4 of 8 - 589A7-21-702 Fire Dwgs.pdf
PDF 2 MB Posted
- Attached to
- Y1DA--589A7-21-702 EHRM Training and Admin Support Space (TASS) Construction - Wichita, KS
- Solicitation number
- 36C77622B0033
About this file
This package includes construction drawings and specifications for a fire alarm and fire suppression system renovation project at the Robert J. Dole VA Medical Center in Wichita, Kansas. The drawings show the design and locations for new and existing fire alarm devices, speakers, strobes, and detectors on the ground level and first floor of Building 61. Specifications require upgrading the fire alarm system to current codes and standards, including adding duct smoke detectors. The fire suppression drawings classify hazard levels and note the wet pipe sprinkler system must maintain temperatures above 40 degrees Fahrenheit. Modifications include relocating valves and installing sprinkler heads in concealed spaces.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRE ALARM LEGEND
WF EXISTING WATERFLOW DEVICE
OUT OF SCOPE AREA
VS EXISTING VALVE SUPERVISORY SWITCH
AIM EXISTING ADDRESSABLE INPUT MODULE
FIRE ALARM GENERAL NOTES
SPD EXISTING SURGE PROTECTIVE DEVICE
FACU EXISTING FIRE ALARM CONTROL UNIT
S EXISTING SMOKE DETECTOR - SPOT TYPE
NEW SPEAKER STROBE
S NEW SPEAKER
SYMBOL MODIFIERS
ncd CANDELA RATING
GENERAL:
1. THE CONTRACTOR SHALL CAREFULLY REVIEW ALL APPLICABLE
DESIGN CRITERIA, THESE DRAWINGS, AND THE PROJECT
SPECIFICATIONS FOR IMPORTANT QUALIFICATION, DEFINITION,
SUBMITTAL, PRODUCT, INSTALLATION, AND TESTING
REQUIREMENTS.
2. ALL SUBMITTALS, INSTALLATION, AND TESTING SHALL BE
COMPLETED IN A NEAT, WORKMAN-LIKE MANNER.
3. PRODUCT, DESIGN, INSTALLATION, AND TESTING ALTERNATE
APPROACHES AND/OR SUBSTITUTIONS WILL BE CONSIDERED BY THE
ENGINEER IF THE CONTRACTOR PROVIDES WRITTEN, WELL-
DOCUMENTED, ENGINEERING-BASED SUBSTANTIATION FOR
PROPOSED ALTERNATIVE.
APPLICABLE CODES AND STANDARDS:
1. VA FIRE PROTECTION DESIGN MANUAL EIGHTH EDITION - JUNE 2021
2. NFPA 70 NATIONAL ELECTRIC CODE (2020)
3. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE (2022)
4. NFPA 101 (2021)
5. INTERNATIONAL BUILDING CODE (2021)
AUDIBILITY AND INTELLIGIBILITY DESIGN:
1. BECAUSE OF UNPREDICTABLE BACKGROUND NOISES AND PROJECT
CONDITIONS, THE AUDIBILITY DESIGN GOALS SHALL BE CONFIRMED
BY MEASUREMENT WITH CALIBRATED TEST EQUIPMENT. IF RESULTS
INDICATE THAT ADDITIONAL NOTIFICATION APPLIANCES ARE
REQUIRED, THE CONTRACTOR SHALL ADD THEM AT NO ADDITIONAL
COST.
2. SPEAKERS MAY BE FIELD-LOCATED WITHIN 6 FT OF THE LOCATION
INDICATED ON THE APPROVED DESIGN WITHOUT CONSULTING THE
ENGINEER.
3. INTELLIGIBILITY OF THE OCCUPANT NOTIFICATION SHALL BE TESTED
IN ACCORDANCE WITH NFPA 72 AND THE VA FIRE PROTECTION
DESIGN MANUAL. QUALITATIVE TESTING IS ALLOWED. ALL SCOPE OF
WORK AREAS ARE REQUIRED TO HAVE A CIS SCORE OF 0.65.
VISUAL NOTIFICATION DESIGN:
1. CLEAR STROBES SHALL BE PROVIDED WHERE INDICATED ON THE
APPROVED DESIGN.
2. STROBES MAY BE FIELD-LOCATED WITHIN 3 FT OF THE LOCATION
INDICATED ON THE APPROVED DESIGN WITHOUT CONSULTING THE
ENGINEER. CONSULT WITH ENGINEER PRIOR TO RELOCATING
STROBES MORE THAN 3 FT.
3. PER DIRECTION FROM THE VA, STROBES ARE NOT REQUIRED IN
INDIVIDUAL OFFICES UP TO 750 SQUARE FEET. STROBES ARE ALSO
NOT REQUIRED IN THE SAME OFFICE SPACES IF THERE ARE MORE
THAN ONE DESK/PERSON OCCUPYING THE OFFICE.
INITIATING DEVICES:
1. INITIATING DEVICES MAY BE FIELD-LOCATED WITHIN 3 FT OF THE
LOCATION INDICATED ON THE APPROVED DESIGN WITHOUT
CONSULTING THE ENGINEER. CONSULT WITH ENGINEER PRIOR TO
RELOCATING INITIATING DEVICES MORE THAN 3 FT.
CIRCUITS AND CONDUIT:
1. ALL CIRCUITS SHALL BE PROVIDED IN CONDUIT IN ACCORDANCE
WITH NFPA 70 AND THE CONDUIT LISTING.
2. NEW SIGNALING LINE CIRCUITS AND NOTIFICATION APPLIANCE
CIRCUITS SHALL BE ARRANGED SO THAT A SINGLE FAULT DOES NOT
CAUSE THE LOSS OF ADDRESSABLE DEVICES ON MORE THAN ONE
SMOKE COMPARTMENT.
3. WIRING SHALL BE INSTALLED IN METAL RACEWAY. PER VA DESIGN
MANUAL THIS IN COMBINATION WITH BUILDINGS PROTECTED
THROUGHOUT BY SPRINKLERS SHALL BE CONSIDERED TO MEET THE
REQUIREMENTS FOR PATHWAY SURVIVABILITY LEVEL 2 IN
ACCORDANCE WITH NFPA 72 AND VA AUTHORITY HAVING
JURISDICTION.
4. SPEAKERS AND STROBES SHALL BE ARRANGED TO OPERATE ON
SEPARATE CIRCUITS.
INSTALLATION:
1. ALL EQUIPMENT SHALL BE INSTALLED TIGHT TO THE BUILDING
STRUCTURE AND SHALL BE INSTALLED PARALLEL OR
PERPENDICULAR TO THE BUILDING STRUCTURE UNLESS NOTED
OTHERWISE.
2. THE CONTRACTOR SHALL NOT APPRECIABLY DEVIATE FROM THE
APPROVED DESIGN WITHOUT WRITTEN APPROVAL FROM THE
ENGINEER.
TESTING:
1. UNLESS SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR
SHALL PERFORM ALL ACCEPTANCE TESTING IN ACCORDANCE WITH
THE APPLICABLE DESIGN CRITERIA AND THE EQUIPMENT
MANUFACTURER'S INSTRUCTIONS.
2. UNLESS SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR
SHALL PERFORM TESTING AND PROVIDE DOCUMENTATION PRIOR TO
REQUESTING ENGINEER'S PRESENCE TO WITNESS TESTING.
s NEW SMOKE DETECTOR - DUCT TYPE
NEW FIRE ALARM PULL STATIONF
FACU
SPD
NOTES:
1. TO DEDICATED 120VAC BRANCH CIRCUIT
2. THIS RISER DIAGRAM IS INTENDED ONLY TO CAPTURE THE SYSTEM DESIGN
INTENT, PANEL CONNECTIONS, AND GENERAL CIRCUIT ROUTING REQUIREMENTS.
EXACT QUANTITIES AND TYPES OF DEVICES NECESSARY TO ACCOMPLISH THE
DESIGN GOALS ARE NOT INDICATED. THE INTENT OF THIS RISER DIAGRAM IS TO
INDICATE THE GENERAL SYSTEM CONFIGURATION AFTER SUCCESSFUL
COMPLETION OF THE PROJECT.
GROUND LEVEL
WF VS
AIM AIMS
SS
F s
3 WATERFLOW/PRESSURE SWITCH X X X X X X X X X 3
5 CONTROL VALVE SUPERVISORY SWITCH X X X X 5
12 ANY OTHER SYSTEM TROUBLE X X X X 12
SUPERVISORY CONDITIONS A B C D E F G H I J K L M N
4 SMOKE DETECTOR - DUCT TYPE X X X X X 4
A B C D E F G H I J K L M N
X PERFORM OPERATION/REPORT DEVICE STATUS
NOTE: THIS MATRIX REPRESENTATIVE OF THE SCOPE OF WORK FOR THIS PROJECT.
ALL EXISTING PROGRAMING FOR BUILDING NOT BE MODIFIED UNLESS REQUIRED BY
SOW FOR THIS PROJECT.
SYSTEM OUTPUTS
SYSTEM INPUTS
F A
C U
A N
N U
N C
IA
T
IO
N
A C
T
IV
A T
E C
O M
M O
N A
L A
R M
S
IG
N A
L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
A L A
R M
S
IG
N A
L
A C
T
IV
A T
E C
O M
M O
N S
U P
E R
V
IS
O R
Y S
IG
N
A L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
S U
P E
R V
IS
O
R Y
S
IG
N A
L
A C
T
IV
A T
E C
O M
M O
N T
R O
U B
L E
S
IG
N A
L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
T R
O U
B L E
S
IG
N A
L
D
IS
P L A
Y /P
R
IN
T C
H A
N G
E O
F S
T A
T U
S
N O
T
IF
IC
A
T
IO
N
A C
T
IV
A T
E T
E M
P O
R A
L
A L E
R T
T O
N E
A N
D P
R E
-R E
C O
R D
E D
F
IR
E
V
A C
U A
T
IO
N M
E S
S A
G E
T H
R O
U G
H O
U T
T H
E A
S S
O C
IA
T
E D
Z O
N E
A C
T
IV
A T
E S
T R
O B
E S
T H
R O
U G
H O
U T
T H
E A
S S
O C
IA
T
E D
Z O
N E
A C
T
IV
A T
E P
R E
-R E
C O
R D
E D
S T
A F
F A
L E
R T
M E
S S
A G
E T
H R
O U
G H
O U
T T
H
B
U
IL
D
IN
G
N O
T
IF
Y F
IR
E
D E
P A
R T
M E
N T
/S U
P E
R V
IS
IN
G S
T A
T
IO
N
A U
X
IL
IA
R
Y F
U N
C T
IO
N
S
S H
U T
D O
W N
A S
S O
C
IA
T E
D A
IR
H
A N
D L
IN
G U
N
IT
A C
T
IV
A T
E E
L E
C T
R
IC
A L D
IS
C
O N
N E
C T
O F
E Q
U
IP
M E
N T
I N
I T
E S
P A
C E
S
C L O
S E
S M
O K
E B
A R
R
IE
R D
O O
R S
O N
A S
S O
C
IA
T E
D F
L O
O R
ALARM CONDITIONS A B C D E F G H I J K L M N
1 MANUAL ALARM PULL STATION X X X X X X X X X 1
2 SMOKE DETECTOR - SPOT TYPE X X X X X X X X 2
TROUBLE CONDITIONS A B C D E F G H I J K L M N
6 AC POWER FAILURE X X X X 6
7 LOW BATTERY X X X X 7
8 OPEN CIRCUIT X X X X 8
9 GROUND FAULT X X X X 9
10 NOTIFICATION APPLIANCE CIRCUIT SHORT X X X X 10
11 REMOTE POWER SUPPLY COMMON TROUBLE X X X X 11
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
KS
KS
ARCH REG. NO.
ENGR REG. NO.
EXP. 12/31/2021
EXP. 12/31/2021
A-930, E-2586, CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
PLUMBING ENGINEER
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8650 ROBERT J. DOLE VA MEDICAL CENTER
SPUR #: 1794.08
/2
/2
:1 :2
P
M
FIRE ALARM GENERAL NOTES, LEGEND, AND
DIAGRAMS
SAB 61BLS
ISSUED FOR CONSTRUCTION
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
ADMINISTRATIVE SPACE
01/28/2021
589A7-21-702
5500 EAST KELLOGG AVENUE
WICHITA, KANSAS 67218
FA001
NOT TO SCALE
FACU RISER DIAGRAM1NOT TO SCALE
FACU INPUT/OUTPUT MATRIX2
No. REVISION DESCRIPTION DATE
LO NG TERMADM INISTRATIO N/SUPPO RTPRO CEDUAL/ANCILLARY / DIAG NO STICACUTE INPATIENTAM BULATO RYLO NG TERMADM INISTRATIO N/SUPPO RTPRO CEDUAL/ANCILLARY / DIAG NO STICM ENTAL HEALTHACUTE INPATIENTAM BULATO RYM ENTAL HEALTH
005B
CLASSROOM
005B
004A
CLASSROOM
004A
003B
CLASSROOM
003B
006B
BREAK
006B
001E
001E
001E
001-2
CORRIDOR
001-2
TOILET (F)
TOILET
(M)
176 001B
ELEC
001B
001C
STOR.
001C
NORTH
STAIR
NORTH
002A
CLASSROOM
002A
OFFICE
GFEDCB
A
001D
OFFICE
001D
001A
OFFICE
001A
004B
CLASSROOM
004B
005A
CLASSROOM
005A
003A
CLASSROOM
003A
002B
CLASSROOM
002B
REQUIRED AUDIBILITY LEGEND
54dB AMBIENT SPL 69dB EXPECTED SPL
30dB AMBIENT SPL 45dB EXPECTED SPL
(STORAGE OCCUPANCIES)
(BUSINESS OCCUPANCIES)
60dB AMBIENT SPL 75dB EXPECTED SPL
45dB AMBIENT SPL 60dB EXPECTED SPL
(EDUCATIONAL OCCUPANCIES)
(ASSEMBLY OCCUPANCIES)
TRAILER
LOT
B61 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
KS
KS
ARCH REG. NO.
ENGR REG. NO.
EXP. 12/31/2021
EXP. 12/31/2021
A-930, E-2586, CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
PLUMBING ENGINEER
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8650 ROBERT J. DOLE VA MEDICAL CENTER
SPUR #: 1794.08
/2
/2
:1 :2
P
M
B61, GROUND LEVEL - FIRE ALARM
AUDIBILITY PLAN
SAB 61BLS
ISSUED FOR CONSTRUCTION
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
ADMINISTRATIVE SPACE
01/28/2021
589A7-21-702
5500 EAST KELLOGG AVENUE
WICHITA, KANSAS 67218
FA101
N
1/8" = 1'-0"
FIRE ALARM AUDIBILITY PLAN - GROUND LEVEL1
KEYPLAN
LO NG TERMADM INISTRATIO N/SUPPO RTPRO CEDUAL/ANCILLARY / DIAG NO STICACUTE INPATIENTAM BULATO RYLO NG TERMADM INISTRATIO N/SUPPO RTPRO CEDUAL/ANCILLARY / DIAG NO STICM ENTAL HEALTHACUTE INPATIENTAM BULATO RYM ENTAL HEALTH
GFEDC
CLASSROOM
CONFERENCE
CORRIDOR
106A
CLASSROOM
106A
106B
CLASSROOM
106B
107A
CLASSROOM
107A
107B
CLASSROOM
107B
CLASSROOM
REQUIRED AUDIBILITY LEGEND
54dB AMBIENT SPL 69dB EXPECTED SPL
30dB AMBIENT SPL 45dB EXPECTED SPL
(STORAGE OCCUPANCIES)
(BUSINESS OCCUPANCIES)
60dB AMBIENT SPL 75dB EXPECTED SPL
45dB AMBIENT SPL 60dB EXPECTED SPL
(EDUCATIONAL OCCUPANCIES)
(ASSEMBLY OCCUPANCIES)
TRAILER
LOT
B61 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
KS
KS
ARCH REG. NO.
ENGR REG. NO.
EXP. 12/31/2021
EXP. 12/31/2021
A-930, E-2586, CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
PLUMBING ENGINEER
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8650 ROBERT J. DOLE VA MEDICAL CENTER
SPUR #: 1794.08
/2
/2
:1 :2
P
M
B61, LEVEL 1 - FIRE ALARM AUDIBILITY PLAN
SAB 61BLS
ISSUED FOR CONSTRUCTION
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
ADMINISTRATIVE SPACE
01/28/2021
589A7-21-702
5500 EAST KELLOGG AVENUE
WICHITA, KANSAS 67218
FA102
N
1/8" = 1'-0"
FIRE ALARM AUDIBILITY PLAN - LEVEL 11
KEYPLAN
.5
W c d
.5
W c d
.2
W c d
.2
W c d
0.25W15cd
0.5W 75cd0.5W 15cd
0.25W75cd0.25W75cd
0.5W 30cd
0.5W 15cd
0.5W15cd
0.25W 15cd
.5
W c d
.5
W c d
.5
W c d
.5
W c d
.5
W c d
.5
W c d
S
.5
W
S
.5
W
S
.5
W
S
.5
W
S
.5
W
S
.5
W
0.5W75cd
S
.2
W
0.25W75cd
F
LO NG TERMADM INISTRATIO N/SUPPO RTPRO CEDUAL/ANCILLARY / DIAG NO STICACUTE INPATIENTAM BULATO RYLO NG TERMADM INISTRATIO N/SUPPO RTPRO CEDUAL/ANCILLARY / DIAG NO STICM ENTAL HEALTHACUTE INPATIENTAM BULATO RYM ENTAL HEALTH
005B
CLASSROOM
005B
004A
CLASSROOM
004A
003B
CLASSROOM
003B
006B
BREAK
006B
001E
001E
001E
001-2
CORRIDOR
001-2
TOILET (F)
TOILET
(M)
001B
ELEC
001B
001C
STOR.
001C
NORTH
STAIR
NORTH
002A
CLASSROOM
002A
OFFICE
GFEDCB
A
001A
OFFICE
001A
001D
OFFICE
001D
005A
CLASSROOM
005A
004B
CLASSROOM
004B
002B
CLASSROOM
002B s
AHU-01
003A
CLASSROOM
003A
001-2
CORRIDOR
001-2
TRAILER
LOT
B61 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
KS
KS
ARCH REG. NO.
ENGR REG. NO.
EXP. 12/31/2021
EXP. 12/31/2021
A-930, E-2586, CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
PLUMBING ENGINEER
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8650 ROBERT J. DOLE VA MEDICAL CENTER
SPUR #: 1794.08
/2
/2
:1 :2
P
M
B61, GROUND LEVEL - FIRE ALARM PLAN
SAB 61BLS
ISSUED FOR CONSTRUCTION
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
ADMINISTRATIVE SPACE
01/28/2021
589A7-21-702
5500 EAST KELLOGG AVENUE
WICHITA, KANSAS 67218
FA103
N
1/8" = 1'-0"
FIRE ALARM PLAN - GROUND LEVEL1
KEYPLAN
SHEET KEYNOTES
MARK KEYNOTE
1 THE ONLY SOW OF THIS AREA IS ADDING DUCT SMOKE
DETECTION TO THE NEW AHU. FIRE ALARM CONTRACTOR TO
COORDINATE WITH MECHANICAL CONTRACTOR ON FINAL
LOCATION. CONTRACTOR TO REFERENCE MECHANICAL
DRAWINGS FOR ANY ADDITIONAL INFORMATION.
LO NG TERMADM INISTRATIO N/SUPPO RTPRO CEDUAL/ANCILLARY / DIAG NO STICACUTE INPATIENTAM BULATO RYLO NG TERMADM INISTRATIO N/SUPPO RTPRO CEDUAL/ANCILLARY / DIAG NO STICM ENTAL HEALTHACUTE INPATIENTAM BULATO RYM ENTAL HEALTH
.5
W c d
0.5W 30cd
0.25W15cd
.2
W c d
.5
W c d
S
.5
W
.5
W c d
S
.5
W
.5
W c d
S
.5
W
.5
W c d
S
.5
W
.5
W c d
S
.5
W
TRAILER
LOT
B61
GFEDC
CLASSROOM
CONFERENCE
CORRIDOR
106A
CLASSROOM
106A
106B
CLASSROOM
106B
107A
CLASSROOM
107A
107B
CLASSROOM
107B
CLASSROOM
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
KS
KS
ARCH REG. NO.
ENGR REG. NO.
EXP. 12/31/2021
EXP. 12/31/2021
A-930, E-2586, CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
PLUMBING ENGINEER
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8650 ROBERT J. DOLE VA MEDICAL CENTER
SPUR #: 1794.08
/2
/2
:1 :2
P
M
B61, LEVEL 1 - FIRE ALARM PLAN
SAB 61BLS
ISSUED FOR CONSTRUCTION
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
ADMINISTRATIVE SPACE
01/28/2021
589A7-21-702
5500 EAST KELLOGG AVENUE
WICHITA, KANSAS 67218
FA104
KEYPLAN
N
1/8" = 1'-0"
FIRE ALARM PLAN - LEVEL 11
LO NG TERMADM INISTRATIO N/SUPPO RTPRO CEDUAL/ANCILLARY / DIAG NO STICACUTE INPATIENTAM BULATO RYLO NG TERMADM INISTRATIO N/SUPPO RTPRO CEDUAL/ANCILLARY / DIAG NO STICM ENTAL HEALTHACUTE INPATIENTAM BULATO RYM ENTAL HEALTH
HAZARD CLASSIFICATION LEGEND
OUT OF SCOPE AREA
FIRE SUPPRESSION GENERAL NOTES:
LIGHT HAZARD
(0.10 GPM/FT² OVER 1,500 FT² WITH
100 GPM EXTERIOR HOSE DEMAND)
1. THE DESIGN AND INSTALLATION OF THE FIRE PROTECTION, FIRE
SUPPRESSION SYSTEM MUST BE IN ACCORDANCE WITH U.S.
DEPARTMENT OF VETERANS AFFAIRS FIRE PROTECTION DESIGN
MANUAL, EIGHTH EDITION, JUNE 2021; NFPA 13: STANDARD FOR
THE INSTALLATION OF SPRINKLER SYSTEMS, 2022 EDITION.
2. THIS INFORMATION HAS BEEN PREPARED TO PROVIDE GUIDANCE
FOR BIDDING. THE FIRE PROTECTION CONTRACTOR SHALL BE
FULLY RESPONSIBLE FOR PROVIDING A COMPLETE AND FULLY
OPERABLE SYSTEM WHICH SHALL BE IN STRICT ACCORDANCE
WITH PROJECT SPECIFICATIONS AND APPLICABLE CODES AND
STANDARDS. THE WORK THAT IS INDICATED IN THIS DOCUMENT IS
AN OVERVIEW OF THE PROJECT, INTENDED TO ESTABLISH THE
MINIMUM SCOPE REQUIREMENTS FOR THE PROJECT AS WELL AS
THE CONTRACTOR’S RESPONSIBILITIES. THE CONTRACTOR SHALL
SUBMIT A COMPLETE SET OF WORKING DRAWINGS, EQUIPMENT,
AND CALCULATIONS TO THE OWNER’S REPRESENTATIVE AND AHJ
FOR REVIEW AND APPROVAL PRIOR TO FABRICATION AND
INSTALLATION WITH THEIR ENGINEERS SEAL. UNLESS
SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR SHALL
PERFORM ALL ACCEPTANCE TESTING IN ACCORDANCE WITH THE
APPLICABLE DESIGN CRITERIA AND THE EQUIPMENT
MANUFACTURER'S INSTRUCTIONS.
3. SPRINKLER CONTRACTOR SHALL COORDINATE LOCATIONS OF
FIRE PROTECTION COMPONENTS INCLUDING PIPING, ALARMS,
DRAINS, SPRINKLERS, TEST POINTS, ETC., WITH ALL
ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL
COMPONENTS. OBSTRUCTIONS TO SPRINKLER DISCHARGE
SHALL BE CONSIDERED DURING INSTALLATION. DO NOT INSTALL
SPRINKLER PIPING BELOW EQUIPMENT OR WITHIN CLEARANCE
SPACES FOR MECHANICAL AND ELECTRICAL EQUIPMENT.
SPRINKLERS SHALL BE INSTALLED UNDER OBSTRUCTIONS IN
ACCORDANCE WITH NFPA 13.
4. MATERIALS AND ACCESSORIES NECESSARY MUST BE INSTALLED
IN ACCORDANCE WITH THE APPLICABLE NFPA CODES AND
STANDARDS, PROJECT SPECIFICATIONS, AND BE UL LISTED OR FM
APPROVED FOR FIRE PROTECTION USE, UNLESS OTHERWISE
NOTED.
5. ALL VALVES INSIDE TO BE PROVIDED WITH ELECTRONIC TAMPER
SWITCHES WIRED TO THE FACU. VALVES IN NORMAL CLOSED
POSITION SHALL BE PROVIDED WITH TAMPER TO ACTIVATE IN
THREE TURNS OR LESS. ALL VALVES OUTSIDE TO BE
ELECTRONICALLY MONITORED BY FIRE ALARM.
6. ALL HANGERS MUST BE PROVIDED AND INSTALLED IN
ACCORDANCE WITH NFPA 13 AND PROJECT SPECIFICATIONS.
7. LOCATION AND INSTALLATION OF PIPE SUPPORTS (HANGERS,
VERTICAL RESTRAINTS, AND GUIDES) SHALL MEET THE
REQUIREMENTS OF NFPA 13 AND THE SPECIAL LISTING
REQUIREMENTS (IF APPLICABLE) OF THE PIPE AND SUPPORTS.
THE SEISMIC DESIGN CATEGORY FOR THIS PROJECT IS D, PLEASE
REFER TO THE STRUCTURAL DESIGN SHEETS FOR MORE
INFORMATION.
8. THE INSPECTOR'S TEST VALVES MUST BE LOCATED NO MORE
THAN 7 FEET AFF.
9. APPLICABLE UL CONSTRUCTION DETAILS AND SYSTEMS SHALL BE
USED WHERE FIRE RATED BARRIERS ARE PENETRATED BY
SPRINKLER PIPING.
10. ALL VALVES (DRAINS, INSPECTOR'S TEST, CONTROL) MUST BE
IDENTIFIED AS REQUIRED BY NFPA 13.
11. PIPING MUST BE ARRANGED FOR FLUSHING. READILY REMOVABLE
FITTINGS MUST BE PROVIDED AT THE END OF ALL CROSS MAINS.
12. ALL PENDENT SPRINKLERS MUST BE INSTALLED IN THE CENTER
OF THE CEILING TILES.
13. DRAINS MUST BE LOCATED TO PROVIDE DRAINAGE IN
ACCORDANCE WITH NFPA 13. ALL DRAINS AND TEST
CONNECTIONS MUST DISCHARGE TO THE EXTERIOR OF THE
BUILDING ON TO A SPLASH BLOCK OR PAVEMENT, AND SHALL NOT
DISCHARGE ACROSS PATHS OF EGRESS.
14. ALL SPRINKLER SYSTEM ALARM INITIATING AND SUPERVISORY
DEVICES MUST BE CONNECTED TO THE FIRE ALARM SYSTEM.
15. ADDITIONAL SPRINKLERS MAY BE REQUIRED UNDER DUCT WORK
TO PROVIDE ADEQUATE COVERAGE PER NFPA 13.
16. A LISTED RELIEF VALVE MUST BE PROVIDED IN ACCORDANCE
WITH NFPA 13, SECTION 8.1.2 FOR THE SPRINKLER SYSTEM.
17. AN AIR VENT MUST BE PROVIDED IN ACCORDANCE WITH NFPA 13,
SECTION 8.1.5 AND SECTION 16.7 FOR THE SPRINKLER SYSTEM.
18. THIS BUILDING WILL HAVE A WET PIPE AUTOMATIC SPRINKLER
SYSTEM WHICH WILL REQUIRE ALL AREAS OF THE BUILDING TO
BE MAINTAINED ABOVE 40 DEGREES F.
19. PROVIDE SPRINKLER PROTECTION WITHIN ALL COMBUSTIBLE
CONCEALED SPACES.
ORDINARY HAZARD 2
(0.20 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
005B
CLASSROOM
005B
004A
CLASSROOM
004A
003B
CLASSROOM
003B
006B
BREAK
006B
001E
001E
001E
001-2
CORRIDOR
001-2
TOILET (F)
TOILET
(M)
176 001B
ELEC
001B
001C
STOR.
001C
NORTH
STAIR
NORTH
002A
CLASSROOM
002A
OFFICE
GFEDCB
A
001D
OFFICE
001D
001A
OFFICE
001A
004B
CLASSROOM
004B
005A
CLASSROOM
005A
003A
CLASSROOM
003A
002B
CLASSROOM
002B
TRAILER
LOT
B61 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
KS
KS
ARCH REG. NO.
ENGR REG. NO.
EXP. 12/31/2021
EXP. 12/31/2021
A-930, E-2586, CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
PLUMBING ENGINEER
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8650 ROBERT J. DOLE VA MEDICAL CENTER
SPUR #: 1794.08
/2
/2
:1 :2
P
M
B61, GROUND LEVEL - FIRE SUPPRESSION
HAZARD CLASSIFICATION PLAN
SAB 61BLS
ISSUED FOR CONSTRUCTION
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
ADMINISTRATIVE SPACE
01/28/2021
589A7-21-702
5500 EAST KELLOGG AVENUE
WICHITA, KANSAS 67218
FX101
N
1/8" = 1'-0"
FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN - GROUND LEVEL1
KEYPLAN
LO NG TERMADM INISTRATIO N/SUPPO RTPRO CEDUAL/ANCILLARY / DIAG NO STICACUTE INPATIENTAM BULATO RYLO NG TERMADM INISTRATIO N/SUPPO RTPRO CEDUAL/ANCILLARY / DIAG NO STICM ENTAL HEALTHACUTE INPATIENTAM BULATO RYM ENTAL HEALTH
GFEDC
CLASSROOM
CONFERENCE
CORRIDOR
106A
CLASSROOM
106A
106B
CLASSROOM
106B
107A
CLASSROOM
107A
107B
CLASSROOM
107B
CLASSROOM
HAZARD CLASSIFICATION LEGEND
OUT OF SCOPE AREA
FIRE SUPPRESSION GENERAL NOTES:
LIGHT HAZARD
(0.10 GPM/FT² OVER 1,500 FT² WITH
100 GPM EXTERIOR HOSE DEMAND)
1. THE DESIGN AND INSTALLATION OF THE FIRE PROTECTION, FIRE
SUPPRESSION SYSTEM MUST BE IN ACCORDANCE WITH U.S.
DEPARTMENT OF VETERANS AFFAIRS FIRE PROTECTION DESIGN
MANUAL, EIGHTH EDITION, JUNE 2021; NFPA 13: STANDARD FOR
THE INSTALLATION OF SPRINKLER SYSTEMS, 2022 EDITION.
2. THIS INFORMATION HAS BEEN PREPARED TO PROVIDE GUIDANCE
FOR BIDDING. THE FIRE PROTECTION CONTRACTOR SHALL BE
FULLY RESPONSIBLE FOR PROVIDING A COMPLETE AND FULLY
OPERABLE SYSTEM WHICH SHALL BE IN STRICT ACCORDANCE
WITH PROJECT SPECIFICATIONS AND APPLICABLE CODES AND
STANDARDS. THE WORK THAT IS INDICATED IN THIS DOCUMENT IS
AN OVERVIEW OF THE PROJECT, INTENDED TO ESTABLISH THE
MINIMUM SCOPE REQUIREMENTS FOR THE PROJECT AS WELL AS
THE CONTRACTOR’S RESPONSIBILITIES. THE CONTRACTOR SHALL
SUBMIT A COMPLETE SET OF WORKING DRAWINGS, EQUIPMENT,
AND CALCULATIONS TO THE OWNER’S REPRESENTATIVE AND AHJ
FOR REVIEW AND APPROVAL PRIOR TO FABRICATION AND
INSTALLATION WITH THEIR ENGINEERS SEAL. UNLESS
SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR SHALL
PERFORM ALL ACCEPTANCE TESTING IN ACCORDANCE WITH THE
APPLICABLE DESIGN CRITERIA AND THE EQUIPMENT
MANUFACTURER'S INSTRUCTIONS.
3. SPRINKLER CONTRACTOR SHALL COORDINATE LOCATIONS OF
FIRE PROTECTION COMPONENTS INCLUDING PIPING, ALARMS,
DRAINS, SPRINKLERS, TEST POINTS, ETC., WITH ALL
ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL
COMPONENTS. OBSTRUCTIONS TO SPRINKLER DISCHARGE
SHALL BE CONSIDERED DURING INSTALLATION. DO NOT INSTALL
SPRINKLER PIPING BELOW EQUIPMENT OR WITHIN CLEARANCE
SPACES FOR MECHANICAL AND ELECTRICAL EQUIPMENT.
SPRINKLERS SHALL BE INSTALLED UNDER OBSTRUCTIONS IN
ACCORDANCE WITH NFPA 13.
4. MATERIALS AND ACCESSORIES NECESSARY MUST BE INSTALLED
IN ACCORDANCE WITH THE APPLICABLE NFPA CODES AND
STANDARDS, PROJECT SPECIFICATIONS, AND BE UL LISTED OR FM
APPROVED FOR FIRE PROTECTION USE, UNLESS OTHERWISE
NOTED.
5. ALL VALVES INSIDE TO BE PROVIDED WITH ELECTRONIC TAMPER
SWITCHES WIRED TO THE FACU. VALVES IN NORMAL CLOSED
POSITION SHALL BE PROVIDED WITH TAMPER TO ACTIVATE IN
THREE TURNS OR LESS. ALL VALVES OUTSIDE TO BE
ELECTRONICALLY MONITORED BY FIRE ALARM.
6. ALL HANGERS MUST BE PROVIDED AND INSTALLED IN
ACCORDANCE WITH NFPA 13 AND PROJECT SPECIFICATIONS.
7. LOCATION AND INSTALLATION OF PIPE SUPPORTS (HANGERS,
VERTICAL RESTRAINTS, AND GUIDES) SHALL MEET THE
REQUIREMENTS OF NFPA 13 AND THE SPECIAL LISTING
REQUIREMENTS (IF APPLICABLE) OF THE PIPE AND SUPPORTS.
THE SEISMIC DESIGN CATEGORY FOR THIS PROJECT IS D, PLEASE
REFER TO THE STRUCTURAL DESIGN SHEETS FOR MORE
INFORMATION.
8. THE INSPECTOR'S TEST VALVES MUST BE LOCATED NO MORE
THAN 7 FEET AFF.
9. APPLICABLE UL CONSTRUCTION DETAILS AND SYSTEMS SHALL BE
USED WHERE FIRE RATED BARRIERS ARE PENETRATED BY
SPRINKLER PIPING.
10. ALL VALVES (DRAINS, INSPECTOR'S TEST, CONTROL) MUST BE
IDENTIFIED AS REQUIRED BY NFPA 13.
11. PIPING MUST BE ARRANGED FOR FLUSHING. READILY REMOVABLE
FITTINGS MUST BE PROVIDED AT THE END OF ALL CROSS MAINS.
12. ALL PENDENT SPRINKLERS MUST BE INSTALLED IN THE CENTER
OF THE CEILING TILES.
13. DRAINS MUST BE LOCATED TO PROVIDE DRAINAGE IN
ACCORDANCE WITH NFPA 13. ALL DRAINS AND TEST
CONNECTIONS MUST DISCHARGE TO THE EXTERIOR OF THE
BUILDING ON TO A SPLASH BLOCK OR PAVEMENT, AND SHALL NOT
DISCHARGE ACROSS PATHS OF EGRESS.
14. ALL SPRINKLER SYSTEM ALARM INITIATING AND SUPERVISORY
DEVICES MUST BE CONNECTED TO THE FIRE ALARM SYSTEM.
15. ADDITIONAL SPRINKLERS MAY BE REQUIRED UNDER DUCT WORK
TO PROVIDE ADEQUATE COVERAGE PER NFPA 13.
16. A LISTED RELIEF VALVE MUST BE PROVIDED IN ACCORDANCE
WITH NFPA 13, SECTION 8.1.2 FOR THE SPRINKLER SYSTEM.
17. AN AIR VENT MUST BE PROVIDED IN ACCORDANCE WITH NFPA 13,
SECTION 8.1.5 AND SECTION 16.7 FOR THE SPRINKLER SYSTEM.
18. THIS BUILDING WILL HAVE A WET PIPE AUTOMATIC SPRINKLER
SYSTEM WHICH WILL REQUIRE ALL AREAS OF THE BUILDING TO
BE MAINTAINED ABOVE 40 DEGREES F.
19. PROVIDE SPRINKLER PROTECTION WITHIN ALL COMBUSTIBLE
CONCEALED SPACES.
ORDINARY HAZARD 2
(0.20 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
TRAILER
LOT
B61 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
KS
KS
ARCH REG. NO.
ENGR REG. NO.
EXP. 12/31/2021
EXP. 12/31/2021
A-930, E-2586, CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
PLUMBING ENGINEER
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8650 ROBERT J. DOLE VA MEDICAL CENTER
SPUR #: 1794.08
/2
/2
:1 :2
P
M
B61, LEVEL 1 - FIRE SUPPRESSION HAZARD
CLASSIFICATION PLAN
SAB 61BLS
ISSUED FOR CONSTRUCTION
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
ADMINISTRATIVE SPACE
01/28/2021
589A7-21-702
5500 EAST KELLOGG AVENUE
WICHITA, KANSAS 67218
FX102
N
1/8" = 1'-0"
FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN - LEVEL 11
KEYPLAN
| 33_FA001_FIRE ALARM GENERAL NOTES, LEGEND, AND DIAGRAMS |
| 34_FA101_B61, GROUND LEVEL -FIRE ALARM AUDIBILITY PLAN |
| 35_FA102_B61, LEVEL 1 -FIRE ALARM AUDIBILITY PLAN |
| 36_FA103_B61, GROUND LEVEL -FIRE ALARM PLAN |
| 37_FA104_B61, LEVEL 1 -FIRE ALARM PLAN |
| 38_FX101_B61, GROUND LEVEL -FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN |
| 39_FX102_B61, LEVEL 1 -FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN |
File details come from the government source that posted it. Updated .