0005 - VA Garland 2026 Elevator Inspection Reports.pdf
PDF 1 MB Posted
- Solicitation number
- 36C77626R0061
About this file
This document is a VA Annual Elevator Inspection report for VA Garland Medical Center, containing inspection records for 14 passenger elevators conducted on March 10-11, 2026. The facility is located at 2300 Marie Currie Boulevard, Garland, Texas 75216.
The inspections were performed by Eugene M Kissinger (QEI License C-5598) of Reliant Elevator Inspections & Consulting, LLC, with testing conducted by Metro Elevator. All 14 elevators underwent annual inspection and testing per A17.1 and A17.2 elevator codes. The facility's elevators include Alpha AEC-H (Unit P1), Baxco BMHC-20 (Units P2 and P14), and multiple KONE Resolve-100 models (Units P3-P10). Two TKE TAC-50 units serve the facility as well (Units P11-P12). Installation years range from 1992 to 2004, with capacities between 300 and 6,500 pounds and speeds between 75 and 350 feet per minute. Unit P2 was noted as out of service due to missing control boards. All passing units documented routine maintenance requirements including monthly fire service testing logs, periodic test tags, and site documentation. Violations identified across multiple units require repairs including fire phase audible signal corrections, emergency phone repairs, emergency lighting and alarm repairs, door restrictor repairs, and worn component replacements. The next five-year safety tests are due in March 2027, with the building contact identified as Doug Person at (469) 797-2100. Metro Elevator (Matt Manning & Chuck Turner) serves as the maintenance contractor at 4500 S Lancaster, Dallas, Texas 75215.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VA ELEVATOR INSPECTION
4602 Deepdale Drive Corpus Christi, Texas 78413 832-734-9977
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
1 of 14 Garland
VA Garland Medical Center P1 Alpha
2300 Marie Currie Blvd, Garland TX 75216 AEC - H
240401-01-H-c1
X
1997 2024 2
125 4500 1
A17.1 8.6.1.4.1 2016 Yes
A17.1 3.27.1 2016 Yes
Doug Person (469) 797-2100
Dallas Texas 75215
MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents
Repair Emergency phone
3/10/2026
Matt Manning & Chuck Turner Metro Elevator
4500 S Lancaster
X
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
2 of 14 Garland
VA Garland Medical Center P2 Baxco
2300 Marie Currie Blvd, Garland TX 75216 BMHC - 20
133010 X
1994 2024 2
75 6500 2
Doug Person (469) 797-2100
Dallas Texas 75215
Unit out of Service (No Control Boards in Controller)
3/10/2026
Matt Manning & Chuck Turner Metro Elevator
4500 S Lancaster
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
3 of 14 Garland
VA Garland Medical Center P3 KONE
2300 Marie Currie Blvd, Garland TX 75216 Resolve - 100
20215624 X
X 1995 2014 5
350 4500 1
A17.1 8.6.1.4.1 2016 YES
A17.1 3.27.1 2016 YES
A17.1 2.27.3.1.6 (h) 2016 YES
Doug Person (469) 797-2100
Dallas Texas 75215
MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents
Repair Emergency phone
Repair Fire Phase I (audible signal shall remain active for a minimum of 5 sec)
3/10/2026
Matt Manning & Chuck Turner Metro Elevator
4500 S Lancaster
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
4 of 14 Garland
VA Garland Medical Center P4 KONE
2300 Marie Currie Blvd, Garland TX 75216 Resolve - 100
20215629 X
X 1995 2014 5
350 4500 1
A17.1 8.6.1.4.1 2016 YES
A17.1 3.27.1 2016 YES
A17.1 2.27.3.1.6 (h) 2016 YES
Doug Person (469) 797-2100
Dallas Texas 75215
MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents
Repair Emergency phone
Repair Fire Phase I (audible signal shall remain active for a minimum of 5 sec)
3/10/2026
Matt Manning & Chuck Turner Metro Elevator
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
5 of 14 Garland
VA Garland Medical Center P5 KONE
2300 Marie Currie Blvd, Garland TX 75216 Resolve - 100
20215608 X
X 1995 2014 5
350 300 1
A17.1 8.6.1.4.1 2016 YES
A17.1 3.27.1 2016 YES
A17.1 2.27.3.1.6 (h) 2016 YES
Doug Person (469) 797-2100
Dallas Texas 75215
MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents
Repair Emergency phone
Repair Fire Phase I (audible signal shall remain active for a minimum of 5 sec)
3/10/2026
Matt Manning & Chuck Turner Metro Elevator
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
6 of 14 Garland
VA Garland Medical Center P6 KONE
2300 Marie Currie Blvd, Garland TX 75216 Resolve - 100
20215619 X
X 1995 2014 5
350 3000 1
A17.1 8.6.1.4.1 2016 YES
A17.1 3.27.1 2016 YES
A17.1 2.27.3.1.6 (h) 2016 YES
Doug Person (469) 797-2100
Dallas Texas 75215
MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents
Repair Emergency phone
Repair Fire Phase I (audible signal shall remain active for a minimum of 5 sec)
3/10/2026
Matt Manning & Chuck Turner Metro Elevator
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
7 of 14 Garland
VA Garland Medical Center P7 KONE
2300 Marie Currie Blvd, Garland TX 75216 Resolve - 100
20215571 X
X 1995 2015 5
350 4000 1
A17.1 8.6.1.4.1 2016 YES
A17.1 3.27.1 2016 YES
A17.1 2.27.3.1.6 (h) 2016 YES
Doug Person (469) 797-2100
Dallas Texas 75215
MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents
Repair Emergency phone
Repair Fire Phase I (audible signal shall remain active for a minimum of 5 sec)
3/10/2026
Matt Manning & Chuck Turner Metro Elevator
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
8 of 14 Garland
VA Garland Medical Center P8 KONE
2300 Marie Currie Blvd, Garland TX 75216 Resolve - 100
20216887 X
X 1995 2015 5
350 4000 1
A17.1 8.6.1.4.1 2016 YES
A17.1 3.27.1 2016 YES
A17.1 2.27.3.1.6 (h) 2016 YES
A17.1 2.21.1.3 2016
Doug Person (469) 797-2100
Dallas Texas 75215
MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents
Repair Emergency phone
Repair Fire Phase I (audible signal shall remain active for a minimum of 5 sec)
Replace worn CWT rollers
3/10/2026
Matt Manning & Chuck Turner Metro Elevator
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
9 of 14 Garland
VA Garland Medical Center P9 KONE
2300 Marie Currie Blvd, Garland TX 75216 Resolve - 100
20216893 X
X 1995 2015 5
350 3000 1
A17.1 8.6.1.4.1 2016 YES
A17.1 3.27.1 2016 YES
A17.1 2.27.3.1.6 (h) 2016 YES
Doug Person (469) 797-2100
Dallas Texas 75215
MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents
Repair Emergency phone
Repair Fire Phase I (audible signal shall remain active for a minimum of 5 sec)
3/10/2026
Matt Manning & Chuck Turner Metro Elevator
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
10 of 14 Garland
VA Garland Medical Center P10 KONE
2300 Marie Currie Blvd, Garland TX 75216 Resolve - 100
20216880 X
X 1995 2015 5
350 3000 1
A17.1 8.6.1.4.1 2016 YES
A17.1 3.27.1 2016 YES
A17.1 2.27.3.1.6 (h) 2016 YES
Doug Person (469) 797-2100
Dallas Texas 75215
MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents
Repair Emergency phone
Repair Fire Phase I (audible signal shall remain active for a minimum of 5 sec)
3/10/2026
Matt Manning & Chuck Turner Metro Elevator
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
11 of 14 Garland
VA Garland Medical Center P11 TKE
2300 Marie Currie Blvd, Garland TX 75216 TAC - 50
CR-2279
X
X 2004 5
350 5200 2
A17.1 8.6.1.4.1 2016 YES
A17.1 3.27.1 2016 YES
Doug Person (469) 797-2100
Dallas Texas 75215
MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents
Repair Emergency phone
3/11/2026
Matt Manning & Chuck Turner Metro Elevator
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
12 of 14 Garland
VA Garland Medical Center P12 TKE
2300 Marie Currie Blvd, Garland TX 75216 TAC - 50
CR-2280
X
X 2004 5
350 5200 2
A17.1 8.6.1.4.1 2016 YES
A17.1 3.27.1 2016 YES
Doug Person (469) 797-2100
Dallas Texas 75215
MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents
Repair Emergency phone
3/11/2026
Matt Manning & Chuck Turner Metro Elevator
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
13 of 14 Garland
VA Garland Medical Center P13 BAXCO
2300 Marie Currie Blvd, Garland TX 75216 BMHC-20
871002-B X
1992 4
125 1500 1
A17.1 8.6.1.4.1 2016 YES
A17.1 3.27.1 2016 YES
A17.1 2.14.5.7 2016 YES
A17.1 2.14.7.1.3 2016
A17.1 3.18.3.7 2016
Doug Person (469) 797-2100
Dallas Texas 75215
MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents
Repair Emergency phone
Restricted opening of car doors (repair or replace door restrictor)
Repair emergency lighting and alarm.
Provide oil leakage collection means
3/11/2026
Matt Manning & Chuck Turner Metro Elevator
4500 S Lancaster
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Elevator and witnessed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
14 of 14 Garland
VA Garland Medical Center P14 BAXCO
2300 Marie Currie Blvd, Garland TX 75216 BMHC-20
871002-A X
1992 4
125 4000 1
A17.1 8.6.1.4.1 2016 YES
A17.1 3.27.1 2016 YES
A17.1 2.14.5.7 2016 YES
A17.1 2.14.7.1.3 2016
Doug Person (469) 797-2100
Dallas Texas 75215
MCP's - Provide Monthly Fire Service Testing Logs, Periodic Test Tag, Site Documents
Repair Emergency phone
Restricted opening of car doors (repair or replace door restrictor)
Repair emergency lighting and alarm.
3/11/2026
Matt Manning & Chuck Turner Metro Elevator
4500 S Lancaster
| Garland - P1.pdf |
| Garland - P2.pdf |
| Garland - P3.pdf |
| Garland - P4.pdf |
| Garland - P5.pdf |
| Garland - P6.pdf |
| Garland - P7.pdf |
| Garland - P8.pdf |
| Garland - P9.pdf |
| Garland - P10.pdf |
| Garland - P11.pdf |
| Garland - P12.pdf |
| Garland - P13.pdf |
| Garland - P14.pdf |
File details come from the government source that posted it. Updated .