657-23-113JB - Construction Drawings - 4 of 14 - AE.pdf
PDF 2 MB Posted
- Attached to
- Z1DA--Create Code Compliant Research Laboratory Space in Building 1, 657-23-113JB Federal contract opportunity
- Solicitation number
- 36C25524R0053
About this file
This document appears to be a set of construction drawings and specifications related to a federal contract opportunity to create code compliant research laboratory space in an existing building. The key details are:
The project involves renovating existing research laboratory spaces in Building 1 at the Saint Louis VA Health Care System to bring them up to current code compliance standards. The drawings provide detailed plans, elevations, and specifications for demolition, architectural finishes, casework, and related MEP work in two specific laboratory spaces, 2C19 and 3C17. The scope includes new partitions, doors, windows, casework, finishes, and mechanical/electrical/plumbing systems to create the compliant laboratory environments. The federal contract opportunity, Solicitation Number 36C25524R0053, is being issued by the Department of Veterans Affairs Veterans Health Administration for this construction project. No additional details about the solicitation, such as response dates, award information, or set-asides, are provided in this document.
View the file
Other files for this federal contract opportunity
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. THE CONTRACTOR SHALL CAREFULLY STUDY AND
COMPARE THE CONTRACT DOCUMENTS WITH EACH
OTHER AND WITH AS-BUILT DRAWINGS PROVIDED
BY THE OWNER AND SHALL AT ONCE REPORT TO
THE ARCHITECT ERRORS, INCONSISTENCIES, OR
OMISSIONS. THE CONTRACTOR SHALL TAKE FIELD
MEASUREMENTS AND VERIFY FIELD CONDITIONS.
2. CONFIRM ALL NEW AND EXISTING CONDITIONS WITH
THE CONTRACT DOCUMENTS. NOTIFY ARCHITECT
IMMEDIATELY IN WRITING OF ALL DISCREPANCIES
OR CONFLICTS. DO NOT PROCEED WITH WORK IN
THE AREA OF DISCREPANCY OR CONFLICT UNTIL
DIRECTION IS GIVEN BY ARCHITECT. IF
CONTRACTOR PROCEEDS WITHOUT DIRECTION
FROM ARCHITECT, IT SHALL BE AT CONTRACTORS
RISK AND CONTRACTOR SHALL BE RESPONSIBLE
FOR ALL REQUIRED CORRECTIVE ACTION.
3. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR
AND HAS CONTROL OVER CONSTRUCTION MEANS,
METHODS, TECHNIQUES, SEQUENCES, AND
PROCEDURES, AND FOR COORDINATING ALL
PORTIONS OF THE WORK.
4. REVIEW THE ARCHITECTURAL DRAWINGS BEFORE
THE INSTALLATION OF SYSTEMS SHOWN ON
CONSULTING ENGINEER'S DOCUMENTS.
DISCREPANCIES BETWEEN THE ARCHITECTURAL
AND CONSULTING ENGINEER;S DOCUMENTS SHALL
BE BROUGHT TO THE ARCHITECT'S ATTETION FOR
DIRECTION. CONSTRUCTION INSTALLED IN
CONFLICT WITH THE ARCHITECTURAL DRAWINGS
SHALL BE CORRECTED BY CONTRACTOR AT NO
EXPENSE TO THE OWNER.
5. THE INTENT OF THE CONTRACT DOCUMENTS IS TO
ALLOW FOR THE PERFORMANCE OF THE WORK.
EVERY ITEM NECESSARILY REQUIRED MAY NOT BE
SPECIFICALLY MENTIONED OR SHOWN. UNLESS
EXPRESSLY STATED, ALL SYSTEMS AND EQUIPMENT
SHALL BE COMPLETED AND APPROPRIATELY
OPERABLE. FURNISH AND INSTALL ALL SPECIFIED
AND APPROPRIATE ITEMS, AND ALL INCIDENTAL,
ACCESSORY, AND OTHER ITEMS NOT SPECIFIED
BUT REQUIRED FOR A COMPLETE AND FINISHED
ASSEMBLY.
6. FOR APPLICABLE CODES AND STANDARDS REFER
TO LS SHEETS.
7. THE CONTRACTOR SHALL ESTABLISH CLEAR
UNDERSTANDING OF REQUIREMENTS OF THE
PROJECT, SYSTEMS AND THEIR COMPONENTS
PRIOR TO ORDERING MATERIALS OR COMMENCING
WORK.
8. THE CONTRACTOR SHALL PROVIDE SHORING,
BRACING, SUPPORT AND PROTECTION AS
REQUIRED.
9. THE CONTRACTOR IS RESPONSIBLE FOR ALL MEANS
AND METHODS OF CONSTRUCTION AND SHALL
COORDINATE ALL CONSTRUCTION EFFORTS WITH
THE OWNER'S REQUIREMENTS.
10. THE CONTRACTOR SHALL COORDINATE ALL WORK
WITH THE OWNER AND OWNER PROVIDED
CONTRACTORS, IF ANY, AS REQUIRED TO
IMPLEMENT THE SCOPE OF WORK.
11. THE ARCHITECT SHALL NOT BE RESPONSIBLE FOR
LOCATING, IDENTIFYING OR SPECIFYING MEANS OF
REMOVAL OF ANY HAZARDOUS MATERIALS.
HAZARDOUS MATERIAL TESTING SHALL BE
COMPLETED BY OWNER CONTRACTED
CONSULTANT.
12. CONTRACTOR TO COORDINATE FLOOR, WALL AND
CEILING FIRE RATINGS WITH CODE COMPLIANCE
SHEETS. ALL PENETRATIONS THROUGH RATED
ASSEMBLIES TO BE SEALED WITH AN APPROPRIATE
FIRESTOP SYSTEM WITH AN EQUAL OR GREATER
RATING THAN THE PENETRATED ASSEMBLY.
13. NON-COMPLIANT DEFECTIVE WORKMANSHIP OR
QUALITY WILL BE REJECTED DESPITE THE
ARCHITECT'S FAILURE TO DISCOVER OR POINT OUT
DEFECTS OR DEFICIENCIES DURING
CONSTRUCTION. DEFECTIVE WORK REVEALED
WITHIN THE TIME REQUIRED BY GUARANTEES
SHALL BE REPLACED BY WORK CONFORMING TO
THE INTENT OF THE CONTRACT. NO PAYMENT,
EITHER PARTIAL OR FINAL, SHALL BE CONSTRUED
AS AN ACCEPTANCE OF DEFECTIVE WORK OR
IMPROPER MATERIALS.
14. CONTRACTOR SHALL PREPARE AS-BUILT DRAWINGS
BASED ON THE ARCHITECTS RECORD DRAWINGS
AND DISTRIBUTE ELECTRONICALLY TO THE OWNER
AT THE CONCLUSION OF THE PROJECT.
15. THROUGHOUT THE DURATION OF THE PROJECT,
THE CONTRACTOR SHALL REFRAIN FROM ACTIONS
THAT COULD LEAD TO THE FILING OF CLAIMS OF
LIEN BY SUBCONTRACTORS, SUPPLIERS OF
MATERIALS, LABOR, SERVICE, EQUIPMENT, OR ANY
OTHER INDIVIDUAL OR COMPANY SO ENTITLED
UNDER GOVERNING LAWS AND REGULATIONS,
UNLESS REASONABLE AND JUSTIFIABLE CAUSE CAN
BE SHOWN. APPROVAL FOR PAYMENT SHALL BE
CONTINGENT UPON THE CONTRACTOR'S OBTAINING
AND FURNISHING TO THE ARCHITECT SIGNED
RELEASES FROM SUCH INDIVIDUALS OR
COMPANIES.
25. COORDINATE ALL WORK WITH BUILDING OWNER SO
AS NOT TO DISTURB OR CAUSE DAMAGE TO ANY
TENANT IN THE BUILDING. AVOID CONFLICT AND
INTERFERENCE WITH NORMAL BUILDING
OPERATIONS BY COMPLYING WITH THE BUILDING'S
REGULATIONS REGARDING SCHEDULING AND USE
OF ELEVATORS AND LOADING DOCKS FOR
DELIVERIES, HANDLING OF MATERIALS, EQUIPMENT,
AND DEBRIS.
26. ALL SIGNAGE IS NIC UNLESS NOTED OTHERWISE.
16. EXECUTE WORK IN ACCORDANCE WITH ANY AND
ALL APPLICABLE LOCAL, STATE, AND FEDERAL
CODES, MANUFACTURER'S RECOMMENDATIONS,
AND TRADE AND REFERENCED STANDARDS,
INCLUDING BUT NOT LIMITED TO: IBC, NEC AND NFPA
(LATEST APPLICABLE ENFORCED EDITIONS
REFERENCED).
17. DO NOT SCALE DRAWINGS; DIMENSIONS SHALL
GOVERN. DETAILS SHALL GOVERN OVER PLANS
AND ELEVATIONS. LARGE SCALE DETAILS SHALL
GOVERN OVER SMALL SCALE DETAILS. WRITTEN
SPECIFICATIONS SHALL GOVERN OVER ALL.
18. THERE SHALL BE NO SUBSTITUTION OF MATERIALS
WHERE A MANUFACTURER IS SPECIFIED. WHERE
THE TERM "OR EQUAL" IS USED, THE ARCHITECT
ALONE SHALL DETERMINE EQUALITY BASED UPON
INFORMATION SUBMITTED BY THE CONTRACTOR,
INCLUDING THE ARCHITECTS SUBSTITUTION FORM
CLEARLY IDENTIFIED AS A "REQUEST FOR
SUBSTITUTION". CONTRACTOR SHALL ALSO LIST
CREDIT TO THE CLIENT FOR USE OF SUBSTITUTION.
19. DO NOT PROCEED WITH ANY WORK REQUIRING
ADDITIONAL COMPENSATION BEYOND THE
CONTRACT AMOUNT WITHOUT WRITTEN
AUTHORIZATION FROM THE OWNER. FAILURE TO
OBTAIN AUTHORIZATION SHALL INVALIDATE ANY
CLAIM FOR EXTRA COMPENSATION.
20. UPON COMPLETION OF THE WORK BY THE
CONTRACTOR, THE CONTRACTOR SHALL NOTIFY
THE ARCHITECT IN WRITING OF SUCH COMPLETION.
THE ARCHITECT SHALL ATTEND THE PUNCH LIST
WALK THROUGH CONDUCTED BY THE GENERAL
CONTRACTOR. THE GENERAL CONTRACTOR SHALL
PREPARE AND DISTRIBUTE A LIST OF ITEMS TO BE
FINISHED OR COMPLETED PRIOR TO THIS WALK
THROUGH. THE GENERAL CONTRACTOR SHALL
TAKE NOTES AND PREPARE A LIST OF FINAL PUNCH
ITEMS TO BE COMPLETED OR CORRECTED AS A
RESULT OF THIS WALK THROUGH. THIS PUNCH LIST
IS TO BE PROMPTLY DISTRIBUTED BY THE GENERAL
CONTRACTOR TO THE TENANT, OWNER AND
ARCHITECT.
21. IT IS THE RESPONSIBILITY OF THE GENERAL
CONTRACTOR TO REVIEW ALL SUBMITTALS AND
SHOP DRAWINGS FOR APPROPRIATENESS AND
COMPLIANCE WITH THE CONTRACT DOCUMENTS
PRIOR TO SENDING SHOP DRAWINGS TO THE
ARCHITECT OR ENGINEER FOR REVIEW. A STAMP
OR STATEMENT TESTIFYING THE CONTRACTOR HAS
REVIEWED THE SHOP DRAWINGS, INCLUDING THE
DATE REVIEWED, MUST BE AFFIXED TO THE FIRST
PAGE OF EACH SUBMITTAL.
22. PROVIDE METAL OR FIRE RETARDANT WOOD
BLOCKING FOR ALL SIGNS, HOOKS, TOILET ROOM
ACCESSORIES, AND ANY OTHER CEILING OR WALL
MOUNTED EQUIPMENT. COORDINATE ALL BLOCKING
REQUIREMENTS REQUIRED WITH ARCHITECT.
23. COORDINATE WORK OF VARIOUS TRADES IN
INSTALLATION OF INTERRELATED WORK BEFORE
INSTALLATION OF WORK BY ANY TRADE, INCLUDING
VENDORS. GENERAL CONTRACTOR TO MAKE
PROPER PROVISIONS TO AVOID INTERFERENCE.
24. GENERAL CONTRACTOR TO PROVIDE PORTABLE
FIRE EXTINGUISHERS AT THE JOB SITE FOR THE
DURATION OF DEMOLITION AND CONSTRUCTION AS
REQUIRED BY THE LOCAL FIRE DEPARTMENT.
Z
Z
LEVEL
#'-##" AFF
A2.3 A1
123A
X X
Door Tag
Window Tag
Keyed Note
Ceiling Tag ACT = Material
Floor Transition Tag X = Material
Revision Tag
Centerline Mark
Existing Construction shown Halftone
Demolished Items shown Dashed
New Construction shown Solid
Exterior Elevation Mark X = Elevation Number Y#.## = Sheet Number
North Arrow & True North Indicator
Wall Section Mark X = Elevation Number Y#.## = Sheet Number
Detail Mark X = Elevation Number Y#.## = Sheet Number
Room Tag A100 = Room Number
Detail / Plan Callout X = Elevation Number Y#.# = Sheet Number
Elevation Datum
New Column Line
Existing Column Line
02.03
Partition Type:
Refer to Partition Type Sheet
X Y#.##
X Y#.##
Y#.##
X
SIM
X
SIM
X
SIM
X
SIM
Y#.##
X
SIM
X
SIM
X
SIM
X
SIM
X Y#.##
X Y#.##
Building Section Mark X = Elevation Number Y#.## = Sheet Number
Interior Elevation Mark X = Elevation Number Y#.## = Sheet Number xxx Corner Guard
99' - 10 11/16"
[L###] Millwork Tag Refer to Millwork Elevation Types Sheet(s)
Fixture / Accessory Tag
ALIGN
Align Items
Survey PointWork Point
Exit Sign (Arrows = Direction to Exit)
TRUE
NORTH
ROOM NAME
A100
150 SF
Volume
X
BRICK & TILE (CUT)
ASPHALT (CUT)
CMU (CUT)
CONCRETE (CUT)
EARTH: COMPACTED FILL
EARTH: UNDISTURBED
GLASS (CUT)
GRAVEL: CRUSHED
GROUT / MORTAR
GYSPUM BOARD: INTERIOR (CUT)
INSULATION: BATT
INSULATION: RIGID (CUT)
INSULATION: SPRAY FOAM
INSULATION: MINERAL
FIBER BOARD
INSULATION: DENSE
PACK CELLULOSE
STEEL
WOOD FRAMING / BLOCKING
WOOD FINISH (FACE)
WOOD FINISH (CUT)
WOOD SHEATHING (FACE)
WOOD SHEATHING (CUT)
ALUMINUM (CUT)
CONTINUOUS NOT CONTINUOUS
GYSPUM BOARD: EXTERIOR (CUT)
STEEL
LEVEL 2
LEVEL 3
2C19
3C17
Project Area, B Business
Occupancy Use Groups
EGRESS DOOR TAG
EXIT
MAXIMUM ACTUAL
A101.1
231 000
DOOR NUMBER
EXISTING 2-HOUR RATED PARTITION
ANTICIPATED OCCUPANT CAPACITY
MAXIMUM OCCUPANT CAPACITY
PATH OF TRAVEL TO EXIT
Demo Area Outside Labs C219 and C317 (Refer to sheet 1-AE-100 for full extent of Demo Scope)
Occupied Spaces Not in Contract (NIC)
NEW 1-HOUR RATED PARTITION (REFER TO SHEET
1-AE-101)
EXISTING 20 MIN PARTITION
1. AREAS SHOWN IN LS SHEETS ARE DIAGRAMMATIC ONLY AND
SHOULD NOT BE USED AS THE BASIS OF MATERIAL
CALCULATIONS OR QUANTITIES.
2. ALL FIRE RATINGS SHOWN IN LS SHEETS ARE TO BE
COORDINATED WITH PARTITION TYPE TAGS IN FLOOR PLANS.
CONTRACTOR TO NOTIFY ARCHITECT OF ANY DESCREPANCIES
BETWEEN TAGS AND LS SHEETS. IF THE CONTRACTOR CHOOSES
TO PROCEED WITHOUT NOTIFYING THE ARCHITECT AND
RECEIVING DIRECTION FOR ANY CLARIFICATION OR
DISCREPANCY, THE CONTRACTOR DOES SO AT THEIR OWN RISK.
3. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL
SUB-CONTRACTORS, INCLUDING THOSE HIRED BY THE OWNER,
TO PROVIDE ALL FIRE RATED REQUIREMENTS ASSOCIATED WITH
ELEMENTS INCLUDING BUT NOT LIMITED TO MECHANICAL,
ELECTRICAL & PLUMBING PENETRATIONS, DOORS AND OTHER
OPENINGS.
4. THE CONTRACTOR IS RESPONSIBLE FOR MAINTAINING SAFE
EGRESS PATHS THROUGHOUT THE DURATION OF DEMOLITION
AND CONSTRUCTION, MAINTAINING REQUIRED MEANS OF
EGRESS FREE OF DEBRIS AND OTHER OBSTRUCTION.
5. EXIT SIGNS NOT SHOWN ON THIS PLAN - COORDINATE WITH RCP
& ELECTRICAL DRAWINGS IF APPLICABLE.
CODE DATA
Primary Structural Frame
Bearing Walls - Exterior
Bearing Walls - Interior
Nonbearing Walls & Partitions - Exterior
Nobearing Walls & Partitions - Interior
Floor Construction & Associated Secondary Members
Roof Construction & Associated Secondary Members
Building Code 2015 International Existing Building Code (IEBC)
2015 International Mechanical CodeMechanical Code
2015 Uniform Plumbing CodePlumbing Code
2014 NFPA 70 National Electrical CodeElectrical Code
B-BusinessUse Group
Fully SprinkleredFire Suppression
IBConstruction Type
302.1
901.6
602.1
Notes:
1. No changes to egress.
2. No changes to occupancy.
3. Renovations per IEBC 2015; Alterations Level 2 (801).
4. NFPA referenced sections are based on 2021 NFPA 101 Existing Business
Occupancy 39.1 and as referenced in IEBC 2021
Fire Resistance Rating Chart
Building Element TYPE I
A B
2015 International Energy Conservation CodeEnergy Code
2015 International Fire CodeFire Protection Code
IBC
Reference
NFPA STATE
6.1.11
9.11.4.1
II (222)
EXIT
MAXIMUM ACTUAL
STAIR
EXIST
EXIT
MAXIMUM ACTUAL
STAIR
EXIST
EXIT
MAXIMUM ACTUAL
STAIR
EXTG
EXIT
MAXIMUM ACTUAL
STAIR
EXTG
DESIGN-AIRE ENGINEERING, INC.
www.daengineering.comwww.daengineering.com voice (317) 464-9090
2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - Create Code Compliant Research Laboratory Space in Building 1
657-23-113JB
Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM
08-6231 1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
100% SPRINKLERED
CONSTRUCTION DOCUMENTS
12-22-2023 RD NB
1-AE-000
ARCHITECTURAL GENERAL - CODE
INFORMATION
No. Name
00-COVER SHEET
1-AE-000 ARCHITECTURAL GENERAL - CODE INFORMATION
40-ARCHITECTURAL DEMOLITION
1-AE-100 ARCHITECTURAL DEMOLITION PLANS
45-ARCHITECTURAL
1-AE-102 3C17 - PLANS
45-ARCHITECTURAL (A)
1-AE-101 2C19 - PLANS
1-AE-103 ROOF PLAN
1-AE-104 FINISH PLANS
1-AE-106 AREA PLANS
1-AE-401 2C19 - INTERIOR ELEVATIONS
1-AE-402 3C17 - INTERIOR ELEVATIONS
1-AE-501 MILLWORK ELEVATIONS & DETAILS
& AND
AB ACOUSTICAL BAFFLE
AC ACOUSTICAL CEILING TILE
ADJ ADJUSTABLE
ADJC ADJACENT
AFF ABOVE FINISHED FLOOR
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZED
AP ACOUSTICAL PANEL
APPL APPLIANCE
ARCH ARCHITECT(URAL)
ASSY ASSEMBLY
AUTO AUTOMATIC
AVG AVERAGE
BD BOARD
BL BLINDS
BLDG BUILDING
BLKG BLOCKING
BOD BOTTOM OF DECK
BR BRICK
BTWN BETWEEN
BU BUILT UP
C CARPET
CAB CABINET
CEM CEMENT(ITIOUS)
CER CERAMIC
CIP CAST-IN-PLACE
CL CENTERLINE
CLG CEILING
CMU CONCRETE MASONRY UNIT
CN CONCRETE
CO CLEANOUT
COILG COILING
COL COLUMN
COMM COMMUNICATION
CONSTR CONSTRUCTION
CONT CONTINUOUS(ATION)
CONTR CONTRACT(OR)
CSJ CONSTRUCTION JOINT
CSWK CASEWORK
CT CERAMIC TILE
D DEEP, DEPTH
DEMO DEMOLISH
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DIM DIMENSION
DIV DIVISION, DIVIDE
DN DOWN
DP DRAPERY
DR DOOR
DS DOWNSPOUT
DW DISHWASHER
DWG DRAWING
EA EACH
EF EPOXY FLOOR
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
ENGR ENGINEER(ED)
ENTR ENTRANCE
EPB ELECTRICAL PANEL BOARD
EQ EQUAL
EQUIP EQUIPMENT
ETC ETCETERA
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXT EXTERIOR
F FABRIC
FD FLOOR DRAIN
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER AND
CABINET
FHC FIRE HOSE AND CABINET
FIN FINISH
FLR FLOOR(ING)
FP FIRE PROTECTION, FIRE
PROOFING
FR FIRE RAT(ING)(ED)
FRMG FRAMING
FRP FIBERGLASS REINFORCED
PANEL
FTG FOOTING
FTWD FIRE TREATED WOOD
FURN FURNITURE
FWC FABRIC WALL COVERING
FWP FABRIC WRAPPED PANEL
FXD FIXED
FXTR FIXTURE
GA GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GF GLASS FILM
GFRC GLASS FIBER REINFORCED
CONCRETE
GL GLASS
GP GRAPHIC
GR GRAD(E)(ING)
GSB GYPSUM SHEATHING BOARD
GT GROUT
GWB GYPSUM WALL BOARD
GYP GYPSUM
HB HOSE BIBB
HD HEAD
HDW HARDWARE
HDWD HARDWOOD
HM HOLLOW METAL
HO HOLD OPEN
HOR HORIZONTAL
HT HEIGHT
HVAC HEATING, VENTILATIING, AND
AIR CONDITIONING
ID INSIDE DIAMETER
IF INSIDE FACE
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
INV INVERT
JAN JANITOR
JT JOINT
KB KNEE BRACE
KIT KITCHEN
LAB LABORATORY
LAV LAVATORY
LB POUND
LF LINEAR FEET
LP LOW POINT
LT LIGHT
LVR LOUVER
MATL MATERIAL
MAX MAXIMUM
MB MARKER BOARD
MD METAL DECK
MDF MEDIUM DENSITY FIBERBOARD
MECH MECHANICAL
MED MEDIUM
MEMB MEMBRANE
MEZZ MEZZANINE
MFD MANUFACTURED
MFR MANUFACTURER
MGT MANAGEMENT
MIN MINIMUM
MIRR MIRROR
MISC MISCELLANEOUS
MLWK MILLWORK
MO MASONRY OPENING
MTD MOUNTED
MTL METAL
MW MICROWAVE
NA NOT APPLICABLE
NIC NOT IN CONTRCT
NO NUMBER
NOM NOMINAL
NOMINAL
NS NARROW STILE
NTS NOT TO SCALE
OA OVERALL
OC ON CENTER
OF OUTSIDE FACE
OHD OVERHEAD DOOR
OPNG OPENING(S)
OPP OPPOSITE
OPT OPTIONAL
ORD OVERFLOW ROOF DRAIN
OVFL OVERVLOW
PBD PARITICLE BOARD
PC PRIVACY CURTAIN
PL PLASTIC LAMINATE
PLAS PLASTER
PLYWD PLYWOOD
PNL PANEL
PORT PORTABLE
PREFAB PREFABRICATED
PREFIN PREFINISHED
PROP PROPERTY
PT PAINT
PTN PARTITION
PTWD PRESSURE TREATED WOOD
PV PAVER
QTR QUARTER
QTY QUANTITY
R RADIUS
RB RESILIENT BASE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RDR READER
RECES RECESSED
RECT RECTANG(LE)(ULAR)
REF REFER(ENCE)
REFL REFLECTED
REFR REFRIGERATOR
REINF REINFORCED(D)(ING)(MENT)
REQD REQUIRED
REV REVISION
RF RESILIENT FLOORING
RFG ROOFING
RL ROOF LEADER
RLG RAILING
RM ROOM
RO ROUGH OPENING
RS ROLLER SHADES
RTU ROOF TOP UNIT
SC SOLID CORE
SCHED SCHEDULE
SCR SCRIBE
SECUR SECURITY
SF SQUARE FEET
SG SINGLE
SHTHG SHEATHING
SIM SIMILAR
SK SINK
SLNT SEALANT
SM SHEET METAL
SPEC SPECIFICATIONS
SQ SQUARE
SS STAINLESS STEEL
SSM SOLID SURFACE MATERIAL
ST STONE
STD STANDARD
STL STEEL
STRUCT STRUCTURAL
SURF SURFACE
SUSP SUSPENDED
SYS SYSTEM(S)
T TILE
T&G TOUNGUE AND GROOVE
TB TACK BOARD
TD TRENCH DRAIN
TEL TELECOM
TGL TEMPERED GLASS
THK THICK
TLT TOILET
TOC TOP OF CONCRETE
TOJ TOP OF JOIST
TOS TOP OF STEEL
TOW TOP OF WALL
TR TREAD
TRTD TREATED
TYP TYPICAL
UNFIN UNDERLAYMENT
UNO UNLESS NOTED OTHERWISE
UP UPHOLSTERY
UR URINAL
UTIL UTILITY
VAR VARI(ES)(ATION)
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VIF VERIFY IN FIELD
VTR VENT THROUGH ROOF
W WIDTH
W/ WITH
W/O WITHOUT
WB WOOD BASE
WBL WOOD BLOCKING
WC WATER CLOSET
WC WALL COVERING
WD WOOD
WDW WINDOW
WO WHERE OCCURS
WP WALL PROTECTION
WT WEIGHT
WTPR WATERPROOFING
YD YARD
TRUE
NORTH
NOT TO SCALE
Key Plan
GENERAL PROJECT NOTES: MATERIAL HATCHES: SYMBOLS LEGEND:
INDEX TO DRAWINGS:
ABBREVIATIONS:
L.S PLAN LEGEND:
GENERAL L.S PLAN NOTES:
SCALE: 1/32" = 1'-0"1-AE-000
4F LIFE SAFETY PLAN - SECOND FLOOR
SCALE: 1/32" = 1'-0"1-AE-000
7F LIFE SAFETY PLAN - THIRD FLOOR
Fox, Inc. dba Fox Architects 1 S Memorial Dr., Suite 1800
St. Louis, MO 63102
LIFE SAFETY CODE REFERENCES
3C172C19
SYMBOLS LEGEND:MATERIAL HATCHES:GENERAL PROJECT NOTES:
Note: Laboratory units and laboratory hoods in which chemicals are present shall be continuously ventilated under normal operating conditions.
01-18-2024
LEVEL 2
LEVEL 3
2C19
3C17
LEVEL 1
1C19
2C17
DEMOLISH EXISTING
PLASTER AND LATH
FURR-OUT
DEMOLISH LOOSE PLASTER,
WIRE BRUSH REMAINING
SURFACES IN PREPARATION OF
NEW FINISH FROM SILL TO
HEAD. SEE THE FINISH PLAN
FOR MORE INFORMATION.
(TYPICAL FOR ALL WINDOW
OPENINGS)
DEMOLISH EXISTING DOOR &
FRAME, SEE PLAN 5F/1-
AE-101 FOR NEW DOOR
DEMO EXISTING WINDOW GLAZING AND INTERIOR
FRAMING, KEEP EXISTING ALUMINUM EXTERIOR FRAME IN
PLACE AND INTACT AS IS, INCLUDING EXISTING EXTERIOR
SEALANT. TWO WINDOWS THIS ROOM
VACANT
3C21
HAC
3C20
DEMOLISH EXISTING
PLASTER AND LATH CHASE
SEE MD-SERIES DRAWING
FOR MORE INFORMATION
DEMOLISH LOOSE PLASTER,
SCRATCH FACE OF REMAINING
PLASTER IN PREPARATION OF NEW
FINISH FROM SILL TO HEAD (TYP)
DEMOLISH EXISTING PLASTER
AND LATH FURR-OUT
DEMOLISH EXISTING DOOR &
FRAME, SEE PLAN 5F/1-AE-102
FOR NEW DOOR
DEMOLISH EXISTING PLASTER
AND LATH, CLAY-TILE
PARTITION FOR NEW DOOR
SEE SHEET 1-AE-102 FOR
NEW DOOR LOCATION
OFFICE
3C26
LAB
3C18
LAB
3C17
LAB
3C15
CORIDOR
H305
CORRIDOR
H304
MECHANICAL
3C23
CHASE
CH-C-8
DEMOLISH THE EXISTING
HANDRAIL AND LOWER
BUMPERRAIL TO NEAREST
SEAM
CHASE
CH-C-6
(TYP) SEE SHEET 1-GJ-001 FOR
MORE INFORMATION ON ICRA
PARTITION REQUIREMNETS
DEMO EXISTING WINDOW GLAZING AND
INTERIOR FRAMING, KEEP EXISTING
ALUMINUM EXTERIOR FRAME IN PLACE AND
INTACT AS IS, INCLUDING EXISTING EXTERIOR
SEALANT. TWO WINDOWS THIS ROOM
(TYP) SEE SHEET 1-GJ-001
FOR
MORE INFORMATION ON ICRA
PARTITION REQUIREMNETS
REMOVE PORTION OR ENTIRETY OF AN EXISTING
COMPONENT - ACCOMPANIED w/ A KEYED NOTE.
COORDINATE w/ NEW WORK.
NOTE:
ALL ITEMS TO BE DEMOLISHED WILL BE SHOWN DASHED AND KEY
NOTED UNLESS IT IS A TYPICAL ITEM BEING DEMOLISHED AND THEN IT
MAY ONLY BE NOTED ONCE, BUT WILL BE GRAPHICALLY SHOWN AS
DEMOLISHED
EXISTING WALL TO REMAIN -
PROTECT DURING CONSTRUCTION
EXISTING DOOR TO REMAIN -
PROTECT DURING CONSTRUCTION
PARTITION TO BE DEMOLISHED
TEMPORARY CONSTRUCTION ICRA BARRIER
DEMOLISHED DOOR IN EXISTING WALL -
PROTECT WALL DURING CONSTRUCTION
OFFICE
2C13
OFFICE
2C14
CORRIDOR
H205
OFFICE
2C12
(TYP) SEE SHEET 1-GJ-001 FOR
MORE INFORMATION ON ICRA
PARTITION REQUIREMNETS
EXTENT OF LAB 3C17 ABOVE
SHARED
OFFICE
C106A
OFFICE
C106
OFFICE
C105
WAITING RM
H115A
EXTENT OF LAB 2C19 ABOVE
(TYP) SEE SHEET 1-GJ-001 FOR
MORE INFORMATION ON ICRA
PARTITION REQUIREMNETS
GWB8'-0"
GWB7'-3"
ACT8'-6"
GWB8'-0"
OFFICE
3C26
MECHANICAL
3C23
VACANT
3C21
LAB
3C18
LAB
3C17
LAB
3C15
CORRIDOR
H304
CORIDOR
H305
HAC
3C20
11'-0"
GWB8'-6"
THIS ROOM HAD BEEN DEMO
UNDER A PREVIOUS PROJECT.
SEE MECH DRAWINGS FOR NEW
WORK, ALL NEW WORK TO BE
HELD 9'-0" AFF. EXISTING CEILING
WAS AT 8'-8" AFF.
THIS ROOM HAD BEEN DEMO
UNDER A PREVIOUS PROJECT.
SEE MECH DRAWINGS FOR NEW
WORK, ALL NEW WORK TO BE
HELD 9'-0" AFF. EXISTING CEILING
WAS AT 8'-8" AFF
THIS ROOM HAD BEEN
DEMO
UNDER A PREVIOUS
PROJECT
(TYP) SEE SHEET 1-GJ-001 FOR
MORE INFORMATION ON ICRA
PARTITION REQUIREMNETS
ACT8'-11"
1' x 4' LAY-IN LIGHT FIXTURE
2' x 4' SURFACE MOUNTED
LIGHT FIXTURE
2' x 4' LAY-IN LIGHT FIXTURE
1' x 1' RETURN AIR DEVICE
2' x 2' SUPPLY AIR DEVICE
SPRINKLER HEAD
FIRE ALARM/STROBE
SMOKE DETECTOR
SPEAKER
EXIT LIGHT
EXISTING LIGHTING
EXISTING MECH
EXISTING LIFE SAFETY
DESIGN-AIRE ENGINEERING, INC.
www.daengineering.comwww.daengineering.com voice (317) 464-9090
2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - Create Code Compliant Research Laboratory Space in Building 1
657-23-113JB
Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM
08-6231 1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
100% SPRINKLERED
CONSTRUCTION DOCUMENTS
12-22-2023 Checker Author
1-AE-100
ARCHITECTURAL DEMOLITION PLANS
TRUE
NORTH
NOT TO SCALE1-AE-100
1 KEY PLAN-DEMOLITION
DEMOLITION NOTES:
FLOOR PLAN LEGEND:
SCALE: 3/16" = 1'-0"1-AE-100
8F LAB - 2C19 CHEMICAL LAB
SCALE: 3/16" = 1'-0"1-AE-100
1F LAB - 3C17 & 3C26 BIOSAFETY LABS
1. THE DEMOLITION PLANS INTEND TO INDICATE THE GENERAL
NATURE OF THE DEMOLITION SCOPE. THE GENERAL
CONTRACTOR IS RESPONSIBLE FOR VISITING THE JOB SITE AND
VERIFYING THE EXISTING CONDITIONS.
2. COORDINATE WITH THE COR BEFORE DEMOLITION OCCURS FOR
STAGING, TEMPORARY SERVICES SHUTDOWNS, AND OTHER
SERVICES AND SITE ACCESS AS NOTED IN THE SPECIFICATIONS
SECTION 02 41 00 DEMOLITION.
3. THIS SHEET SHOWS THE EXISTING CEILING AREAS BELOW THE
PRIMARY PROJECT AREA. THE DEMOLITION SHOULD BE LIMITED
TO REMOVING EXISTING CEILING TILES, SOME GRID SECTIONS,
AND EXISTING, MECHANICAL AND ELECTRICAL CEILING DEVICES
AS REQUIRED TO ACCESS THE MEP ITEMS NOTED ABOVE.
REINSTALL EXISTING CEILING ITEMS REMOVED
SCALE: 3/16" = 1'-0"1-AE-100
5B SECOND FLOOR RCP - BELOW LAB 3C17SCALE: 3/16" = 1'-0"1-AE-100
1B FIRST FLOOR RCP - BELOW LAB 2C19
SCALE: 3/16" = 1'-0"1-AE-100
1D THIRD FLOOR RCP
RCP DEMO LEGEND:
FOR MORE INFORMATION, SEE THE
LEGEND ON THIS SHEET FOR THE
HATCH AREA KEY AND 1F/1-AE-100.
01-18-2024 RD NB
UNDER CABINET
TASK LIGHTS
UNDER CABINET
TASK LIGHTS
1'-9"
ACT-1
8'-10'' AFF
SEE THE EXTENT OF THE FIRE PROTECTION SCOPE ON SHEET
1-FP-101, BUT DIMENSIONALLY LOCATE THE SPRINKLER HEADS
CENTERED IN THE CEILING PAD AS INDICATED HERE. (TYP)
SKIM COAT EXTG PLASTER
WITH MODIFIED GWB MUD AT
HEAD. (TYP)
SEE MECH DWGS FOR
CONNECTIONS
PROVIDE METAL
SHROUD FROM THE
TOP OF THE HOOD
TO THE UNDERSIDE
OF THE CEILING,
MATCHING
CASEWORK.
SEE MECH DWGS
FOR THROUGH
CEILING
CONNECTIONS
FROM HOOD TO
DUCTWORK ABOVE.
1-AE-401
2F
7F
1-AE-401
4D
LAB
2C19
CHEMICAL HOOD:
CO2, VACUUM, LPG
AND TYPE 2 WATER
POWER COMM, AIR, VACUUM,
AND LPG
SAFETY SHOWER &
EYE WASH
POWER/COMM, AIR,
VACCUM, AND LPG
9'-6"
MOBILE LAB CART
-80 FREEZER-20 FREEZER+4 REFRIGERATOR
GLASWARE WALL
AND COUNTER
DRYING STATION
24''
15''
MOBILE
18''
MOVABLE
15''
MOBILE
18''
MOVABLE
24''
M O
B
IL
E
A D
A
M O
B
IL
E
ALIGN
G2
G1
G11
F3F2F1
RE: 3D/1-AE-402
FOR TANK RACK
3 1/8" 2'-7"
1-AE-4017D
1'-3"
ALIGN
N TANKS
MED GAS TANKS
ALIGN
1-AE-401
4D
SIM
36''
2D 1-AE-4012D
SIM
PULL-OUT U.C.
VACUUM PUMP
G6
C1.2 1C1.2 1
TYPE 2 EQUIPMENT
WALL MOUNTED
TYPE 2 TANK MOUNTED
TO WALL
ABOVE EQUIP
C2A
C2B
C1.2 Ab
SOLID SURFACE
INTEGRAL BOWL
SINK
TYPE 2 WATER
DISPENSER
.5
W x
"D
.5 "H
C L E
A R
G7
SKIM COAT EXTG PLASTER
WITH MODIFIED GWB MUD
FROM SILL TO HEAD. (TYP)
REPLACE THE EXISTING DEMOLISHED
CHASE WITH NEW PARTITION C1.2 Ab IN
SAME LOCATION
NEW PARTITION B1.2 Ab IN SAME
LOCATION AS DEMOLISHED CHASE
FURR-OUT IN
FRONT OF THE
EXISTING
PARTITIONS WITH
THE NEW
PARTITION C1.2 Ab
G2
G1
P U
M P
C A
B
24''
TYPE 1 WATER
EQUIP MOUNTED TO
WALL
G3
8B
1-AE-401
B1.2 Ab A2.3 Ab
G8
B3
T2
T3
TYPICAL ALIGN EXPOSED
CABINET CHASE IN-FILL
PANEL WITH FACE OF
BASE
T1
36" AFF
34" AFF
G5
C1.2 Ab
3 1/8" 2'-6" 4'-9" 10'-5"(+/-) 2'-6" 3 1/8"4'-9"
2C
EXISTING WALL TO REMAIN -
PROTECT DURING CONSTRUCTION
EXISTING DOOR TO REMAIN -
PROTECT DURING CONSTRUCTION
TEMPORARY CONSTRUCTION BARRIER
1. SEE A0 SHEETS FOR TYPICAL FIXTURE & ACCESSORY MOUNTING
HEIGHTS AND REQUIRED CLEARANCES.
2. REFER TO CIVIL, STRUCTURAL AND MEP-FP DOCUMENTS FOR
REMAINDER INFORMATION NOT INDICATED ON ARCHITECTURAL
PLANS.
3. THE WORD "ALIGN" AS USED IN THESE DOCUMENTS SHALL
SUPERSEDE ANY DIMENSIONAL INFORMATION INDICATED. IF
DISREPENCIES OCCUR NOTIFY THE ARCHITECT IMMIDIATELY.
4. TYPICAL DIMENSIONS ARE TO THE FACE OF NEW CONSTRUCTION
OR TO THE COLUMN CENTER LINE. REFER TO ENLARGED PLAN
DETAILS FOR ADDITIONAL INFORMATION.
5. ALL ANGLES ARE 45, 90, 135 DEGREES UNO.
6. CONTROL JOINTS IN GYPSUM BOARD ASSEMBLIES INDICATED ON
PLANS AND INTERIOR ELEVATIONS ARE SHOWN AT SELECT
AREAS ONLY. IT IS GENERAL CONTRACTORS RESPONSIBILITY TO
PROVIDE CONTROL JOINTS IN ALL GYPSUM BOARD ASSEMBLIES
TO MEET REQUIREMENTS OUTLINED BY USG.
7. DIMENSIONS NOTED "CLEAR", "CLR" OR "HOLD" MUST BE
ACCURATELY MAINTAINED AND SHALL NOT VARY MORE THAN
+/- 1/8" WITHOUT APPROVAL FROM THE ARCHITECT.
8. INSTALL WATER RESISTANT GYPSUM WALL BOARD AT ALL "WET"
LOCATIONS.
9. PATCH AND REPAIR ALL EXISTING SURFACES AS NECESSARY
BEFORE APPLICATION OF NEW FINISHES/MATERIAL. ALL
DEFECTIVE FINISHES SHALL BE REMOVED AND REPAIRED PRIOR
TO APPLICATION OF NEW MATERIAL.
1. PROVIDE LEVEL 4 FINISH UNLESS NOTED OTHERWISE. PATCH AND
REPAIR SURFACES TO MATCH ADJACENT OR ADJONING SURFACES
WHERE REQUIRED. ALL SURFACES TO BE ALIGNED.
2. ALL NON-LOAD BEARING PARTITIONS SHALL BE CONSTRUCTED TO LIMIT
DEFLECTION PER LATEST PUBLISHED BUILDING CODE RESTRICTIONS
AND MANUFATURERS DATA - MOST STRINGENT.
3. PROVIDE APPROVED SHEET METAL BACKING OR FIRE TREATED WOOD
BLOCKING AT LOCATIONS INCLUDING BUT NOT LIMITED TO: SHELVING,
WALL CABINETS & SIGNAGE. CONTRACTOR IS RESPONSIBLE FOR
DETERMINING AND COORDINATING BLOCKING FOR ALL ITEMS
DESCRIBED IN DRAWINGS.
4. ALL GYPSUM BOARD PARTITIONS RECEIVING RUBBER BASE
(REGARLDESS OF HEIGHT) TO BE FINISHED SMOOTH TO FLOOR.
5. PROVIDE DOUBLE FRAMING AT ALL JAMBS AND CASED OPENINGS.
6. ISOLATE NON-LOAD BEARING PARTITIONS FROM STRUCTURAL
ELEMENTS WITH SLIP CONNECTIONS TO PREVENT TRANSFER OF LOADS
TO PARTITION FRAMING.
7. IT IS THE CONTRACTORS RESPONSIBILITY TO PROVIDE CONTROL
JOINTS IN ALL GYPSUM BOARD ASSEMBLIES TO MEET REQUIREMENTS
OUTLINED BY USG. REVIEW FINAL LOCATIONS OF CONTROL JOINTS
WITH ARCHITECT PRIOR INSTALLATION.
8. METAL STUD SPACING TO BE 16" O.C. UON.
9. ALL GYPSUM BOARD TO BE 5/8" UON.
10. FINISH MATERIALS SUCH AS TILE, WALL PANELING, TRIM, BASE, ETC.
ARE NOT SHOWN AS AN INTEGRAL PART OF THE PARTITION TYPE.
REFER TO FINISH SCHEDULE AND INTERIOR ELEVATIONS.
11. WALLS TO BE FULLY BRACED TO ABOVE FINISH CEILING, UON.
12. PROVIDE BRACING AT MAX STUD SPACING INDICATED.
13. MAINTAIN FIRE RATING
14. ALL GYPSUM BOARD IN WET LOCATIONS TO BE REPLACED WITH
MOISTURE & MOLD RESISTANT GYPSUM BOARD.
A1.3
PARTITION TYPE
Ab
FRAMING SIZE
ACOUSTICAL REQUIREMENTS
PARTITION HEIGHT / FIRE RATING
ID SIZE
1. 1 5/8"
2. 2 1/2"
3. 3 5/8" (OR MATCH EXTG
PARTITION THICKNESS)
FRAMING SIZE
ID REQUIREMENT
~ NO INSULATION REQUIRED
b UNFACED SOUND ATTENUATION BATT - FULL
HEIGHT OF CAVITY, ALL STUD BAYS TO BE FILLED
ACOUSTICAL REQUIREMENTS
ID REQUIREMENT
A EXTEND STUDS TO B.O. STRUCTURE ABOVE
EXTEND GYPSUM WALLBOARD ABOVE CEILING 6" MIN
PARTITION HEIGHT / FIRE RATING DESIGNATION
B.0. STRUCTURE
LINE OF CEILING
FINISHED FLOOR
A
A2
SOUND ATTENUATION
BLANKETS PER ACOUSTICAL
/ THERMAL REQUIREMENTS
GYPSUM WALLBOARD -
EACH SIDE
MTL. STUDS
@ 16" O.C. (MAX.)
SOUND RATING NOTE:
@ ACOUSTICALLY SOUND RATED
WALLS: STC 45-49
B1
REF: PLAN
SOUND ATTENUATION
BLANKETS PER ACOUSTICAL
/ THERMAL REQUIREMENTS
GYPSUM WALLBOARD -
ONE SIDE
MTL. STUDS
@ 16" O.C. (MAX.)
EXTERIOR WALL, SUBSTRATE,
REFERENCE LINE OR OTHER
WHERE OCCURS
UON MATCH EXISTING
C1
SOUND ATTENUATION
BLANKETS PER ACOUSTICAL
/ THERMAL REQUIREMENTS
GYPSUM WALLBOARD
C-H MTL. STUDS
@ 24" O.C. (MAX.)
FIRE RATING NOTE:
@ 1 HOUR RATED LOCATIONS:
ASSEMBLY SHALL CONFORM TO UL
DESIGN NO. U415
1" PLASTERBOARD
SHAFT LINER
1/2" CONTROL JOINT
1/2" CONTROL JOINT
RUNNER TRACK
SILL CONDITION
STUD CRIPPLE
STUD CRIPPLE - OMITTED AT
CONNECTION FOR CLARITY
RUNNER TRACK, COPE AND BEND
JAMB STUDS (DOUBLE STUDS AT
JAMB FOR PARTITION OPENINGS
GREATER THAN 2'-0" IN WIDTH
RUNNER TRACK
CONTRACTOR'S OPTION: IN LIEU
OF COPED AND BENT RUNNER
TRACK, PROVIDE ANGLE
2x2xSTUD WIDTHx16 GA -
FASTENED TO JAMB STUDS AND
RUNNER TRACK.
FASTENER, TYP
HEAD CONDITION
LEVEL 2
LEVEL 3
2C19
3C17
DESIGN-AIRE ENGINEERING, INC.
www.daengineering.comwww.daengineering.com voice (317) 464-9090
2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - Create Code Compliant Research Laboratory Space in Building 1
657-23-113JB
Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM
08-6231 1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
100% SPRINKLERED
CONSTRUCTION DOCUMENTS
12-22-2023 RD NB
1-AE-101
2C19 - PLANS
TRUE
NORTH
SCALE: 1/2" = 1'-0"1-AE-101
1F 2C19 - RCP
TRUE
NORTH
SCALE: 1/2" = 1'-0"1-AE-101
5F 2C19 - FLOOR PLAN
SHEET NOTES:
GENERAL PLAN NOTES:
FLOOR PLAN LEGEND:
A. REFER TO SHEET 1-AE-101 FOR GENERAL NOTES, PLAN LEGEND,
CEILING LEGEND, AND LIGHT FIXTURE LEGEND, APPLICABLE TO THIS
SHEET'S PLANS.
Equipment Schedule
# Equipment Name Count
Size
CommentsHeight Width Depth
B2.1 1
B3 2 7'-6" 4'-0" 3'-3"
T1 1
T2 1
T3 1
Biology
B2 Tissue Culture Incubator 1
G11 Safety Cabinet 1 5'-5" 3'-0" 1'-10"
Common Both Labs
G1 Nitrogen Gas Tanks 3 3-6" 0'-10" 0'-10"
G2 Nitrogen Gas Tanks 1 3-6" 0'-10" 0'-10"
G8 Tank Rack 2 2'-6" 3'-10" 2'-2" 5
Freezer/Cooler
F1 +4 Refridgerator 2 5'-9" 2'-9" 2'-10" 1
F2 -20 Freezer 2 5'-9" 2'-9" 2'-10" 1
F3 -80 Freezer 1 5'-9" 2'-9" 2'-10" 1
General Equipment
G2 Med Tanks 3 3-6" 0'-10" 0'-10"
G3 LPG Gas Tanks 1 3-6" 0'-10" 0'-10" SEE G10
G4 CO2 Gas Tanks 1 3-6" 0'-10" 0'-10"
G5 Safety Shower & Eye Wash 1 4
G6 Pull-out U. C. Vaccum Pump 2 2'-0" 2'-2 1'-8'
G7 U. C. Glassware Washer 2 2'-11" 2-'0" 2'-0 1/2" 6
G10 Gas Tank Cabinet 2 6'-0" 2'-0" 1-5" 2
CHEMISTRY LAB
COMMENTS
1. WIRELESS TEMP-TRACK INSTALLED BY MEDICAL CENTER FOR
EQUIPMENT TEMP ALARM
2. VENTED LPG TANK CABINET SEE MEP DRAWINGS FOR CONTROLS
3. PROVIDE WALL MOUNTING BRACKETS
4. PROVIDE ALARM WITH HORN & STROBE
5. 2 X 2 RACKS TOTAL (4) TANKS STORAGE
6. PROVIDE TYPE 2 WATER RINSE
GENERAL PARTITION NOTES: PARTITION TAG & LABELING:
PARTITION TYPES
SCALE: 1 1/2" = 1'-0"1-AE-101
DETAIL - TYP PTN OPENING (LESS THAN
4'-0" IN WIDTH)
TRUE
NORTH
NOT TO SCALE
Key Plan 2C19
1'-0"
1' -0
1' -0
2'-0"
UNDER CABINET
TASK LIGHTS
UNDER CABINET
TASK LIGHTS
UNDER CABINET
TASK LIGHTS
SKIM COAT EXTG PLASTER WITH
MODIFIED GWB MUD AT HEAD. (TYP)
SEE THE EXTENT OF THE FIRE PROTECTION SCOPE
ON SHEET 1-FP-101, BUT DIMENSIONALLY LOCATE THE
SPRINKLER HEADS CENTERED IN THE CEILING PAD AS
INDICATED HERE. (TYP)
ACT-1
8'-10" AFF
UNDER CABINET
TASK LIGHTS
PROVIDE METAL SHROUD FROM THE TOP
OF THE HOOD TO THE UNDERSIDE OF THE
CEILING, MATCHING CASEWORK
SEE MECH DWGS FOR THROUGH CEILING
CONNECTIONS FROM HOOD TO
DUCTWORK ABOVE
SEE MECH DWGS FOR
CONNECTIONS
SEE THE EXTENT OF THE FIRE PROTECTION SCOPE ON SHEET
1-FP-101, BUT DIMENSIONALLY LOCATE THE SPRINKLER HEADS
CENTERED IN THE CEILING PAD AS INDICATED HERE. (TYP)
1'-9"
1'-0"
1'-0"
LAB
3C17
1-AE-402 4F
1F
1-AE-402
8D
TISSUE HOOD: N, CO2,
VACUUM, AND LPG
THE LONG SHORT DASHED
LINE DENOTES THE
CASEWORK TOE-KICK &
BASE
COORDINATE THE SIZE OF
AIR VACUUM, AND LPG
CUTOUTS IN COUNTERTOP
SAFETY CABINET
NEW TISSUE
CULTURE
INCUBATOR
1.
EXISTING TISSUE
CULTURE
INCUBATOR
COORDINATE THE SIZE OF AIR,
VACUUM, AND LPG CUTOUTS IN
COLUMN FACE
18''
15''
MOBILE
18''
MOBILE
''x
C L E
R
A D
18''
MOBILE
15''
MOBILE
15''
MOBILE
18''
24''
PULL-OUT U.C.
VACUUM PUMP
-20 FREEZER
+4 REFRIGERATOR
MOBILE CART
TYPE 2 WATER
DISPENSER
GLASSWARE WALL
AND COUNTER
DRYING STATION
U.C DISHWASHER
N TANKS
MED GAS TANK
ALIGN
OVERHEAD
SHELVING
G7
B2
G6
RE: 3D/1-AE-402
FOR TANK RACK
ALIGN
1-AE-4023D
F2
F1
7F
1-AE-402
8D
SIMOPP
6D
TYPE 2 MACHINE
MOUNTED TO WALL
TYPE 2 TANK
MOUNTED TO WALL
B4
DECK MOUNT EYE WASH
COORDINATE THE
NUMBER/SIZE OF PLUMBING
CUTOUTS
G2
G4
G2
G1
CO2 TANKS
SKIM COAT THE EXISTING PLASTER JAMBS AND
HEAD WITH MODIFIED GWB MUD. (TYP)
B2.3 Ab
ALIGN
3'-6" 3'-1"
G3
G10
G8
3C
8B
1-AE-401
B1.2 Ab
B1.2 Ab
B2.1
/8
/6
TYPICAL ALIGN THE
EXPOSED CABINET CHASE
IN-FILL PANEL WITH FACE
OF THE HOOD BASE
P U
M P
C A
B
TYPICAL ALIGN THE
EXPOSED CABINET CHASE
IN-FILL PANEL WITH FACE
OF THE BASE
/2
/2
/4
/8
B3
STORED
U.C.
DIAGONAL HATCHED
AREA DENOTES THE
MEP CHASE BEHIND THE
CASEWORK
/2
" C L E
A R
M
IN
RETAINING CLIP - FASTEN TO
ADJOINING CONSTRUCTION
EDGE MOLDING
MAIN BEAM OR
CROSS-TEE
PERIMETER
HANGER
WIRE
1 MAX
IBC 2015 A/B, CISCA 01
8" MAX
45°
(2) 12 GA
HANGER
WIRES @ OPP
CORNERS TO
STRUCTURE
ACT & GRID
12 GA HANGER WIRE
ELECTRICAL
FIXTURE
MECHANICALLY
FASTEN
TO SUSPENSION
SYSTEM
ELECTRICAL/HVAC
FIXTURE
MECHANICALLY
FASTEN
TO SUSPENSION
SYSTEM
LFB
LATERAL
FORCE BRACE
EC
EXPANSION
CLIP
SJCG CLIP
MAIN GRID RUN
AT LAY-IN FIXTURE
AT RECESSED DOWNLIGHT
UNATTACHED SIDE
U N
A T
T A
C H
E D
S
ID
E
UNATTACHED SIDE
U N
A T
T A
C H
E D
S
ID
E
LEGEND:
CROSS-TEE
MAIN BEAM
SUSPENDED CEILING GENERAL NOTES:
1. HANGER WIRES: 4'-0" O.C. EACH WAY (MAX.);
NOT MORE THAN 6:1 OUT OF PLUMB UNLESS
COUNTER SLOPING WIRES PROVIDED.
2. PERIMETER CLOSURE: EDGE MOLDING, 7/8"
WIDE (MIN.), UNLESS OTHERWISE SPECIFIED.
3. SEISMIC DESIGN CRITERIA: COMPLY WITH
CISCA RECOMMENDATIONS FOR DIRECT-
HUNG ACOUSTICAL TILE AND LAY-IN PANEL
CEILINGS (SEISMIC ZONE 0-1) FOR IBC 2015
SEISMIC DESIGN CATEGORY A AND B.
4. FIXTURES AND SERVICES: REFER TO MEP/FP
DOCUMENTS AND CISCA REQUIREMENTS FOR
SUPPORT OF LIGHT FIXTURES AND OTHER
SERVICES WITHIN THE CEILING.
IBC 2015 A/B, CISCA 01
HANGER WIRE
1-AE-102
1-AE-102
1. LIGHT FIXTURES SHOWN ON ARCHITECTURAL REFLECTED
CEILING PLAN ARE FOR REFERENCE/DESIRED LOCATION
ONLY. SEE ELECTRICAL DRAWINGS FOR MORE INFORMATION
REGARDING FIXTURE TYPES, ELECTRICAL REQUIREMENTS,
ETC.
2. CONTRACTOR SHALL BECOME FAMILIAR WITH THE PROJECT
AND VERIFY ALL CONDITIONS, MATERIALS, AND DIMENSIONS
WHICH WILL AFFECT THE WORK.
3. REVIEW FINAL LOCATIONS OF CEILING AIR DEVICES WITH
ARCHITECT PRIOR TO INSTALLATION.
4. REFER TO SPECIFICATIONS FOR GENERAL CONDITIONS AND
ADDITIONAL INFORMATION.
5. COORDINATE ALL DEVICE LOCATIONS WITH EXISTING
CONDITIONS AND WITH PROJECT DESIGN INTENT - CLARIFY
INTENT WITH THE COR.
6. ALL CEILING HEIGHTS INSTALLED AT THE EXISTING CEILING
HEIGHTS TO MINIMIZE SPRINKLER HEAD CHANGES, U.N.O.
7. PROVIDE LATERAL BRACING FOR SUSPENDED CEILING
SYSTEMS AND ADDITIONAL HANGERS AND SAFETY WIRES FOR
LIGHT FIXTURES, DUCTWORK, SPEAKERS, ETC. SEE TYPICAL
BRACING DETAILS FOR MORE INFORMATION.
8. REFER TO MECHANICAL DRAWINGS FOR SUSPENDED
MECHANICAL DUCTWORK DISTRIBUTION SYSTEM.
9. PROVIDE NON COMBUSTIBLE BLOCKING AND BRACING
REQUIRED FOR FIXTURE INSTALLATION AND ALL ELECTRICAL
COMPONENTS.
10. COORDINATE ANY NEW ROOF PENETRATIONS WITH THE
OWNER.
11. ANY AND ALL CEILING DEVICES SHALL BE PLACES IN CENTER
OF THE CEILING TILE UNO.
12. ALL SUSPENDED CEILING GRIDS TO BE INSTALLED AS
DIMENSIONED ON PLAN UNO.
13. ALL ACT CEILINGS AT EXISTING HEIGHTS AS NOTED ON RCP.
14. PAINT ALL EXPOSED ELEMENTS AND STRUCTURE IN
OCCUPIED SPACES WITHOUT CEILING, INCLUDING STORAGE,
JANITOR CLOSETS, SERVER ROOMS, ETC.
SYMBOL DESCRIPTION
2' x 4' LED LAY-IN FIXTURE ON EMERGENCY POWER
UNDER CABINET SHELVING LED LIGHT FIXTURE
2' x 4' LED LAY-IN FIXTURE
LEVEL 2
LEVEL 3
2C19
3C17
DESIGN-AIRE ENGINEERING, INC.
www.daengineering.comwww.daengineering.com voice (317) 464-9090
2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - Create Code Compliant Research Laboratory Space in Building 1
657-23-113JB
Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM
08-6231 1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
100% SPRINKLERED
CONSTRUCTION DOCUMENTS
12-22-2023 RD NB
1-AE-102
3C17 - PLANS
TRUE
NORTH
SCALE: 1/2" = 1'-0"1-AE-102
1F 3C15-3C21 - RCP
TRUE
NORTH
SCALE: 1/2" = 1'-0"1-AE-102
5F 3C17 - FLOOR PLAN
SHEET NOTES:
A. REFER TO SHEET 1-AE-101 FOR GENERAL NOTES, PLAN LEGEND,
AND
CEILING LEGEND, APPLICABLE TO THIS SHEET'S PLANS
Biology Lab
Equipment Schedule
# Equipment Name Count
Size
CommentsHeight Width Depth
B2.1 1
B3 2 7'-6" 4'-0" 3'-3"
T1 1
T2 1
T3 1
Biology
B2 Tissue Culture Incubator 1
G11 Safety Cabinet 1 5'-5" 3'-0" 1'-10"
Common Both Labs
G1 Nitrogen Gas Tanks 3 3-6" 0'-10" 0'-10"
G2 Nitrogen Gas Tanks 1 3-6" 0'-10" 0'-10"
G8 Tank Rack 2 2'-6" 3'-10" 2'-2" 5
Freezer/Cooler
F1 +4 Refridgerator 2 5'-9" 2'-9" 2'-10" 1
F2 -20 Freezer 2 5'-9" 2'-9" 2'-10" 1
F3 -80 Freezer 1 5'-9" 2'-9" 2'-10" 1
General Equipment
G2 Med Tanks 3 3-6" 0'-10" 0'-10"
G3 LPG Gas Tanks 1 3-6" 0'-10" 0'-10" SEE G10
G4 CO2 Gas Tanks 1 3-6" 0'-10" 0'-10"
G5 Safety Shower & Eye Wash 1 4
G6 Pull-out U. C. Vaccum Pump 2 2'-0" 2'-2 1'-8'
G7 U. C. Glassware Washer 2 2'-11" 2-'0" 2'-0 1/2" 6
G10 Gas Tank Cabinet 2 6'-0" 2'-0" 1-5" 2
COMMENTS
1. WIRELESS TEMP-TRACK INSTALLED BY MEDICAL CENTER FOR
EQUIPMENT TEMP ALARM
2. VENTED LPG TANK CABINET SEE MEP DRAWINGS FOR CONTROLS
3. PROVIDE WALL MOUNTING BRACKETS
4. PROVIDE ALARM WITH HORN AND STROBE
5. 2 X 2 RACKS TOTAL (4) TANKS STORAGE
6. PROVIDE TYPE 2 WATER RINSE
SCALE: 3" = 1'-0"1-AE-102 REF: 7 / 1-AE-102
3 A/B - ISOMETRIC - UNATTACHED SIDE
SCALE: 1" = 1'-0"1-AE-102
5 DETAIL - SEISMIC LIGHT FIXTURE
SCALE: 1/8" = 1'-0"1-AE-102
A/B - PLAN - CEILING SUSPENSION
DIAGRAM AND SEISMIC CRITERIA
GENERAL RCP NOTES:
Legend - LIGHTING FIXTURE
TRUE
NORTH
NOT TO SCALE
Key Plan 3C17
16. PIPE SUPPORTS LYING ON THE ROOF SHALL BE CONSTRUCTED
UTILIZING TREATED WOOD BLOCKS WITH SHEET METAL COVERS
AND LOOSE SHEET METAL STRAPS. BLOCKS SHALL BE
SUPPORTED ON WALK PADS WEIGHT ON BLOCKS SHALL NOT
EXCEED 1.5 POUNDS PER SQUARE INCH. SEE DETAIL 6/A2.16.
17. ALL WOOD TO BE FIRE RETARDANT TREATED IN ACCORDANCE
WITH LOCAL CODES AND ORDINANCES.
1. ANY PENETRATION THRU ROOFING MUST BE PLACED NO LESS
THAN 24" FROM ANY NEW OR EXISTING PENETRATION, MECH.
CURB, WALL OR SIM. ITEM.
2. NO UNPROTECTED PITCH-POCKETS SHALL BE USED. USE
HOODED BOX OR UMBRELLA HOOD DETAIL.
3. WHERE IT IS NECESSARY TO CLUSTER SMALL PIPES (I.E. OR
REFRIGERANT LINES) CONSTRUCT METAL BOX WITH HOOD AND
ELBOW PIPING 6" TO 12" ABOVE THE MEMBRANE ELEVATION IN
ONE OR TWO DIRECTIONS ONLY.
4. ALL PLASTIC PIPES SHALL HAVE A TWO-PART LEAD JACKET OR
AN ALTERNATIVE FLASHING THAT ALLOWS FOR DIMENSIONAL
CHANGE OF THE PIPING. THE LOW PROFILE TYPE FLANGED-
NEOPRENE TYPE FLASHINGS ARE NOT ACCEPTABLE.
5. ALL CURBED HVAC UNITS SHALL HAVE 24-GAUGE GALVANIZED
IRON SHEET METAL COUNTERFLASHINGS OF MINIMUM OF 4"
GIRTH SCREWED TO WOOD BLOCKING AT TOP OF CURB.
6. GAS PIPES AND CONTINUOUS RUNS OF OTHER PIPING SHALL NOT
EXCEED 150 FT. OR HAVE "U" EXPANSION JOINT PROVISIONS. GAS
PIPE REGULATORS AND T'S OR TRAPS SHALL BE SET MINIMUM 1"
ABOVE THE ROOF ELEVATION.
7. ROOFTOP PENETRATIONS AND UNITS SHALL HAVE SHOP
DRAWINGS SUBMITTED FOR APPROVAL.
8. ALL SHEET METAL TO BE INSTALLED IN ACCORDANCE WITH
SMACNA STANDARDS.
9. PROVIDE WALKWAY PROTECTION MATERIAL AS SPECIFIED
AROUND MECH. UNITS, ETC.
10. PROVIDE CONVENIANCE ELECTRICAL OUTLETS AND EQUIPMENT
DISCONNECT AT ROOF TOP UNITS, SEE "E" DRAWINGS.
11. SEE PLUMBING DRAWINGS FOR VENT THRU ROOF (VTR)
LOCATIONS AND INTERIOR ROOF DRAINS W/ PRIMARY AND
SECONDARY (OVERFLOW) LOCATIONS.
12. PROVIDE TAPERED INSUL. CRICKETS (7.53 C) AT ROOF MOUNTED
EQUIPMENT, ROOF PENETRATIONS, & AT AREAS SHOWN ON
PLANS TO PROVIDE POSITIVE DRAINAGE.
13. PROVIDE OSHA COMPLIANT GALV. STEEL SAFETY HOOKS/
ANCHORS ON ROOF. SECURE ANCHORS TO STRUCTURAL STEEL
FRAMING & FLASH PENETRATION WATERTIGHT. SPACE & LOCATE
ANCHORS, SO THAT ANY POINT ON ROOF IS WITHIN 100 FT OF AN
ANCHOR DO NOT PENETRATE FREEZER OR COOLER ROOF.
COORD. LOCATIONS W/ OWNER.
14. PROVIDE A ROOF ACCESS WALKWAY OF 18" x 30" WALKWAY
ACCESS PADS (AN ADDITIONAL LAYER OF ROOF MEMBRANE)
OVER THE BASE LAYER OF ROOF MEMBRANE.
15. WALKWAYS SHALL BE INSTALLED FROM ALL ROOF ACCESS
POINTS, IN A DIRECT ROUTE, TO ALL MECHANICAL EQUIPMENT,
AND AROUND ALL SIDES OF EQUIPMENT THAT REQUIRES
SERVICE.
AREA OF ROOF RELATED WORK.
SEE MEP DRAWINGS FOR LOCATIONS
OF EXACT PENETRATIONS
REFERENCE DETAIL 1B/1-AE-103, TYP (3)
M
A X
M
IN
Equipment Shown Dashed
Vibration Isolating Connection, REF: M- Series Drawings - Set on Neoprene Pad, Set Bolt in Mastic
Premanufactured Galvanized Steel Equipment Support - Continuous.
Roof Deck, REF:
S-Series Drawings
Rigid Insulation
Roof membrane
Continuous Welded 1-1/2"
MIN
Scheduled Roof Membrane Flashing in Full Mastic
Sheet Metal Flashing
PTWD Blocking - Configure to Obtain Proper Equipment Height & Maintain Level
DESIGN-AIRE ENGINEERING, INC.
www.daengineering.comwww.daengineering.com voice (317) 464-9090
2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - Create Code Compliant Research Laboratory Space in Building 1
657-23-113JB
Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM
08-6231 1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
100% SPRINKLERED
CONSTRUCTION DOCUMENTS
12-22-2023 RD NB
1-AE-103
ROOF PLAN
KEYED NOTES:
ROOF ASSEMBLIES /
SHEET NOTES:
GENERAL ROOF NOTES:
ROOF TYPE 'A'
MATCH EXISTING
COLD ADHESIVE STYRENE-BUTADIENE-STYRENE
MODIFIED BITUMINOUS MEMBRANE ROOFING
TRUE
NORTH
SCALE: 1/16" = 1'-0"1-AE-103
4F Roof Plan - Documentation
SCALE: 1 1/2" = 1'-0"1-AE-103
1B Typical Equipment Support at Roof
ROOM NAME
F
B
C
R
W A
L
LS
CONFERENCE ROOM
VCT-1/CT-2
RB-1
N: P-X/P-X E: P-X/P-X S: P-X/P-X W: P-X/P-X1, 2
ACT1
ROOM NUMBER
FLOOR FINISH
WALL BASE
CEILING FINISH
ROOM FINISH REMARKS
WALL FINISHES
(N = NORTH, E = EAST, S = SOUTH, W = WEST)
1. NEW FINISHES OVER EXISTING PARTITIONS; ALL EXISTING
PARTITIONS TO BE FILLED LEVEL AND SMOOTH ACCEPTABLE
FOR THE MANUFACTURER OF THE NEW SCHEDULED FINISH.
2. ALL EXISTING CONCRETE SLABS ARE TO BE SANDED OR
GROUND SMOOTH REMOVING DEFORMITIES AS REQUIRED IN
PREPARATION OF NEW SCHEDULED FLOOR FINISHES.
3. PATCH ALL WALLS TO REMAIN AS REQUIRED WHERE EXISTING
DEVICES HAVE BEEN REMOVED. GYPSUM BOARD WALL ARE TO
BE PATCHED WITH STUDS, BOARD AND FINISH MATERIALS AS
REQUIRED.
4. NO "BLACK" ADHESIVES WILL BE ALLOWED FOR FLOORING
MATERIALS.
5. DUE TO VCT TILE FLOORS EASILY SHOWING DEVIATIONS, SUB-
CONTRACTOR TO INSPECT SUBSTRATE CONDITIONS AND
IDENTIFY ANY NEEDED CORRECTIONS PRIOR TO INSTALLATION
OF ANY NEW MATERIALS TO ENSURE FLOOR IS SMOOTH AND
LEVEL.
6. LOCATE CONTROL JOINTS IN PORCELAIN OR CERAMIC TILE AS
REQUIRED BY MANUFACTURER.
7. PROVIDE REDUCER OR TRANSITION STRIPS AT FLOORING
MATERIALS OF DIFFERENT THICKNESSES.
8. FLOAT ALL FLOORS AS NECESSARY EACH SIDE OF DIFFERING
FLOOR MATERIALS AND/ OR DIFFERENT THICKNESSES TO
PROVIDE A SMOOTH UNDETECTABLE TRANSITION AND ALIGNING
TOP SURFACES OF EACH DIFFERING MATERIAL. INSTALL
EDGING OR TRANSITION STRIPS PER DOCUMENTS.
9. PROVIDE WOOD BLOCKING OR STEEL FRAMING, PLATES,
STRAPS, ETC.. IN GYPSUM BOARD PARTITIONS FOR SUPPORT OF
ALL WALL MOUNTED DEVICES AND EQUIPMENT INCLUDING BUT
NOT LIMITED TO WALL CABINETS, MARKER AND TACKBOARDS,
HANDRAILS, WOOD TRIM, SHELVING, TOILET ACCESSORIES,
MECHANICAL/ ELECTRICAL/ PLUMBING & FIRE PROTECTION
EQUIPMENT AND DEVICES AS WELL AS OWNER FURNISHED
ITEMS.
10. PAINT ALL EXPOSED GYP.BD. INCLUDING CEILINGS AND
SOFFITS - SEE RCP SHEETS FOR ADDITIONAL INFORMATION.
11. PAINT ALL NEW AND EXISTING HOLLOW METAL DOORS AND
FRAMES TRIM TO MATCH EXISTING.
12. ALL HARDWOOD DOORS SHALL RECEIVE FINISH BY MFGR. PRIOR
TO DELIVERY TO SITE UNLESS NOTED OTHERWISE.
13. ALL GYP.BD. TO BE PATCHED, TAPED, MUDDED, SAND, & PAINT
TO 4" ABOVE CEILING UNLESS NOTED OTHERWISE.
14. SEE RCP, FINISH PLANS, & MATERIAL LEGEND FOR CEILING
FINISHES.
F
B
C
R
W A
L
LS
LAB
EPY-1
2C19
EPY-1
N: PT-1
E: PT-1
S: PT-1
W: PT-11,2
ACT-1
SS-1 CORNER
GUARD FROM TOP
OF BASE TO 60" AFF
STAINLESS STEEL
CORNER GUARD
BELOW COUNTERTOP
LINE OF COUNTERTOP
LINE OF COVE BASE
SS-1 CORNER
GUARD FROM TOP
OF BASE TO 60" AFF
F
B
C
R
W A
L
LS
LAB
EPY-1
3C17
EPY-1
N: PT-1
E: PT-1
S: PT-1
W: PT-11,2
ACT-1
1.
ACT-1 Acoustical Ceiling Tile
Armstrong Calla Health Zone - AirAssure Square Lay-In Smooth Texture 24x48 15/16" Clean Room Grid System
Code Item Manufacturer Description Remarks
MATERIAL SCHEDULE
PT-1 Paint Benjamin Moore Product: OC - 17 Color: White Dove Finish: Walls - Scrub-able Eggshell Door Frames - Scrub-able Semi-Gloss
All Walls and Door Frames
EPY-1 Epoxy Resin Desco Rime Flooring and Integral Cove Base 4" High
PT-2 Paint Benjamin Moore Product: OC - 152 Color: Super White Finish: Ceilings - Scrub-able Eggshell Flat
GWB Ceilings
S-1 Solid Surface FunderMax Color: Light Pastel Grey #0074 Thru-Core-Color
LEVEL 2
LEVEL 3
2C19
3C17
General Notes - Door & Frame:
A. ALL NEW DOORS ARE TO MATCH EXISTING
AB ACOUSTICAL BAFFLE
AC ACOUSTICAL CEILING TILE
AP ACOUSTICAL PANEL
BL BLINDS
BR BRICK
C CARPET
CN CONCRETE
DP DRAPERY
EF EPOXY FLOOR
F FABRIC
FRP FIBERGLASS REINFORCED
PANEL
FWP FABRIC WRAPPED PANEL /
STRETCHED FABRIC WALL
SYSTEM
GF GLASS FILM
GL GLASS
GP
GT GROUT
MB MARKER BOARD
MTL METAL
KEYED NOTES:
ROOM FINISH TAG LEGEND:
MATERIAL ABBREVIATIONS
PC PRIVACY CURTAIN
PL PLASTIC LAMINATE
PT PAINT
PV PAVER
RB BASE (RESILIENT, RUBBER,
ETC.)
RF RESILIENT FLOORING
RS ROLLER SHADES
SM SOLID SURFACE MATERIAL
/ QUARTZ
SS STAINLESS STEEL
ST STONE
SVT SHEET VINYL TILE
T TILE
TB TACK BOARD
TR TREAD
UP UPHOLSTERY
WC WALLCOVERING
WD WOOD
WF WOOD FLOOR
WP WALL PROTECTION
SCALE: 1/2" = 1'-0"1-AE-104
1F 2C19 - FINISH PLAN
SCALE: 1/2" = 1'-0"1-AE-104
5F 3C17 - FINISH PLAN
DESIGN-AIRE ENGINEERING, INC.
www.daengineering.comwww.daengineering.com voice (317) 464-9090
2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - Create Code Compliant Research Laboratory Space in Building 1
657-23-113JB
Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM
08-6231 1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
100% SPRINKLERED
CONSTRUCTION DOCUMENTS
12-22-2023 Checker NB
1-AE-104
FINISH PLANS
GENERAL FINISH NOTES:
TRUE
NORTH
NOT TO SCALE
Key Plan
DOOR/OPENING SCHEDULE
NO. ROOM NAME
DOOR LEAF / OPENING FRAME HDW
GROUP
FIRE
RATING COMMENTSTYPE WIDTH HEIGHT THICK MATL FINISH TYPE MATL FINISH
2C19 LAB 3' - 6" 7' - 0" 1 3/4" 3/4 HR
3C17 LAB 3' - 6" 7' - 0" 1 3/4" 3/4 HR
Sherwin-Williams SW7008 Alabaster, 255-C2
High Reflective White, 256-C1 SW7757Sherwin-Williams
Fine Fissured 24 x 48 x 3/4"
01-18-2024 RD NB
B102 36"
B201 24"
MOBILE
CART
G2 G2
G8
1'-6" 2'-6" 2'-6"
8B
1-AE-401
T3
T2
G10
4D
1-AE-501
OPEN
UNDER COUNTER TASK LIGHTS
POWER, COMMUNICATIONS,
AND GAS DISTRIBUTION THRU
CASEWORK MANUF. COLUMN
B201 24"
B253M 15"
B201M 24"
6F
1-AE-501
SAFETY SHOWER
WITH EYE WASH
UNDER COUNTER
TASK LIGHTS
FILLER PANEL 2'-6" 1'-0" 1'-0" 1'-3" 1'-3" 2'-0"
SAFETY CABINET
67"H x 43"W x 18"D
B102 30"
B201 24"
FILLER PANEL
B451 33"
W102 30"
W301 15"
T1
G5
G11
6D
1-AE-501
4D
1-AE-501
UNDER COUNTER
TASK LIGHTS
FILLER PANEL 3'-0" 3'-0" 3'-0" 1'-3" 4'-0"
B253M B201M 24"
W102 36"
W102 36"
W102 36"
W101 15"
B102V 30"
B231 48"
6F
1-AE-501
B102 36"
COVE BASE; REF: 1-AE-104
5/8" GWB
2 1/2" MTL STUDS @ 16" O.C.
SOLID SURFACE SILL TO
MATCH COUNTER TOP
NEW GLAZING IN EXISTING
ALUMINUM FRAME; SEE 6B 1-AE-401
FINISH FLOORING;
REF: 1-AE-104
CAVITY INSULATION
CONTINUOUS SEALANT
EXISTING STRUCTURE TO REMAIN
6B
1-AE-401
OPP
DESIGN-AIRE ENGINEERING, INC.
www.daengineering.comwww.daengineering.com voice (317) 464-9090
2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - Create Code Compliant Research Laboratory Space in Building 1
657-23-113JB
Saint Louis VA Health Care System 1 Jefferson Barracks Saint Louis, MO 63125 o n e e ig h th in c h o n e fo o t
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM
08-6231 1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
100% SPRINKLERED
CONSTRUCTION DOCUMENTS
12-22-2023 RD NB
1-AE-401
2C19 - INTERIOR ELEVATIONS
SCALE: 1/2" = 1'-0"1-AE-401 REF: 5F / 1-AE-101
2F 2C19 - NORTH ELEVATION
SCALE: 1/2" = 1'-0"1-AE-401 REF: 5F / 1-AE-101
4D 2C19 - ISLAND ELEVATION
SCALE: 1/2" = 1'-0"1-AE-401 REF: 5F / 1-AE-101
7F 2C19 - EAST ELEVATION
SCALE: 1/2" = 1'-0"1-AE-401 REF: 5F / 1-AE-101
7D 2C19-WEST ELEVATION
SCALE: 1/2" = 1'-0"1-AE-401 REF: 5F / 1-AE-101
2D 2C19 - ISLAND ELEVATION - SIDE
SCALE: 1 1/2" = 1'-0"1-AE-401 REF: 5F / 1-AE-101
8B TYPICAL SECTION AT WINDOW SILL
B253M 15"
SLOPE METAL TOP PER SPEC METAL SHROUD TOP PER SPEC FROM
TOP OF HOOD TO UNDERSIDE OF
CEILING
SLOPE METAL TOP PER SPEC
TYPICAL ABOVE ALL CABINETS ABOVE
THE COUNTERTOP
T400 70"
SLOPE METAL TOP PER SPEC
TYPICAL ABOVE ALL CABINETS ABOVE
THE COUNTERTOP
4" 6" 1-
1/ 4"
2' -1
1- 3/
4"
T4
1- 1/
4"
2' -1
1- 3/
4"
2' -1
1- 3/
4"
2' -1
1- 3/
4"
1- 1/
4" 4"
2' -1
1- 3/
4"
PROVIDE ALUMINUM TRIM
SLOPE METAL TOP PER SPEC
TYPICAL ABOVE ALL CABINETS ABOVE
THE COUNTERTOP
TYPICAL SEE SHEET 1-AE-501
FOR MORE INFORMATION
TYPICAL SEE SHEET 1-AE-501
FOR MORE INFORMATION
B253 15"
B212 36"
B253 15"
4" BACK SPLASH
+4 REFRIGERATOR
SAFETY CABINET
-20 FREEZER
B201
6D
1-AE-501
OPEN
UNDER COUNTER TASK LIGHTS
B201
B253M
6F
1-AE-501
W102 36"
B201 B201
W102 36"
2'-0"
4D
1-AE-501
W10…