657-23-113JB - Construction Drawings - 8 of 14 - FP.pdf

PDF 562 KB Posted

Attached to
Z1DA--Create Code Compliant Research Laboratory Space in Building 1, 657-23-113JB Federal contract opportunity
Solicitation number
36C25524R0053
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15

About this file

This document is a set of construction drawings for the renovation of a research laboratory space in Building 1 at the Saint Louis VA Health Care System, as part of federal contract opportunity 36C25524R0053.

The drawings provide details on the fire protection system modifications required, including removing and relocating sprinkler heads, raising existing piping sections, and adding new branch lines and heads to provide adequate coverage for the laboratory space. The work must comply with NFPA-13 requirements for an Ordinary Hazard (Group 2) occupancy. The fire protection contractor is responsible for obtaining flow test data, preparing hydraulic calculations, and coordinating any system shutdowns with the VA. The drawings also include notes on seismic bracing requirements for the sprinkler piping.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--Create Code Compliant Research Laboratory Space in Building 1, 657-23-113JB, newest first.
File Type Posted
S02-657-23-113JB - Create Code Compliant Research Laboratory Space Prebid Questions 20240422.pdf PDF
Pre-Bid Conference Sign-in Sheet 657-23-113 --- Scan04-09-2024-102719.pdf PDF
S02-3- As Built from-657-10-104JB_1C-A1.pdf PDF
36C25524R0053 0001.docx DOCX document
657-23-113JB - Construction Drawings - 14 of 14 - TT.pdf PDF
657-23-113JB - Construction Drawings - 12 of 14 - EP.pdf PDF
657-23-113JB - Construction Drawings - 9 of 14 - MG.pdf PDF
657-23-113JB - Construction Drawings - 1 of 14 - GI.pdf PDF
657-23-113JB - Construction Drawings - 11 of 14 - EG.pdf PDF
657-23-113JB - Construction Drawings - 2 of 14 - GJ.pdf PDF
657-23-113JB Specifications - Reduced File Size.pdf PDF
657-23-113JB - Construction Drawings - 13 of 14 - TG.pdf PDF
657-23-113JB - Construction Drawings - 7 of 14 - PM.pdf PDF
657-23-113JB - Construction Drawings - 6 of 14 - PL.pdf PDF
657-23-113JB - Construction Drawings - 5 of 14 - PG.pdf PDF
657-23-113JB - Construction Drawings - 4 of 14 - AE.pdf PDF
657-23-113JB - Construction Drawings - 3 of 14 - HA.pdf PDF
36C25524R0053_1.docx DOCX document
657-23-113JB - Construction Drawings - 10 of 14 - MH.pdf PDF
Show all 19

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LAB

3C17OFFICE

3C18

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

01-18-2024

CONSTRUCTION DOCUMENTS

FCA - Create Code Compliant Research Laboratory Space in Building 1

657-23-113JB

Saint Louis VA Health Care System 1 Jefferson Barracks

Saint Louis, MO 63125

DEH DAE 44

100% SPRINKLERED

LAB 2C19 AND LAB 3C17 FIRE

PROTECTION PLANS

DEMOLITION NOTES#

KEYED NOTES#

GENERAL NOTES

1. REMOVE SECTION OF 1" SPRINKLER PIPE AND TWO EXISTING HEADS.

SECTION TO BE RAISED APPROXIMATELY 8".

2. REMOVE SECTION OF 1" SPRINKLER PIPE AND ONE EXISTING HEAD.

SECTION TO BE RAISED APPROXIMATELY 12".

3. REMOVE EXISTING HEAD BRANCH AND HEAD AND EXTEND 1" PIPE

TO NEW HEAD LOCATION.

4. EXISTING DRAIN VALVE.

1. EVERYTHING IS EXISTING TO REMAIN UNLESS OTHERWISE NOTED.

1. NEW 1" BRANCH AND NEW HEAD.

2. NEW RAISED SECTION OF EXISTING PIPING.

3. CONNECT NEW 3/4" FP PIPE TO GAS CABINET HOOD, ITEM #G10.

EXIST. 1" FP

EXIST. 1" FP

EXIST. 1" FP

EXIST. 1" FP

EXIST. 1" FP

EXIST. 1" FP

EXIST. 2" FP

SPRINKLER HEAD LEGEND

SEMI-RECESSED HEAD, CHROME WITH ESCUTCHEON. CENTER HEAD IN TILE.

EXIST. 1" FP

EXIST. 2" FP

SPRINKLER HEAD LOCATION DETAIL F

SP0

A. ALL PIPING 2-1/2 IN. NOMINAL DIAMETER AND LARGER MUST BE BRACED.

B. TRANSVERSE AND VERTICAL BRACING SHALL OCCUR AT 40 FT.

INTERVALS (MAX) AND LONGITUDINAL BRACING AT 80 FT. INTERVALS

(MAX).

C. BRACING IS NOT REQUIRED FOR PIPING SUSPENDED BY HANGERS 12 IN.

OR LESS IN LENGTH AS MEASURED FROM THE TOP OF THE PIPE TO THE

BOTTOM OF THE SUPPORT WHERE THE HANGER IS ATTACHED.

1. FIRE PROTECTION CONTRACTOR SHALL DESIGN AND INSTALL THE REQUIRED NEW

SYSTEM OR MODIFICATIONS TO THE EXISTING HYDRAULICALLY CALCULATED WET

PIPE SPRINKLER SYSTEM FOR THE LABORATORY SPACE INDICATED HEREIN THESE

DOCUMENTS. THE SYSTEM SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE

WITH THE REQUIREMENTS OF NFPA-13 FOR ORDINARY HAZARD (GROUP 2)

OCCUPANCY, PROVIDING A SPRINKLER DENSITY OF .20 GPM SQFT OVER THE MOST

REMOTE 1500 SQ.FT. SPRINKLER HEAD SPACING SHALL NOT EXCEED 130 SQ.FT. PER

HEAD.

2. FIRE PROTECTION CONTRACTOR SHALL PREPARE AND SUBMIT SPRINKLER SHOP

DRAWINGS AND HYDRAULIC CALCULATIONS TO THE A/E AND VA COR.

3. FIRE PROTECTION SYSTEMS ARE TO BE MAINTAINED IN ACCORDANCE WITH

ORIGINAL INSTALLATION STANDARDS. REQUIRED FIRE PROTECTION SYSTEM SHALL

BE MODIFIED AS NECESSARY TO MAINTAIN PROTECTION WHENEVER BUILDING IS

ALTERED.

4. FOR EXISTING SYSTEM REMOVE OR RELOCATE EXISTING SPRINKLER HEADS AND

FURNISH AND INSTALL NEW AS PER NFPA-13 RECOMMENDATIONS, TO PROVIDE

ADEQUATE COVERAGE OF THE ENTIRE SPACE.

3. THE FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING FLOW

TEST DATA AND PREPARING HYDRAULIC CALCULATIONS.

4. NEW SPRINKLER HEADS SHALL BE APPROVED STANDARD TYPES, PENDENT AND

UPRIGHT, AND DESIGNED FOR ORDINARY HAZARD COVERAGE. CHROME PLATED

"TYCO", "GRINNELL", "VIKING", "STAR" OR EQUAL. SEE PLANS FOR SPRINKLER HEAD

TYPES.

5. ALL SPRINKLER WORK SHALL COMPLY WITH ALL NFPA-13 RECOMMENDATIONS, AND

SHALL BE PERFORMED IN ACCORDANCE WITH THE RULES AND REGULATIONS OF

THE VA, LOCAL FIRE RATING ORGANIZATION, FIRE AND/OR BUILDING

DEPARTMENTS AND ALL AUTHORITIES IN JURISDICTION.

6. FIRE PROTECTION CONTRACTOR SHALL ARRANGE FOR ANY SHUTDOWNS OF THE

EXISITING SYSTEM WITH THE VA COR AND VA SHOPS, AND SHALL SECURE IN

WRITING PRIOR TO SHUTDOWN, APPROVALS FROM SAME. ADDITIONALLY, THE FIRE

PROTECTION CONTRACTOR SHALL PAY FOR ANY LABOR, MATERIALS, AND FEES

NECESSARY FOR SHUTDOWN.

7. IN THE EVENT OF THE FIRE PROTECTION SYSTEM BEING "OUT OF SERVICE", THE FIRE

DEPARTMENT & LOCAL CODE OFFICIALS SHALL BE NOTIFIED IMMEDIATELY, AND IF

REQUIRED BY THE VA AND/OR CODE OFFICIAL, SAID BUILDING TO BE EVACUATED

OR PROVIDED WITH AN APPROVED FIRE WATCH SYSTEM WILL BE PROVIDED FOR

ALL UNPROTECTED OCCUPANTS UNTIL SYSTEM IS RETURNED TO SERVICE.

8. WHEN UTILIZED, FIRE WATCHES SHALL BE PROVIDED W/ MIN. OF ONE APPROVED

MEANS OF NOTIFICATION OF THE FIRE DEPT. THE ONLY DUTY OF THE FIRE WATCH IS

TO PERFORM CONSTANT PATROLS OF THE PREMISES AND KEEP WATCH FOR FIRES.

9. FIRE PROTECTION CONTRACTOR SHALL CAREFULLY EXAMINE ALL EXISTING

SPRINKLER SYSTEM PIPING AND COMPONENTS, AND SHALL REPAIR OR REPLACE ANY

LEAKING OF DEFECTIVE PIPING OR COMPONENTS, FOR SPACE BEING PROTECTED.

10. SPRINKLER PIPE MATERIAL AND INSTALLATION SHALL MATCH EXISTING. FIRE

PROTECTION CONTRACTOR SHALL PROVIDE ALL REQUIRED TEST AND DRAIN

CONNECTIONS, WHETHER OR NOT THEY ARE INDICATED HEREON THESE PLANS.

FIRE PROTECTION CONTRACTOR SHALL PROVIDE AND INSTALL ALL NECESSARY

ALARM INITIATING DEVICES AND SUPERVISORY DEVICES, AND SHALL COORDINATE

THE ELECTRICAL REQUIREMENTS FOR THEM WITH THE E.C. AND/OR FIRE ALARM

CONTRACTOR FOR THEIR CONNECTION TO THE FIRE ALARM SYSTEM.

11. FIRE PROTECTION CONTRACTOR IS RESPONSIBLE FOR ALL DAMAGES TO ANY

PORTION OF THE EXISTING SPRINKLER SYSTEM ON ANY PORTION OF THE BUILDING

INCURRED BY HIM DURING CONSTRUCTION.

SPRINKLER SYSTEM NOTES

1-FP-101

G10

NEW 3/4" FP

EXIST. FP MAIN

NEW 1" FP

NEW 3/4" FP

EXIST. 1" FP

EXIST. 2" FP

SEISMIC BRACING NOTES

AutoCAD SHX Text %%ULab 2C19 Fire Protection - Demolition

AutoCAD SHX Text

SCALE: 1/4" = 1'-0"

AutoCAD SHX Text N

AutoCAD SHX Text %%ULab 3C17 Fire Protection - Demolition

AutoCAD SHX Text

SCALE: 1/4" = 1'-0"

AutoCAD SHX Text N

AutoCAD SHX Text %%ULab 3C17 Fire Protection Plan

AutoCAD SHX Text

SCALE: 1/4" = 1'-0"

AutoCAD SHX Text N

AutoCAD SHX Text %%ULab 2C19 Fire Protection Plan

AutoCAD SHX Text

SCALE: 1/4" = 1'-0"

AutoCAD SHX Text N

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ENGINEER

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text I

AutoCAD SHX Text L

AutoCAD SHX Text L

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text 062-073724

AutoCAD SHX Text

REGISTERED

AutoCAD SHX Text

PROFESSIONAL

AutoCAD SHX Text R

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text

PENDENT TYPE SPK. HD. LOCATION

AutoCAD SHX Text

2' X 4' ACOUSTIC CEILING TILE

AutoCAD SHX Text

PENDENT TYPE SPK. HD. LOCATION

AutoCAD SHX Text

2' X 4' ACOUSTIC CEILING TILE

AutoCAD SHX Text

PENDENT TYPE SPK. HD. LOCATION

AutoCAD SHX Text

2' X 2' ACOUSTIC CEILING TILE

AutoCAD SHX Text

PENDENT TYPE SPK. HD. LOCATION

AutoCAD SHX Text

PARTIAL ACOUSTIC CEILING TILE

AutoCAD SHX Text 1'-0"

AutoCAD SHX Text 1'-0"

AutoCAD SHX Text 2'-0"

AutoCAD SHX Text 1'-0"

AutoCAD SHX Text 1'-0"

AutoCAD SHX Text 1'-0"

AutoCAD SHX Text 1'-0"

AutoCAD SHX Text C

AutoCAD SHX Text L

File details come from the government source that posted it. Updated .