ATTACHMENT 9 - Drawings Telecommunications.pdf
PDF 32 MB Posted
- Solicitation number
- 36C77626B0009
About this file
This attachment contains telecommunications infrastructure design drawings, abbreviations, legends, and technical specifications for the EHRM Infrastructure Upgrades project at Syracuse VA facilities (Project 528A7-22-700). The document includes comprehensive design documentation for voice, data, and telecommunications systems across Buildings 1, 2, 16, and the Rome CBOC, with construction scheduled for completion in accordance with 100% Construction Documents dated May 19, 2025.
The specifications require Category 6A cabling installation from all work area outlets (WAOs) to telecommunications rooms (TRs), fiber optic backbone infrastructure with redundant A-side and B-side routing, and compliance with BICSI and TIA/EIA standards including ANSI/TIA-606-C labeling requirements. Key technical requirements include: minimum 3/4-inch interior and 4-inch exterior/underground conduit; 12 AWG grounding conductors for all raceways; fire-rated penetration seals; segregation of data cabling from security, fire alarm, and nurse call systems; and detailed specifications for data rack configurations, patch panel installations, fiber splice cassettes (OM4, OS1, OS2 types), and cable management systems. The contractor must provide factory-terminated Category 6A patch cords (50% 3-foot and 50% 5-foot lengths with blue or white jackets) for each TR, fiber optic patch cables matching cable types with specified jacket colors (OM4 aqua, OS1 and OS2 yellow), and horizontal distribution equipment within main control rooms. All installations require coordination with architectural, mechanical, electrical, and structural disciplines; submission of redlined record drawings upon completion; and certification by authorized contractor agents prior to work commencement. Multiple telecommunications rooms across facility levels require data racks following VA's "rule of thirds" equipment positioning standard with seismic bracing and comprehensive labeling per infrastructure standards.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1PH SINGLE-PHASE
1P SINGLE POLE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE-PHASE
4/C FOUR-CONDUCTOR
4W FOUR-WIRE
A/C AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC
FREQUENCY CONTROL, OR AVAILABLE
FAULT CURRENT
AFCI ARC-FAULT CURRENT INTERRUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BAT BATTERY
BD BOARD
BFF BELOW FINISH FLOOR
BLDG BUILDING
BRKR BREAKER
BYP BY PASS
C CONDUIT
CAB CABINET
CALC CALCULATE
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
CD CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/
CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/
OWNER INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
C/B CIRCUIT BREAKER
CL CONNECTOR LIGHTING
CLF CURRENT LIMITING FUSE
CLG CEILING
CO CONDUIT ONLY
COAX COAX CABLE
COMM COMMUNICATION
COMPT COMPARTMENT
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CUR CURRENT
DB DECIBEL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DDC DIRECT DIGITAL CONTROLS
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DP DISTRIBUTION PANEL
DMR SW DIMMER SWITCH
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EL ELEVATION OR EXISTING TO BE RELOCATED
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMER/EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
EN EXISTING IN NEW LOCATION
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
EPRF EXPLOSION PROOF
ER EXISTING TO REMAIN
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST(E) EXISTING
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCIO FURNISHED BY CONTRACTOR,
INSTALLED BY OWNER
FOIC FURNISHED BY OWNER,
INSTALLED BY CONTRACTOR
FIXT FIXTURE
FLA FULL LOAD AMPS
FLUOR FLUORESCENT
FP FIRE PROTECTION
FT FEET OR FOOT
FU SW FUSED SWITCH
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G ELECTRICAL GROUND
GEN GENERATOR
GFCI GROUND FAULT
CIRCUIT INTERRUPTER
GFP GROUND FAULT PROTECTION
GND GROUND
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
IG ISOLATED GROUND
IESNA ILLUMINATION ENGINEERING
SOCIETY OF NORTH AMERICA
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT AMPERE
KVAH KILOVOLT AMPERE PER HOUR
KVAR KILOVOLT AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
KWHM KILOWATT HOUR METER
LCP LIGHTING CONTROL PANEL
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MS MOTOR STARTER
MT MOUNT
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
NA NOT APPLICABLE
NAC NOTIFICATION APPLIANCE CABINET
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NEUT, N NEUTRAL
NFC NOT FOR CONSTRUCTION
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OL OVERLOAD
OS OCCUPANCY SENSOR
P POLE
PB PULL BOX
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PIV POST INDICATOR VALVE
PF POWER FACTOR
PH PHASE
PNL PANEL
PS POWER SUPPLY
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
R EXISTING TO BE REMOVED
RCP REFLECTED CEILING PLAN
REC RECESSED
RECPT RECEPTACLE
RM ROOM
RMC RIGID METAL CONDUIT
RMS ROOT MEAN SQUARE
REQD REQUIRED
SAC SMALL APPLIANCE CIRCUIT
SCC SHORT CIRCUIT CAPACITY
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SM SMART METER
SPD SURGE PROTECTIVE DEVICE
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD OR SB SWITCHBOARD
SWGR OR SG SWITCHGEAR
TEL TELEPHONE
TR TAMPER RESISTANT
TV TELEVISION
TYP TYPICAL
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER
POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
W WATT/WEATHERPROOF
(WHILE IN USE)
WH WATER HEATER
WP/W WEATHERPROOF
XFER TRANSFER
XFMR TRANSFORMER
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
35.
36.
37.
38.
39.
THESE "GENERAL NOTES" SHALL APPLY TO ALL DRAWINGS WITHIN THIS DRAWING SET.
WHERE THE SPECIFICATIONS OR DRAWINGS CONFLICT WITH EACH OTHER THE MORE STRINGENT CRITERIA/SCOPE OF WORK SHALL BE REQUIRED.
BLACKENED OR BOLDED EQUIPMENT INDICATES THE EQUIPMENT SHALL BE PROVIDED OR MODIFIED, CONTRACTOR FURNISHED CONTRACTOR INSTALLED, UNLESS OTHERWISE
NOTED.
ALL TELECOMMUNICATIONS SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE BICSI AND TIA/EIA STANDARDS.
ALL CONDUIT, SLEEVES AND PATHWAYS SHALL BE FREE OF DEBRIS OR BLOCKAGES. ALL FIELD CUT RAW EDGES SHALL BE DEBURRED BY THE INSTALLING CONTRACTOR. ALL CONDUITS THAT FEED CATEGORY 6A CABLE TO A WORK ARE OUTLET BOX SHALL HAVE A PLASTIC BUSHING PLACED ON THE END OF THE CONDUIT.
ALL BLOCKS, PANELS, AND CABLE SHALL BE ASSIGNED, LABELED, AND RECORDED BY THE CONTRACTOR AND DELIVERED TO THE ENGINEER.
ALL DATA CABLING AND ASSOCIATED RACEWAY INSTALLATIONS AND LAYOUTS SHALL BE COORDINATED WITH ALL OBSTACLES, EQUIPMENT, AND ARCHITECTURAL FEATURES.
REPORT ANY MAJOR DEVIATIONS TO CONSTRUCTION MANAGER FOR APPROVAL.
ALL RACEWAYS SHALL BE PROVIDED WITH A 12 AWG GROUNDING CONDUCTOR UNLESS OTHERWISE NOTED.
MINIMUM CONDUIT SIZE SHALL BE 4” IN DIAMETER FOR EXTERIOR AND UNDERGROUND CONDUIT. MINIMUM CONDUIT SIZE SHALL BE 3/4 ” IN DIAMETER FOR INTERIOR CONDUIT. ALL CONDUIT SHALL BE CONCEALED. THE ABOVE COMMENTS SHALL BE ADHERED TO UNLESS OTHERWISE NOTED ON THE DRAWINGS.
ALL LOW-VOLTAGE CABLING SHALL NOT BE INSTALLED IN ELECTRICAL BRANCH OR FEEDER CIRCUIT RACEWAYS.
ALL EQUIPMENT AND DEVICES INCLUDING, BUT NOT LIMITED TO, LOW-VOLTAGE EQUIPMENT, DATA OUTLETS, CABLING, AND SPECIAL SYSTEM DEVICES, SHALL HAVE THEIR EXACT LOCATION COORDINATED WITH ARCHITECTURAL DRAWINGS AND ALL TRADES PRIOR TO INSTALLATION.
COORDINATE WITH DOOR SECURITY MANUFACTURER FOR ALL ACCESS CONTROL EQUIPMENT AND APPURTENANCES; PROVIDE ANY ADDITIONAL MOTION SENSORS, REQUEST-TO- EXIT BUTTONS, DOOR POSITION SENSORS, OR OTHER HARDWARE AS REQUIRED. ALL CONDUIT, WIRE, POWER SUPPLIES, AND APPURTENANCES REQUIRED FOR THE ACCESS CONTROL SYSTEM SHALL BE PROVIDED TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL SYSTEM. .
ALL RACEWAY AND/OR SLEEVE FLOOR AND WALL PENETRATIONS SHALL BE SEALED WITH FIRE RATED ASSEMBLIES, CAULKING, AND APPURTENANCES. ELECTRICAL BOXES
LOCATED IN FIRE RATED WALLS SHALL BE RATED FOR USE IN FIRE RATED WALLS.
ALL EQUIPMENT AND INSTALLATION METHODS SHALL BE LISTED AND LABELED PER NEC, UL LISTED, OR REVIEWED EQUAL.
FOR ALL EQUIPMENT, COORDINATE WITH ALL TRADES (ARCHITECTURAL, MECHANICAL, PLUMBING, ETC) FOR ELECTRICAL AND LOW-VOLTAGE REQUIREMENTS AND INSTALLATION
LOCATIONS PRIOR TO INSTALLATION.
FOR ANY EXISTING WALL MOUNTED DEVICES THAT REQUIRE MODIFICATION OR REPLACEMENT THAT DO NOT HAVE RACEWAY FROM DEVICE TO ACCESSIBLE CEILING SPACE, PROVIDE MINIMUM 3/4"C ROUTED FROM DEVICE THROUGH WALL INTO THE ACCESSIBLE CEILING SPACE. CABLING SHALL NOT BE ROUTED IN WALLS OR IN AN INACCESSIBLE
LOCATION WITHOUT CONDUIT. .
NO STRUCTURAL MEMBERS SHALL BE CUT, DRILLED, OR NOTCHED WITHOUT PRIOR WRITTEN CONSENT FROM THE STRUCTURAL ENGINEER OR ARCHITECT.
FOR EXISTING EQUIPMENT, SUCH AS LOW-VOLTAGE DEVICES, WIRING DEVICES, CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP CONDUITS AT THE AREA OF WORK PERIMETER AND REMOVE CONDUIT WITHIN THE WORK AREA, DISCONNECT CABLING FROM THE DEVICE BEING REMOVED AND COMPLETELY REMOVE CABLING
FROM ABANDONED CONDUITS BACK TO SOURCE.
MAINTAIN AND RESTORE, IF INTERRUPTED, ALL RACEWAYS AND CABLING PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.
CONTRACTOR SHALL PROVIDE, INSTALL, AND TERMINATE HORIZONTAL CAT6A CABLING FROM EACH WORK AREA OUTLET (WAO) TO ITS RESPECTIVE TELECOMMUNICATIONS ROOM
(TR) DATA RACK, UNLESS OTHERWISE NOTED.
PRIOR TO INSTALLING NEW CABLING, ALL EXISTING CABLES SHALL BE SEGREGATED INTO DIFFERENT GROUP TYPES; ONCE SEPARATED, CONTRACTOR SHALL DETERMINE WHICH CABLES SHALL BE REMOVED AND WHICH SHALL REMAIN. DEMOLISH ALL CABLES TO BE REMOVED BACK TO SOURCE IN ITS ENTIRETY, UNLESS OTHERWISE NOTED.
ONCE CONSTRUCTION IS COMPLETED, CONTRACTOR SHALL PROVIDE REDLINED/RECORD DRAWINGS OF COMPLETE PROJECT TO CLIENT AND ENGINEER FOR REVIEW AND
APPROVAL.
ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS; ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.
ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL FIELD VERIFY ALL EQUIPMENT DEVICES AND ASSOCIATED RACEWAYS AS REQUIRED TO
COORDINATE THE PROJECT SCOPE OF WORK (DEMOLITION AND NEW INSTALLATIONS).
PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE REPAIRED OR
REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE ACCEPTANCE OF THE OWNER.
CONTRACTOR SHALL COORDINATE ALL CATEGORY 6A AND FIBER OPTIC LOCATIONS AND PATHWAYS WITH THE AE PRIOR TO THE START OF ANY WORK. ONCE ALL LOCATIONS ARE CONFIRMED BY ALL PARTIES, THE CONTRACTOR SHALL PROVIDE TO THE AE COPIES OF THE DRAWINGS SIGNED BY A CONTRACTORS AUTHORIZED AGENT. THESE DOCUMENTS
SHALL BE PROVIDED TO THE ELECTRICAL CONTRACTOR FOR COORDINATION.
THE INSTALLATION OF ALL COMMUNICATIONS PATHWAYS, SLEEVES AND CABLE TRAYS SHALL BE LAID OUT BY THE CONTRACTOR AND SUBMITTED TO THE AE FOR APPROVAL PRIOR TO ANY WORK. DRAWINGS SHALL SHOW PROPOSED ROUTES THAT WILL NOT CONFLICT WITH OTHER TRADES SUCH AS HVAC, ELECTRICAL AND ARCHITECTURAL.
THE DATA CENTER SHALL HAVE AN ALPHA-NUMERIC GRID ANNOTATED ON THE WALLS IN ACCORDANCE WITH ANSI/TIA 606-C. STARTING IN THE NORTHWEST CORNER WORKING THE ALPHABET LEFT TO RIGHT AND NUMBERS TOP TO BOTTOM IN 24-INCH INCREMENTS USING BLACK LETTERS AND NUMBERS FOUR INCHES MINIMUM IN HEIGHT NOT PLACED
MORE THAN SIX INCHES BELOW THE CEILING. (REFER TO TN507 FOR EXAMPLES)
All SSTV AND ACCESS CONTROL SYSTEMS WILL BE INSTALLED AND MAINTAINED BY A CERTIFIED INSTALLER FOR EACH SPECIFIC SYSTEM.
ALL CEILING TILES WILL BE REINSTALLED AT THE END OF EACH WORK SHIFT.
ALL FIRE RATED PENETRATIONS WILL HAVE PROPER TEMPORARY FIRESTOP INSTALLED AT THE END OF EACH SHIFT AND UNTIL PERMANENT FIRESTOPPING IS COMPLETE.
ANY ACTIVE ANALOG PORT WILL BE PHASED. REFER TO TN506 CALL OUT 3.
GROUNDING & BONDING: AN ANTIOXIDANT SHALL BE USED ON ALL MECHANICAL CONNECTIONS AND TERMINATIONS.
DEMO’D TR’S SUPPORTING EXISTING/REMAINING SYSTEMS – COPPER & FIBER PHASING.
COPPER: CONTRACTOR TO PULL (12) CAT6A CABLES FROM DEMO’D TR TO NEW TR. TERMINATE, TEST AND COIL UP ON BOTH ENDS.
FIBER: CONTRACTOR TO PULL (12-STRAND OM4 AND 12-STRAND SM FROM DEMO’D TR TO NEW TR. TERMINATE WITH LC CONNECTORS ON NEW TR END.
MATCH CONNECTOR TYPE WITH EXISTING EQUIPMENT ON DEMO ’D TR END. TEST AND COIL UP ON BOTH ENDS.
FOR DEMO’D WAO’S THAT WON’T BE REPLACED: CABLE WILL BE REMOVED BACK TO THE SOURCE, A BLANK FACEPLATE WILL BE INSTALLED OVER THE DEMO ’S BOX.
CONDUIT WILL REMAIN.
THE DATA CENTER SHALL HAVE AN ALPHA-NUMERIC GRID ANNOTATED ON THE WALLS IN ACCORDANCE WITH ANSI/TIA 606-C. STARTING IN THE NORTHWEST CORNER WORKING THE ALPHABET LEFT TO RIGHT AND NUMBERS TOP TO BOTTOM IN 24-INCH INCREMENTS USING BLACK LETTERS AND NUMBERS FOUR INCHES MINIMUM IN HEIGHT NOT PLACED
MORE THAN SIX INCHES BELOW THE CEILING. (REFER TO TN507 CALLOUT 6 FOR EXAMPLES).
THE CONTRACTOR SHALL INSTALL FIBER OPTIC CABLES, CONDUITS AND CABLE TRAYS PER THE MANUFACTURER ’S INSTALLATION REQUIREMENTS AND IN ACCORDANCE WITH ALL TIA AND BICSI TDMM EDITION 15 STANDARDS AND BEST PRACTICES FOR SEPARATION DISTANCE FROM SOURCES OF RFI AND EMI INTERFERENCE.
THE CONTRACTOR SHALL PROVIDE ALL COPPER CATEGORY 6A PATCH CORDS FOR ALL TRS IN SCOPE. TR CATEGORY 6A PATCH CORDS SHALL BE 50% 3 FEET IN LENGTH AND 50% 5 FEET IN LENGTH. 28 AWG STRANDED PATCH CORDS ARE NOT ALLOWED. CONTRACTOR SHALL PROVIDE 48 CATEGORY 6A PATCH CORDS FOR EACH 48-PORT SWITCH. JACKET COLORS SHALL BE BLUE OR WHITE. CONTRACTOR SHALL ALSO PROVIDE FIBER OPTIC PATCH CABLES (JUMPERS) FOR ALL FIBER OPTIC CABLES TERMINATED IN THE TRS. THESE CABLES MUST MATCH THE FIBER TYPE, OM4, OS1 AND OS2. FIBER OPTIC PATCH CABLES SHALL BE JACKETED WITH TWO (2) STRANDS EACH AND BE FACTORY TERMINATED WITH LC STYLE CONNECTORS. THE QUANTITY OF FIBER OPTIC PATCH CORDS SHALL MATCH THE NUMBER OF STRANDS TO EACH TR. FOR EXAMPLE, A TR HAVING 24 STRANDS OF OM4 FIBER OPTIC CABLE SHALL HAVE 12 OM4 FIBER OPTIC PATCH CABLES. IN THE TRS THE FIBER OPTIC PATCH CORDS WILL BE 5 FEET IN LENGTH AND BE JACKETED AS FOLLOWS: OM4
AQUA, OS1 AND OS2 YELLOW.
THE CONTRACTOR SHALL PROVIDE ALL FACTORY TERMINATED CATEGORY 6A CABLES IN QUANTITIES LISTED IN THE DRAWINGS WITHIN THE MCR. 28 AWG STRANDED PATCH CORDS ARE NOT ACCEPTABLE. CABLE LENGTHS SHALL BE DETERMINED BY THE CONTRACTOR AFTER ALL CABINETS AND WIRE MANAGEMENT HAVE BEEN INSTALLED. CABLES SHALL HAVE AS LITTLE SLACK AS POSSIBLE, AND THAT SLACK SHALL BE CONTAINED WITHIN THE VERTICAL WIRE MANAGERS. CABLE JACKET COLORS SHALL BE BLUE OR WHITE.
CONTRACTOR SHALL PROVIDE ALL FACTORY TERMINATED FIBER OPTIC PATCH CABLES REQUIRED AS LISTED IN THE DRAWINGS FOR THE MCR. THESE FIBER OPTIC CABLES, SHALL MATCH THE FIBER OPTIC CABLE TYPE. THESE CABLE TYPES ARE OM4, OS1 AND OS2. EACH PATCH CORD SHALL BE JACKETED TO MATCH THE FIBER TYPE, OM4 AQUA, OS1 AND OS2 YELLOW. EACH FIBER OPTIC PATCH CORD SHALL CONSIST OF TWO STRANDS OF THE CORRECT FIBER TYPE TERMINATED ON LC STYLE CONNECTORS. FIBER OPTIC PATCH CORD
LENGTHS SHALL NOT HAVE IN EXCESS OF 1 FOOT OF SLACK ON EACH END.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
19/05/2025 8:04:31 am
Autodesk Docs://528A7-22-700 VA Syracuse EHRM infrastructure Upgrades/VASY_SHEET_INDEX_EL_SDB.rvt
TNG001
ABBREVIATIONS, GENERAL NOTES, AND
SHEET INDEX
KG RTS/JGD
95% DESIGN DEVELOPMENT
05/19/2024
528A7-22-700EHRM INFRASTRUCTURE
UPGRADES - SYRACUSE VA
VA NY SYRACUSE
800 IRVING AVE., SYRACUSE, NY 13210
S H E E T I N D E XG E N E R A L N O T E SA B B R E V I A T I O N S
Revisions: Date:
TNG001 - ABBREVIATIONS, GENERAL NOTES, AND SHEET INDEX
TNG002 - TELECOMMUNICATIONS LEGENDS
TNG003 - ABBREVIATIONS, GENERAL NOTES, AND SHEET INDEX
01TN100Sa - BLDG 01 - LEVEL 00S - AREA A - TELECOMMUNICATIONS PLAN 01TN100Sb - BLDG 01 - LEVEL 00S - AREA B - TELECOMMUNICATIONS PLAN 01TN100Ba - BLDG 01 - LEVEL 00B - AREA A - TELECOMMUNICATIONS PLAN 01TN100Bb - BLDG 01 - LEVEL 00B - AREA B - TELECOMMUNICATIONS PLAN 01TN100Ga - BLDG 01 - LEVEL 00G - AREA A - TELECOMMUNICATIONS PLAN 01TN100Gb - BLDG 01 - LEVEL 00G - AREA B - TELECOMMUNICATIONS PLAN 01TN101a - BLDG 01 - LEVEL 01 - AREA A - TELECOMMUNICATIONS PLAN 01TN101b - BLDG 01 - LEVEL 01 - AREA B - TELECOMMUNICATIONS PLAN 01TN102a - BLDG 01 - LEVEL 02 - AREA A - TELECOMMUNICATIONS PLAN 01TN102b - BLDG 01 - LEVEL 02 - AREA B - TELECOMMUNICATIONS PLAN
01TN102.5 - BLDG 01 - LEVEL 02.5 - TELECOMMUNICATIONS PLAN
01TN103a - BLDG 01 - LEVEL 03 - AREA A - TELECOMMUNICATIONS PLAN 01TN103b - BLDG 01 - LEVEL 03 - AREA B - TELECOMMUNICATIONS PLAN 01TN104a - BLDG 01 - LEVEL 04 - AREA A - TELECOMMUNICATIONS PLAN 01TN104b - BLDG 01 - LEVEL 04 - AREA B - TELECOMMUNICATIONS PLAN 01TN105a - BLDG 01 - LEVEL 05 - AREA A - TELECOMMUNICATIONS PLAN 01TN105b - BLDG 01 - LEVEL 05 - AREA B - TELECOMMUNICATIONS PLAN 01TN106a - BLDG 01 - LEVEL 06 - AREA A - TELECOMMUNICATIONS PLAN 01TN106b - BLDG 01 - LEVEL 06 - AREA B - TELECOMMUNICATIONS PLAN
01TN107 - BLDG 01 - LEVEL 07 - TELECOMMUNICATIONS PLAN
01TN108 - BLDG 01 - LEVEL 08 - TELECOMMUNICATIONS PLAN
01TN109 - BLDG 01 - LEVEL 09 - TELECOMMUNICATIONS PLAN
01TN110 - BLDG 01 - LEVEL 10 - TELECOMMUNICATIONS PLAN
01TN111 - BLDG 01 - LEVEL 11 - TELECOMMUNICATIONS PLAN
02TN100B - BLDG 02 - LEVEL 00B - TELECOMMUNICATIONS PLAN
02TN100G - BLDG 02 - LEVEL 00G - TELECOMMUNICATIONS PLAN
02TN101 - BLDG 02 - LEVEL 01 - TELECOMMUNICATIONS PLAN
02TN102 - BLDG 02 - LEVEL 02 - TELECOMMUNICATIONS PLAN
16TN101 - BLDG 16 - LEVEL 01 - TELECOMMUNICATIONS PLAN
ROMETN100 - BLDG ROME - LEVEL 00 - TELECOMMUNICATIONS PLAN
01TN402a - BLDG 01 - LEVEL 02 - ENLARGED TELECOMMUNICATIONS PLANS 01TN400Ba - BLDG 01 - LEVEL 00B - ENLARGED TELECOMMUNICATIONS PLANS 01TN400Bb - BLDG 01 - LEVEL 00B - ENLARGED TELECOMMUNICATIONS PLANS 01TN400Bc - BLDG 01 - LEVEL 00B - ENLARGED TELECOMMUNICATIONS PLANS 01TN400Ga - BLDG 01 - LEVEL 00G - ENLARGED TELECOMMUNICATIONS PLANS 01TN400Gb - BLDG 01 - LEVEL 00G - ENLARGED TELECOMMUNICATIONS PLANS 01TN400Gc - BLDG 01 - LEVEL 00G - ENLARGED TELECOMMUNICATIONS PLANS 01TN400Gd - BLDG 01 - LEVEL 00G - ENLARGED TELECOMMUNICATIONS PLANS 01TN400Ge - BLDG 01 - LEVEL 00G - ENLARGED TELECOMMUNICATIONS PLANS 01TN401a - BLDG 01 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS 01TN401b - BLDG 01 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS 01TN401c - BLDG 01 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS 01TN401d - BLDG 01 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS 01TN402b - BLDG 01 - LEVEL 02 - ENLARGED TELECOMMUNICATIONS PLANS 01TN402c - BLDG 01 - LEVEL 02 - ENLARGED TELECOMMUNICATIONS PLANS 01TN402d - BLDG 01 - LEVEL 02 - ENLARGED TELECOMMUNICATIONS PLANS
01TN402.5 - BLDG 01 - LEVEL 02.5 - ENLARGED TELECOMMUNICATIONS PLANS
01TN403a - BLDG 01 - LEVEL 03 - ENLARGED TELECOMMUNICATIONS PLANS 01TN403b - BLDG 01 - LEVEL 03 - ENLARGED TELECOMMUNICATIONS PLANS 01TN404a - BLDG 01 - LEVEL 04 - ENLARGED TELECOMMUNICATIONS PLANS 01TN404b - BLDG 01 - LEVEL 04 - ENLARGED TELECOMMUNICATIONS PLANS 01TN404c - BLDG 01 - LEVEL 04 - ENLARGED TELECOMMUNICATIONS PLANS 01TN405a - BLDG 01 - LEVEL 05 - ENLARGED TELECOMMUNICATIONS PLANS 01TN405b - BLDG 01 - LEVEL 05 - ENLARGED TELECOMMUNICATIONS PLANS 01TN406a - BLDG 01 - LEVEL 06 - ENLARGED TELECOMMUNICATIONS PLANS 01TN406b - BLDG 01 - LEVEL 06 - ENLARGED TELECOMMUNICATIONS PLANS 01TN406c - BLDG 01 - LEVEL 06 - DATA CENTER - TELECOMMUNICATIONS PLAN 01TN406d - BLDG 01 - LEVEL 06 - DATA CENTER - HORIZONTAL DISTRIBUTION
OVERHEAD PLAN
01TN406e - BLDG 01 - LEVEL 06 - DATA CENTER - FIBER BACKBONE OVERHEAD PLAN 01TN407a - BLDG 01 - LEVEL 07 - ENLARGED TELECOMMUNICATIONS PLANS 01TN407b - BLDG 01 - LEVEL 07 - ENLARGED TELECOMMUNICATIONS PLANS 01TN408a - BLDG 01 - LEVEL 08 - ENLARGED TELECOMMUNICATIONS PLANS 01TN408b - BLDG 01 - LEVEL 08 - ENLARGED TELECOMMUNICATIONS PLANS 01TN409a - BLDG 01 - LEVEL 09 - ENLARGED TELECOMMUNICATIONS PLANS 01TN409b - BLDG 01 - LEVEL 09 - ENLARGED TELECOMMUNICATIONS PLANS
02TN400B - BLDG 02 - LEVEL 00B - ENLARGED TELECOMMUNICATIONS PLANS
16TN401 - BLDG 16 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS
ROMETN400 - BLDG ROME - LEVEL 00 - ENLARGED TELECOMMUNICATIONS PLANS
TN501 - TELECOMMUNICATIONS DETAILS
TN502 - TELECOMMUNICATIONS DETAILS
TN503 - TELECOMMUNICATIONS DETAILS
TN504 - TELECOMMUNICATIONS DETAILS
TN505 - TELECOMMUNICATIONS DETAILS
TN506 - TELECOMMUNICATIONS DETAILS
TN701 - TELECOMMUNICATIONS SCHEDULES
100% CONSTRUCTION
DOCUMENTS
THE CONTRACTOR SHALL INSTALL FIBER OPTIC CABLES, CONDUITS AND CABLE TRAYS PER THE MANUFACTURER ’S INSTALLATION REQUIREMENTS AND IN ACCORDANCE WITH ALL TIA AND BICSI TDMM EDITION 15 STANDARDS AND BEST PRACTICES FOR SEPARATION DISTANCE FROM SOURCES OF RFI AND EMI INTERFERENCE.
THE CONTRACTOR SHALL PROVIDE ALL COPPER CATEGORY 6A PATCH CORDS FOR ALL TRS IN SCOPE. TR CATEGORY 6A PATCH CORDS SHALL BE 50% 3 FEET IN LENGTH AND 50% 5 FEET IN LENGTH. 28 AWG STRANDED PATCH CORDS ARE NOT ALLOWED. CONTRACTOR SHALL PROVIDE 48 CATEGORY 6A PATCH CORDS FOR EACH 48-PORT SWITCH. JACKET COLORS SHALL BE BLUE OR WHITE. CONTRACTOR SHALL ALSO PROVIDE FIBER OPTIC PATCH CABLES (JUMPERS) FOR ALL FIBER OPTIC CABLES TERMINATED IN THE TRS. THESE CABLES MUST MATCH THE FIBER TYPE, OM4, OS1 AND OS2. FIBER OPTIC PATCH CABLES SHALL BE JACKETED WITH TWO (2) STRANDS EACH AND BE FACTORY TERMINATED WITH LC STYLE CONNECTORS. THE QUANTITY OF FIBER OPTIC PATCH CORDS SHALL MATCH THE NUMBER OF STRANDS TO EACH TR. FOR EXAMPLE, A TR HAVING 24 STRANDS OF OM4 FIBER OPTIC CABLE SHALL HAVE 12 OM4 FIBER OPTIC PATCH CABLES. IN THE TRS THE FIBER OPTIC PATCH CORDS WILL BE 5 FEET IN LENGTH AND BE JACKETED AS FOLLOWS: OM4
AQUA, OS1 AND OS2 YELLOW.
THE CONTRACTOR SHALL PROVIDE ALL FACTORY TERMINATED CATEGORY 6A CABLES IN QUANTITIES LISTED IN THE DRAWINGS WITHIN THE MCR. 28 AWG STRANDED PATCH CORDS ARE NOT ACCEPTABLE. CABLE LENGTHS SHALL BE DETERMINED BY THE CONTRACTOR AFTER ALL CABINETS AND WIRE MANAGEMENT HAVE BEEN INSTALLED. CABLES SHALL HAVE AS LITTLE SLACK AS POSSIBLE, AND THAT SLACK SHALL BE CONTAINED WITHIN THE VERTICAL WIRE MANAGERS. CABLE JACKET COLORS SHALL BE BLUE OR WHITE.
CONTRACTOR SHALL PROVIDE ALL FACTORY TERMINATED FIBER OPTIC PATCH CABLES REQUIRED AS LISTED IN THE DRAWINGS FOR THE MCR. THESE FIBER OPTIC CABLES, SHALL MATCH THE FIBER OPTIC CABLE TYPE. THESE CABLE TYPES ARE OM4, OS1 AND OS2. EACH PATCH CORD SHALL BE JACKETED TO MATCH THE FIBER TYPE, OM4 AQUA, OS1 AND OS2 YELLOW. EACH FIBER OPTIC PATCH CORD SHALL CONSIST OF TWO STRANDS OF THE CORRECT FIBER TYPE TERMINATED ON LC STYLE CONNECTORS. FIBER OPTIC PATCH CORD
LENGTHS SHALL NOT HAVE IN EXCESS OF 1 FOOT OF SLACK ON EACH END.
37.
38.
Location
VA NY SYRACUSE
800 IRVING AVE., SYRACUSE, NY 13210
08/22/2025
SECTION
SCALE
SECTION LETTER
SHEET WHERE
SECTION IS
TAKEN FROM
SECTION LETTER
DETAIL NUMBER
SHEET ON WHICH
DETAIL APPEARS
DETAIL AREA
XXX CONDUIT & WIRE TAG
(REFER TO CONDUIT
AND WIRE SCHEDULE)
XX FAULT CURRENT TAG
(3 PH, SYM AMPS)
KEY NOTE
XXX
FIGURE OR PHOTO
DETAIL NUMBER
IF PHOTO, ARROW
DENOTES DIRECTION
TAKEN
SHEET WHERE
DETAIL IS
TAKEN FROM
DETAIL/PLAN
DETAIL/PLAN NUMBER1
XXX
A
XXX
A
XXX
SHEET WHERE
SECTION IS
TAKEN FROM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
19/05/2025 5:15:27 am
Autodesk Docs://528A7-22-700 VA Syracuse EHRM infrastructure Upgrades/VA SYRACUSE - GENERAL SHEETS.rvt
TNG002
TELECOMMUNICATIONS LEGENDS
KG RTS/JGD
100% CONSTRUCTION
DOCUMENTS
05/19/2025
528A7-22-700EHRM INFRASTRUCTURE
UPGRADES - SYRACUSE VA
VA NY SYRACUSE
800 IRVING AVE., SYRACUSE, NY 13210
G E N E R A L S Y M B O L D I V 2 7 - L E G E N D D I V 2 8 - L E G E N D
OUTLET, COMBINATION TELEPHONE/DATA COMMUNICATION
CABLE TELEVISION LINE = CATV
CLOSED CIRCUIT TELEVISION LINE = CCTV. MINIMUM 1" [25mm] CONDUIT
FIBEROPTICS LINE = FO
SPEAKER, CEILING MOUNTED, "X" INDICATES THE TYPE, PROVIDE SCHEDULE ON LEGEND
SPEAKER, WALL MOUNTED, "X" INDICATES THE TYPE, PROVIDE SCHEDULE
ON LEGEND. MTD. 7'-6" [2286mm] AFF UNLESS OTHERWISE NOTED.
OUTLET DATA OR VOIP TELEPHONE, "X" INDICATES NUMBER OF OUTLET PORTS. BOX AROUND
SYMBOL INDICATES FLOOR MOUNTED. "Y" INDICATES AS FOLLOWS:
P = POLE/PEDESTAL MOUNTED
F = FURNITURE MOUNTED
C = OUTLET WITH NEW CONDUIT INSTALLED, 3/4" MINIMUM UNLESS OTHERWISE STATED
TELEPHONE LINE = T
INTERCOM LINE = I. MINIMUM 3/4" [19mm] CONDUIT.
SOUND LINE = S
NURSE CALL LINE = NC. MINIMUM 3/4" [19mm] CONDUIT.
OUTLET; LETTER INDICATES AS FOLLOWS:
A = AUDIO V = VIDEO I = INTERCOM
RADIO CONDUIT RUN, MINIMUM 3/4" [19mm] CONDUIT.
RADIO CHANNEL SELECTOR FACILITIES, MTD. 4'-6" [1372mm] AFF UNLESS OTHERWISE NOTED.
SPEAKER PROGRAM SELECTOR SWITCH & VOLUME
CONTROL MTD. 4'-6" [1372mm] AFF UNLESS OTHERWISE NOTED.
OUTLET, TELEVISION
BLANK = 4 11/16" [119mm] MASTER ANTENNA OUTLET BOX W/BLANK
COVER, MTD. 18" [457mm] AFF UNLESS OTHERWISE NOTED.
C = CAMERA (CCTV SYSTEM), MTD 18" [457mm] AFF
M = MONITOR (CTTV SYSTEM).
NURSE'S CALL MASTER STATION MTD ON
NURSE'S COUNTER TOP UNLESS OTHERWISE NOTED.
NURSE CALL TERMINAL CABINET.
NURSE CALL STATION.
2 = DUPLICATE FACILITIES FOR TWO BEDS (SEPARATE INDICATORS AT MASTER
STATION) MTD 5'-0" [1524mm] AFF UNLESS OTHERWISE NOTED.
D = DUTY STATION. MTD 5'-0" [1524mm] AFF UNLESS NOTED OTHERWISE.
E = MTD 6'-0" [1829mm] AFF FOR SHOWER LOCATION, MTD 4'-6" [1372mm] AFF FOR TUB
LOCATION, & MTD 3'-0" [914mm] AFF FOR TOILET LOCATION.
P = PSYCHIATRIC CORRIDOR STATION WITH KEY SWITCH
S = AUDIO VISUAL MALL STATION (STAFF) MTD 5'-0" [1524mm] AFF UNLESS OTHERWISE
NOTED.
U = UTILITY CALL STATION, MTD 5'-0" [1524mm] AFF UNLESS OTHERWISE NOTED.
NURSE CALL STATION.
2 = NURSE'S CALL DOME LIGHT (SUFFIX INDICATES No OF
LAMP) MTD 6" [152mm] ABOVE DOOR.
D = CORRIDOR DOME LIGHT.
I = AUXILIARY INTERSECTIONAL DOME LIGHT.
TELEPHONE TERMINAL CABINET
TELEPHONE BACKBOARD (WALL MOUNTED)
3-POLE TWIST-LOCK RECEPTACLE FOR MICROPHONE, MTD. 4'-6" 1372mm] AFF.
REMOTE DICTATING OUTLET MTD 1'-6" [457mm] AFF. UNLESS OTHERWISE NOTED.
INTERCOM STATION (REFER TO SPECS. FOR FUNCTIONAL
OPERATION OF INSTRUMENT & TYPE REQUIRED).
INTERCOM STAFF STATION.
TELECOMMUNICATIONS MANHOLE
DATA/COMMUNICATION AUDIO DEVICE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BELL C-CHIME H-HORN K-KLAXON
L-LISTEN-IN M-MICROPHONE S-SOUNDER S-SPEAKER Z-BUZZER
BI-STATIC BEAM SENSOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
I-INFRARED M-MICROWAVE
F=FUNCTION
RX-RECEIVE TX-TRANSMIT
BIOMETRICS ACCESS CONTROL DEVICE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
F-FINGER PRINT H-HAND GEOMETRY I-EYE IRIS
R-EYE RETINA V-VOICE
CARD ACCESS READER; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BARCODE F-ELEVATOR FLOOR CALL H-ELEVATOR HALL CALL
M-MAG STRIP P-PROXIMITY S-SMART CARD
T-TOKEN
CARD READER WITH KEYPAD; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
CARD READER WITH TIME AND ATTENDANCE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
CENTRAL PROCESSING UNIT
CONTROL PANEL; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BURGLAR D-DOOR F-FIRE P-PERIMETER
ELECTRONIC LOCK; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
D-DEADBOLT H-HYBRID L-LATCH SET M-MAGNETIC S-STRIKE
EXIT DEVICE; LETTER INDICATES AS FOLLOWS:
T=TECHNOLOGY/TYP E
D-DELAYED EGRESS E-ELECTRIFIED M-MECHANICAL X-HIGH SECURITY
FIBER OPTIC MODULE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
R-RECEIVER T-TRANSCEIVER TX-TRANSMITTER
FIELD PANEL; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
A-ALARM C-CARD READER
GLASS BREAKAGE SENSOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
A-AUDIO S-SHOCK
INTERCOM; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
M-MASTER S-SUBSTATION
KEYBOARD
KEYPAD DEVICE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
MONITOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
D-DATA G-GRAPHIC M-MULTISCREEN V-VIDEO
MOTION DETECTOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
D-DUAL TECHNOLOGY IR-INFRARED M-MICROWAVE U-ULTRASONIC
X-REQUEST-FOR-EXIT
RECORDER; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
A-AUDIO D-DIGITAL V-VIDEO
SECURITY ACCESS, ANNUNCIATOR PANEL
SECURITY ACCESS, BUZZER. MTD 1'-6" [457mm] AFF
UNLESS OTHERWISE NOTED
SECURITY ACCESS, CONTROL UNIT WITH
CLOSED CIRCUIT TELEVISION CAMERA
SECURITY ACCESS, GENERIC "X" INDICATES THE
TYPE, PROVIDE SCHEDULE OR LEGEND
SECURITY ACCESS, HORN OR SIREN
SECURITY ACCESS, OUTDOOR MICROWAVE TRANSMISSION UNIT
SECURITY ACCESS, PANIC ALARM
SECURITY ACCESS, VIDEO CAMERA WITH LENS
M = MOTION DETECTOR
PZ = MOTION DETECTOR WITH PAN AND ZOOM
PTZ= MOTION DETECTOR WITH PAN, TILT, AND ZOOM
SECURITY ACCESS, VOLUMETRIC SENSOR
SECURITY SCREEN WITH ALARM; LETTER INDICATES AS FOLLOWS:
T=TECHNOLOGY/TYPE
B-BLIND S-SHADE
SECURITY WINDOW SCREEN; LETTER INDICATES AS FOLLOWS:
T=TECHNOLOGY/TYPE
B-BLIND
VIDEO CONTROL KEYBOARD
VIDEO MOTION DETECTOR
SECURITY ACCESS, PANNING CAMERA TRAVERSE ANGLE
C = CEILING MOUNTED
SECURITY ACCESS, SENSOR, BURIED VEHICULAR
SECURITY ACCESS, SWITCH, BALANCED MAGNETIC CONTROL
SECURITY ACCESS, TELEPHONE HANDSET
SECURITY ACCESS, VIDEO CAMERA WITH LENS, ANGLE OF VIEW
ALARM, CHECK VALVE
ALARM, FIRE, COMMUNICATOR
ALARM, FIRE, PANEL; LETTERS INDICATE AS FOLLOWS:
FACC = CENTRAL CONSOLE FACP = CONTROL PANEL
MFACP= MASTER CONTROL PANEL FAAP = ANNUNCIATOR PANEL
ALARM, FIRE, MANUAL PULL STATION
ALARM, GONG
ALARM, HORN/LIGHT, ONE ASSEMBLY WITH CHIME
ALARM, HORN/LIGHT, SEPARATE ASSEMBLY
ALARM, LAMP LIGHT, SIGNAL LIGHT, STROBE
ALARM, MANUAL CONTROL
ALARM, MINI
HORN
ALARM, SPRINKLER SYSTEM WATER FLOW BELL
ALARM, TAMPER SWITCH
DETECTION, GAS
DETECTION, SMOKE CONTROL AND PRESSURE PANEL
DETECTION SWITCH, ABORT
DETECTION SWITCH, VALVE TAMPER
DETECTOR, FLAME FLICKER
DETECTOR, FLOW SWITCH
DETECTOR, HEAT
DETECTOR, HEAT; LETTER INDICATES AS FOLLOWS:
R/T = COMBINATION F = FIXED TEMPERATURE RISE
R/C = RATE COMPENSATION R = RATE OF
DETECTOR; LETTER INDICATES AS FOLLOWS:
BLANK = SMOKE DETECTOR
H = HEAT SMOKE
I = IONIZATION SMOKE
P = PHOTOELECTRIC SMOKE
IH = IONIZATION AND HEAT SMOKE
IP = IONIZATION AND PHOTOELECTRIC SMOKE
PH = PHOTOELECTRIC AND HEAT SMOKE
IPH = IONIZATION, PHOTOELECTRIC, AND HEAT
DETECTOR, SMOKE, FOR DUCT
DETECTOR, SWITCH LEVEL
PUSH BUTTON; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BELL PUSH D-DURESS P-PANIC R-DOOR RELEASE
X-REQUEST-FOR-EXIT
CODE ONE CONTROL AND ALARM STATION. MTD 5'-0"
AFF UNLESS OTHERWISE NOTED.
CODE ONE TERMINAL CABINET.
CODE ONE ANNUNCIATOR PANEL.
CODE ONE BEDSIDE STATION.
CODE ONE DUTY STATION, MTD 5'-0" AFF UNLESS
OTHERWISE NOTED.
ALARM, FIRE; LETTERS INDICATE AS FOLLOWS:
BATT = BATTERIES CHR = CHARGER FAR = RECORDER
ALARM, FIRE, VALVE SUPERVISORY SWITCH.
ALARM, FIRE, TERMINAL CABINET.
ALARM, FIRE, POST INDICATOR VALVE.
ALARM, TRANSPONDER OR TRANSMITTER
ALARM, VOICE COMMUNICATION PANEL
FIRE ALARM STATION, MANUAL PULL
FIRE ALARM LINE = FA
ELECTROMAGNETIC TYPE DOOR HOLDER OUTLET
CITY FIRE ALARM MASTER STATION MTD 5'-6" [1676mm] AFF UNLESS NOTED.
FIRE ALARM TRANSMITTER (BASE LOOP) NUMERALS DENOTE CODE.
FIRE ALARM TROUBLE TRANSMITTER (BASE LOOP) NUMERALS DENOTE CODE.
ALARM, HORN/LIGHT, ONE ASSEMBLY C = WITH CHIME
360°
40°
X
M PTZ
FAT
2-4-6
FAT
2-4-6
AP
NIP
NIT
NIA
NI
NID
FAC
FACP
P
C
BATT
OSY
FATC
PIV
M
TS
FTR
SCCP
HD
R/T
HD
H
FS
N
TTB
A
S X
S X
M
N
R M
C
DH
R
R M
NCS
NCT
S
WB
M
T
M
T
M
F
T
M
T
T
M
M
M
M
T
T
M
T
M
T
M
T
M
T
M
M
T
M
T
M
T
M
T
T
T
CP
EPO
FA
CATV
CCTV
FO
T
I
S
NC
R
= 3 - BUTTON EMERGENCY STATION. MTD 5'-0" AFF.3
WIRELESS ACCESS POINT.
"S" = STAFF; "G" = GUEST. IF NOTED LIKE THIS "S,G", CONTRACTOR SHALL PROVIDE
(2) SEPARATE WAPs, (1) WAP FOR EACH SERVICE.
X X
XWAP
CONDUIT OR EQUIPMENT TO BE REMOVED
CONDUIT CONCEALED IN WALL, CEILING, UNDER FLOOR, IN
FLOOR
SLAB, OR ROUTED UNDERGROUND
CONDUIT CONCEALED WHERE POSSIBLE, OTHERWISE EXPOSED
EXTRA-HARD USAGE FLEXIBLE CORD
FLEXIBLE CONDUIT
CONDUIT TURNED UP OR TOWARD
CONDUIT TURNED DOWN OR AWAY
CONDUIT CAPPED
Y
M-MULLION
Y
THESE ARE GENERAL LEGENDS. NOT ALL SYMBOLS MAY BE SHOWN.
REFERENCE PLANS FOR ALL UTILIZED SYMBOLS.
P/D POWER/DATA POLE
OUTLET TELEPHONE; "X" INDICATES NUMBER OF OUTLET PORTS. "Y" INDICATES AS FOLLOWS:
BLANK=EXISTING CONDUIT WITH NEW CAT6A CABLE
P=POLE/ PEDESTAL MOUNTED
F=FURNITURE MOUNTED
C=OUTLET WITH NEW CONDUIT INSTALLED, 3/4" MINIMUM UNLESS OTHERWISE STATED
"Z" INDICATES AS FOLLOWS:
J = JACK TYPE W = WALL TYPE A = ANALOG PORT
Z Y
X
P
P
VERTICAL CEILING/STRUCTURE PENETRATION
HORIZONTAL WALL/STRUCTURE PENETRATION
HORIZONTAL CABLE SLEEVE
VERTICAL CABLE SLEEVE
C
Revisions: Date:
100% CONSTRUCTION
DOCUMENTS
U FIBER OPTIC UMBILICAL CABLE
Location
VA NY SYRACUSE
800 IRVING AVE., SYRACUSE, NY 13210
U
AREA SHOWN
JI K LHFE L.1 M N P Q R Si.2 K.9
17.1
16.1
19.1
DATA OUTLETS AND DEVICES IN THIS AREA SHALL BE SERVED
FROM TELECOMMUNICATIONS ROOM SL06 ON LEVEL 00B.
AREA A
AREA B
SHAFT 3
DC429
MECHANICAL ROOM
CL55
AREA A
- 1/16" = 1'-0"
1 BLDG 01 - LEVEL 00S - AREA A - TELECOMMUNICATIONS PLAN
TRUE
NORTH8'0 16' 32'
PROJECT
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
5/15/2025 12:50:41 PM
Autodesk Docs://528A7-22-700 VA Syracuse EHRM infrastructure Upgrades/VASY_01.00S_EL_SDB.rvt
01TN100Sa
BLDG 01 - LEVEL 00S - AREA A -
TELECOMMUNICATIONS PLAN
SHM/LRL RTS/JGD
100% CONSTRUCTION
DOCUMENTS
05/19/2025
528A7-22-700EHRM INFRASTRUCTURE
UPGRADES - SYRACUSE VA
VA NY SYRACUSE
800 IRVING AVE., SYRACUSE NY, 13210
Revisions: Date:
GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL DATA DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL
RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED
SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS
TO EXTEND TO ASSOCIATED TR AS REQUIRED.
A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF
A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 3/4" CONDUIT FROM NEW 4"-SQUARE
BACKBOX TO ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING
FROM OUTLET TO TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, PROVIDE J-
HOOKS AS REQUIRED.
PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES FOR INSTALLATION WHERE AIR ASSISTED FIBER IS NOT POSSIBLE.
PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL
IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.
ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN
RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL
SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;
ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS
REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.
CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE DIAGRAMMATICAL
EXACT ROUTING WITH EXISTING CONDITIONS, ARCHITECTURAL FEATURES,
MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND ANY OTHER OBSTRUCTIONS
PRIOR TO INSTALLATION.
CONTRACTOR TO BID AN ADDITIONAL 10% OF THE TOTAL NUMBER OF WAO'S PER
FLOOR. A WAO IS DEFINED AS TWO CAT6A OUTLETS.
THE CONTRACTOR SHALL BID AND INSTALL CAT6A CABLE WITH AN OD NOT
GREATER THAN 0.250 INCH (6.35mm) (4) CAT6A CABLES WITH AN 0.250 INCH (6.35mm)
OD OR SMALLER CAN BE INSTALLED IN A ¾” CONDUIT SUPPORTING A 40% FILL
RATIO.
KEY PLAN
KEY NOTES
1 PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO
REPLACE EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT
SHALL REMAIN AND BE UTILIZED TO FEED NEW CABLING; REFERENCE DETAIL '1' ON
SHEET TN501 AND THE GENERAL NOTES ON THIS SHEET FOR ADDITIONAL
INFORMATION. COORDINATE WITH VA FOR EXACT OUTLET PLACEMENT.
100% CONSTRUCTION
DOCUMENTS
Location
VA NY SYRACUSE
800 IRVING AVE., SYRACUSE, NY 13210
Checked
KG08/22/2025
AREA SHOWN
AREA A
AREA B
DATA OUTLETS AND DEVICES IN THIS AREA SHALL BE SERVED
FROM TELECOMMUNICATIONS ROOM SL06 ON LEVEL 00B.
JI K LHFE L.1 M N P Q R Si.2 K.9
SU STEAM ROOM
BL21
SHAFT 2
DC430
SHAFT 1
DC431
DV1N2
- 1/16" = 1'-0"
1 BLDG 01 - LEVEL 00S - AREA B - TELECOMMUNICATIONS PLAN
TRUE
NORTH8'0 16' 32'
PROJECT
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
5/15/2025 12:50:42 PM
Autodesk Docs://528A7-22-700 VA Syracuse EHRM infrastructure Upgrades/VASY_01.00S_EL_SDB.rvt
01TN100Sb
BLDG 01 - LEVEL 00S - AREA B -
TELECOMMUNICATIONS PLAN
SHM/LRL RTS/JGD
100% CONSTRUCTION
DOCUMENTS
05/19/2025
528A7-22-700EHRM INFRASTRUCTURE
UPGRADES - SYRACUSE VA
VA NY SYRACUSE
800 IRVING AVE., SYRACUSE, NY 13210
Revisions: Date:
GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL DATA DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL
RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED
SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS
TO EXTEND TO ASSOCIATED TR AS REQUIRED.
A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF
A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 3/4" CONDUIT FROM NEW 4"-SQUARE
BACKBOX TO ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING
FROM OUTLET TO TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, PROVIDE J-
HOOKS AS REQUIRED.
PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES FOR INSTALLATION WHERE AIR ASSISTED FIBER IS NOT POSSIBLE.
PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL
IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.
ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN
RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL
SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;
ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS
REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.
CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE DIAGRAMMATICAL
EXACT ROUTING WITH EXISTING CONDITIONS, ARCHITECTURAL FEATURES,
MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND ANY OTHER OBSTRUCTIONS
PRIOR TO INSTALLATION.
CONTRACTOR TO BID AN ADDITIONAL 10% OF THE TOTAL NUMBER OF WAO'S PER
FLOOR. A WAO IS DEFINED AS TWO CAT6A OUTLETS.
THE CONTRACTOR SHALL BID AND INSTALL CAT6A CABLE WITH AN OD NOT
GREATER THAN 0.250 INCH (6.35mm) (4) CAT6A CABLES WITH AN 0.250 INCH (6.35mm)
OD OR SMALLER CAN BE INSTALLED IN A ¾” CONDUIT SUPPORTING A 40% FILL
RATIO.
KEY PLAN
KEY NOTES
AREA B
1 PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO
REPLACE EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT
SHALL REMAIN AND BE UTILIZED TO FEED NEW CABLING; REFERENCE DETAIL '1' ON
SHEET TN501 AND THE GENERAL NOTES ON THIS SHEET FOR ADDITIONAL
INFORMATION. COORDINATE WITH VA FOR EXACT OUTLET PLACEMENT.
100% CONSTRUCTION
DOCUMENTS
Location
VA NY SYRACUSE
800 IRVING AVE., SYRACUSE, NY 13210
Checked
KG08/22/2025
180°
180°
180°
180°
180°
0°
180°
180° 180°
180°
180°
0°
180°
180° 180°
180°
180°
180°
WAP
WAP
WAP
WAP
WAP
WAP WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
W
AP
WAP
WAP
WAP
WAP WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
01TN400Bb
(CL45 SWITCH), FIBER HOMERUN
TO CCTV CLOSET C134
DV1
N2
N2
DV1
DD2 DV1
N2
DV1
N2
DV1
DD3
N2
DV1
DD3
N2
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
DV1
DD2
N2
DV1
DD2
N2
DV1
N2
N2
N2N2N2
DV1
DD2
DV1
DD2
DV1
DD2
N2
DV1
DD2
DV1
DD2
N2
DV1
DD2
N2
N2
DV1
DD2
N2 N2 N2
N2
DV1
DD2
DV1
DD2 DV1
DD2
DV1
DD2
DV1
DD2
N2DV1
DD2
N2
DV1
DD2
N2
N2
N2
N2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
N2
DV1
DD2
DV2
DD2
N2N2
DV1
DD2
DV1
DD2
N2
DV1
N2
DV1
N2
DV1
N2
DV1
N2
DV1
DV1
N2
N2
DV1
N2
DV1
N2
DV1
DD3
DV1
DD1
N2
N2
DV1
DD2
N2
DV1
DD3
N2
DV1
DD3
N2N2
DV1
AREA B
AREA A
01TN400Bb
01TN400Bb
01TN400Bb
01TN400Bc
01TN400Bc
N2
N2
N2
DD3
DD3
DD3
N2
N2
DV1
N2
DV1
DD3
N2
DV1
DD3
N2
DV1
DD2
DV1
DD2N2
N2
DV1
DD2
N2
DV1
N2
N2
DV1
JI K L
HFE L.1 M N P Q R S
17.1
16.1
19.1 i.2 K.9
DATA OUTLETS AND DEVICES IN THIS AREA SHALL BE
SERVED FROM TELECOMMUNICATIONS ROOM SL06.
TYP.
2 2
DV1
DD1
N2
DV1
DD2
N2
DV1
DD2
N2 N2 N2 N2 N2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
DV2
DD2
DV2
DD2
DV2
DD2
DV2
DD2
DV2
DD2
N2 N2
DV1
DD2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2 N2
DV1
DD2
N2
DV1
DD2
DV1
DD1
N2
DV2
DD2
N2
DV1
DD2
N2
N2
DV1
DD2 N2
DV1
DD2
N2
DV1
DD2
N2
DV1
N2
DV1
DV1
N2
DV1
N2
U
WATERMETER
SL64
89 SF
STAIRS 18
NL18
220 SF
ELEVATOR
NL17
255 SF
ELECT
CLOSET
SL57
59 SF
Room
SL16
1095 SF
LOADING
SL55
1531 SF
HEAT
EXCHANGER
SL42
375 SF
SHREDDING
SL44
373 SF
SOILED
SL46
552 SF
CORRIDOR
SL58
282 SF
SOILED
SL52
525 SF
STEAM
SL50
379 SF
BATTERY
CHARGE
SL41
241 SF
ELEV.
MACHINE
NL20
115 SF
ELEVATOR
NL21
230 SF
DOMESTIC
WATER
SL51
328 SF
STAIR 17
SL 17
243 SF
DISPATCH
SL23A
246 SF
SOILED LINEN
CARTS
SL47
314 SF
GENERAL
STORAGE
SL23
1590 SF
GROUNDS
SL49
1061 SF
ELECT
CLOSET
SL61
78 SF
UPS ROOM
SL62
291 SF
SWITCH GEAR
SL60
386 SF
HVAC
SL19
499 SF
LOCK SHOP
SL17
410 SF
LOW VOLTAGE
SL63
1039 SF
UNIFORM
SL15
414 SF
SWITCHGEAR
SL20
668 SF
EMERGENCY
GENERATOR
SL14
1170 SF
MECHANICAL
ROOM
SL64A
2409 SF
ELECT
CLOSET
SL04
78 SF
PBX ROOM
SL06
386 SF
WOMENS
SL08
145 SF
MENS
SL12
111 SF
HK
SL10
77 SF
STAIR 4
BS4
170 SF
SHAFT 3
CL55C
118 SF
EMS STORAGE
CL56
330 SF MEZZANINE
FLOOR
CL55B
300 SF
MECHANICAL
ROOM
CL55A
295 SF
MECHANICAL
ROOM
DC428
609 SF
AM&M
CL51
192 SF
TRAINING
CL54
148 SF
SUPERVISOR
CL52
246 SFEMS SUPPLY
CL50
183 SF
TSS OFFICE
CL48
505 SF
TSS OFFICE
CL49
431 SF
AM&M
CL47
758 SF
ELECTRICAL
CL17
289 SFNUTS & BOLTS
CL14
156 SF
CARPENTRY
CL16
2168 SF
LAUNDRY
CHUTE
CL18
65 SF
FLOOR
SCRUBBER
CL20
116 SF
ELECT
CLOSET
CL40
60 SF
MASONRY
CL62
76 SF
STAIR 3
BS3
251 SF
CLOSET
CL19B
23 SF
CARPENTRY
CL19
958 SF
CARPENTRY
CL19A
162 SF
BIO MEDICAL
CL21
1095 SF
CAVE
NL33B
383 SF
LOCKER
NL33A
199 SF
FABRICATION
CL24
415 SF BIO MEDICAL
CL23
373 SF
PLUMBING
CL25
383 SF
LOCKER
CL26
203 SF
PLUMBING
CL27
835 SF
OFFICE
CL27A
99 SF
ELECTRICAL
CL28
493 SF
LOCKSMITH
CL29
164 SF
PAINTERS
CL30
788 SF
MECHANICAL
NL30A
971 SF
MECHANICAL
NL34
243 SF
CAVE
NL33
755 SF
TRANSFORMER
NL31A
722 SF
CHILLER
NL31
3586 SF
ELEVATOR
SHAFT
S5
75 SF
CORRIDOR
NL19
2274 SF
ELEVATOR
LOBBY
ELEV-00B
1842 SF
2" SLEEVE TO
TR SG95
AREA SHOWN
AREA A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
19/05/2025 4:58:04 am
Autodesk Docs://528A7-22-700 VA Syracuse EHRM infrastructure Upgrades/VASY_01.00B_EL_SDB.rvt
01TN100Ba
BLDG 01 - LEVEL 00B - AREA A -
TELECOMMUNICATIONS PLAN
KG RTS/JGD
100% CONSTRUCTION
DOCUMENTS
05/19/2025
528A7-22-700EHRM INFRASTRUCTURE
UPGRADES - SYRACUSE VA
VA NY SYRACUSE
800 IRVING AVE., SYRACUSE, NY 13210
- 1/16" = 1'-0"
1 BLDG 01 - LEVEL 00B - AREA A - TELECOMMUNICATIONS PLAN
0 30' 60'
PROJECT
NORTH
TRUE
NORTH
GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL DATA DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL
RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED
SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS
TO EXTEND TO ASSOCIATED TR AS REQUIRED.
A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF
A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 3/4" CONDUIT FROM NEW 4"-SQUARE
BACKBOX TO ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING
FROM OUTLET TO TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, PROVIDE J-
HOOKS AS REQUIRED.
PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES FOR INSTALLATION WHERE AIR ASSISTED FIBER IS NOT POSSIBLE.
PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL
IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.
ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN
RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL
SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;
ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS
REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.
CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE DIAGRAMMATICAL
EXACT ROUTING WITH EXISTING CONDITIONS, ARCHITECTURAL FEATURES,
MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND ANY OTHER OBSTRUCTIONS
PRIOR TO INSTALLATION.
CONTRACTOR TO BID AN ADDITIONAL 10% OF THE TOTAL NUMBER OF WAO'S PER
FLOOR. A WAO IS DEFINED AS TWO CAT6A OUTLETS.
THE CONTRACTOR SHALL BID AND INSTALL CAT6A CABLE WITH AN OD NOT
GREATER THAN 0.250 INCH (6.35mm) (4) CAT6A CABLES WITH AN 0.250 INCH (6.35mm)
OD OR SMALLER CAN BE INSTALLED IN A ¾” CONDUIT SUPPORTING A 40% FILL
RATIO.
KEY PLAN
KEY NOTES
PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO REPLACE
EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT SHALL REMAIN
AND BE UTILIZED TO FEED NEW CABLING; REFERENCE DETAIL '1' ON SHEET TN501 AND
THE GENERAL NOTES ON THIS SHEET FOR ADDITIONAL INFORMATION. COORDINATE
WITH VA FOR EXACT OUTLET PLACEMENT.
EXISTING WIRELESS ACCESS…