0005 - VA Garland 2026 Elevator Inspection Reports.pdf

PDF 1 MB Posted

Attached to
Y1DA--Replace Elevators at Garland VA Medical Center 549-24-425
Solicitation number
36C77626R0061
Issued by

About this file

This document is a VA Annual Elevator Inspection report for VA Garland Medical Center, containing inspection records for 14 passenger elevators conducted on March 10-11, 2026. The facility is located at 2300 Marie Currie Boulevard, Garland, Texas 75216.

The inspections were performed by Eugene M Kissinger (QEI License C-5598) of Reliant Elevator Inspections & Consulting, LLC, with testing conducted by Metro Elevator. All 14 elevators underwent annual inspection and testing per A17.1 and A17.2 elevator codes. The facility's elevators include Alpha AEC-H (Unit P1), Baxco BMHC-20 (Units P2 and P14), and multiple KONE Resolve-100 models (Units P3-P10). Two TKE TAC-50 units serve the facility as well (Units P11-P12). Installation years range from 1992 to 2004, with capacities between 300 and 6,500 pounds and speeds between 75 and 350 feet per minute. Unit P2 was noted as out of service due to missing control boards. All passing units documented routine maintenance requirements including monthly fire service testing logs, periodic test tags, and site documentation. Violations identified across multiple units require repairs including fire phase audible signal corrections, emergency phone repairs, emergency lighting and alarm repairs, door restrictor repairs, and worn component replacements. The next five-year safety tests are due in March 2027, with the building contact identified as Doug Person at (469) 797-2100. Metro Elevator (Matt Manning & Chuck Turner) serves as the maintenance contractor at 4500 S Lancaster, Dallas, Texas 75215.

View the file

Other files

File Type Posted
0005 - Responses to Tech Questions - 6-5-26.pdf PDF
01 - Specifications_6-5-2026.pdf PDF
36C77626R0061 0005.pdf PDF
0004 - Responses to Tech Questions - 5-29-26.pdf PDF
36C77626R0061 0004.pdf PDF
0003 - Site Visit Sign-in Sheet 5-15-26.pdf PDF
0003 - SCA Wages - Dallas County - 05-13-2026.pdf PDF
0003 - DBA Wages - Dallas County - 05-18-2026.pdf PDF
36C77626R0061 0003.pdf PDF
36C77626R0061 0002.pdf PDF
0002 - Site Visit Instructions.pdf PDF
0002 - Site Visit Campus Maps.pdf PDF
36C77626R0061 0001.pdf PDF
0001 - SCA Wages - Dallas County - 04-29-2026.pdf PDF
0001 - Site Visit Sign-in Sheet 4-23-26.pdf PDF
RFP 36C77626R0061 - 4-14-26.pdf PDF
05 - Asbestos Survey Report.pdf PDF
08 - DBA Wages - Dallas County - 01-02-2026.pdf PDF
15 - PPQ.docx DOCX document
13 - Site Visit Campus Maps.pdf PDF
06 - SAFETY PIN PCRA-ICRA.pdf PDF
14 - Project Information Sheet.docx DOCX document
12 - Site Visit Instructions.pdf PDF
09 - SCA Wages - Dallas County - 12-03-2025.pdf PDF
04 - Drawings.pdf PDF
01 - Specifications_4-9-2026.pdf PDF
07 - Special Notice - Guarantee Period Services.pdf PDF
11 - Division Cost Breakdown.xlsx XLSX spreadsheet
10 - 852.219-75 Limitations on Subcontracting.pdf PDF
02 - Supplement to Spec Section 01 00 00.pdf PDF
03 - Narrative.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VA ELEVATOR INSPECTION

4602 Deepdale Drive Corpus Christi, Texas 78413 832-734-9977

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

1 of 14 Garland

VA Garland Medical Center P1 Alpha

2300 Marie Currie Blvd, Garland TX 75216 AEC - H

240401-01-H-c1

X

1997 2024 2

125 4500 1

A17.1 8.6.1.4.1 2016 Yes

A17.1 3.27.1 2016 Yes

Doug Person (469) 797-2100

Dallas Texas 75215

MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents

Repair Emergency phone

3/10/2026

Matt Manning & Chuck Turner Metro Elevator

4500 S Lancaster

X

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

2 of 14 Garland

VA Garland Medical Center P2 Baxco

2300 Marie Currie Blvd, Garland TX 75216 BMHC - 20

133010 X

1994 2024 2

75 6500 2

Doug Person (469) 797-2100

Dallas Texas 75215

Unit out of Service (No Control Boards in Controller)

3/10/2026

Matt Manning & Chuck Turner Metro Elevator

4500 S Lancaster

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

3 of 14 Garland

VA Garland Medical Center P3 KONE

2300 Marie Currie Blvd, Garland TX 75216 Resolve - 100

20215624 X

X 1995 2014 5

350 4500 1

A17.1 8.6.1.4.1 2016 YES

A17.1 3.27.1 2016 YES

A17.1 2.27.3.1.6 (h) 2016 YES

Doug Person (469) 797-2100

Dallas Texas 75215

MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents

Repair Emergency phone

Repair Fire Phase I (audible signal shall remain active for a minimum of 5 sec)

3/10/2026

Matt Manning & Chuck Turner Metro Elevator

4500 S Lancaster

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

4 of 14 Garland

VA Garland Medical Center P4 KONE

2300 Marie Currie Blvd, Garland TX 75216 Resolve - 100

20215629 X

X 1995 2014 5

350 4500 1

A17.1 8.6.1.4.1 2016 YES

A17.1 3.27.1 2016 YES

A17.1 2.27.3.1.6 (h) 2016 YES

Doug Person (469) 797-2100

Dallas Texas 75215

MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents

Repair Emergency phone

Repair Fire Phase I (audible signal shall remain active for a minimum of 5 sec)

3/10/2026

Matt Manning & Chuck Turner Metro Elevator

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

5 of 14 Garland

VA Garland Medical Center P5 KONE

2300 Marie Currie Blvd, Garland TX 75216 Resolve - 100

20215608 X

X 1995 2014 5

350 300 1

A17.1 8.6.1.4.1 2016 YES

A17.1 3.27.1 2016 YES

A17.1 2.27.3.1.6 (h) 2016 YES

Doug Person (469) 797-2100

Dallas Texas 75215

MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents

Repair Emergency phone

Repair Fire Phase I (audible signal shall remain active for a minimum of 5 sec)

3/10/2026

Matt Manning & Chuck Turner Metro Elevator

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

6 of 14 Garland

VA Garland Medical Center P6 KONE

2300 Marie Currie Blvd, Garland TX 75216 Resolve - 100

20215619 X

X 1995 2014 5

350 3000 1

A17.1 8.6.1.4.1 2016 YES

A17.1 3.27.1 2016 YES

A17.1 2.27.3.1.6 (h) 2016 YES

Doug Person (469) 797-2100

Dallas Texas 75215

MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents

Repair Emergency phone

Repair Fire Phase I (audible signal shall remain active for a minimum of 5 sec)

3/10/2026

Matt Manning & Chuck Turner Metro Elevator

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

7 of 14 Garland

VA Garland Medical Center P7 KONE

2300 Marie Currie Blvd, Garland TX 75216 Resolve - 100

20215571 X

X 1995 2015 5

350 4000 1

A17.1 8.6.1.4.1 2016 YES

A17.1 3.27.1 2016 YES

A17.1 2.27.3.1.6 (h) 2016 YES

Doug Person (469) 797-2100

Dallas Texas 75215

MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents

Repair Emergency phone

Repair Fire Phase I (audible signal shall remain active for a minimum of 5 sec)

3/10/2026

Matt Manning & Chuck Turner Metro Elevator

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

8 of 14 Garland

VA Garland Medical Center P8 KONE

2300 Marie Currie Blvd, Garland TX 75216 Resolve - 100

20216887 X

X 1995 2015 5

350 4000 1

A17.1 8.6.1.4.1 2016 YES

A17.1 3.27.1 2016 YES

A17.1 2.27.3.1.6 (h) 2016 YES

A17.1 2.21.1.3 2016

Doug Person (469) 797-2100

Dallas Texas 75215

MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents

Repair Emergency phone

Repair Fire Phase I (audible signal shall remain active for a minimum of 5 sec)

Replace worn CWT rollers

3/10/2026

Matt Manning & Chuck Turner Metro Elevator

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

9 of 14 Garland

VA Garland Medical Center P9 KONE

2300 Marie Currie Blvd, Garland TX 75216 Resolve - 100

20216893 X

X 1995 2015 5

350 3000 1

A17.1 8.6.1.4.1 2016 YES

A17.1 3.27.1 2016 YES

A17.1 2.27.3.1.6 (h) 2016 YES

Doug Person (469) 797-2100

Dallas Texas 75215

MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents

Repair Emergency phone

Repair Fire Phase I (audible signal shall remain active for a minimum of 5 sec)

3/10/2026

Matt Manning & Chuck Turner Metro Elevator

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

10 of 14 Garland

VA Garland Medical Center P10 KONE

2300 Marie Currie Blvd, Garland TX 75216 Resolve - 100

20216880 X

X 1995 2015 5

350 3000 1

A17.1 8.6.1.4.1 2016 YES

A17.1 3.27.1 2016 YES

A17.1 2.27.3.1.6 (h) 2016 YES

Doug Person (469) 797-2100

Dallas Texas 75215

MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents

Repair Emergency phone

Repair Fire Phase I (audible signal shall remain active for a minimum of 5 sec)

3/10/2026

Matt Manning & Chuck Turner Metro Elevator

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

11 of 14 Garland

VA Garland Medical Center P11 TKE

2300 Marie Currie Blvd, Garland TX 75216 TAC - 50

CR-2279

X

X 2004 5

350 5200 2

A17.1 8.6.1.4.1 2016 YES

A17.1 3.27.1 2016 YES

Doug Person (469) 797-2100

Dallas Texas 75215

MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents

Repair Emergency phone

3/11/2026

Matt Manning & Chuck Turner Metro Elevator

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

12 of 14 Garland

VA Garland Medical Center P12 TKE

2300 Marie Currie Blvd, Garland TX 75216 TAC - 50

CR-2280

X

X 2004 5

350 5200 2

A17.1 8.6.1.4.1 2016 YES

A17.1 3.27.1 2016 YES

Doug Person (469) 797-2100

Dallas Texas 75215

MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents

Repair Emergency phone

3/11/2026

Matt Manning & Chuck Turner Metro Elevator

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

13 of 14 Garland

VA Garland Medical Center P13 BAXCO

2300 Marie Currie Blvd, Garland TX 75216 BMHC-20

871002-B X

1992 4

125 1500 1

A17.1 8.6.1.4.1 2016 YES

A17.1 3.27.1 2016 YES

A17.1 2.14.5.7 2016 YES

A17.1 2.14.7.1.3 2016

A17.1 3.18.3.7 2016

Doug Person (469) 797-2100

Dallas Texas 75215

MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents

Repair Emergency phone

Restricted opening of car doors (repair or replace door restrictor)

Repair emergency lighting and alarm.

Provide oil leakage collection means

3/11/2026

Matt Manning & Chuck Turner Metro Elevator

4500 S Lancaster

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

14 of 14 Garland

VA Garland Medical Center P14 BAXCO

2300 Marie Currie Blvd, Garland TX 75216 BMHC-20

871002-A X

1992 4

125 4000 1

A17.1 8.6.1.4.1 2016 YES

A17.1 3.27.1 2016 YES

A17.1 2.14.5.7 2016 YES

A17.1 2.14.7.1.3 2016

Doug Person (469) 797-2100

Dallas Texas 75215

MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents

Repair Emergency phone

Restricted opening of car doors (repair or replace door restrictor)

Repair emergency lighting and alarm.

3/11/2026

Matt Manning & Chuck Turner Metro Elevator

4500 S Lancaster

Garland - P1.pdf
Garland - P2.pdf
Garland - P3.pdf
Garland - P4.pdf
Garland - P5.pdf
Garland - P6.pdf
Garland - P7.pdf
Garland - P8.pdf
Garland - P9.pdf
Garland - P10.pdf
Garland - P11.pdf
Garland - P12.pdf
Garland - P13.pdf
Garland - P14.pdf