61_M-601-MECHANICAL SCHEDULES_ADD1.pdf

PDF 743 KB Posted

Attached to
Y1DA--589A7-21-702 EHRM Training and Admin Support Space (TASS) Construction - Wichita, KS
Solicitation number
36C77622B0033
Issued by

About this file

This document contains mechanical schedules and specifications for the EHRM Training and Admin Support Space construction project at the Robert J. Dole VA Medical Center in Wichita, Kansas. The project involves renovations of approximately 12,000 square feet and includes specifications for ductwork, diffusers, variable air volume terminal units, exhaust fans, air handling units, and packaged chillers. Mechanical equipment is to be provided in accordance with the manufacturers and models listed in the schedules. Duct material, pressure class, seal class, and leakage classes are specified for different system types. Performance requirements are outlined for terminal units, fans, air handling units, and chillers.

View the file

Other files

File Type Posted
36C77622B0033 0006.pdf PDF
Tech Questions - Wichita TASS - 7-19-22.pdf PDF
Geotech Report - Wichita.pdf PDF
36C77622B0033 0005.pdf PDF
61_E-600_ADD1.pdf PDF
DBA Wage Rates - Sedgwick County - 07-08-22.pdf PDF
Tech Questions - Wichita TASS - 7-14-22.pdf PDF
36C77622B0033 0004.pdf PDF
Spec Section 23 73 00_ADD1.pdf PDF
61_ES100_ADD1.pdf PDF
36C77622B0033 0003.pdf PDF
36C77622B0033 0002.pdf PDF
DBA Wage Rates - Sedgwick County - 06-17-22.pdf PDF
36C77622B0033 0001.pdf PDF
DBA Wage Rates - Sedgwick County - 06-03-22.pdf PDF
Pre-Bid Site Visit Sign-in Sheet - Wichita TASS.pdf PDF
V02 589A7-21-702 IFC Specifications.pdf PDF
1 of 8 - 589A7-21-702 General Dwgs.pdf PDF
V01 589A7-21-702 IFC Specifications.pdf PDF
8 of 8 - 589A7-21-702 Tech Dwgs.pdf PDF
Infection Control Risk Assessment.pdf PDF
589A7-21-702 Project Narratives.pdf PDF
5 of 8 - 589A7-21-702 Plumbing Dwgs.pdf PDF
3 of 8 - 589A7-21-702 Arch Dwgs.pdf PDF
2a of 8 - 589A7-21-702 Civil Dwgs.pdf PDF
2b of 8 - 589A7-21-702 Civil Dwgs.pdf PDF
6 of 8 - 589A7-21-702 Mech Dwgs.pdf PDF
Limitations on Subcontracting.docx DOCX document
Contractor Safety and Environmental Form.docx DOCX document
VHA Supp Contract Reqs COVID-19 - 12-14-21.pdf PDF
Wichita IFB 36C77622B0033 - 6-2-22.pdf PDF
DBA Wage Rates - Sedgwick County - 04-08-22.pdf PDF
4 of 8 - 589A7-21-702 Fire Dwgs.pdf PDF
7 of 8 - 589A7-21-702 Elec Dwgs.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

KS

KS

ARCH REG. NO.

ENGR REG. NO.

EXP. 12/31/2021

EXP. 12/31/2021

A-930, E-2586, CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

PLUMBING ENGINEER

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8650 ROBERT J. DOLE VA MEDICAL CENTER

SPUR #: 1794.08

/2

/2

:2

:5

P

M

MECHANICAL SCHEDULES

RDC 61 88CSC

ISSUED FOR CONSTRUCTION

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

ADMINISTRATIVE SPACE

01/28/2022

589A7-21-702

5500 EAST KELLOGG AVENUE

WICHITA, KANSAS 67218

M-601

DUCT CONSTRUCTION SCHEDULE

DUCTS CONNECTED TO DUCT MATERIAL PRESSURE

CLASS

SEAL

CLASS

LEAKAGE

CLASS (RECT)

LEAKAGE

CLASS (RND)

SUPPLY

FAN COIL UNITS, FURNACES, HEAT PUMPS, AND TERMINAL UNITS GALVANIZED SHEETMETAL 1 A 16 8

CONSTANT VOLUME AIR HANDLING UNITS GALVANIZED SHEETMETAL 2 A 8 4

VARIABLE AIR VOLUME AIR HANDLING UNITS - MED PRESSURE GALVANIZED SHEETMETAL 3 A 8 4

VARIABLE AIR VOLUME AIR HANDLING UNITS - HIGH PRESSURE GALVANIZED SHEETMETAL 4 A 4 2

EQUIPMENT NOT LISTED GALVANIZED SHEETMETAL 2 A 8 4

OUTSIDE AIR

EQUIPMENT NOT LISTED GALVANIZED SHEETMETAL 1 A 16 8

RETURN

FAN COIL UNITS, FURNACES, HEAT PUMPS, AND TERMINAL UNITS GALVANIZED SHEETMETAL 1 A 16 8

CONSTANT VOLUME AIR HANDLING UNITS GALVANIZED SHEETMETAL 1 A 16 8

VARIABLE AIR VOLUME AIR HANDLING UNITS GALVANIZED SHEETMETAL 2 A 8 4

EQUIPMENT NOT LISTED GALVANIZED SHEETMETAL 1 A 16 8

EXHAUST

GENERAL CLEAN EXHAUST (ASHRAE 62.1 CLASS 1 OR 2) GALVANIZED SHEETMETAL 1 A 16 8

AIR HANDLING UNITS GALVANIZED SHEETMETAL 2 A 8 4

KITCHEN HOODS 304 STAINLESS STEEL 2 A 4 2

DISHWASHER OR HIGH HUMIDITY LOCATIONS 304 STAINLESS STEEL 2 A 4 2

FUME HOOD, LABORATORY AND PROCESS AIR (ASHRAE 62.1 CLASS 3 OR 4) 316 STAINLESS STEEL 3 A 4 2

EQUIPMENT NOT LISTED GALVANIZED SHEETMETAL 2 A 16 8

NOTES

1. CLASSES LISTED IN SCHEDULE REFER TO SMACNA HVAC DUCT CONSTRUCTION STANDARDS

DIFFUSER, REGISTER, AND GRILLE SCHEDULE

MARK

BASIS OF DESIGN

(MANUFACTURER / MODEL) MOUNTING TYPE FACE SIZE NECK SIZE MAX NC MAX PD (IN/WC) NOTES

EXHAUST

EG-1 TITUS / 355RS CEILING LOUVERED GRILLE 35° DEF - 1/2" SPACING 12"x12" 10"x10" 20 0.20 2-6

EG-2 TITUS / 355RS CEILING LOUVERED GRILLE 35° DEF - 1/2" SPACING 24"X12" 22"x10" 20 0.20 2-6

RETURN

RG-1 TITUS / 50F CEILING LOUVERED RETURN GRILLE 24"x12" 20 0.20 2-5

RG-2 TITUS / 50F CEILING LOUVERED RETURN GRILLE 24"x24" 20 0.20 2-5

SUPPLY

SD-1 TITUS / TMS CEILING SQUARE FACE DIFFUSER W/ROUND NECK 12"x12" 6"ø 20 0.20 1-6

SD-2 TITUS / TMS CEILING SQUARE FACE DIFFUSER W/ROUND NECK 12"x12" 8"ø 20 0.20 1-6

SD-3 TITUS / TMS CEILING SQUARE FACE DIFFUSER W/ROUND NECK 24"x24" 6"ø 20 0.20 1-6

SD-4 TITUS / TMS CEILING SQUARE FACE DIFFUSER W/ROUND NECK 24"x24" 8"ø 20 0.20 1-6

SD-5 TITUS / TMS CEILING SQUARE FACE DIFFUSER W/ROUND NECK 24"x24" 10"ø 20 0.20 1-6

SD-6 TITUS / TMS CEILING SQUARE FACE DIFFUSER W/ROUND NECK 24"x24" 12"ø 20 0.20 1-6

SINGLE DUCT VAV TERMINAL UNIT - HOT WATER REHEAT (VAV)

MARK

BASIS OF DESIGN

(MANUFACTURER

/ MODEL) LOCATION INLET SIZE

DESIGN

AIRFLOW

(CFM)

MIN

OA

(CFM)

HEATING COIL CONTROL XFMR

NOTES

HEATING

(CFM)

EAT DB

(°F)

CAPACITY

(BTUH)

EWT

HEATING

# OF

ROWS

FLOW

(GPM) INPUT V/PH

61 VAV-0-6 TITUS / DESV 06 6" 270 115 120 55.0 6.5 160 1 1.2 120/1 ALL LISTED

61 VAV-0C TITUS / DESV C 10" 860 335 345 55.0 15.7 160 1 1.1 120/1 ALL LISTED

61 VAV-0TF TITUS / DESV TF 6" 450 0 450 55.0 5 160 2 1.2 120/1 ALL LISTED

61 VAV-0TM TITUS / DESV TM 6" 315 0 315 55.0 3.7 160 1 0.5 120/1 ALL LISTED

61 VAV-01A TITUS / DESV 01A 10" 930 170 305 55.0 14.8 160 2 5.4 120/1 ALL LISTED

61 VAV-01E TITUS / DESV 01E 6" 340 105 120 55.0 9.3 160 1 1.9 120/1 ALL LISTED

61 VAV-02A TITUS / DESV 02A 10" 785 215 325 55.0 14.8 160 2 1.0 120/1 ALL LISTED

61 VAV-02B TITUS / DESV 02B 12" 1285 215 500 55.0 22.2 160 2 1.6 120/1 ALL LISTED

61 VAV-03A TITUS / DESV 03A 10" 1145 210 440 55.0 22.2 160 2 1.6 120/1 ALL LISTED

61 VAV-03B TITUS / DESV 03B 10" 810 190 335 55.0 18.5 160 2 1.6 120/1 ALL LISTED

61 VAV-04A TITUS / DESV 04A 10" 900 235 370 55.0 18.5 160 2 1.6 120/1 ALL LISTED

61 VAV-04B TITUS / DESV 04B 10" 810 200 335 55.0 17.6 160 2 1.4 120/1 ALL LISTED

61 VAV-05A TITUS / DESV 05A 10" 805 200 335 55.0 16.7 180 2 1.2 120/1 ALL LISTED

61 VAV-05B TITUS / DESV 05B 10" 920 230 380 55.0 15.7 160 2 1.1 120/1 ALL LISTED

61 VAV-07 TITUS / DESV 07 6" 340 115 140 55.0 7 160 1 1.9 120/1 ALL LISTED

61 VAV-08 TITUS / DESV 08 6" 485 90 110 55.0 11.3 160 1 0.7 120/1 ALL LISTED

61 VAV-09 TITUS / DESV 09 10" 1010 285 350 55.0 20.4 160 2 1.4 120/1 ALL LISTED

61 VAV-101 TITUS / DESV 108 10" 1320 100 550 55.0 20.4 160 2 1.4 120/1 ALL LISTED

61 VAV-102 TITUS / DESV 107B 10" 1215 70 525 55.0 19.4 160 2 1.3 120/1 ALL LISTED

61 VAV-103 TITUS / DESV 107A 10" 1215 140 525 55.0 19.4 160 2 1.3 120/1 ALL LISTED

61 VAV-104 TITUS / DESV 106B 10" 1210 220 525 55.0 19.4 160 2 1.3 120/1 ALL LISTED

61 VAV-105 TITUS / DESV 106A 5" 270 215 150 55.0 5.6 160 1 2.5 120/1 ALL LISTED

61 VAV-106 TITUS / DESV 105 8" 870 215 435 55.0 16.1 160 2 1.2 120/1 ALL LISTED

61 VAV-107 TITUS / DESV 103A 7" 600 215 300 55.0 11.3 160 2 0.7 120/1 ALL LISTED

61 VAV-108 TITUS / DESV 104 12" 1775 240 700 55.0 25.9 160 2 1.4 120/1 ALL LISTED

EXHAUST FAN SCHEDULE (EF)

MARK

BASIS OF DESIGN

(MANUFACTURER/MODEL)

FAN DATA

MOUNTING DRIVE

ELECTRICAL

WEIGHT (LBS) NOTESDESIGN AIRFLOW (CFM) ESP ("WC) HP FLA (A) VOLTS/PH

61 EF-9 GREENHECK / CUE-140-VG 1,450 0.5 0.25 ROOF DIRECT 3.8 120/1 61 1-4

61 EF-10 GREENHECK / CUE-160-VG 2,500 0.5 0.50 ROOF DIRECT 6.6 120/1 74 1-4

61 EF-11 GREENHECK / CUE-090-VG 150 0.5 0.10 ROOF DIRECT 1.5 120/1 31 1-4

AIR HANDLING UNIT SCHEDULE (AHU)

MARK

BASIS OF DESIGN

(MANUFACTURER / MODEL) LOCATION

SUPPLY FAN ARRAY FAN ARRAY VFD COOLING COIL HEATING COIL HUMIDIFICATION COIL

WEIGHT

(LBS) NOTES

DESIGN

CFM MIN O/A

FAN RPM

(MAX)

ESP

(IN WC)

MOTORS

HP

(EA)

FLA

(EA) V/PH QTY HP

AMPS

(EA)

FLOW

(GPM)

TOTAL

(MBH)

SENSIBLE

(MBH)

EWT

(°F)

LWT

(°F) ROWS

EAT DB

(°F)

LAT DB

(°F)

APD

("WC)

WPD

('WC)

SENSIBLE

(MBH)

EAT DB

(°F)

LAT DB

(°F)

APD

("WC)

STEAM PRESSURE

(psig) CAP (LBS/HR)

STEAM PRESSURE

(psig)

61 AHU-01 Temtrol / AHU-1 MECHANICAL ROOM 18,500 3,850 3,930 4.3 4 8.5 10.0 460/3 1 30 40.0 131.9 662.3 531.5 45.0 55.0 12 79.5 52.9 0.6 7.5 752.2 55 91.5 0.2 10 355.4 10 11538 ALL LISTED

EXISTING AIR COOLED PACKAGED CHILLER SCHEDULE (ACPC)

MARK

BASIS OF DESIGN

(INSTANCE) TYPE

COOLING SECTION ELECTRICAL EFFICIENCY

NOTESCAPACITY (TONS) DESIGN FLOW (GPM) P.D. (FT) FLUID TYPE VOLTS/PH MCA (A) EER IPLV

61 ACPC-1 TRANE / RTAC-170 SCREW 153 360 14 30% GLYCOL 460/3 333 10.4 14.1

61 ACPC-2 TRANE / RTAC-170 SCREW 153 360 14 30% GLYCOL 460/3 333 10.4 14.1

FOR REFERENCE ONLY:

1. PROVIDE WITH ROOF CURB, BIRDSCREEN AND BACKDRAFT DAMPER.

2 PROVIDE FACTORY MOUNTED DISCONNECT SWITCH.

3 INTERLOCK FAN OPERATION WITH GROUND FLOOR AIR HANDLING UNIT.

4 PROVIDE FAN WITH ECM MOTOR.

1 PROVIDE FACTORY MOUNTED DISCONNECT INSTALLED ON SERVICE SIDE OF UNIT

2 VARIABLE FREQUENCY DRIVE TO BE FURNISHED BY FACTORY.

3 SPECIFIED FAN ESP ACCOUNTS FOR DUCT LOSSES EXTERNAL TO UNIT.

4 FIRE ALARM CONTRACTOR SHALL PROVIDE SMOKE DETECTORS IN SUPPLY AIR DUCTS.

5 UNIT SHALL BE DRAW THRU CONFIGURATION.

6 SELECT EQUIPMENT FOR ELEVATION OF 1360 FEET ABOVE SEA LEVEL.

7 MINIMUM CASING THICKNESS OF 3", FIBERGLASS INSULATION CONSTRUCTION. REFER SPEC TABLE 237300-2.1.C.2 FOR FULL CRITERIA.

1 BRANCH DUCT SIZE SHALL BE SAME AS NECK SIZE UNLESS OTHERWISE SHOWN ON DRAWINGS.

2 FINISH - BAKED ENAMEL FINISH, WHITE TO MATCH CEILING COLOR.

3 FRAME TYPE TO MATCH CEILING CONSTRUCTION, COORDINATE WITH ARCHITECTURAL REFLECTED CEILING PLAN.

4 4-WAY THROW PATTERN UNLESS OTHERWISE SHOWN ON DRAWINGS.

5 ALUMINUM CONSTRUCTION

6 PROVIDE OPPOSED BLADE DAMPER ADJUSTABLE FROM FACE OF AIR DEVICE (IN GYP CEILINGS).

1 BOX SELECTED AT 1360-FEET ABOVE SEA LEVEL.

2 INLET SIZE SHOWN IS THE MINIMUM ALLOWABLE INLET SIZE. NO SMALLER SIZES SHALL BE ACCEPTED.

3 PROVIDE FACTORY INSTALLED CONTROL POWER (CP) TRANSFORMER. COORDINATE PRIMARY POWER WITH ELECTRICAL. COORDINATE CONTROLS WITH TEMPERATURE

CONTROL CONTRACTOR.

4 PROVIDE FACTORY-INSTALLED, PRESSURE INDEPENDENT, DDC CONTROL PACKAGE.

5 PROVIDE BOX WITH EITHER RIGHT HAND OR LEFT HAND CONFIGURATION AS SHOWN ON DRAWINGS.

VARIES

VARIES

RETURN FAN SCHEDULE

MARK BASIS OF DESIGN LOCATION

FAN DATA

MOUNTING DRIVE VOLTS/PH FLA (A) WEIGHT (LBS) NOTESDESIGN AIR FLOW ESP (" W.C.) HP

RF-3 GREENHECK AX-90-400-0914 FIRST FLOOR MECHANICAL ROOM ALL LISTED16780 3.75 20 FLOOR DIRECT 460/3 27 436

1. PROVIDE BASE WITH RUBBER IN SHEAR VIBRATION ISOLATION.

2. VARIABLE FREQUENCY DRIVE TO BE PROVIDED BY CONTROLS CONTRACTOR, INSTALLED BY ELECTRICAL CONTRACTOR.

3. INTERLOCK FAN OPERATION WITH AHU-01 AND ASSOCIATED RELIEF AND OUTSIDE AIR DAMPERS THROUGH BUILDING AUTOMATION SYSTEM.

No. REVISION DESCRIPTION DATE

ADD 1 SCHEDULE NOTE ADD 7-8-2022