4 of 8 - 589A7-21-702 Fire Dwgs.pdf

PDF 2 MB Posted

Attached to
Y1DA--589A7-21-702 EHRM Training and Admin Support Space (TASS) Construction - Wichita, KS
Solicitation number
36C77622B0033
Issued by

About this file

This package includes construction drawings and specifications for a fire alarm and fire suppression system renovation project at the Robert J. Dole VA Medical Center in Wichita, Kansas. The drawings show the design and locations for new and existing fire alarm devices, speakers, strobes, and detectors on the ground level and first floor of Building 61. Specifications require upgrading the fire alarm system to current codes and standards, including adding duct smoke detectors. The fire suppression drawings classify hazard levels and note the wet pipe sprinkler system must maintain temperatures above 40 degrees Fahrenheit. Modifications include relocating valves and installing sprinkler heads in concealed spaces.

View the file

Other files

File Type Posted
36C77622B0033 0006.pdf PDF
Tech Questions - Wichita TASS - 7-19-22.pdf PDF
Geotech Report - Wichita.pdf PDF
36C77622B0033 0005.pdf PDF
61_E-600_ADD1.pdf PDF
61_M-601-MECHANICAL SCHEDULES_ADD1.pdf PDF
DBA Wage Rates - Sedgwick County - 07-08-22.pdf PDF
Tech Questions - Wichita TASS - 7-14-22.pdf PDF
36C77622B0033 0004.pdf PDF
Spec Section 23 73 00_ADD1.pdf PDF
61_ES100_ADD1.pdf PDF
36C77622B0033 0003.pdf PDF
36C77622B0033 0002.pdf PDF
DBA Wage Rates - Sedgwick County - 06-17-22.pdf PDF
36C77622B0033 0001.pdf PDF
DBA Wage Rates - Sedgwick County - 06-03-22.pdf PDF
Pre-Bid Site Visit Sign-in Sheet - Wichita TASS.pdf PDF
V02 589A7-21-702 IFC Specifications.pdf PDF
1 of 8 - 589A7-21-702 General Dwgs.pdf PDF
V01 589A7-21-702 IFC Specifications.pdf PDF
8 of 8 - 589A7-21-702 Tech Dwgs.pdf PDF
Infection Control Risk Assessment.pdf PDF
589A7-21-702 Project Narratives.pdf PDF
5 of 8 - 589A7-21-702 Plumbing Dwgs.pdf PDF
3 of 8 - 589A7-21-702 Arch Dwgs.pdf PDF
2a of 8 - 589A7-21-702 Civil Dwgs.pdf PDF
2b of 8 - 589A7-21-702 Civil Dwgs.pdf PDF
6 of 8 - 589A7-21-702 Mech Dwgs.pdf PDF
Limitations on Subcontracting.docx DOCX document
Contractor Safety and Environmental Form.docx DOCX document
VHA Supp Contract Reqs COVID-19 - 12-14-21.pdf PDF
Wichita IFB 36C77622B0033 - 6-2-22.pdf PDF
DBA Wage Rates - Sedgwick County - 04-08-22.pdf PDF
7 of 8 - 589A7-21-702 Elec Dwgs.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FIRE ALARM LEGEND

WF EXISTING WATERFLOW DEVICE

OUT OF SCOPE AREA

VS EXISTING VALVE SUPERVISORY SWITCH

AIM EXISTING ADDRESSABLE INPUT MODULE

FIRE ALARM GENERAL NOTES

SPD EXISTING SURGE PROTECTIVE DEVICE

FACU EXISTING FIRE ALARM CONTROL UNIT

S EXISTING SMOKE DETECTOR - SPOT TYPE

NEW SPEAKER STROBE

S NEW SPEAKER

SYMBOL MODIFIERS

ncd CANDELA RATING

GENERAL:

1. THE CONTRACTOR SHALL CAREFULLY REVIEW ALL APPLICABLE

DESIGN CRITERIA, THESE DRAWINGS, AND THE PROJECT

SPECIFICATIONS FOR IMPORTANT QUALIFICATION, DEFINITION,

SUBMITTAL, PRODUCT, INSTALLATION, AND TESTING

REQUIREMENTS.

2. ALL SUBMITTALS, INSTALLATION, AND TESTING SHALL BE

COMPLETED IN A NEAT, WORKMAN-LIKE MANNER.

3. PRODUCT, DESIGN, INSTALLATION, AND TESTING ALTERNATE

APPROACHES AND/OR SUBSTITUTIONS WILL BE CONSIDERED BY THE

ENGINEER IF THE CONTRACTOR PROVIDES WRITTEN, WELL-

DOCUMENTED, ENGINEERING-BASED SUBSTANTIATION FOR

PROPOSED ALTERNATIVE.

APPLICABLE CODES AND STANDARDS:

1. VA FIRE PROTECTION DESIGN MANUAL EIGHTH EDITION - JUNE 2021

2. NFPA 70 NATIONAL ELECTRIC CODE (2020)

3. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE (2022)

4. NFPA 101 (2021)

5. INTERNATIONAL BUILDING CODE (2021)

AUDIBILITY AND INTELLIGIBILITY DESIGN:

1. BECAUSE OF UNPREDICTABLE BACKGROUND NOISES AND PROJECT

CONDITIONS, THE AUDIBILITY DESIGN GOALS SHALL BE CONFIRMED

BY MEASUREMENT WITH CALIBRATED TEST EQUIPMENT. IF RESULTS

INDICATE THAT ADDITIONAL NOTIFICATION APPLIANCES ARE

REQUIRED, THE CONTRACTOR SHALL ADD THEM AT NO ADDITIONAL

COST.

2. SPEAKERS MAY BE FIELD-LOCATED WITHIN 6 FT OF THE LOCATION

INDICATED ON THE APPROVED DESIGN WITHOUT CONSULTING THE

ENGINEER.

3. INTELLIGIBILITY OF THE OCCUPANT NOTIFICATION SHALL BE TESTED

IN ACCORDANCE WITH NFPA 72 AND THE VA FIRE PROTECTION

DESIGN MANUAL. QUALITATIVE TESTING IS ALLOWED. ALL SCOPE OF

WORK AREAS ARE REQUIRED TO HAVE A CIS SCORE OF 0.65.

VISUAL NOTIFICATION DESIGN:

1. CLEAR STROBES SHALL BE PROVIDED WHERE INDICATED ON THE

APPROVED DESIGN.

2. STROBES MAY BE FIELD-LOCATED WITHIN 3 FT OF THE LOCATION

INDICATED ON THE APPROVED DESIGN WITHOUT CONSULTING THE

ENGINEER. CONSULT WITH ENGINEER PRIOR TO RELOCATING

STROBES MORE THAN 3 FT.

3. PER DIRECTION FROM THE VA, STROBES ARE NOT REQUIRED IN

INDIVIDUAL OFFICES UP TO 750 SQUARE FEET. STROBES ARE ALSO

NOT REQUIRED IN THE SAME OFFICE SPACES IF THERE ARE MORE

THAN ONE DESK/PERSON OCCUPYING THE OFFICE.

INITIATING DEVICES:

1. INITIATING DEVICES MAY BE FIELD-LOCATED WITHIN 3 FT OF THE

LOCATION INDICATED ON THE APPROVED DESIGN WITHOUT

CONSULTING THE ENGINEER. CONSULT WITH ENGINEER PRIOR TO

RELOCATING INITIATING DEVICES MORE THAN 3 FT.

CIRCUITS AND CONDUIT:

1. ALL CIRCUITS SHALL BE PROVIDED IN CONDUIT IN ACCORDANCE

WITH NFPA 70 AND THE CONDUIT LISTING.

2. NEW SIGNALING LINE CIRCUITS AND NOTIFICATION APPLIANCE

CIRCUITS SHALL BE ARRANGED SO THAT A SINGLE FAULT DOES NOT

CAUSE THE LOSS OF ADDRESSABLE DEVICES ON MORE THAN ONE

SMOKE COMPARTMENT.

3. WIRING SHALL BE INSTALLED IN METAL RACEWAY. PER VA DESIGN

MANUAL THIS IN COMBINATION WITH BUILDINGS PROTECTED

THROUGHOUT BY SPRINKLERS SHALL BE CONSIDERED TO MEET THE

REQUIREMENTS FOR PATHWAY SURVIVABILITY LEVEL 2 IN

ACCORDANCE WITH NFPA 72 AND VA AUTHORITY HAVING

JURISDICTION.

4. SPEAKERS AND STROBES SHALL BE ARRANGED TO OPERATE ON

SEPARATE CIRCUITS.

INSTALLATION:

1. ALL EQUIPMENT SHALL BE INSTALLED TIGHT TO THE BUILDING

STRUCTURE AND SHALL BE INSTALLED PARALLEL OR

PERPENDICULAR TO THE BUILDING STRUCTURE UNLESS NOTED

OTHERWISE.

2. THE CONTRACTOR SHALL NOT APPRECIABLY DEVIATE FROM THE

APPROVED DESIGN WITHOUT WRITTEN APPROVAL FROM THE

ENGINEER.

TESTING:

1. UNLESS SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR

SHALL PERFORM ALL ACCEPTANCE TESTING IN ACCORDANCE WITH

THE APPLICABLE DESIGN CRITERIA AND THE EQUIPMENT

MANUFACTURER'S INSTRUCTIONS.

2. UNLESS SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR

SHALL PERFORM TESTING AND PROVIDE DOCUMENTATION PRIOR TO

REQUESTING ENGINEER'S PRESENCE TO WITNESS TESTING.

s NEW SMOKE DETECTOR - DUCT TYPE

NEW FIRE ALARM PULL STATIONF

FACU

SPD

NOTES:

1. TO DEDICATED 120VAC BRANCH CIRCUIT

2. THIS RISER DIAGRAM IS INTENDED ONLY TO CAPTURE THE SYSTEM DESIGN

INTENT, PANEL CONNECTIONS, AND GENERAL CIRCUIT ROUTING REQUIREMENTS.

EXACT QUANTITIES AND TYPES OF DEVICES NECESSARY TO ACCOMPLISH THE

DESIGN GOALS ARE NOT INDICATED. THE INTENT OF THIS RISER DIAGRAM IS TO

INDICATE THE GENERAL SYSTEM CONFIGURATION AFTER SUCCESSFUL

COMPLETION OF THE PROJECT.

GROUND LEVEL

WF VS

AIM AIMS

SS

F s

3 WATERFLOW/PRESSURE SWITCH X X X X X X X X X 3

5 CONTROL VALVE SUPERVISORY SWITCH X X X X 5

12 ANY OTHER SYSTEM TROUBLE X X X X 12

SUPERVISORY CONDITIONS A B C D E F G H I J K L M N

4 SMOKE DETECTOR - DUCT TYPE X X X X X 4

A B C D E F G H I J K L M N

X PERFORM OPERATION/REPORT DEVICE STATUS

NOTE: THIS MATRIX REPRESENTATIVE OF THE SCOPE OF WORK FOR THIS PROJECT.

ALL EXISTING PROGRAMING FOR BUILDING NOT BE MODIFIED UNLESS REQUIRED BY

SOW FOR THIS PROJECT.

SYSTEM OUTPUTS

SYSTEM INPUTS

F A

C U

A N

N U

N C

IA

T

IO

N

A C

T

IV

A T

E C

O M

M O

N A

L A

R M

S

IG

N A

L I

N D

IC

A

T O

R

A C

T

IV

A T

E A

U D

IB

L E

A L A

R M

S

IG

N A

L

A C

T

IV

A T

E C

O M

M O

N S

U P

E R

V

IS

O R

Y S

IG

N

A L I

N D

IC

A

T O

R

A C

T

IV

A T

E A

U D

IB

L E

S U

P E

R V

IS

O

R Y

S

IG

N A

L

A C

T

IV

A T

E C

O M

M O

N T

R O

U B

L E

S

IG

N A

L I

N D

IC

A

T O

R

A C

T

IV

A T

E A

U D

IB

L E

T R

O U

B L E

S

IG

N A

L

D

IS

P L A

Y /P

R

IN

T C

H A

N G

E O

F S

T A

T U

S

N O

T

IF

IC

A

T

IO

N

A C

T

IV

A T

E T

E M

P O

R A

L

A L E

R T

T O

N E

A N

D P

R E

-R E

C O

R D

E D

F

IR

E

V

A C

U A

T

IO

N M

E S

S A

G E

T H

R O

U G

H O

U T

T H

E A

S S

O C

IA

T

E D

Z O

N E

A C

T

IV

A T

E S

T R

O B

E S

T H

R O

U G

H O

U T

T H

E A

S S

O C

IA

T

E D

Z O

N E

A C

T

IV

A T

E P

R E

-R E

C O

R D

E D

S T

A F

F A

L E

R T

M E

S S

A G

E T

H R

O U

G H

O U

T T

H

B

U

IL

D

IN

G

N O

T

IF

Y F

IR

E

D E

P A

R T

M E

N T

/S U

P E

R V

IS

IN

G S

T A

T

IO

N

A U

X

IL

IA

R

Y F

U N

C T

IO

N

S

S H

U T

D O

W N

A S

S O

C

IA

T E

D A

IR

H

A N

D L

IN

G U

N

IT

A C

T

IV

A T

E E

L E

C T

R

IC

A L D

IS

C

O N

N E

C T

O F

E Q

U

IP

M E

N T

I N

I T

E S

P A

C E

S

C L O

S E

S M

O K

E B

A R

R

IE

R D

O O

R S

O N

A S

S O

C

IA

T E

D F

L O

O R

ALARM CONDITIONS A B C D E F G H I J K L M N

1 MANUAL ALARM PULL STATION X X X X X X X X X 1

2 SMOKE DETECTOR - SPOT TYPE X X X X X X X X 2

TROUBLE CONDITIONS A B C D E F G H I J K L M N

6 AC POWER FAILURE X X X X 6

7 LOW BATTERY X X X X 7

8 OPEN CIRCUIT X X X X 8

9 GROUND FAULT X X X X 9

10 NOTIFICATION APPLIANCE CIRCUIT SHORT X X X X 10

11 REMOTE POWER SUPPLY COMMON TROUBLE X X X X 11

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

KS

KS

ARCH REG. NO.

ENGR REG. NO.

EXP. 12/31/2021

EXP. 12/31/2021

A-930, E-2586, CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

PLUMBING ENGINEER

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8650 ROBERT J. DOLE VA MEDICAL CENTER

SPUR #: 1794.08

/2

/2

:1 :2

P

M

FIRE ALARM GENERAL NOTES, LEGEND, AND

DIAGRAMS

SAB 61BLS

ISSUED FOR CONSTRUCTION

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

ADMINISTRATIVE SPACE

01/28/2021

589A7-21-702

5500 EAST KELLOGG AVENUE

WICHITA, KANSAS 67218

FA001

NOT TO SCALE

FACU RISER DIAGRAM1NOT TO SCALE

FACU INPUT/OUTPUT MATRIX2

No. REVISION DESCRIPTION DATE

LO NG TERMADM INISTRATIO N/SUPPO RTPRO CEDUAL/ANCILLARY / DIAG NO STICACUTE INPATIENTAM BULATO RYLO NG TERMADM INISTRATIO N/SUPPO RTPRO CEDUAL/ANCILLARY / DIAG NO STICM ENTAL HEALTHACUTE INPATIENTAM BULATO RYM ENTAL HEALTH

005B

CLASSROOM

005B

004A

CLASSROOM

004A

003B

CLASSROOM

003B

006B

BREAK

006B

001E

001E

001E

001-2

CORRIDOR

001-2

TOILET (F)

TOILET

(M)

176 001B

ELEC

001B

001C

STOR.

001C

NORTH

STAIR

NORTH

002A

CLASSROOM

002A

OFFICE

GFEDCB

A

001D

OFFICE

001D

001A

OFFICE

001A

004B

CLASSROOM

004B

005A

CLASSROOM

005A

003A

CLASSROOM

003A

002B

CLASSROOM

002B

REQUIRED AUDIBILITY LEGEND

54dB AMBIENT SPL 69dB EXPECTED SPL

30dB AMBIENT SPL 45dB EXPECTED SPL

(STORAGE OCCUPANCIES)

(BUSINESS OCCUPANCIES)

60dB AMBIENT SPL 75dB EXPECTED SPL

45dB AMBIENT SPL 60dB EXPECTED SPL

(EDUCATIONAL OCCUPANCIES)

(ASSEMBLY OCCUPANCIES)

TRAILER

LOT

B61 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

KS

KS

ARCH REG. NO.

ENGR REG. NO.

EXP. 12/31/2021

EXP. 12/31/2021

A-930, E-2586, CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

PLUMBING ENGINEER

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8650 ROBERT J. DOLE VA MEDICAL CENTER

SPUR #: 1794.08

/2

/2

:1 :2

P

M

B61, GROUND LEVEL - FIRE ALARM

AUDIBILITY PLAN

SAB 61BLS

ISSUED FOR CONSTRUCTION

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

ADMINISTRATIVE SPACE

01/28/2021

589A7-21-702

5500 EAST KELLOGG AVENUE

WICHITA, KANSAS 67218

FA101

N

1/8" = 1'-0"

FIRE ALARM AUDIBILITY PLAN - GROUND LEVEL1

KEYPLAN

LO NG TERMADM INISTRATIO N/SUPPO RTPRO CEDUAL/ANCILLARY / DIAG NO STICACUTE INPATIENTAM BULATO RYLO NG TERMADM INISTRATIO N/SUPPO RTPRO CEDUAL/ANCILLARY / DIAG NO STICM ENTAL HEALTHACUTE INPATIENTAM BULATO RYM ENTAL HEALTH

GFEDC

CLASSROOM

CONFERENCE

CORRIDOR

106A

CLASSROOM

106A

106B

CLASSROOM

106B

107A

CLASSROOM

107A

107B

CLASSROOM

107B

CLASSROOM

REQUIRED AUDIBILITY LEGEND

54dB AMBIENT SPL 69dB EXPECTED SPL

30dB AMBIENT SPL 45dB EXPECTED SPL

(STORAGE OCCUPANCIES)

(BUSINESS OCCUPANCIES)

60dB AMBIENT SPL 75dB EXPECTED SPL

45dB AMBIENT SPL 60dB EXPECTED SPL

(EDUCATIONAL OCCUPANCIES)

(ASSEMBLY OCCUPANCIES)

TRAILER

LOT

B61 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

KS

KS

ARCH REG. NO.

ENGR REG. NO.

EXP. 12/31/2021

EXP. 12/31/2021

A-930, E-2586, CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

PLUMBING ENGINEER

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8650 ROBERT J. DOLE VA MEDICAL CENTER

SPUR #: 1794.08

/2

/2

:1 :2

P

M

B61, LEVEL 1 - FIRE ALARM AUDIBILITY PLAN

SAB 61BLS

ISSUED FOR CONSTRUCTION

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

ADMINISTRATIVE SPACE

01/28/2021

589A7-21-702

5500 EAST KELLOGG AVENUE

WICHITA, KANSAS 67218

FA102

N

1/8" = 1'-0"

FIRE ALARM AUDIBILITY PLAN - LEVEL 11

KEYPLAN

.5

W c d

.5

W c d

.2

W c d

.2

W c d

0.25W15cd

0.5W 75cd0.5W 15cd

0.25W75cd0.25W75cd

0.5W 30cd

0.5W 15cd

0.5W15cd

0.25W 15cd

.5

W c d

.5

W c d

.5

W c d

.5

W c d

.5

W c d

.5

W c d

S

.5

W

S

.5

W

S

.5

W

S

.5

W

S

.5

W

S

.5

W

0.5W75cd

S

.2

W

0.25W75cd

F

LO NG TERMADM INISTRATIO N/SUPPO RTPRO CEDUAL/ANCILLARY / DIAG NO STICACUTE INPATIENTAM BULATO RYLO NG TERMADM INISTRATIO N/SUPPO RTPRO CEDUAL/ANCILLARY / DIAG NO STICM ENTAL HEALTHACUTE INPATIENTAM BULATO RYM ENTAL HEALTH

005B

CLASSROOM

005B

004A

CLASSROOM

004A

003B

CLASSROOM

003B

006B

BREAK

006B

001E

001E

001E

001-2

CORRIDOR

001-2

TOILET (F)

TOILET

(M)

001B

ELEC

001B

001C

STOR.

001C

NORTH

STAIR

NORTH

002A

CLASSROOM

002A

OFFICE

GFEDCB

A

001A

OFFICE

001A

001D

OFFICE

001D

005A

CLASSROOM

005A

004B

CLASSROOM

004B

002B

CLASSROOM

002B s

AHU-01

003A

CLASSROOM

003A

001-2

CORRIDOR

001-2

TRAILER

LOT

B61 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

KS

KS

ARCH REG. NO.

ENGR REG. NO.

EXP. 12/31/2021

EXP. 12/31/2021

A-930, E-2586, CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

PLUMBING ENGINEER

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8650 ROBERT J. DOLE VA MEDICAL CENTER

SPUR #: 1794.08

/2

/2

:1 :2

P

M

B61, GROUND LEVEL - FIRE ALARM PLAN

SAB 61BLS

ISSUED FOR CONSTRUCTION

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

ADMINISTRATIVE SPACE

01/28/2021

589A7-21-702

5500 EAST KELLOGG AVENUE

WICHITA, KANSAS 67218

FA103

N

1/8" = 1'-0"

FIRE ALARM PLAN - GROUND LEVEL1

KEYPLAN

SHEET KEYNOTES

MARK KEYNOTE

1 THE ONLY SOW OF THIS AREA IS ADDING DUCT SMOKE

DETECTION TO THE NEW AHU. FIRE ALARM CONTRACTOR TO

COORDINATE WITH MECHANICAL CONTRACTOR ON FINAL

LOCATION. CONTRACTOR TO REFERENCE MECHANICAL

DRAWINGS FOR ANY ADDITIONAL INFORMATION.

LO NG TERMADM INISTRATIO N/SUPPO RTPRO CEDUAL/ANCILLARY / DIAG NO STICACUTE INPATIENTAM BULATO RYLO NG TERMADM INISTRATIO N/SUPPO RTPRO CEDUAL/ANCILLARY / DIAG NO STICM ENTAL HEALTHACUTE INPATIENTAM BULATO RYM ENTAL HEALTH

.5

W c d

0.5W 30cd

0.25W15cd

.2

W c d

.5

W c d

S

.5

W

.5

W c d

S

.5

W

.5

W c d

S

.5

W

.5

W c d

S

.5

W

.5

W c d

S

.5

W

TRAILER

LOT

B61

GFEDC

CLASSROOM

CONFERENCE

CORRIDOR

106A

CLASSROOM

106A

106B

CLASSROOM

106B

107A

CLASSROOM

107A

107B

CLASSROOM

107B

CLASSROOM

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

KS

KS

ARCH REG. NO.

ENGR REG. NO.

EXP. 12/31/2021

EXP. 12/31/2021

A-930, E-2586, CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

PLUMBING ENGINEER

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8650 ROBERT J. DOLE VA MEDICAL CENTER

SPUR #: 1794.08

/2

/2

:1 :2

P

M

B61, LEVEL 1 - FIRE ALARM PLAN

SAB 61BLS

ISSUED FOR CONSTRUCTION

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

ADMINISTRATIVE SPACE

01/28/2021

589A7-21-702

5500 EAST KELLOGG AVENUE

WICHITA, KANSAS 67218

FA104

KEYPLAN

N

1/8" = 1'-0"

FIRE ALARM PLAN - LEVEL 11

LO NG TERMADM INISTRATIO N/SUPPO RTPRO CEDUAL/ANCILLARY / DIAG NO STICACUTE INPATIENTAM BULATO RYLO NG TERMADM INISTRATIO N/SUPPO RTPRO CEDUAL/ANCILLARY / DIAG NO STICM ENTAL HEALTHACUTE INPATIENTAM BULATO RYM ENTAL HEALTH

HAZARD CLASSIFICATION LEGEND

OUT OF SCOPE AREA

FIRE SUPPRESSION GENERAL NOTES:

LIGHT HAZARD

(0.10 GPM/FT² OVER 1,500 FT² WITH

100 GPM EXTERIOR HOSE DEMAND)

1. THE DESIGN AND INSTALLATION OF THE FIRE PROTECTION, FIRE

SUPPRESSION SYSTEM MUST BE IN ACCORDANCE WITH U.S.

DEPARTMENT OF VETERANS AFFAIRS FIRE PROTECTION DESIGN

MANUAL, EIGHTH EDITION, JUNE 2021; NFPA 13: STANDARD FOR

THE INSTALLATION OF SPRINKLER SYSTEMS, 2022 EDITION.

2. THIS INFORMATION HAS BEEN PREPARED TO PROVIDE GUIDANCE

FOR BIDDING. THE FIRE PROTECTION CONTRACTOR SHALL BE

FULLY RESPONSIBLE FOR PROVIDING A COMPLETE AND FULLY

OPERABLE SYSTEM WHICH SHALL BE IN STRICT ACCORDANCE

WITH PROJECT SPECIFICATIONS AND APPLICABLE CODES AND

STANDARDS. THE WORK THAT IS INDICATED IN THIS DOCUMENT IS

AN OVERVIEW OF THE PROJECT, INTENDED TO ESTABLISH THE

MINIMUM SCOPE REQUIREMENTS FOR THE PROJECT AS WELL AS

THE CONTRACTOR’S RESPONSIBILITIES. THE CONTRACTOR SHALL

SUBMIT A COMPLETE SET OF WORKING DRAWINGS, EQUIPMENT,

AND CALCULATIONS TO THE OWNER’S REPRESENTATIVE AND AHJ

FOR REVIEW AND APPROVAL PRIOR TO FABRICATION AND

INSTALLATION WITH THEIR ENGINEERS SEAL. UNLESS

SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR SHALL

PERFORM ALL ACCEPTANCE TESTING IN ACCORDANCE WITH THE

APPLICABLE DESIGN CRITERIA AND THE EQUIPMENT

MANUFACTURER'S INSTRUCTIONS.

3. SPRINKLER CONTRACTOR SHALL COORDINATE LOCATIONS OF

FIRE PROTECTION COMPONENTS INCLUDING PIPING, ALARMS,

DRAINS, SPRINKLERS, TEST POINTS, ETC., WITH ALL

ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL

COMPONENTS. OBSTRUCTIONS TO SPRINKLER DISCHARGE

SHALL BE CONSIDERED DURING INSTALLATION. DO NOT INSTALL

SPRINKLER PIPING BELOW EQUIPMENT OR WITHIN CLEARANCE

SPACES FOR MECHANICAL AND ELECTRICAL EQUIPMENT.

SPRINKLERS SHALL BE INSTALLED UNDER OBSTRUCTIONS IN

ACCORDANCE WITH NFPA 13.

4. MATERIALS AND ACCESSORIES NECESSARY MUST BE INSTALLED

IN ACCORDANCE WITH THE APPLICABLE NFPA CODES AND

STANDARDS, PROJECT SPECIFICATIONS, AND BE UL LISTED OR FM

APPROVED FOR FIRE PROTECTION USE, UNLESS OTHERWISE

NOTED.

5. ALL VALVES INSIDE TO BE PROVIDED WITH ELECTRONIC TAMPER

SWITCHES WIRED TO THE FACU. VALVES IN NORMAL CLOSED

POSITION SHALL BE PROVIDED WITH TAMPER TO ACTIVATE IN

THREE TURNS OR LESS. ALL VALVES OUTSIDE TO BE

ELECTRONICALLY MONITORED BY FIRE ALARM.

6. ALL HANGERS MUST BE PROVIDED AND INSTALLED IN

ACCORDANCE WITH NFPA 13 AND PROJECT SPECIFICATIONS.

7. LOCATION AND INSTALLATION OF PIPE SUPPORTS (HANGERS,

VERTICAL RESTRAINTS, AND GUIDES) SHALL MEET THE

REQUIREMENTS OF NFPA 13 AND THE SPECIAL LISTING

REQUIREMENTS (IF APPLICABLE) OF THE PIPE AND SUPPORTS.

THE SEISMIC DESIGN CATEGORY FOR THIS PROJECT IS D, PLEASE

REFER TO THE STRUCTURAL DESIGN SHEETS FOR MORE

INFORMATION.

8. THE INSPECTOR'S TEST VALVES MUST BE LOCATED NO MORE

THAN 7 FEET AFF.

9. APPLICABLE UL CONSTRUCTION DETAILS AND SYSTEMS SHALL BE

USED WHERE FIRE RATED BARRIERS ARE PENETRATED BY

SPRINKLER PIPING.

10. ALL VALVES (DRAINS, INSPECTOR'S TEST, CONTROL) MUST BE

IDENTIFIED AS REQUIRED BY NFPA 13.

11. PIPING MUST BE ARRANGED FOR FLUSHING. READILY REMOVABLE

FITTINGS MUST BE PROVIDED AT THE END OF ALL CROSS MAINS.

12. ALL PENDENT SPRINKLERS MUST BE INSTALLED IN THE CENTER

OF THE CEILING TILES.

13. DRAINS MUST BE LOCATED TO PROVIDE DRAINAGE IN

ACCORDANCE WITH NFPA 13. ALL DRAINS AND TEST

CONNECTIONS MUST DISCHARGE TO THE EXTERIOR OF THE

BUILDING ON TO A SPLASH BLOCK OR PAVEMENT, AND SHALL NOT

DISCHARGE ACROSS PATHS OF EGRESS.

14. ALL SPRINKLER SYSTEM ALARM INITIATING AND SUPERVISORY

DEVICES MUST BE CONNECTED TO THE FIRE ALARM SYSTEM.

15. ADDITIONAL SPRINKLERS MAY BE REQUIRED UNDER DUCT WORK

TO PROVIDE ADEQUATE COVERAGE PER NFPA 13.

16. A LISTED RELIEF VALVE MUST BE PROVIDED IN ACCORDANCE

WITH NFPA 13, SECTION 8.1.2 FOR THE SPRINKLER SYSTEM.

17. AN AIR VENT MUST BE PROVIDED IN ACCORDANCE WITH NFPA 13,

SECTION 8.1.5 AND SECTION 16.7 FOR THE SPRINKLER SYSTEM.

18. THIS BUILDING WILL HAVE A WET PIPE AUTOMATIC SPRINKLER

SYSTEM WHICH WILL REQUIRE ALL AREAS OF THE BUILDING TO

BE MAINTAINED ABOVE 40 DEGREES F.

19. PROVIDE SPRINKLER PROTECTION WITHIN ALL COMBUSTIBLE

CONCEALED SPACES.

ORDINARY HAZARD 2

(0.20 GPM/FT² OVER 1,500 FT² WITH

250 GPM EXTERIOR HOSE DEMAND)

005B

CLASSROOM

005B

004A

CLASSROOM

004A

003B

CLASSROOM

003B

006B

BREAK

006B

001E

001E

001E

001-2

CORRIDOR

001-2

TOILET (F)

TOILET

(M)

176 001B

ELEC

001B

001C

STOR.

001C

NORTH

STAIR

NORTH

002A

CLASSROOM

002A

OFFICE

GFEDCB

A

001D

OFFICE

001D

001A

OFFICE

001A

004B

CLASSROOM

004B

005A

CLASSROOM

005A

003A

CLASSROOM

003A

002B

CLASSROOM

002B

TRAILER

LOT

B61 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

KS

KS

ARCH REG. NO.

ENGR REG. NO.

EXP. 12/31/2021

EXP. 12/31/2021

A-930, E-2586, CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

PLUMBING ENGINEER

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8650 ROBERT J. DOLE VA MEDICAL CENTER

SPUR #: 1794.08

/2

/2

:1 :2

P

M

B61, GROUND LEVEL - FIRE SUPPRESSION

HAZARD CLASSIFICATION PLAN

SAB 61BLS

ISSUED FOR CONSTRUCTION

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

ADMINISTRATIVE SPACE

01/28/2021

589A7-21-702

5500 EAST KELLOGG AVENUE

WICHITA, KANSAS 67218

FX101

N

1/8" = 1'-0"

FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN - GROUND LEVEL1

KEYPLAN

LO NG TERMADM INISTRATIO N/SUPPO RTPRO CEDUAL/ANCILLARY / DIAG NO STICACUTE INPATIENTAM BULATO RYLO NG TERMADM INISTRATIO N/SUPPO RTPRO CEDUAL/ANCILLARY / DIAG NO STICM ENTAL HEALTHACUTE INPATIENTAM BULATO RYM ENTAL HEALTH

GFEDC

CLASSROOM

CONFERENCE

CORRIDOR

106A

CLASSROOM

106A

106B

CLASSROOM

106B

107A

CLASSROOM

107A

107B

CLASSROOM

107B

CLASSROOM

HAZARD CLASSIFICATION LEGEND

OUT OF SCOPE AREA

FIRE SUPPRESSION GENERAL NOTES:

LIGHT HAZARD

(0.10 GPM/FT² OVER 1,500 FT² WITH

100 GPM EXTERIOR HOSE DEMAND)

1. THE DESIGN AND INSTALLATION OF THE FIRE PROTECTION, FIRE

SUPPRESSION SYSTEM MUST BE IN ACCORDANCE WITH U.S.

DEPARTMENT OF VETERANS AFFAIRS FIRE PROTECTION DESIGN

MANUAL, EIGHTH EDITION, JUNE 2021; NFPA 13: STANDARD FOR

THE INSTALLATION OF SPRINKLER SYSTEMS, 2022 EDITION.

2. THIS INFORMATION HAS BEEN PREPARED TO PROVIDE GUIDANCE

FOR BIDDING. THE FIRE PROTECTION CONTRACTOR SHALL BE

FULLY RESPONSIBLE FOR PROVIDING A COMPLETE AND FULLY

OPERABLE SYSTEM WHICH SHALL BE IN STRICT ACCORDANCE

WITH PROJECT SPECIFICATIONS AND APPLICABLE CODES AND

STANDARDS. THE WORK THAT IS INDICATED IN THIS DOCUMENT IS

AN OVERVIEW OF THE PROJECT, INTENDED TO ESTABLISH THE

MINIMUM SCOPE REQUIREMENTS FOR THE PROJECT AS WELL AS

THE CONTRACTOR’S RESPONSIBILITIES. THE CONTRACTOR SHALL

SUBMIT A COMPLETE SET OF WORKING DRAWINGS, EQUIPMENT,

AND CALCULATIONS TO THE OWNER’S REPRESENTATIVE AND AHJ

FOR REVIEW AND APPROVAL PRIOR TO FABRICATION AND

INSTALLATION WITH THEIR ENGINEERS SEAL. UNLESS

SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR SHALL

PERFORM ALL ACCEPTANCE TESTING IN ACCORDANCE WITH THE

APPLICABLE DESIGN CRITERIA AND THE EQUIPMENT

MANUFACTURER'S INSTRUCTIONS.

3. SPRINKLER CONTRACTOR SHALL COORDINATE LOCATIONS OF

FIRE PROTECTION COMPONENTS INCLUDING PIPING, ALARMS,

DRAINS, SPRINKLERS, TEST POINTS, ETC., WITH ALL

ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL

COMPONENTS. OBSTRUCTIONS TO SPRINKLER DISCHARGE

SHALL BE CONSIDERED DURING INSTALLATION. DO NOT INSTALL

SPRINKLER PIPING BELOW EQUIPMENT OR WITHIN CLEARANCE

SPACES FOR MECHANICAL AND ELECTRICAL EQUIPMENT.

SPRINKLERS SHALL BE INSTALLED UNDER OBSTRUCTIONS IN

ACCORDANCE WITH NFPA 13.

4. MATERIALS AND ACCESSORIES NECESSARY MUST BE INSTALLED

IN ACCORDANCE WITH THE APPLICABLE NFPA CODES AND

STANDARDS, PROJECT SPECIFICATIONS, AND BE UL LISTED OR FM

APPROVED FOR FIRE PROTECTION USE, UNLESS OTHERWISE

NOTED.

5. ALL VALVES INSIDE TO BE PROVIDED WITH ELECTRONIC TAMPER

SWITCHES WIRED TO THE FACU. VALVES IN NORMAL CLOSED

POSITION SHALL BE PROVIDED WITH TAMPER TO ACTIVATE IN

THREE TURNS OR LESS. ALL VALVES OUTSIDE TO BE

ELECTRONICALLY MONITORED BY FIRE ALARM.

6. ALL HANGERS MUST BE PROVIDED AND INSTALLED IN

ACCORDANCE WITH NFPA 13 AND PROJECT SPECIFICATIONS.

7. LOCATION AND INSTALLATION OF PIPE SUPPORTS (HANGERS,

VERTICAL RESTRAINTS, AND GUIDES) SHALL MEET THE

REQUIREMENTS OF NFPA 13 AND THE SPECIAL LISTING

REQUIREMENTS (IF APPLICABLE) OF THE PIPE AND SUPPORTS.

THE SEISMIC DESIGN CATEGORY FOR THIS PROJECT IS D, PLEASE

REFER TO THE STRUCTURAL DESIGN SHEETS FOR MORE

INFORMATION.

8. THE INSPECTOR'S TEST VALVES MUST BE LOCATED NO MORE

THAN 7 FEET AFF.

9. APPLICABLE UL CONSTRUCTION DETAILS AND SYSTEMS SHALL BE

USED WHERE FIRE RATED BARRIERS ARE PENETRATED BY

SPRINKLER PIPING.

10. ALL VALVES (DRAINS, INSPECTOR'S TEST, CONTROL) MUST BE

IDENTIFIED AS REQUIRED BY NFPA 13.

11. PIPING MUST BE ARRANGED FOR FLUSHING. READILY REMOVABLE

FITTINGS MUST BE PROVIDED AT THE END OF ALL CROSS MAINS.

12. ALL PENDENT SPRINKLERS MUST BE INSTALLED IN THE CENTER

OF THE CEILING TILES.

13. DRAINS MUST BE LOCATED TO PROVIDE DRAINAGE IN

ACCORDANCE WITH NFPA 13. ALL DRAINS AND TEST

CONNECTIONS MUST DISCHARGE TO THE EXTERIOR OF THE

BUILDING ON TO A SPLASH BLOCK OR PAVEMENT, AND SHALL NOT

DISCHARGE ACROSS PATHS OF EGRESS.

14. ALL SPRINKLER SYSTEM ALARM INITIATING AND SUPERVISORY

DEVICES MUST BE CONNECTED TO THE FIRE ALARM SYSTEM.

15. ADDITIONAL SPRINKLERS MAY BE REQUIRED UNDER DUCT WORK

TO PROVIDE ADEQUATE COVERAGE PER NFPA 13.

16. A LISTED RELIEF VALVE MUST BE PROVIDED IN ACCORDANCE

WITH NFPA 13, SECTION 8.1.2 FOR THE SPRINKLER SYSTEM.

17. AN AIR VENT MUST BE PROVIDED IN ACCORDANCE WITH NFPA 13,

SECTION 8.1.5 AND SECTION 16.7 FOR THE SPRINKLER SYSTEM.

18. THIS BUILDING WILL HAVE A WET PIPE AUTOMATIC SPRINKLER

SYSTEM WHICH WILL REQUIRE ALL AREAS OF THE BUILDING TO

BE MAINTAINED ABOVE 40 DEGREES F.

19. PROVIDE SPRINKLER PROTECTION WITHIN ALL COMBUSTIBLE

CONCEALED SPACES.

ORDINARY HAZARD 2

(0.20 GPM/FT² OVER 1,500 FT² WITH

250 GPM EXTERIOR HOSE DEMAND)

TRAILER

LOT

B61 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

KS

KS

ARCH REG. NO.

ENGR REG. NO.

EXP. 12/31/2021

EXP. 12/31/2021

A-930, E-2586, CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

PLUMBING ENGINEER

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8650 ROBERT J. DOLE VA MEDICAL CENTER

SPUR #: 1794.08

/2

/2

:1 :2

P

M

B61, LEVEL 1 - FIRE SUPPRESSION HAZARD

CLASSIFICATION PLAN

SAB 61BLS

ISSUED FOR CONSTRUCTION

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

ADMINISTRATIVE SPACE

01/28/2021

589A7-21-702

5500 EAST KELLOGG AVENUE

WICHITA, KANSAS 67218

FX102

N

1/8" = 1'-0"

FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN - LEVEL 11

KEYPLAN

33_FA001_FIRE ALARM GENERAL NOTES, LEGEND, AND DIAGRAMS
34_FA101_B61, GROUND LEVEL -FIRE ALARM AUDIBILITY PLAN
35_FA102_B61, LEVEL 1 -FIRE ALARM AUDIBILITY PLAN
36_FA103_B61, GROUND LEVEL -FIRE ALARM PLAN
37_FA104_B61, LEVEL 1 -FIRE ALARM PLAN
38_FX101_B61, GROUND LEVEL -FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN
39_FX102_B61, LEVEL 1 -FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN

File details come from the government source that posted it. Updated .