This document combines a solicitation for construction services and related construction drawings. The solicitation is for Project #552-19-103 to improve a sub-specialty waiting area at the Dayton VA Medical Center located at 4100 W. Third Street, Dayton, OH. The project scope includes fully renovating approximately 4,000 square feet in Building 310 to increase privacy for patients and comfort. Work includes creating 10 new exam rooms, upgrading 27 existing exam rooms, and finishing unfinished areas. The project also involves abatement, finish upgrades, new LED lighting, and mechanical, electrical and plumbing work. The procurement is set aside exclusively for service-disabled veteran-owned small businesses. The estimated value is between $2-5 million and the North American Industry Classification System code is 236220. The small business size standard is $39.5 million. The service-disabled veteran-owned small business must perform a minimum of 15% of the construction work. The performance period is 220 calendar days from notice to proceed. The construction drawings provide details on mechanical, electrical and architectural aspects of the planned renovations.
View the file
Other files
Show 40 more
Latest 50 of 75 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Architecture Engineering Design-Build paradigm
AutoCAD SHX Text 200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com
AutoCAD SHX Text
BID DOCUMENTS FOR CONSTRUCTION
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text
IMPROVE SUB-SPECIALTY WAITING AREA B310
AutoCAD SHX Text 552-19-103
AutoCAD SHX Text 03-20-2020
AutoCAD SHX Text
4100 W THIRD ST, DAYTON, OH 45428
AutoCAD SHX Text
DAYTON VA MEDICAL CENTER
AutoCAD SHX Text
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text F
AutoCAD SHX Text I
AutoCAD SHX Text Exp. 6-30-21
AutoCAD SHX Text No. M 35425
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text P
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text D
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text H
AutoCAD SHX Text L.
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text M-502
AutoCAD SHX Text
MECHANICAL DETAILS
AutoCAD SHX Text F9
AutoCAD SHX Text
NTS
AutoCAD SHX Text
FLEXIBLE DUCT CONNECTIONS
AutoCAD SHX Text
%%UROUND FLEXIBLE CONNECTION
AutoCAD SHX Text
%%URECTANGULAR FLEXIBLE CONNECTION
AutoCAD SHX Text
FLANGED CONNECTION ON FAN SIDE
AutoCAD SHX Text
WASHER
AutoCAD SHX Text
1-1/2"MIN. TO 3"MAX. INSTALLED. 6"NOMINAL WITH MATERIAL TAUT
AutoCAD SHX Text
FLEXIBLE MATERIAL AS SPECIFIED
AutoCAD SHX Text 1"x1/8" DRAW BAND
AutoCAD SHX Text 1"x1/8" BAND IRON
AutoCAD SHX Text
BOLT ON 4" CENTERS
AutoCAD SHX Text
5/16" FLANGE
AutoCAD SHX Text
DUCT
AutoCAD SHX Text
SHEET METAL SCREWS ON 12" CENTERS
AutoCAD SHX Text
RIVET ON 4" CENTERS
AutoCAD SHX Text
SHEET METAL AS SPECIFIED FOR DUCTWORK.
AutoCAD SHX Text 1"x1/8" BAND IRON
AutoCAD SHX Text
BOLT ON 4" CENTERS
AutoCAD SHX Text
1" FLANGE & HEM
AutoCAD SHX Text
ALTERNATE POSITION OF BOLT
AutoCAD SHX Text
1 1/2" POCKET SLIP
AutoCAD SHX Text
DUCT
AutoCAD SHX Text
SHEET METAL AS SPECIFIED FOR DUCTWORK.
AutoCAD SHX Text
1 1/2" MIN. TO 3" MAX. INSTALLED. 6" NOMINAL WITH MATERIAL TAUT
AutoCAD SHX Text
FLANGED CONNECTION ON FAN SIDE
AutoCAD SHX Text
WASHER
AutoCAD SHX Text
FLEXIBLE MATERIAL AS SPECIFIED
AutoCAD SHX Text D9
AutoCAD SHX Text
NTS
AutoCAD SHX Text
FIRE DAMPER INSTALLATION
AutoCAD SHX Text
SECTION THRU
AutoCAD SHX Text
NOTE: 1. 2. 3. 4. 5. 6. 7.
AutoCAD SHX Text A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION, 1S SIMILAR. FOLLOW DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND GAGES FOR SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE INSTALLED IN THE PARTITION OR FLOOR AND NOT OUTSIDE THE PENETRATION. GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO DAMPER FRAME AND TO PERIMETER ANGLES. PERIMETER ANGELS: GALVANIZED STEEL, NOT LESS THAN 1 1/2"x1 1/2", 14 GAGE, TO PROVIDE 1" MINIMUM OVERLAP OF OPENING ON ALL 4 SIDES. BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES SHOWN IN SMACNA. ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR LINKS. PROVIDE 1/4" TO 1/2" CLEARANCE ON HEIGHT AND WIDTH. FILL OPEN SPACE WITH ROCK WOOL FIRESTOP FIBER. ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS AND MECHANICAL ROOM FLOORS, SHALL BE PROVIDED WITH 3" HIGH CONCRETE CURB AROUND OPENING FOR DUCT.
AutoCAD SHX Text
SLEEVE, NOTE 2
AutoCAD SHX Text
DUCT CONNECTION NOTE 4
AutoCAD SHX Text
DAMPER, NOTE 1
AutoCAD SHX Text
DAMPER COLLAR EXTENSION INTEGRAL PART OF SLEEVE
AutoCAD SHX Text
SLEEVE, NOTE 2
AutoCAD SHX Text
NOTE 6
AutoCAD SHX Text
FIRE BARRIER PARTITION OR CHASE
AutoCAD SHX Text
TYPICAL DUCT INSULATION
AutoCAD SHX Text
PERIMETER ANGLE, NOTE 3 (NOTE FASTENED TO PARTITION)
AutoCAD SHX Text
ACCESS PANEL NOTE 5
AutoCAD SHX Text B9
AutoCAD SHX Text
NTS
AutoCAD SHX Text
ROUND DUCT HANGERS
AutoCAD SHX Text 2500 [1133]
AutoCAD SHX Text 1320 [598]
AutoCAD SHX Text 420 [190]
AutoCAD SHX Text ONE 1 x 18 GA STRAP
AutoCAD SHX Text
AutoCAD SHX Text
TWO 1/2%%C RODS
AutoCAD SHX Text
TWO 3/8%%C. RODS
AutoCAD SHX Text ONE 1 x 16 GA STRAP
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 700 [317]
AutoCAD SHX Text ONE 1 x 22 GA STRAP
AutoCAD SHX Text
QUANTITY/SIZE
AutoCAD SHX Text
MAX. DUCT %%C
AutoCAD SHX Text
AutoCAD SHX Text
HANGER STRAPS OR RODS
AutoCAD SHX Text
MAX. LOAD
AutoCAD SHX Text LBS. [kg]
AutoCAD SHX Text 260 [119]
AutoCAD SHX Text
MAX.
AutoCAD SHX Text
AutoCAD SHX Text
IN.
AutoCAD SHX Text
SPACING
AutoCAD SHX Text
IN.
AutoCAD SHX Text IN. [mm]
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text NOTE: TABULATED DATA FROM SMACNA ALLOWS FOR DUCT REINFORCING AND INSULATION, BUT NO EXTERNAL LOAD.
AutoCAD SHX Text
BAND
AutoCAD SHX Text
OVER 50"
AutoCAD SHX Text
HANGER RODS
AutoCAD SHX Text
BAND OF SAME SIZE AS HANGER STRAP
AutoCAD SHX Text
LOAD RATED FASTENERS
AutoCAD SHX Text
50" &UNDER
AutoCAD SHX Text F6
AutoCAD SHX Text
NTS
AutoCAD SHX Text
FROM STRUCTURE
AutoCAD SHX Text
SAME AS DIFFUSER
AutoCAD SHX Text
INLET: 5'-0" MAX
AutoCAD SHX Text
FLEXIBLE DUCT SIZE
AutoCAD SHX Text
LENGTH.
AutoCAD SHX Text 12"
AutoCAD SHX Text
CEILING
AutoCAD SHX Text
SUPPORT SADDLE
AutoCAD SHX Text
VOLUME DAMPER W/
AutoCAD SHX Text
LOCKING QUAD
AutoCAD SHX Text
SADDLE
AutoCAD SHX Text
SHEET METAL
AutoCAD SHX Text
CONICAL OUTLET
AutoCAD SHX Text
BRANCH DUCT
AutoCAD SHX Text
FOR CHANGE OF
AutoCAD SHX Text
DIRECTION GREATER
AutoCAD SHX Text
USE RIGID ELBOWS
AutoCAD SHX Text
THAN 45%%D
AutoCAD SHX Text
FLEXIBLE AIR DUCT CONNECTOR
AutoCAD SHX Text
SEE SPECIFICATIONS FOR CLAMPS AND SEALANT (TYP.)
AutoCAD SHX Text NOTE: THE USE OF FLEXIBLE AIR DUCT CONNECTORS ARE NOT PERMITTED FOR THE DEDICATED AHU SERVING THE SURGICAL SUITE.
AutoCAD SHX Text
TYPICAL DIFFUSER OR REGISTER IN LAY-IN CLG.
AutoCAD SHX Text
THERMAL INSULATION SEE SPECIFICATIONS
AutoCAD SHX Text D6
AutoCAD SHX Text
NTS
AutoCAD SHX Text
ROOM THERMOSTAT/SENSOR WALL MOUNTED 48"AFF.
AutoCAD SHX Text
CONSTANT VOLUME AIR TERMINAL UNIT CONTROL DIAGRAM
AutoCAD SHX Text
NO SUPPLEMENTAL HEATING
AutoCAD SHX Text
AIR FLOW (CFM)
AutoCAD SHX Text
ROOM TEMPERATURE (°F)
AutoCAD SHX Text
CV CFM
AutoCAD SHX Text
TU
AutoCAD SHX Text
RHC
AutoCAD SHX Text
HWS
AutoCAD SHX Text
HWR
AutoCAD SHX Text V-1
AutoCAD SHX Text
REHEAT COIL
AutoCAD SHX Text
AIR TERMINAL UNIT
AutoCAD SHX Text
AIR FLOW
AutoCAD SHX Text
TE
AutoCAD SHX Text
ATU CONTROLLER
AutoCAD SHX Text
PC
AutoCAD SHX Text
TE
AutoCAD SHX Text
CV BOX CONTROL SEQUENCE
AutoCAD SHX Text
NO DEADBAND
AutoCAD SHX Text
AIR FLOW (CFM)
AutoCAD SHX Text
ROOM TEMPERATURE (°F)
AutoCAD SHX Text
CV CFM
AutoCAD SHX Text
CV BOX CONTROL SEQUENCE
AutoCAD SHX Text
W/DEADBAND
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
FE
AutoCAD SHX Text
REHEAT FLOW
AutoCAD SHX Text
REHEAT FLOW
AutoCAD SHX Text A. UPON FALL IN SPACE TEMPERATURE BELOW SET POINT VALVE V-1 WILL MODULATE TO MAINTAIN SET POINT + + .5°, THE ADJUSTABLE TOLERANCE OF + .5° HAS BEEN SELECTED TO PREVENT VALVE HUNTING B. THE REVERSE SHALL OCCUR ON RISE IN SPACE TEMPERATURE.
AutoCAD SHX Text A. SET POINTS SHALL SET AS FOLLOWS: COOLING 75° F (ADJ) HEATING 70° F (ADJ) DEADBAND OF 5° F BETWEEN HEATING AND COOLING SET POINT WILL BE MAINTAINED B. UPON FALL IN SPACE TEMPERATURE BELOW SET POINT VALVE V-1 WILL MODULATE TO MAINTAIN SET POINT + + .5°,THE ADJUSTABLE TOLERANCE OF + .5° HAS BEEN SELECTED TO PREVENT VALVE HUNTING C. THE REVERSE SHALL OCCUR ON RISE IN SPACE TEMPERATURE.
AutoCAD SHX Text F1
AutoCAD SHX Text
NTS
AutoCAD SHX Text
HWS
AutoCAD SHX Text
HWR
AutoCAD SHX Text V-2
AutoCAD SHX Text
ROOM THERMOSTAT/SENSOR WALL MOUNTED 48" AFF.
AutoCAD SHX Text
ROOM THERMOSTAT/SENSOR WALL MOUNTED 48" AFF.
AutoCAD SHX Text
VARIABLE VOLUME AIR TERMINAL UNIT CONTROL DIAGRAM
AutoCAD SHX Text
NO SUPPLEMENTAL HEATING
AutoCAD SHX Text
WITH SUPPLEMENTAL HEATING
AutoCAD SHX Text
AIR FLOW (CFM)
AutoCAD SHX Text
ROOM TEMPERATURE (°F)
AutoCAD SHX Text
HEATING MINIMUM
AutoCAD SHX Text
VAV BOX CONTROL SEQUENCE
AutoCAD SHX Text
SP
AutoCAD SHX Text
TU
AutoCAD SHX Text
RHC
AutoCAD SHX Text
HWS
AutoCAD SHX Text
HWR
AutoCAD SHX Text V-1
AutoCAD SHX Text
REHEAT COIL
AutoCAD SHX Text
AIR TERMINAL UNIT
AutoCAD SHX Text
AIR FLOW
AutoCAD SHX Text
TE
AutoCAD SHX Text
ATU CONTROLLER
AutoCAD SHX Text
PC
AutoCAD SHX Text
TE
AutoCAD SHX Text
TU
AutoCAD SHX Text
RHC
AutoCAD SHX Text
HWS
AutoCAD SHX Text
HWR
AutoCAD SHX Text V-1
AutoCAD SHX Text
REHEAT COIL
AutoCAD SHX Text
AIR TERMINAL UNIT
AutoCAD SHX Text
AIR FLOW
AutoCAD SHX Text
TE
AutoCAD SHX Text
ATU CONTROLLER
AutoCAD SHX Text
PC
AutoCAD SHX Text
TE
AutoCAD SHX Text
AIR FLOW (CFM)
AutoCAD SHX Text
ROOM TEMPERATURE (°F)
AutoCAD SHX Text
HEATING MINIMUM
AutoCAD SHX Text
SP
AutoCAD SHX Text
AIR FLOW (CFM)
AutoCAD SHX Text
ROOM TEMPERATURE (°F)
AutoCAD SHX Text
HEATING MINIMUM
AutoCAD SHX Text
SP
AutoCAD SHX Text
AIR FLOW (CFM)
AutoCAD SHX Text
ROOM TEMPERATURE (°F)
AutoCAD SHX Text
HEATING MINIMUM
AutoCAD SHX Text
NO DEADBAND
AutoCAD SHX Text
VAV BOX CONTROL SEQUENCE
AutoCAD SHX Text
W/DEADBAND
AutoCAD SHX Text
VAV BOX CONTROL SEQUENCE
AutoCAD SHX Text
NO DEADBAND
AutoCAD SHX Text
VAV BOX CONTROL SEQUENCE
AutoCAD SHX Text
W/DEADBAND
AutoCAD SHX Text
SUPPLEMENTAL HEAT
AutoCAD SHX Text
SP
AutoCAD SHX Text
FE
AutoCAD SHX Text 100%
AutoCAD SHX Text 100%
AutoCAD SHX Text 100%
AutoCAD SHX Text 100%
AutoCAD SHX Text
REHEAT FLOW
AutoCAD SHX Text
VAV AIR FLOW
AutoCAD SHX Text
VAV AIR FLOW
AutoCAD SHX Text
VAV AIR FLOW
AutoCAD SHX Text
VAV AIR FLOW
AutoCAD SHX Text
REHEAT FLOW
AutoCAD SHX Text
REHEAT FLOW
AutoCAD SHX Text
SUPP FLOW
AutoCAD SHX Text
REHEAT FLOW
AutoCAD SHX Text
SUPP FLOW
AutoCAD SHX Text A. UPON FALL IN SPACE TEMPERATURE THE VAV DAMPER WILL MODULATE TO MINIMUM POSITION. B. UPON FURTHER DROP IN SPACE TEMPERATURE VALVE V-1 WILL MODULATE TO MAINTAIN SET POINT + .5 F. THE + .5 F. THE .5° F. THE ADJUSTABLE TOLERANCE OF + .5 F HAS + .5 F HAS .5° F HAS BEEN SELECTED TO PREVENT VALVE HUNTING C. THE REVERSE SHALL OCCUR ON THE RISE IN SPACE TEMPERATURE.
AutoCAD SHX Text A. SET POINTS SHALL BE SET AS FOLLOWS: COOLING 75°F (ADJ) HEATING 70°F(ADJ) DEADBAND OF 5° F BETWEEN HEATING AND COOLING SET POINTS WILL BE MAINTAINED. B. UPON FALL IN SPACE TEMPERATURE THE VAV DAMPER WILL MODULATE TO MINIMUM POSITION. C. UPON FURTHER DROP IN SPACE TEMPERATURE VALVE V-1 WILL MODULATE TO MAINTAIN SET POINT + .5 F. THE + .5 F. THE .5° F. THE ADJUSTABLE TOLERANCE OF + .5 F HAS + .5 F HAS .5° F HAS BEEN SELECTED TO PREVENT VALVE HUNTING D. THE REVERSE SHALL OCCUR ON THE RISE IN SPACE TEMPERATURE.
AutoCAD SHX Text A. UPON FALL IN SPACE TEMPERATURE THE VAV DAMPER WILL MODULATE TO MINIMUM POSITION. B. UPON FURTHER DROP IN SPACE TEMPERATURE VALVE V-1 WILL MODULATE TO MAINTAIN SET POINT + .5 F. THE + .5 F. THE .5° F. THE ADJUSTABLE TOLERANCE OF + .5 F HAS + .5 F HAS .5° F HAS BEEN SELECTED TO PREVENT VALVE HUNTING C. VALVE V-2 SHALL BE ENABLED WHEN OUTSIDE AIR FALLS BELOW 40° F (ADJ) AND VALVE V-1 HAS BEEN MODULATED OPEN ABOVE 30% (ADJ). VALVE V-2 SHALL MAINTAIN SET POINT + .5 F. THE + .5 F. THE .5° F. THE ADJUSTABLE TOLERANCE OF + .5 F HAS + .5 F HAS .5°F HAS BEEN SELECTED TO PREVENT VALVE HUNTING. THE REVERSE SHALL OCCUR ON A RISE IN SPACE TEMPERATURE.
AutoCAD SHX Text A. SET POINTS SHALL BE SET AS FOLLOWS: COOLING 75°F (ADJ) HEATING 70°F(ADJ) DEADBAND OF 5° F BETWEEN HEATING AND COOLING SET POINTS WILL BE MAINTAINED. B. UPON FALL IN SPACE TEMPERATURE THE VAV DAMPER WILL MODULATE TO MINIMUM POSITION. C. UPON FURTHER DROP IN SPACE TEMPERATURE VALVE V-1 WILL MODULATE TO MAINTAIN SET POINT + .5 F. THE + .5 F. THE .5° F. THE ADJUSTABLE TOLERANCE OF + .5 F HAS + .5 F HAS .5° F HAS BEEN SELECTED TO PREVENT VALVE HUNTING D. VALVE V-2 SHALL BE ENABLED WHEN OUTSIDE AIR FALLS BELOW 40° F (ADJ) AND VALVE V-1 HAS BEEN MODULATED OPEN ABOVE 30% (ADJ). VALVE V-2 SHALL MAINTAIN SET POINT + .5 F. THE + .5 F. THE .5° F. THE ADJUSTABLE TOLERANCE OF + .5 F HAS + .5 F HAS .5°F HAS BEEN SELECTED TO PREVENT VALVE HUNTING. E. THE REVERSE SHALL OCCUR ON THE RISE IN SPACE TEMPERATURE.
AutoCAD SHX Text
FE
AutoCAD SHX Text C4
AutoCAD SHX Text
NTS
AutoCAD SHX Text
DUCT CONNECTIONS - AIR TERMINAL UNITS
AutoCAD SHX Text
NOTE: 1. 2. 3. 4. 5. 6.
AutoCAD SHX Text RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A MINIMUM OF 3 TIMES THE DIAMETER OF INLET A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET TO THIS BOX, BUT ALLOWED TO ACCOMMODATE MINOR OFFSETS. MAXIMUM LENGTH 3'-0". A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE SAME SIZE AS THE BOX INLET, PROVIDED THE EQUIVALENT LENGTH OF THE BRANCH DUCT, AS SHOWN, DOES NOT EXCEED 10 FEET (3 METERS). FOR LONGER LENGTHS, INCREASE THE DUCT SIZE AND PROVIDE A DUCT TRANSITION TO MAINTAIN THE DUCT STATIC PRESSURE DROP AT OR BELOW 0.2"/100' [1.64Pa/m]. FLEXIBLE AIR DUCT CONNECTORS, WHEN USED FROM TERMINAL UNIT SUPPLY AIR DUCT TO DIFFUSER, SHALL NOT EXCEED 5'-0" [1500mm]. USE RIGID ELBOWS FOR CHANGE OF DIRECTION GREATER THAN 45°.COMPONENT ARRANGEMENT MAY VARY BY MANUFACTURER. PROVIDE INSULATION W/VAPOR BARRIER FOR CONNECTING DUCT SECTIONS. USE OF THE FLEXIBLE AIR DUCT CONNECTORS ARE NOT PERMITTED FOR THE DEDICATED AHU SERVING THE SURGICAL SUITE.
AutoCAD SHX Text
AIR TERMINAL UNIT (CV OR VAV)
AutoCAD SHX Text
REHEAT COIL
AutoCAD SHX Text
SOUND ATTENUATOR SEE EQUIPMENT SCHEDULE
AutoCAD SHX Text
FLEXIBLE AIR DUCT CONNECTOR. SEE DETAIL
AutoCAD SHX Text
DIFFUSER (TYP.)
AutoCAD SHX Text
SEE SPECIFICATIONS FOR CLAMPS AND SEALANT (TYP.)
AutoCAD SHX Text
SEE NOTE 5
AutoCAD SHX Text
DESIGNER'S NOTE: 1.INDICATE SOUND ATTENUATOR AS REQUIRED BY ACOUSTICAL ANALYSIS
AutoCAD SHX Text C1
AutoCAD SHX Text
NTS
AutoCAD SHX Text
ACCESS SECTION FOR ROUND/OVAL DUCT
AutoCAD SHX Text
HOUSING WELDED TO DUCT SECTION
AutoCAD SHX Text
ROUND OR FLAT OVAL DUCT SECTION
AutoCAD SHX Text
COVER WITH HANDLE AND CHAIN RETAINER GASKETED AND PRESSURE SEALED
AutoCAD SHX Text
DH
AutoCAD SHX Text
RN
AutoCAD SHX Text POINTS LIST (EACH TERMINAL UNIT) 1. ROOM TEMPERATURE ROOM TEMPERATURE 2. ROOM SET POINT ROOM SET POINT 3. TERMINAL UNIT AIRFLOW MEASURED TERMINAL UNIT AIRFLOW MEASURED 4. TERMINAL UNIT AIRFLOW SETPOINT TERMINAL UNIT AIRFLOW SETPOINT 5. TERMINAL UNIT DISCHARGE AIR TEMPERATURETERMINAL UNIT DISCHARGE AIR TEMPERATURE