO SHOW EVERY VERTICAL OR HORIZONTAL
OFFSET WHICH MAY BE NECESSARY TO COMPLETE THE SYSTEMS. COORDINATE WORK IN
ADVANCE WITH ALL OTHER TRADES AND REPORT IMMEDIATELY AND DIFFICULTIES
WHICH CAN BE ANTICIPATED.
P. ALL ABANDONED EXTRANEOUS CONDUITS, WIRING, DEVICES, ETC. SHALL BE REMOVED.
Q. REFER TO MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION CONCERNING
MECHANICAL EQUIPMENT THAT REQUIRES ELECTRICAL CONNECTIONS.
• R.
DESIGN-AIRE ENGINEERING, INC.
www.daengineering.comwww.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - Create Code Compliant Research Laboratory Space in Building 1
657-23-113JB
Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM
08-6231 1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
CONSTRUCTION DOCUMENTS
12-22-2023Project Number: 2023-05162.00
JSF PJM
1-EG-001
LEGEND, GENERAL NOTES, INDEX
ELECTRICAL SHEET LIST
SHEET NUMBER SHEET NAME
1-EG-001 LEGEND, GENERAL NOTES, INDEX
1-EG-002 SCHEDULES
1-EP-100 PARTIAL SECOND FLOOR PLANS - ELECTRICAL
1-EP-101 PARTIAL THIRD FLOOR PLANS - ELECTRICAL
1-EP-102 PARTIAL ROOF PLAN
35 44
DESIGN-AIRE ENGINEERING, INC.
www.daengineering.comwww.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - Create Code Compliant Research Laboratory Space in Building 1
657-23-113JB
Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM
08-6231 1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
CONSTRUCTION DOCUMENTS
01-18-2024Project Number: 2023-05162.00
JSF PJM
1-EG-002
SCHEDULES
3.76 kVA 3.76 kVA (10 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: EXISTING PANEL. NORMAL POWER.
$ = GFCI BREAKER
Total Est. Demand: 10 A
Total Conn.: 10 A
Total Est. Demand: 3.76 kVA
Total Conn. Load: 3.76 kVA
Receptacle 3760 VA 100.00% 3760 VA
Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 1.44 kVA 0.54 kVA 1.78 kVA
41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42
39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40
37 Spare 20 A 1 0 VA 0 VA 1 20 A SPARE 38
35 Spare 20 A 1 0 VA 0 VA 1 20 A SPARE 36
33 Spare 20 A 1 0 VA 0 VA 1 20 A SPARE 34
31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 32
29 $REC 2C19 20 A 1 1600... 0 VA 1 20 A Spare 30
27 Spare 20 A 1 0 VA 360 VA 1 20 A REC 2C19 28
25 REC 2C19 20 A 1 360 VA 900 VA 1 20 A REC 2C19 26
23 Spare 20 A 1 0 VA 180 VA 1 20 A REC 2C19 24
21 Spare 20 A 1 0 VA 180 VA 1 20 A REC 2C19 22
19 Spare 20 A 1 0 VA 180 VA 1 20 A REC 2C19 20
17 LIGHTS RMS... 20 A 1 0 VA 0 VA 1 20 A RECPT RMS 2C11,12 18
15 RECEPT RM... 20 A 1 0 VA 0 VA 1 20 A REC LTS 2C12, 13 16
13 COMPUTER LTS... 20 A 1 0 VA 0 VA 1 20 A LTS 2C5, 6 7, COMP... 14
11 CORRIDOR LTS 20 A 1 0 VA 0 VA 1 20 A LTS RM 2C5,6,7 12
9 -- -- -- 0 VA 0 VA 1 20 A RECEPT LTS 2C3 10
7 AC ROOM 2C3 20 A 2 0 VA 0 VA 1 20 A RECEPT RM 2C3 8
5 RECEPT SW WALL 2C4 20 A 1 0 VA 0 VA 1 20 A LTS, REC, FCU 2C29 6
3 RECEPT NE WALL... 20 A 1 0 VA 0 VA 1 20 A LTS 2C27,28 RCPT... 4
1 RECEPT NW WALL... 20 A 1 0 VA 0 VA 1 20 A LIGHTS RMS 2C25-26 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 208Y/120V-3PH-4W-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type:
Location: CORRIDOR H205 Mounting: Surface A.I.C. Rating:
Panel: 1-L22L
1.72 kVA 1.97 kVA (5 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: EXISTING PANEL. NORMAL POWER.
Total Est. Demand: 5 A
Total Conn.: 5 A
Total Est. Demand: 1.97 kVA
Receptacle 720 VA 100.00% 720 VA Total Conn. Load: 1.72 kVA
Lighting 1000 VA 125.00% 1250 VA
Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 0.18 kVA 0.00 kVA 1.54 kVA
41 -- -- -- 0 VA 360 VA 1 20 A REC 2C19 42
39 USED 20 A 2 0 VA 0 VA -- -- -- 40
37 Receptacle 20 A 1 180 VA 0 VA 2 30 A SPARE 38
35 Lighting 2C19 20 A 1 1000... 0 VA -- -- -- 36
33 RM 2C2 AC 20 A 1 0 VA 0 VA 2 20 A 2C10 UPS 34
31 RECPT RM2C203 20 A 1 0 VA 0 VA 1 20 A SPARE 32
29 RECPT RM2C20 20 A 1 0 VA 0 VA 1 20 A RECPT 210 RM 220 30
27 RECPT RM 2C20/30 4W 20 A 1 0 VA 0 VA 1 20 A RECPT 2C7 28
25 -- -- -- 0 VA 0 VA 1 20 A RECPT 2C7 26
23 RECPT RM 2C19 30 A 2 0 VA 0 VA 1 20 A LTS RC RM 2C9 24
21 -- -- -- 0 VA 0 VA 1 20 A RECPT ROOM 2C3 22
19 2C16 USED 30 A 2 0 VA 0 VA -- -- -- 20
17 REC 2C13,2C14 20 A 1 0 VA 0 VA 2 40 A FCU RM C219 18
15 USED 20 A 1 0 VA 0 VA 1 30 A RECP RMC219 16
13 USED 30 A 1 0 VA 0 VA 1 30 A 208V REC KITCHEN 14
11 RECPT RM 2C13,14,15 30 A 1 0 VA 0 VA 1 20 A 208V REC KITCHEN 12
9 RECEPT RM 2C15 20 A 1 0 VA 0 VA 1 20 A FLOOR CLEANER 10
7 FLOOR CLEANER 20 A 1 0 VA 0 VA 1 20 A FLOOR CLEANER 8
5 REC 2C19 20 A 1 180 VA 0 VA -- -- -- 6
3 -- -- -- 0 VA 0 VA -- -- -- 4
1 2C10 UPS 20 A 2 0 VA 0 VA 3 15 A FCU 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 208Y/120V-3PH-4W-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type:
Location: CORRIDOR H205 Mounting: Surface A.I.C. Rating:
Panel: 1-L22R
3.4 kVA 3.4 kVA (9 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: EXISTING PANEL. NORMAL POWER.
$ = GFCI BREAKER
Total Est. Demand: 9 A
Total Conn.: 9 A
Total Est. Demand: 3.4 kVA
Total Conn. Load: 3.4 kVA
Receptacle 3400 VA 100.00% 3400 VA
Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 1.60 kVA 1.26 kVA 0.54 kVA
41 FUME HOOD 3C13 20 A 1 0 VA 0 VA -- -- -- 42
39 CORR EAST END... 20 A 1 0 VA 0 VA -- -- -- 40
37 CORR E END CENTER 20 A 1 0 VA 0 VA 3 20 A AC 3C09 38
35 REC N WALL 3C26 20 A 1 0 VA 0 VA 1 20 A PLUGMOLD C7,C9 36
33 REC W WALL 3C26 20 A 1 0 VA 0 VA 1 20 A SHORTED 34
31 CEILING LTS AND... 20 A 1 0 VA 0 VA 1 20 A REC RM 3C18 N & S 32
29 ISLAND TABLE REC 20 A 1 0 VA 0 VA 1 20 A LTS 3C20,21,22,23 30
27 PLUGMOLD WALL 20 A 1 0 VA 0 VA 1 20 A LTS 3C18,19 28
25 CLNG LTS RM 3C17 20 A 1 0 VA 0 VA 1 20 A AUTOCLAVE 3C15,16 26
23 RECEPTS N WALL,... 20 A 1 0 VA 0 VA 1 20 A E WALL 3C26 24
21 Receptacle LAB 3C17 20 A 1 720 VA 0 VA 1 20 A 3C14 RECPT 22
19 CEILING LTS 3C13-14 20 A 1 0 VA 1600... 1 20 A $ REC 3C17 20
17 REC 3C17 20 A 1 360 VA 180 VA 1 20 A REC 3C17 18
15 Receptacle Room 3C17 20 A 1 540 VA 0 VA 1 20 A CEILING LTS 3C12 16
13 CEILING LITS 3C11 20 A 1 0 VA 0 VA 1 20 A CEILING LTS C7, 3C9 14
11 3C4 RECPT WEST... 20 A 1 0 VA 0 VA 1 20 A Spare 12
9 3C4 RECEPT E WALL 20 A 1 0 VA 0 VA 1 20 A Spare 10
7 CEILING LITES 3C4 20 A 1 0 VA 0 VA 1 20 A 3C6 CEILING LITES &... 8
5 WIREMOLD ROOM 301 20 A 1 0 VA 0 VA 1 20 A RECPT C304, 305 6
3 LITES 3C30-C 20 A 1 0 VA 0 VA 1 20 A WIREMOLD RM 301 4
1 ICE MACHINE 3C29 20 A 1 0 VA 0 VA 1 20 A LITES RC301,2,3,4 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 208Y/120V-3PH-4W-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type:
Location: CORRIDOR H304 Mounting: Surface A.I.C. Rating:
Panel: 1-L32L
1.17 kVA 1.33 kVA (4 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: EXISTING PANEL. NORMAL POWER.
Total Est. Demand: 4 A
Total Conn.: 3 A
Total Est. Demand: 1.33 kVA
Receptacle 540 VA 100.00% 540 VA Total Conn. Load: 1.17 kVA
Lighting 629 VA 125.00% 786 VA
Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 0.87 kVA 0.18 kVA 0.12 kVA
47 -- -- -- 0 VA 0 VA 1 20 A USED 48
45 Spare 20 A 2 0 VA 0 VA 1 20 A USED 46
43 Spare 20 A 1 0 VA 0 VA 1 20 A USED 44
41 Spare 20 A 1 0 VA 0 VA 1 20 A PLUG MOLD RM 3C27 42
39 3C26 20 A 1 0 VA 0 VA 1 20 A WEST RECEPT 3C17 40
37 3C26 20 A 1 0 VA 0 VA 1 20 A FC 3C26,27 38
35 Spare 20 A 1 0 VA 0 VA 1 20 A FC... 36
33 Receptacle 20 A 1 180 VA 0 VA 1 20 A FC 3C12, 3C4,8 34
31 3C23 RECEPT 20 A 1 0 VA 0 VA -- -- -- 32
29 3C23 RECEPT 20 A 1 0 VA 0 VA 2 20 A Spare 30
27 3C6 CENTER FUSE 20 A 1 0 VA 0 VA -- -- -- 28
25 3C6 CENTER FUSE 20 A 1 0 VA 0 VA 2 20 A Spare 26
23 -- -- -- 0 VA 0 VA -- -- -- 24
21 SPARE 20 A 2 0 VA 0 VA 2 20 A TWIST LOCK RM C11 22
19 -- -- -- 0 VA 360 VA 1 20 A REC 3C17 20
17 SPARE 20 A 2 0 VA 117 VA 1 20 A Lighting LAB 3C17 18
15 CENTER FUSE 3C26 20 A 1 0 VA 0 VA 1 20 A Spare 16
13 CENTER FUSE 3C26 20 A 1 0 VA 512 VA 1 20 A Lighting LAB 3C17 14
11 -- -- -- 0 VA 0 VA -- -- -- 12
9 -- -- -- 0 VA 0 VA -- -- -- 10
7 SUBFEED PNL SP1L43 20 A 3 0 VA 0 VA 3 20 A Spare 8
5 -- -- -- 0 VA 0 VA -- -- -- 6
3 -- -- -- 0 VA 0 VA -- -- -- 4
1 PENTHOUSE PNL 20 A 3 0 VA 0 VA 3 20 A FUME HOOD 3C18 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 208Y/120V-3PH-4W-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type:
Location: CORRIDOR H304 Mounting: Surface A.I.C. Rating:
Panel: 1-L32R
NOTES:
LUMINAIRES
MARK
LAMPS
VA VOLTAGE MANUFACTURER CATALOG NO. DESCRIPTION
OTHER ACCEPTABLE
MANUFACTURERS DIFFUSING MEDIA
MOUNTING SIZE
S E
E N
O T
E
LUMENS COLOR
S-SURFACE
R-RECESSED
SM-STEM MTD
WM-WALL MTD
C-CHAIN MTD
UC-UNDER CAB
CS-CEIL SURFACE D
IA
M
E T
E R
W
ID
T H
L E
N G
T H
D E
P T
H
FP24 6000 4000K 128 120 ACUITY EPANL-2X4-4800LM-80CRI-40K-MIN10-ZT-MVOLT LED FLAT PANEL WITH WHITE TRIM, 2'X4' 4000K COLOR OR APPROVED EQUAL R 24" 48" 6"
UC1 550/FT 4000K 13 120 AIREY THOMPSON 13HC-H-40K-24-2-0-AMS UNDER CABINET LUMINAIRE ANTI-MICROBIAL FINISH HOPSITAL GRADE, 24" OR APPROVED EQUAL S 2.5" 24" 1"
0.00 kVA
TOTAL CONNECTED ESTIMATED DEMAND
Notes: EXISTING PANEL
EMERGENCY POWER
Total Est. Demand: 0 A
Total Conn.: 0 A
Total Est. Demand: 0 kVA
Total Conn. Load: 0 kVA
Motor 0 VA 0.00% 0 VA
Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 0.00 kVA 0.00 kVA 0.00 kVA
29 AIR COND. 20 A 1 0 VA 0 VA 1 20 A 3C21 PLUGMOLD 30
27 PENTHOUSE 20 A 1 0 VA 0 VA 1 20 A 3C21 PLUGMOLD 28
25 PENTHOUSE MW 20 A 1 0 VA 0 VA 1 20 A 3C28 PLUGMOLD 26
23 3C26 RECPT 20 A 1 0 VA 0 VA 1 20 A MICROWAVE 24
21 3C13 20 A 1 0 VA 0 VA 1 20 A 3C18 PLUGMOLD 22
19 Motor LAB 3C17 20 A 1 0 VA 0 VA 1 20 A 3C18 20
17 -- -- -- 0 VA 0 VA 1 20 A 3C26 WIREMOLD 18
15 BC-2 3C17 20 A 2 0 VA 0 VA 1 20 A 3C26 REF 16
13 3C15 PLUGMOLD 20 A 1 0 VA 0 VA 1 20 A 3C13 LGHTS 14
11 3C15 PLUGMOLD 20 A 1 0 VA 0 VA -- -- -- 12
9 3C18 N PLUGMOLD 20 A 1 0 VA 0 VA 2 20 A CENTRIFUGE 10
7 3C13 20 A 1 0 VA 0 VA -- -- -- 8
5 -- -- -- 0 VA 0 VA 2 20 A 3C15 30A RECPT 6
3 -- -- -- 0 VA 0 VA -- -- -- 4
1 EXHAUST FAN ROOF 20 A 3 0 VA 0 VA 2 20 A 3C18 REC 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 208Y/120V-3PH-4W-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type:
Location: CORRIDOR H304 Mounting: Surface A.I.C. Rating:
Panel: 3CEC
9.02 kVA 9.08 kVA (25 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: EXISTING PANEL
EMERGENCY POWER.
Total Est. Demand: 25 A
Total Conn.: 25 A
Receptacle 8760 VA 100.00% 8760 VA Total Est. Demand: 9.08 kVA
Motor 0 VA 0.00% 0 VA Total Conn. Load: 9.02 kVA
Lighting 256 VA 125.00% 320 VA
Load Classification Connected... Demand Factor Estimated... Panel Totals
D Total Load: 3.54 kVA 2.17 kVA 3.31 kVA
41 Lighting 2C19 20 A 1 128 VA 0 VA 1 20 A BLANK 42
39 NOT USED 20 A 1 0 VA 128 VA 1 20 A Lighting LAB 3C17 40
37 -- -- -- 0 VA 0 VA 1 20 A 2C10 RECPT 38
35 -- -- -- 0 VA 0 VA 1 20 A SPARE 36
33 DATA RM 2C10 20 A 3 0 VA 360 VA 1 20 A Receptacle 34
31 Motor 20 A 1 0 VA 360 VA 1 20 A Receptacle 32
29 REC 2C18 20 A 1 0 VA 0 VA 1 20 A GFCI MENS RM 2C08 30
27 NOT USED 20 A 1 0 VA 0 VA 1 20 A RE 2C08 +LTS 28
25 NOT USED 20 A 1 0 VA 0 VA 1 20 A REC 2C08, 07 26
23 REC 3C17 20 A 1 1500... 0 VA 1 20 A REC 2C13 24
21 LTS 2C10 20 A 1 0 VA 0 VA 1 20 A REC 2C01 22
19 REC 3C17 20 A 1 1500... 0 VA 1 20 A REC 2C01, 2C23 20
17 Receptacle 20 A 1 180 VA 0 VA 1 20 A REC 2C19 18
15 Receptacle 20 A 1 180 VA 0 VA 1 20 A FA 2C18 16
13 Receptacle LAB 3C17 20 A 1 180 VA 1500... 1 20 A REC 2C19 14
11 -- -- -- 0 VA 1500... 1 20 A REC 2C19 12
9 BC-1 2C19 20 A 2 0 VA 1500... 1 20 A REC 2C19 10
7 NOT USED 20 A 1 0 VA 0 VA 1 20 A REC 2C10 8
5 REC RM 2C119 20 A 1 0 VA 0 VA 1 20 A REC 2C10 SWALL 6
3 NOT USED 20 A 1 0 VA 0 VA 1 20 A NOT USED 4
1 RACK RM 2C10 20 A 1 0 VA 0 VA 1 20 A NOT USED 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 208Y/120V-3PH-4W-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type:
Location: Mounting: Surface A.I.C. Rating:
Panel: 2CEC
NOTES
1. PROVIDE NEW CIRCUIT BREAKER. MATCH
MANUFACTURER TO OTHER EXISTING CIRCUIT BREAKERS
WITHIN PANEL.
36 44