RevisedResponsesAdditional Questions Clev-Rud FA Project-DB Solicitation10.21.2020.docx

DOCX document 25 KB Posted

Attached to
REQUEST FOR PROPOSAL NO 47PB0020R0027 DESIGN BUILD FOR REPLACMENT OF FIRE ALARM SYSTEM AT JAMES C. CLEVELAND FEDERAL BUILDING & WAREN B. RUDMAN FEDERAL COURTHOUSE, CONCORD, NH
Solicitation number
47PB0020R0027
Issued by

About this file

This document contains questions and responses related to a solicitation for design-build replacement of the fire alarm system at two federal buildings in Concord, New Hampshire. Key details include specifications for replacing the existing Simplex fire alarm system, which has undergone numerous modifications and lacks some functions required by standards; installation of a new voice evacuation system; coordination required with the U.S. Marshals Service on locations of operations centers and design standards; and clarification provided on sprinkler system components, elevator controls, and other existing building elements and systems. Floor plans and other attachments provide additional information on the existing conditions to support bidding on the project.

View the file

Other files

File Type Posted
28 31 01 Voice Evac Fire Alarm Systems October 2018 due to bidder questions 10.21.2020.docx DOCX document
Final DB Fire Alarm SOW_with amendment changes due to bidder questions 10.21.2020.docx DOCX document
ATTACHMENT L PHOTOS OF INSIDE OF ELEVATOR BUTTONS.docx DOCX document
ATTACHMENT J RUDMAN FLOOR PLANS.pdf PDF
Solicitation Amendment 47PB0020R0027_0007.pdf PDF
ATTACHMENT K CLEVELAND FLOOR PLANS.pdf PDF
ATTACHMENT M - MAR - 2020.docx DOCX document
SF1442v.pdf PDF
Amendment 47PB0020R0027_0006 (1).pdf PDF
Solicitation Amendment 47PB0020R0027_0005.pdf PDF
revised due date SF1442 47PB0020R0027 Form.pdf PDF
SBU Document Security Request for Construction Documents FORM B1.pdf PDF
Solicitation Amendment 47PB0020R0027_0005.pdf PDF
Solicitation Amendment 47PB0020R0027_0004.pdf PDF
Additional Questions Cleveland-Rudman FA Project - DB Solicitation QA 10.07.2020.docx DOCX document
Final DB Fire Alarm SOW_Amendment 2 changes due to bidder questions 10.07.2020.docx DOCX document
Solicitation Amendment 47PB0020R0027_0003 (2).pdf PDF
2020-08-26 SMPLEX.pdf PDF
SF 30 Amendment 0002.pdf PDF
2020-02-26 SIMPLEX.pdf PDF
2019-11-27 SIMPLEX.pdf PDF
28 31 01 Voice Evac Fire Alarm Systems October 2018 due to bidder questions 09.25.2020.docx DOCX document
Final DB Fire Alarm SOW_with amendment changes due to bidder questions 09.25.2020.docx DOCX document
REVISED SF1442.pdf PDF
2020-05-27 SIMPLEX.pdf PDF
Cleveland-Rudman FA Project - DB Solicitation Questions and Answers 09.25.2020.pdf PDF
Pre-Proposal Conference On Site Visit. 9-16-2020.pdf PDF
Pre Proposal Conference -Attendance Sheet .pdf PDF
47B0020R0027 TAB 9 Cleveland Rudman Fire Alarm Replacement Conference.pdf PDF
Amendment 47PB0020R0027_0001.pdf PDF
SF1442.pdf PDF
Appendix C and D - Attachments A-H Documents.pdf PDF
DB final 1 Phase Solicitation 2020 09 02.docx DOCX document
Final DB 1 Phase Agreement 2020 09 02. .docx DOCX document
Wage Determination dated 8-14-2020.pdf PDF
GC Reps andCerts 2020 09 02..docx DOCX document
Bid Bond SF24.pdf PDF
Appendix B Specificatons.pdf PDF
Design Build Statement of Work 2020 03 05.pdf PDF
PBS_Past_Performance_Form 2020 09 02..pdf PDF
Pre Proposal Conference -Site Visit information 2020 09 02.docx DOCX document
Show all 41

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Design Build Replacement of the fire alarm system at the James C. Cleveland Federal Building and the Warren B Rudman Federal Courthouse:

Questions and Answers

Section Design build statement of work

38. Page 16 item G indicates sprinkler system devices connected to the fire alarm system shall be replaced and additional devices shall be provided where required, i.e.: water flow switches tamper switches etc. The documents call for the existing system to remain in service completely until the new system is installed tested and accepted by the government. How do we connect flow switches and tamper switches to the existing sprinkler system without removing the existing units? This will require some portions of the existing fire alarm system to be removed and deactivated prior to the new system being fully accepted Response: Please refer to Fire Alarm Impairment Sections Appendix D- Guidelines for Fire Watches During Sprinkler or Fire Alarm Impairment in Federal Buildings.

39. Page 16 item H calls for relays and monitor modules be installed associated with the existing elevators to affect the necessary control. Are the existing elevators capable of accepting the external control and connections as called for or will modifications to the existing elevators controllers be required? If modifications are required can you tell us who presently maintains the elevator systems, and can you provide drawings for the elevator controllers?

Response: BID the documents as specified.

40. Page 16 item J Can you tell us where the US marshals office is located in the building?

Response: Reference Attachment J: Rudman floor Plans

41. Page 16 item K Can you tell us where the USMS command and Control Center is within the building?

Response: Reference Attachment J: Rudman floor Plans

42. page 16 item L Can you provide drawings relative to the sprinkler system portion that is to be removed under this item? Can you also provide any details regarding the existing structure of the wall around the elevator machine room?

Response: Please see Attachments A through E for available information on the existing building layout, fire alarm system and components.

Reference page 15 paragraph in the revised SOW.

43. Page 16 item M Can you provide any information regarding the presence of asbestos in the building and where we may encounter it or can this item be carved out of the project as an allowance to address for any hazardous materials found?

Response: Refer to Solicitation. Available Hazmat information has been provided in Attachment G.

44. Page 17 item 4 Can you tell us where the fire command room is?

Response: Reference Attachment J: Rudman floor Plans

45. Page 17 item 5 Can you provide some additional guidance regarding the extent to which fire watch is anticipated to be needed on this project?

Response: Please see Attachment D to the Scope of Work.

46. Page 18 item 7 At one location in the documents the requirement for smoke detectors seems to indicate that all the existing smoke detectors are to be replaced in kind with new smoke detectors. This note indicates smoke detectors should only be provided in accordance with NF PA 72 and PBS P-100. Is it a correct understanding that smoke detectors are only required where NFPA 72 and PBS P-100 require them not at every location presently existing on the drawings?

Response: Smoke detectors shall be provided per the guidance of GSA P-100, NFPA-90A and NFPA-72.

47. Page 18 item 13 Can flexible cabling be utilized on individual floors in lieu of conduit?

Response: Installation shall comply with PBS P-100.

48. Page 18 item 15 This item seems to indicate that a separate speaker /strobe unit will be required in every room. Is this the intent of the RFP?

Response: Location, quantities, and coverage of notification devices shall comply with GSA P-100 and NFPA-72.

49. Page 19 item 19 Can you identify in the drawings where each of the judge’s private restrooms are located? Can you provide information regarding the US courts design guide listed in this item? Where can this document be obtained?

Response: Judge’s private restrooms are located in 4th floor of the Rudman Courthouses in the hatched areas. Please see Attachments A through E for available information on the existing building layout, fire alarm system and components.

50. page 19 item 21 We did not observe any existing firefighter phones in the building during the walkthrough. Can you provide on the drawings locations where these devices exist?

Response: Please see Attachments A through E for available information on the existing building layout, fire alarm system and components.

Reference page 19, item 21 in the revised SOW.

51. Page 19 item 26 Can you identify the location of the USMS operation and Control Center? This item indicates we are to coordinate the installation of the remote annunciators with the USMS. Are there any special requirements we should be aware of when establishing the remote annunciated location?

Response: Reference Attachment J: Rudman floor Plans.

Please see Attachments A through E for available information on the existing building layout, fire alarm system and components. The remote annunciator shall follow PBS P-100 requirements. The egress shall follow PBS P-100 and NFPA 72 Chapter 7. All incidental work to the Fire Alarm System in the area shall follow USMS Pub 64 requirements.

52. Page 19 item 27 Indicates we are to interface with the smoke evacuation control panel. Can you define what interface means? Can you tell us how many smoke evacuation zones exist? Can you tell us how these existing smoke evacuation zones are controlled? Can you tell us where the existing smoke evacuation control panel is located? Is this control manual or automatic from the fire alarm control panel?

Response: Reference page 19, item 27 in the revised SOW.

The new smoke evacuation control panel shall comply with the UL listing requirements in compliance with the IBC as referenced in PBS P-100. Please see Attachments A through E for available information on the existing building layout, fire alarm system and components.

53. Page 20 item 37 Can you tell us who presently handles the sprinkler system maintenance for the building?

Response: BID the documents as specified.

54. Page 20 item 38 This item seems to indicate we are replacing the switches on the existing valves and tampers and not replacing those devices. Is it the intent of this project to replace the flow and tamper switches or two replace the fire alarm devices that monitor these items?

also, we need clarification relative to keeping the existing system in place while the new system is installed and accepted by the owner prior to demolishing the existing fire alarm system Response: Please refer to Fire Alarm Impairment Sections Appendix D – Guidelines for Fire Watches During Sprinkler or Fire Alarm Impairment in Federal Buildings

Appendix B specification - Section 28 31 01

55. In this section 1.4 Paragraph a 2, 3, 4 and within the design build statement of work the government mentions Class A wiring and class X wiring. Within this specification section the government indicates individual floors may be wired Class B. These two systems are mutually exclusive what is the intent of the RFP?

Response: Please refer to NFPA 72 and PBS P-100. Please see Attachments A through E for available information on the existing building layout, fire alarm system and components.

56. Within section 1.4 subparagraph A the RFP speaks of level 2 and Level 3 survivability. Can the government provide the definition of these two standards or can they direct us to available materials we can review?

Response: Please refer to NFPA 72, Chapter 12. Please see Attachments A through E for available information on the existing building layout, fire alarm system and components.

57. Page 12 item 13B indicates a telephone line to be installed and an alarm monitoring account creation/transfer coordinated with the property manager. Where is the phone service located within the building? Is a phone line available near the existing FACP? Who is responsible for establishing the alarm monitoring account, or does one exist?

Response: GSA’s remote monitoring station is the Mega Center.

Reference Attachment M- MAR 2020: The MAR Form will need to be filled out by the design-build contractors. Reference Attachment K Cleveland floor Plans. Reference page 12, item 13B of specification section 283101.

58. Page 12 item 13 C indicates a second means of transmission will be required. Can the radio transmitter for the city loop be considered the second means or primary means of transmission?

Response: BID the documents as specified.

59. In the specifications duct smoke detectors are mentioned several times. We cannot see any of these on the plans can the owner provide us with any information regarding how many and where are these devices are located?

Response: See Attachments A through E for available information on the existing building layout, fire alarm system and components.

60. The specifications refer in several locations to PROM and EPROM memory storage for the audio portion of the system. This is old technology; will newer technology be accepted?

Response: BID the documents as specified. Follow PBS P-100.

61. On page 39-line item K the specification calls for field programmability. The systems are programmable in the field, but you must be factory trained to perform this work. You should also be knowledgeable of fire alarm operations and other considerations. Is it the intent of the RFP that building personnel will be reprogramming this system at some point? Or is this to allow for future changes to the system through growth and modification of the building?

Response: BID the documents as specified.

62. Page 43 item 2.13 calls for a video display unit. To ensure we provide what is desired, can you provide a general description of what this unit is supposed to do? Is this unit supposed to display what the fire alarm panel displays? Is it supposed to give a graphic representation of the building floor plan? Please provide a little more description of the operation you are attempting to accomplish with this device.

Response: Bid documents as specified.

63. Page 49 section 2.18 Is the elevator presently equipped with firefighter telephones? – Response: Please see Attachments A through E for available information on the existing building layout, fire alarm system and components. Reference Attachment L Photos of Inside of Elevators Buttons.

64. Fire alarm system will require power feeds from the emergency panels. Can you identify the emergency panels on the drawings? Or can you provide a room location where the emergency panels are located throughout the building?

Response: Emergency Panels are located in electrical rooms throughout the buildings. Reference Attachment J: Rudman floor Plans and Attachment K Cleveland floor Plans.

65. Does the building have an existing emergency generator, if so where are panels fed from? Is this generator located within the building?

Response: Each building has an existing emergency generator. Reference Attachment J: Rudman floor Plans and Attachment K Cleveland floor Plans.

66. Page 54 item E .1 indicates smoke detectors are to be located where shown on the drawings, can we assume this is the final design drawings provided by our engineer not the existing drawings showing building present conditions?

Response: Your Fire Protection Engineer will design the new system and locate the detectors in accordance with GSA P-100 and NFPA-72. Reference page 54, item E.1 of specification section 283101.

67. The drawings provided in appendix C & D say they are 1/8” =1’. This means the building is 60’ across. This we know is not true. Can you tell us the correct scale or the size the drawings should be printed to be a correct scale.

Response: Reference Attachment J: Rudman floor Plans and Attachment K Cleveland floor Plans