657-23-113JB - Construction Drawings - 10 of 14 - MH.pdf

PDF 659 KB Posted

Attached to
Z1DA--Create Code Compliant Research Laboratory Space in Building 1, 657-23-113JB Federal contract opportunity
Solicitation number
36C25524R0053
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15

About this file

This document appears to be a set of construction drawings for a federal contract opportunity at the Saint Louis VA Health Care System. The solicitation number is 36C25524R0053, with the title "Z1DA--Create Code Compliant Research Laboratory Space in Building 1, 657-23-113JB". The project involves creating code-compliant research laboratory space in Building 1 at the Saint Louis VA Health Care System facility located at Jefferson Barracks. The drawings provide detailed plans for the mechanical, HVAC, and plumbing systems, including demolition work and new construction. Key details include the installation of new ductwork, exhaust fans, piping, and controls to serve the research laboratory space in Rooms 2C19 and 3C17. The drawings are part of the 100% construction documents for this contract opportunity.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--Create Code Compliant Research Laboratory Space in Building 1, 657-23-113JB, newest first.
File Type Posted
S02-657-23-113JB - Create Code Compliant Research Laboratory Space Prebid Questions 20240422.pdf PDF
Pre-Bid Conference Sign-in Sheet 657-23-113 --- Scan04-09-2024-102719.pdf PDF
S02-3- As Built from-657-10-104JB_1C-A1.pdf PDF
36C25524R0053 0001.docx DOCX document
657-23-113JB - Construction Drawings - 14 of 14 - TT.pdf PDF
657-23-113JB - Construction Drawings - 12 of 14 - EP.pdf PDF
657-23-113JB - Construction Drawings - 9 of 14 - MG.pdf PDF
657-23-113JB - Construction Drawings - 8 of 14 - FP.pdf PDF
657-23-113JB - Construction Drawings - 1 of 14 - GI.pdf PDF
657-23-113JB - Construction Drawings - 11 of 14 - EG.pdf PDF
657-23-113JB - Construction Drawings - 2 of 14 - GJ.pdf PDF
657-23-113JB Specifications - Reduced File Size.pdf PDF
657-23-113JB - Construction Drawings - 13 of 14 - TG.pdf PDF
657-23-113JB - Construction Drawings - 7 of 14 - PM.pdf PDF
657-23-113JB - Construction Drawings - 6 of 14 - PL.pdf PDF
657-23-113JB - Construction Drawings - 5 of 14 - PG.pdf PDF
657-23-113JB - Construction Drawings - 4 of 14 - AE.pdf PDF
657-23-113JB - Construction Drawings - 3 of 14 - HA.pdf PDF
36C25524R0053_1.docx DOCX document
Show all 19

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

T

4 4

"x

"x

24"x10" 36"x10"

30"x12"10"ø

8" x1

0"

8"x10"

6 6

EXIST. 1/2" CHWS, 1/2"

CHWR, AND 3/4" CD

LAB

2C19

"x

30"x12"

30"x12"

24"x10" 36"x10"

A10

600 CFM

A10

600 CFM

A10

345 CFM

N E

W

NEW VCD-1

BC-1

14"x14"

14"x14"

10"ø

10"ø

8"ø

B12x12

600 CFM

B12x12

600 CFM

6 NEW

HOOD

C-1

8" ø

NEW

NEW

NEW

NEW

NEW

N E

W

BC-1

NEW

8"øNEW

8"øNEW9

DP

DP

LAB

2C19

BC-1

5NEW 1/2" CHWS

NEW 1/2" CHWR

NEW 3/4" CD

EXIST. 1/2" CHWS, 1/2"

CHWR, AND 3/4" CD

NEW 1/2" HWS

NEW 1/2" HWR

EXISTING HWS & HWR

PE−2021014461P

R

O F

E S S I O N A L E N G

I N E

E R

HANNAH

ROSE

KIGER

S T

A

T E

OF MI SSO

U

R I

DESIGN-AIRE ENGINEERING, INC.

www.daengineering.comwww.daengineering.com voice (317) 464-9090

2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

FCA - Create Code Compliant Research Laboratory Space in Building 1

657-23-113JB

Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM

08-6231 1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

01-18-2024

100% CONSTRUCTION DOCUMENTS

100% SPRINKLERED

DEH RE

1-MH-101

SECOND FLOOR PLANS -

MECHANICAL DEMOLITION AND

REVISED

N

1/4" = 1'-0" Lab 2C19 Mechanical HVAC Plan - Demolition

N

1/4" = 1'-0" Lab 2C19 Mechanical HVAC Plan

DEMOLITION NOTES

1. REMOVE EXISTING CAPS ON DUCT FOR NEW CONNECTION.

2. REMOVE SECTION OF EXISTING EXHAUST DUCT AND UP TO

3. REMOVE EXISTING FAN COIL UNIT. GIVE TO VA.

4. REMOVE EXISTING RADIATOR UNDER WINDOW.

5. EXISTING HYDRONIC PIPING TO REMAIN FOR NEW CONNECTION.

6. CAP LPS/CR PIPING BELOW FINISHED FLOOR.

7. REMOVE DUCT COMPLETE.

8. PREPARE DUCT TAP FOR NEW DUCT TAP.

KEYED NOTES

1. CONNECT NEW INSULATED DUCT TO EXISTING AT THIS LOCATION.

2. INSTALL DUCT ACCESS DOOR FOR FIRE DAMPER ACCESS.

3. FLEXIBLE CONNECTION ON INLET AND OUTLET; TYPICAL.

4. MOUNT UNIT AS HIGH AS POSSIBLE NEXT TO DECK.

5. CONNECT CHILLED WATER AND CONDENSATE DRAIN TO

EXISTING AS REQUIRED.

6. CONNECT EXHAUST DUCT TO NEW HOOD AS REQUIRED.

7. CONNECT 8"Ø SUPPLY TO EXISTING TAP AS REQUIRED.

8. 2-WAY CONTROL VALVE ON CHWR AND HWR. SEE DETAIL 'C7' AND

'D9' ON SHEET 1-MG-003.

9. DUCT TO BE STAINLESS STEEL.

10. CONNECT TO GAS CABINET AS REQUIRED.

11. NEW 8"Ø UP WITH HORIZONTAL FIRE DAMPER AT CEILING

PENETRATION. SEE SHEET 1-MH-102.

GENERAL NOTES

1. EVERYTHING IS EXISTING TO REMAIN UNLESS OTHERWISE NOTED.

N

1/4" = 1'-0" Lab 2C19 Mechanical PIPING PLAN

TT

LAB

3C17

NEW 8"Ø DOWN

SEE SHEET 1-MH-101

NEW 12"Ø UP TO PENTHOUSE

SEE SHEET 1-MH-103

BC-2

12"x8"

12"ø

8"ø

A10

475 CFM

A12

600 CFM

A12

600 CFM

B12x12

600 CFM

B12x14

600 CFM

14"x14"

"x

8"

EXIST. DUCT

EXIST. DUCT

EXIST. DUCT EXIST. DUCT EXIST. DUCT

NEW

NEW HOOD B-1

3 24"x12"

24"x8"

24"x12"

N E

W

PROSTHETICS

3C26

MECH

3C23

HSPK

3C20

CORRIDOR

H305

CORRIDOR

H304

8 8

NEW

NEW 8"Ø

1-EF3-LAB

OFFICE

3C21

10"øNEW

OFFICE

3C18

BC-2

DP

DP

1-EF4-LAB

10"øNEW

M 8" ø

24"x8"

24"x8"

24"x12"

24"x12"

30"x12"

66"x14"

16"x8"14"x8"

24"x12"

10"ø10"ø

10"ø 10"ø

30"x12"

30"x12"

36"x12" 36"x12" 34"x12" 30"x12"

16"x10"

OFFICE

3C21

OFFICE

3C28

PROSTHETICS

3C26

MECH

3C23

HSPK

3C20

CORRIDOR

H305

CORRIDOR

H304

EXIST. HWS

EXIST. HWR

EXIST. CHWS & CHWREXIST. CD

LAB

3C17

LAB

3C17

BC-2

NEW 1/2" HWS

EXIST. HWS

EXIST. HWR

1/2" CHWS & CHWR

3/4" CD

EXIST. CHWS & CHWR

EXIST. CD

CORRIDOR

H304

NEW 1/2" HWR

PE−2021014461P

R

O F

E S S I O N A L E N G

I N E

E R

HANNAH

ROSE

KIGER

S T

A

T E

OF MI SSO

U

R I

DESIGN-AIRE ENGINEERING, INC.

www.daengineering.comwww.daengineering.com voice (317) 464-9090

2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

FCA - Create Code Compliant Research Laboratory Space in Building 1

657-23-113JB

Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM

08-6231 1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

01-18-2024

100% CONSTRUCTION DOCUMENTS

100% SPRINKLERED

DEH RE

1-MH-102

THIRD FLOOR PLANS - MECHANICAL

DEMOLITION AND REVISED

N

1/4" = 1'-0" Floor 03 Mechanical HVAC Plan

N

1/4" = 1'-0" Floor 03 Mechanical HVAC Plan - Demolition

DEMOLITION NOTES

1. REMOVE EXISTING EXHAUST FAN AND EXISTING EXHAUST DUCT

UP TO THIMBLE /CONNECTION TO ROOF CAP.

2. EXISTING RETURN DUCT 9'-4" FROM FLOOR TO BOTTOM OF DUCT.

3. EXISTING SUPPLY DUCT 9'-2" FROM FLOOR TO BOTTOM OF DUCT.

4. EXISTING SUPPLY DUCT 8'-8" FROM FLOOR TO BOTTOM OF DUCT.

5. EXISTING HEATING WATER SUPPLY AND RETURN 10'-0" A.F.F.

6. REMOVE HEATING WATER SUPPLY AND RETURN BRANCH PIPING.

PREPARE TAPS FOR NEW PIPING.

7. REMOVE EXISTING 16"x 10" DUCT.

8. REMOVE 21"x 21" EXHAUST DUCT AND FIRE DAMPER. FILL IN

OPENING TO ACCEPT NEW 8"⌀ EXHAUST DUCT AND FIRE DAMPER.

SEE ARCHITECTURAL PLANS FOR INFILL DETAIL.

9. REMOVE EXISTING DUCT COMPLETE.

10. REMOVE EXISTING DUCT COMPLETE UP TO PENTHOUSE.

11. REMOVE REHEAT COIL.

12. CAP SIDE OF DUCT AND REINSULATE DUCT.

13. REMOVE ALL CONTROLS FROM WALL COMPLETE.

14. REMOVE WINDOW A.C. UNIT COMPLETE.

KEYED NOTES

1. NEW 2-WAY CONTROL VALVE ON CHWR AND HWR. SEE DETAIL 'C7' AND

'D9' ON SHEET 1-MG-003.

2. INSTALL FIRE DAMPER AT FLOOR PENETRATION AND DUCT ACCESS

DOOR BELOW FLOOR.

3. MOUNT UNIT AS HIGH AS POSSIBLE NEXT TO DECK.

4. NEW 38"x 15"x 15" EXTERNALLY INSULATED SUPPLY PLENUM.

5. DROP NEW 10"⌀ DOWN AND UNDER EXISTING 24"x 12" AND CONNECT TO

NEW HOOD AS REQUIRED.

6. FIRE DAMPER WITH DUCT ACCESS DOOR IN PENTHOUSE.

7. PATCH WALL AROUND NEW DUCT WITH 5/8" GYPSUM BOARD OVER

OPENING LEFT FROM DUCT DEMOLITION WORK.

8. DUCT TO BE STAINLESS STEEL.

9. CONNECT NEW 10"Ø EXHAUST DUCT TO EXISTING EXHAUST DUCT RISER.

10. CONNECT NEW 8"Ø EXHAUST DUCT TO GAS CABINET IN THIS LOCATION.

11. NEW 24"x 24" ACCESS DOOR IN WALL. BOTTOM AT 6" A.F.F.

12. SEE DUCT DETAIL 'A1' ON SHEET 1-MH-104.

13. NEW MANUAL VOLUME DAMPER; TYPICAL.

14. NEW VCD-2.

15. PATCH FLOOR OPENING FROM DUCT DEMOLITION. SEE DETAIL 'A8' ON

SHEET 1-MG-003.

GENERAL NOTES

1. EVERYTHING IS EXISTING TO REMAIN UNLESS OTHERWISE NOTED.

N

1/4" = 1'-0"

FLOOR 03 MECHANICAL PIPING PLAN

29"ø

"x

29"ø

30"x20"

26"ø 26"ø

26"ø

14"ø

RTU

AC02B AC02

"ø

12"ø

LAB EXHAUST FAN (N+1)

1-EF1-LAB AND 1-EF2-LAB

EXIST. RTU

EXIST. DUCT EXIST. DUCT

E X

IS

T

. D U

C T

AC02B

N E

W

AC02

NEW

5 6

E1

1-MG-004

E4

1-MG-004

MINIMUM OF 2'-0"

VFD FOR 1-EF1-LAB

VFD FOR 1-EF2-LAB

CONTROL PANEL FOR EXHAUST FANS

PE−2021014461P

R

O F

E S S I O N A L E N G

I N E

E R

HANNAH

ROSE

KIGER

S T

A

T E

OF MI SSO

U

R I

DESIGN-AIRE ENGINEERING, INC.

www.daengineering.comwww.daengineering.com voice (317) 464-9090

2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

FCA - Create Code Compliant Research Laboratory Space in Building 1

657-23-113JB

Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM

08-6231 1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

01-18-2024

100% CONSTRUCTION DOCUMENTS

100% SPRINKLERED

DEH RE

1-MH-103

ROOF PLANS - MECHANICAL

DEMOLITION AND REVISED

KEYED NOTES

1. INSTALL NEW FIRE DAMPER WITH DUCT ACCESS DOOR AT FLOOR PENETRATION.

2. EXISTING 70"x 35" EIFS INFIL AREA FROM OLD LOUVER REMOVAL.

3. CUT NEW HOLE THROUGH EXISTING EIFS INSIL. CONTRACTOR SHALL FLASH, CAULK, AND

SEAL EXTERIOR EIFS WATERTIGHT. PATCH/REPAIR AS REQUIRED.

4. SUPPORT DUCT APPROXIMATELY 42" A.F.F. TO PENETRATE EIFS INFILL AREA. FIELD VERIFY.

5. INSTALL DUCT ROOF RAIL SUPPORT; TYPICAL. SEE DETAILS.

6. DUCT TO BE STAINLESS STEEL.

7. NEW STAINLESS STEEL ROOF EXHAUST THIMBLE, STACK, VENT CAP, AND ROOF CURB.

FLASH INTO EXISTING ROOF.

N

1/4" = 1'-0" Roof Mechanical Plan - Demolition

N

1/4" = 1'-0" Roof Mechanical Plan

DEMOLITION NOTES

1. REMOVE SECTION OF EXISTING 16"x 16" DUCT AT THIS LOCATION AND CAP. INSULATE

CAP TO MATCH EXISTING DUCTWORK.

2. REMOVE 46"x 16" DUCT THROUGH FLOOR AND ELBOW FITTING COMPLETE.

3. REMOVE EXISTING EXHAUST STACK/FLUE FOR NEW CONNECTION ON THIRD FLOOR.

4. PROTECT EXISTING EIFS AND INFILL OPENING FROM DUCT REMOVAL. SEE DETAIL 'D9'

ON SHEET -1-MG-003.

5. PATCH CONCRETE FLOOR WITH SUPPORTED CONCRETE FROM DUCT REMOVAL. SEE

DETAIL 'A8' ON SHEET 1-MG-003.

GENERAL NOTES

1. EVERYTHING IS EXISTING TO REMAIN UNLESS OTHERWISE NOTED.

EXHAUST FAN 1-EF3-LAB

CONNECTION TO

G3-GAS CABINET

10"ø 14"x14"

10"ø

BLOWER COIL BC-1

CONNECTION TO

C1-CHEMICAL HOOD

CEILING OF ROOM 2C19

CEILING OF ROOM 3C17

14"x14"

8"ø

30"x12"

EXISTING 30"x12"

EXISTING 30"x12"

8"Ø SS

8"Ø SS

8"ø

12"Ø SS

CONNECTION TO

B1-BIOSAFETY CABINET 10"Ø SS

LAB EXHAUST FAN

1-EF1-LAB AND 1-EF2-LAB

12"x8"

12"ø

BLOWER COIL BC-2

14"x14"

CONNECTION TO

G10-GAS CABINET

8"Ø SS

10"Ø SS

12"Ø SS

PE−2021014461P

R

O F

E S S I O N A L E N G

I N E

E R

HANNAH

ROSE

KIGER

S T

A

T E

OF MI SSO

U

R I

DESIGN-AIRE ENGINEERING, INC.

www.daengineering.comwww.daengineering.com voice (317) 464-9090

2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

FCA - Create Code Compliant Research Laboratory Space in Building 1

657-23-113JB

Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM

08-6231 1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

01-18-2024

100% CONSTRUCTION DOCUMENTS

100% SPRINKLERED

Checker Author

1-MH-104

LAB 2C19 AND LAB 3C17 HVAC

OVERALL 3D VIEW

NO SCALE

LAB 2C19 AND LAB 3C17 HVAC OVERALL 3D VIEW

KEYED NOTES

1. MANUAL VOLUME DAMPER.

2. FIRE DAMPER WITH DUCT ACCESS DOOR AT FLOOR PENETRATION.

3. LAB HOOD EXHAUST FAN TRANSDUCER AND PRESSURE PROBE AND 10"x 10"

DUCT ACCESS DOOR.

4. CONNECTION TO EXISTING ROOF THIMBLE/TERMINAL.

5. CONNECTION TO EXISTING OUTSIDE AIR DUCT.

6. SEE DETAIL 'A1' ON SHEET 1-MH-104.

3/4" = 1'-0" A1

EXHAUST DUCT DETAIL