This solicitation package describes a construction project to improve a sub-specialty waiting area at the Dayton VA Medical Center in Ohio. The project scope involves fully renovating approximately 4,000 square feet on the first floor of Building 310, including creating ten new exam rooms in an adjoining unfinished area of around 2,080 square feet. Additional areas will receive new finishes and plumbing. Approximately 27 existing exam rooms will be upgraded with new sinks and fire alarm and nurse call systems. Corridors in the scope will be abated and receive finish upgrades, and most areas will get new LED light fixtures. The estimated project value is between $2-5 million. Interested service-disabled veteran-owned small businesses must respond within 30 days of the July 29, 2020 posting date. The selected firm must perform a minimum of 15% of on-site construction work. The project duration shall not exceed 220 calendar days from the receipt of notice to proceed. Performance and payment bonds will be required. The project is set aside exclusively for service-disabled veteran-owned small businesses registered in the relevant websites.
View the file
Other files
Show 40 more
Latest 50 of 75 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Architecture Engineering Design-Build paradigm
AIR DEVICE SCHEDULE (SUPPLY)
MARK TYPE
AIR FLOW MAX
APD MOUNTING
PANEL/F
RAME
SIZE
NECK
SIZE
NC DAMPER FINISH REMARKS
MIN MAX
IN x IN IN
CFM CFM IN WG
SD-11 LOUVERED FACE 40 160 0.080 CEILING 24 x 24 6 ø 19 NONE WHITE ----
SD-12 LOUVERED FACE 70 280 0.100 CEILING 24 x 24 8 ø 23 NONE WHITE -----
SD-13 LOUVERED FACE 110 380 0.090 CEILING 24 x 24 10 ø 22 NONE WHITE -----
NOTES:
1. SEE FLOOR PLAN FOR THROW PATTERN.
2. SEE DETAIL FOR DAMPER IN BRANCH DUCT SERVING EACH DIFFUSER.
3. PROVIDE SQUARE TO ROUND ADAPTER.
AIR DEVICE SCHEDULE (RETURN)
MARK TYPE
AIR FLOW MAX
APD MOUNTING
PANEL/FR
AME SIZE NECK SIZE
NC DAMPER FINISH REMARKSMIN MAX
CFM CFM IN WG IN x IN IN x IN
RG-21/EG-21 PERFORATED 60 100 0.088 CEILING 24 x 24 6 DIAM 13 NONE WHITE -----
RG-22/EG-22 PERFORATED 110 170 0.088 CEILING 24 x 24 8 DIAM 13 NONE WHITE -----
RG-23/EG-23 PERFORATED 170 250 0.088 CEILING 24 x 24 10 DIAM 14 NONE WHITE -----
RG-24/EG-24 PERFORATED 240 400 0.088 CEILING 24 x 24 12 DIAM 12 NONE WHITE -----
NOTE:
PROVIDE SQUARE TO ROUND ADAPTER WHERE REQUIRED.
AIR TERMINAL UNIT SIZING SCHEDULE
SIZE
MIN ALLOWABLE AIR
FLOW
MAX ALLOWABLE AIR
FLOW DUCT INLET SIZE MAX APD
MAXIMUM SOUND POWER LEVEL (Re: 10 -12 WATTS) FOR BOX
DISCHARGE AT MAXIMUM INLET DUCT STATIC HOT WATER HEATING COIL
REMARKSOCTAVE BANDS EAT EWT FLOW MAX WPD PIPE RUNOUT SIZE TO COIL
CFM CFM IN IN WG 2 3 4 5 6 7 °F °F GPM FT IN
A 60 170 4 0.4 69 65 58 52 51 47 55 140 0.50 3 3/4 ----
B 90 260 5 0.4 69 63 59 52 51 47 55 140 0.50 3 3/4 ----
C 130 380 6 0.4 69 67 61 55 52 49 55 140 0.70 4 3/4 ----
D 160 490 7 0.4 70 68 63 57 53 49 55 140 0.70 4 3/4 ----
E 230 680 8 0.4 71 68 59 53 51 47 55 140 1.00 3 3/4 ----
F 270 790 9 0.4 71 69 60 54 51 47 55 140 1.50 4 3/4 ----
G 350 1050 10 0.4 74 68 61 57 54 52 55 140 1.50 4 3/4 ----
H 500 1500 12 0.4 73 69 64 59 57 53 55 140 2.50 3 3/4 ----
I 750 2250 14 0.4 73 68 65 61 61 59 55 140 3.50 4 3/4 ----
J 1000 3000 16 0.4 73 68 66 60 58 55 55 140 4.50 4 1 ----
NOTES:
1. INLET STATIC BASED ON ARI 885-98.
2. THIS SCHEDULE IS USED WITH THE TERMINAL UNIT SCHEDULE.
3. CONTROL SEQUENCE SHALL BE AS INDICATED ON THE AIR TERMINAL UNIT SCHEDULE.
4. PROVIDE SOUND ATTENUATION AFTER-SECTION AS REQUIRED TO MEET ROOM NC LEVEL.
SINGLE DUCT AIR TERMINAL UNIT SCHEDULE
MARK LOCATION AREA AND/OR ROOM SERVED
SYSTEM
AIR
HANDLING
SIZE
AIR FLOW ADDITIONAL
SOUND
ATTUNATION
REQUIRED
CONTROL
TYPE CONTROL SEQUENCE
REHEAT PERIMETER
SUPPLEMENTAL
HEAT LINK
REMARKSMAX MIN
CFM CFM HW ELEC NONE
TU-1 C1-9 1E-104, 1E-110B, 1E-110A,1E-110C (E)AC-2 E 515 515 NONE VAV 5 DEGREE DEADBAND X ---- ----
TU-2 C-36 1E-105, 1E-106, 1E-109D, 1E-109C,
CORRIDOR
(E)AC-2 F 755 755 NONE VAV 5 DEGREE DEADBAND X ---- ----
TU-3 C1-7 1E-146 (E)AC-2 C 280 280 NONE VAV 5 DEGREE DEADBAND X ---- ----
TU-4 1E-170a 1E-170 (E)AC-2 C 310 310 NONE VAV 5 DEGREE DEADBAND X ---- ----
TU-5 1E-142 C1-31, 1E-142 (E)AC-7 G 800 800 NONE VAV 5 DEGREE DEADBAND X ---- ----
TU-6 C1-19 1E-135,1E-136 G (E)AC-7 E 620 410 NONE VAV 5 DEGREE DEADBAND X ---- ----
TU-7 C1-24 1E-109e,1E-152,C1-24, WAITING (E)AC-2 E 570 570 NONE VAV 5 DEGREE DEADBAND X ---- ----
TU-8 C1-14 C1-21 (E)AC-2 B 215 215 NONE VAV 5 DEGREE DEADBAND X ---- ----
TU-9 1E-143 1E-143 (E)AC-2 C 300 300 NONE VAV 5 DEGREE DEADBAND X ---- ----
TU-10 1E-143 1E-173,1E-173a (E)AC-2 B 200 200 NONE VAV 5 DEGREE DEADBAND X ---- ----
TU-11 1E-142 1E-170e (E)AC-7 A 90 90 NONE VAV 5 DEGREE DEADBAND X ---- ----
TU-12 C1-14 C1-21 A (E)AC-2 A 120 120 NONE VAV 5 DEGREE DEADBAND X ---- ----
TU-13 C-36 109B, 109A (E)AC-2 C 300 300 NONE VAV 5 DEGREE DEADBAND X ---- ----
TU-14 C1-2C 1E-134A (E)AC-2 A 110 110 NONE VAV 5 DEGREE DEADBAND X ---- ----
NOTES:
1. REFER TO AIR TERMINAL UNIT SIZING SCHEDULE FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text 200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com
AutoCAD SHX Text
BID DOCUMENTS FOR CONSTRUCTION
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text
IMPROVE SUB-SPECIALTY WAITING AREA B310
AutoCAD SHX Text 552-19-103
AutoCAD SHX Text 03-20-2020
AutoCAD SHX Text
4100 W THIRD ST, DAYTON, OH 45428
AutoCAD SHX Text
DAYTON VA MEDICAL CENTER
AutoCAD SHX Text
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text F
AutoCAD SHX Text I
AutoCAD SHX Text Exp. 6-30-21
AutoCAD SHX Text No. M 35425
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text P
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text D
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text H
AutoCAD SHX Text L.
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text M-601
AutoCAD SHX Text
MECHANICAL SCHEDULES
AutoCAD SHX Text
DH
AutoCAD SHX Text
RN
| Sheets and Views |
| M-601 |
File details come from the government source that posted it. Updated .