ATTACHMENT 7 - Drawings Structural Updated 5-20-26.pdf
PDF 5 MB Posted
- Solicitation number
- 36C77626B0009
About this file
This document is a set of structural design and construction specifications and details for a federal building construction project, specifically addressing concrete, structural steel, steel deck, and associated construction requirements.
The specifications establish design criteria, material standards, and construction procedures for multiple building systems. Concrete work requires compliance with ACI standards, with specified compressive strengths of 3,500 PSI for general use and 7,000 PSI for grout and drypack applications. Construction joints in slabs on deck must be located per specific criteria, with rough joints required at all construction joint locations. Electrical conduit installation in slabs is restricted to maximum 1.5-inch outside diameter, with specified spacing, cover, and placement requirements; conduit installation in parking level slabs and weather-exposed slabs is prohibited. No loads shall be placed on concrete slabs within seven days of placement, and the contractor must notify the architect 48 hours prior to all concrete pours and survey work within 48 hours of placement. Structural steel must conform to ASTM A992 (Fy=50 KSI), ASTM A913 Grade 65 (Fy=65 KSI), or ASTM A36 (Fy=36 KSI) standards and be fabricated per AISC detailing specifications. All exposed structural steel shall be hot-dip galvanized per ASTM A123 G60 after fabrication, with abraded areas touched up using cold galvanizing compound per ASTM A780. Steel deck design and installation must comply with the Steel Deck Institute (SDI) specification, with deck sizes and gauges based on current Vulcraft Verco catalogs for gravity design loads and unshored construction spans. Roof deck shall be galvanized per ASTM A653 with minimum G60 coating and prime painted gray per ASTM A1008. Floor deck shall be galvanized per ASTM A653 with minimum G60 coating, with conduit placement, penetrations, and embeds requiring structural engineer coordination. Special inspections and testing requirements are mandated per International Building Code Chapter 17, including post-installed anchor inspection, concrete reinforcement verification, and material identification documentation. The testing and inspection agency must submit proposed testing programs for approval at least two weeks prior to work commencement and furnish inspection reports to the building official, owner, architect, structural engineer, and general contractor within 48 hours of inspected work.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
4/
/2
4:
:1
PM
Au to de sk
D oc s:
//5
A7
-2 2-
VA
S yr ac us e
EH
R
M in fra st ru ct ur e
U pg ra de s/
VA
SY
_0
1_
ST
_I M
EG
.rv t
S000
GENERAL NOTES
EB GRB
100% CONSTRUCTION
DOCUMENTS
08/29/2025
528A7-22-700EHRM INFRASTRUCTURE
UPGRADES - SYRACUSE VA
VA NY SYRACUSE
800 IRVING AVE., SYRACUSE, NY 13210
Revisions: Date:
DESIGN CRITERIA
STRUCTURE HAS BEEN DESIGNED TO COMPLY WITH 2020 BUILDING CODE OF NEW YORK
STATE (IBC 2018) AND SUBSEQUENT REFERENCE STANDARDS.
1.
RISK CATEGORY: IV2.
LIVE LOADS: LIVE LOAD REDUCTION USED AS ALLOWED PER CODE3.
ROOF TYPICAL 20 PSF
FLOOR
TYPICAL MCR FLOOR 250 PSF (UNREDUCIBLE)
UPS LOBBY FLOOR 100 PSF (UNREDUCIBLE)
UPS ROOM 300 PSF (UNREDUCIBLE)
OTHER HANDRAILS
MAX OF 50 PLF HORIZ PLUS
50 PLF VERT OR 200 LBS IN
ANY DIRECTION, APPLIED AT
TOP OF RAILING
MECHANICAL UNITS: THE CONTRACTOR SHALL CONFIRM THE ACTUAL MECHANICAL UNITS
PURCHASED ARE OF WEIGHT AND SIZE SUCH THAT:
4.
a.
b.
c.
THE UNIT WEIGHT IS LESS THAN OR EQUAL TO WEIGHT LISTED ON PLAN.
THE UNIT LENGTH IS LESS THAN 15 FEET. IF UNIT LENGTH IS GREATER THAN 15
FEET, SNOW DRIFT ON ROOF SHALL BE ACCOUNTED FOR.
THE TOTAL SUPERIMPOSED LOAD UNDER EACH UNIT DOES NOT EXCEED THE LIVE
LOAD FOR WHICH THE FLOOR WAS DESIGNED IN THE FLOOR AREA WHERE THE
UNIT IS LOCATED AS INDICATED BY THE EQUATION BELOW:
TOTAL SUPERIMPOSED
LOAD UNDER UNIT =
TOTAL EQUIPMENT WEIGHT
/ UNIT FOOTPRINT AREA =
INDICATED SERVICE LEVEL
DESIGN LIVE LOAD
TOTAL EQUIPMENT WEIGHT
OPERATING WEIGHT OF UNIT + CONCRETE
HOUSEKEEPING PAD + INTERTIA BLOCK + OTHER
ANCILLARY ITEMS ASSOCIATED WITH THE EQUIPMENT
UNIT FOOTPRINT AREA = EFFECTIVE AREA OF UNIT OR HOUSEKEEPING PAD,
WHICHEVER IS LARGER
EFFECTIVE AREA = (LENGTH + 6 FEET) x (WIDTH + 6 FEET)
CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER PRIOR TO CONSTRUCTION ON
THE LOCATION OF ANY MECHANICAL UNITS WHERE THE SUPERIMPOSED LOAD UNDER
THE UNIT EXCEEDS THE INDICATED DESIGN SIZE AND LOAD FOR THE ROOF AND/OR LIVE
LOAD FOR THE FLOOR AS INDICATED ON THE PLAN.
SNOW:5.
GROUND SNOW 55 PSF
SNOW EXPOSURE FACTOR 1.0
THERMAL FACTOR 1.0
IMPORTANCE FACTOR 1.2
FLAT-ROOF SNOW 46 PSF
DESIGN SNOW 46 PSF
SEE S002 FOR SNOW DRIFT PLAN.
SEISMIC:6.
SEISMIC DESIGN CATEGORY C
IMPORTANCE FACTOR 1.50
SITE CLASS D (DEFAULT)
SS 0.14 g
S1 0.051 g
SDS 0.15 g
SD1 0.081 g
SEISMIC FORCE RESISTING SYSTEM MOMENT FRAME
RESPONSE MODIFICATION COEFFICIENT, R 3
ANALYSIS PROCEDURE EQUIVALENT LATERAL FORCE
WIND:7.
BASIC WIND SPEED VULT = 121MPH
EXPOSURE CLASS B
INTERNAL PRESSURE
COEFFICIENT, GCpi ±0.18
MAIN WIND FORCE
PRESSURE
(STRENGTH LEVEL)
30.5 PSF
COMPONENTS & CLADDING:
ROOF COMPONENTS ZONE 1 ZONE 2 ZONE 3
SUPPORT BEAMS
(A>100 SF) -39 PSF -64 PSF -87 PSF
ROOF SHEATHING (A=
50 SF) -42 PSF -67 PSF -92 PSF
DECK FASTENERS (A=
10 SF) -48 PSF -76 PSF -104 PSF
WALL COMPONENTS ZONE 4 ZONE 5
A=200 SF -29 PSF -43 PSF
A=50 SF -31 PSF -53 PSF
A=20 SF -33 PSF -61 PSF
C & C NOTES:
a.
b.
c.
d.
THE PRESSURES LISTED ARE IN ACCORDANCE IBC CBC AND ASCE 7, AND THE
DESIGN FORCES USED BY THE SUBCONTRACTOR FOR A SPECIFIC APPLICATION
ARE THE RESPONSIBILITY OF THE SUBCONTRACTOR.
WIND PRESSURES ARE ULTIMATE DESIGN LEVEL.
SEE ASCE 7 FOR ZONE DEFINITIONS AND EXTENT OF ZONES.
SUBMIT DESIGN CALCULATIONS SIGNED AND SEALED BY A LICENSED ENGINEER IN
THE PROJECT’S JURISDICTION FOR ANY DESIRED MODIFICATION TO THE STATED
PRESSURES.
ALL LATERAL LOAD RESISTANCE AND STABILITY OF THE BUILDING IN THE COMPLETED
STRUCTURE IS PROVIDED BY _____ IN EACH ORTHOGONAL DIRECTION. SEE PLANS FOR
LOCATIONS. THE ____ SERVE AS HORIZONTAL DIAPHRAGMS DISTRIBUTING THE LATERAL
FORCES TO THE VERTICAL LATERAL ELEMENTS WHICH IN TURN CARRY THE LOAD TO THE
BUILDING FOUNDATIONS.[ENGR NOTE: KEEP IF HAVE STEEL IN THE PROJECT AS THIS IS
REQUIRED BY THE AISC CODE OF STANDARD PRACTICE.]
8.
GENERAL
DURING THE CONSTRUCTION PERIOD, THE CONTRACTOR SHALL BE RESPONSIBLE FOR
THE SAFETY OF PERSONNEL AND PROPERTY ON AND AROUND THE JOBSITE. THE
CONTRACTOR SHALL PROVIDE ADEQUATE SHORING, BRACING, GUYS, ETC. IN
ACCORDANCE WITH ALL NATIONAL, STATE, AND LOCAL SAFETY ORDINANCES.
TEMPORARY BRACING, SHORING, GUYING, ETC. SHALL AVOID EXCESSIVE STRESSES AND
HOLD STRUCTURAL ELEMENTS IN PLACE DURING CONSTRUCTION. THE STRUCTURE
SHOULD NOT BE CONSIDERED STABLE UNTIL ALL STRUCTURAL ELEMENTS HAVE BEEN
CONSTRUCTED IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.
1.
ALL DRAWINGS AND SPECIFICATIONS ARE CONSIDERED TO BE A PART OF THE CONTRACT
DOCUMENTS. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE REVIEW AND
COORDINATION OF ALL DRAWINGS PRIOR TO THE START OF CONSTRUCTION. ANY
DISCREPANCIES OR OMISSIONS SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT PRIOR TO THE START OF CONSTRUCTION SO A CLARIFICATION CAN BE
ISSUED. ANY WORK THAT DEVIATES FROM OR IS PERFORMED IN CONFLICT WITH THE
CONTRACT DOCUMENTS OR ANY CODE REQUIREMENTS SHALL BE CORRECTED BY THE
CONTRACTOR AT THEIR OWN EXPENSE AND AT NO EXPENSE TO THE OWNER OR THE
DESIGN PROFESSIONALS.
2.
THE CONTRACT DOCUMENTS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT
INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR IS RESPONSIBLE FOR
DETERMINING ALLOWABLE CONSTRUCTION LOADS AND FOR DETERMINING SEQUENCES
OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO
PROTECT THE STRUCTURE AND SAFETY OF WORKERS DURING CONSTRUCTION. SUCH
MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO: FALSEWORK, FORMWORK, STAGING,
BRACING, AND SHORING FOR LOADS DUE TO CONSTRUCTION EQUIPMENT, ETC.
OBSERVATION VISITS TO THE SITE BY THE ARCHITECT SHALL NOT INCLUDE INSPECTION
OR APPROVAL OF THE ABOVE ITEMS AND DO NOT IN ANY WAY RELIEVE THE CONTRACTOR
OF THEIR RESPONSIBILITIES FOR THE ABOVE. THE CONTRACTOR SHALL TAKE ALL
NECESSARY PRECAUTIONS TO MAINTAIN AND ENSURE THE INTEGRITY OF THE
STRUCTURE AT ALL STAGES OF CONSTRUCTION.
3.
ALL DIMENSIONS AND SITE CONDITIONS SHALL BE VERIFIED BY THE CONTRACTOR AT THE
JOBSITE PRIOR TO BID SUBMITTAL, START OF SHOP DRAWINGS, START OF
CONSTRUCTION, AND/OR FABRICATION OF MATERIALS. IF DISCREPANCIES ARE
ENCOUNTERED, OR CONDITIONS DEVELOP THAT ARE NOT COVERED BY THE CONTRACT
DOCUMENTS, THE ARCHITECT SHALL BE NOTIFIED FOR CLARIFICATION.
4.
STRUCTURAL SUBSTITUTIONS MAY BE ALLOWED WITH THE APPROVAL OF THE
STRUCTURAL ENGINEER. SUPPLIER SHALL PROVIDE SIGNED AND SEALED DESIGN
CALCULATIONS OR SUITABLE PRODUCT LITERATURE FOR THE COMPONENTS. ALL
PRODUCT SUBSTITUTIONS SHALL INCLUDE A CODE EVALUATION REPORT SPECIFIC TO
THE BUILDING CODE LISTED IN THE DESIGN CRITERIA.
5.
STRUCTURAL DRAWINGS INCLUDE DESIGN REQUIREMENTS AND DIMENSIONS FOR
STRUCTURAL INTEGRITY BUT DO NOT SHOW ALL DETAIL DIMENSIONS TO FIT INTRICATE
ARCHITECTURAL AND MECHANICAL DETAILS. CONTRACTOR SHALL CONSTRUCT THE
WORK SO IT WILL CONFORM TO THE CLEARANCES REQUIRED BY ARCHITECTURAL,
MECHANICAL, AND ELECTRICAL DESIGN.
6.
ALL SYMBOLS AND ABBREVIATIONS USED ON THE DRAWINGS ARE CONSIDERED TO BE
CONSTRUCTION STANDARDS. IF CLARIFICATION IS REQUIRED, THE CONTRACTOR SHALL
NOTIFY THE ARCHITECT PRIOR TO PROCEEDING WITH THE WORK.
7.
DO NOT SCALE DRAWINGS. PRINTED DIMENSIONS HAVE PRECEDENCE OVER SCALED
DRAWINGS AND LARGE-SCALE OVER SMALL-SCALE DRAWINGS. CONTRACTOR TO
DETERMINE FINAL DIMENSION WITH ARCHITECT.
8.
TYPICAL DETAILS SHALL APPLY TO SITUATIONS OCCURRING ON THE PROJECT THAT ARE
THE SAME OR SIMILAR TO THOSE SPECIFICALLY REFERENCED. WHERE NO DETAILS ARE
GIVEN, CONSTRUCTION SHALL BE AS SHOWN FOR SIMILAR WORK.
9.
SEE ARCHITECTURAL, ELECTRICAL, AND MECHANICAL DRAWINGS FOR DETAILS,
CONDITIONS, PITS, TRENCHES, PADS, DEPRESSIONS, ROOF / FLOOR OPENINGS, TOP OF
WALL ELEVATIONS, STAIRS, SLEEVES, ITEMS TO BE EMBEDDED OR ATTACHED TO
STRUCTURAL ELEMENTS, ETC., NOT SHOWN ON THE STRUCTURAL DRAWINGS. FOR THESE
NON-STRUCTURAL ELEMENTS SHOWN ON STRUCTURAL DRAWINGS, THEY ARE FOR
GENERAL INFORMATION ONLY.
10.
COORDINATE FLOOR FINISH INCLUDING, BUT NOT LIMITED TO THE "FLATNESS" AND
"LEVELNESS" REQUIREMENTS, WITH THE FLOOR FINISH CONTRACTOR. PROVIDE
UNDERLAYMENT / TOPPING WHERE REQUIRED TO PROVIDE A SURFACE ACCEPTABLE FOR
INSTALLATION OF FLOOR FINISHES. SEE ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
11.
ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS FOR MECHANICAL, ELECTRICAL, AND
PLUMBING WITH APPROPRIATE TRADE CONTRACTORS. OPENING SIZES AND LOCATIONS
SHOWN FOR DUCTS, PIPE, INSERTS, AND OTHER PENETRATIONS WHEN SHOWN ARE FOR
GENERAL INFORMATION ONLY AND SHALL BE VERIFIED PRIOR TO FORMING.
12.
THE EXACT WEIGHTS, DIMENSIONS, AND LOCATIONS OF ALL MECHANICAL UNITS AND
ELECTRICAL GEAR SUPPORTED ON STRUCTURAL FRAMING SHALL BE DETERMINED AND
COORDINATED BY THE CONTRACTOR PRIOR TO DETAILING THE STRUCTURAL FRAMING
SUPPORTING THOSE UNITS. IF THE UNIT WEIGHTS ARE GREATER THAN THE WEIGHTS
SHOWN ON THE STRUCTURAL DRAWINGS, THE STRUCTURAL ENGINEER SHALL BE
NOTIFIED PRIOR TO DETAILING THE STRUCTURE. UNIT WEIGHTS, DIMENSIONS, AND
LOCATIONS SHOWN ON THE STRUCTURAL DRAWINGS ARE APPROXIMATE ONLY AND
SHALL NOT BE USED FOR DETAILING THE STRUCTURE.
13.
PROVIDE TEMPORARY BLOCKOUTS AND TEMPORARY OPENINGS IN THE STRUCTURE AS
REQUIRED TO PERMIT INSTALLATION OF ALL WORK. BLOCKOUTS AND TEMPORARY
OPENINGS SHALL BE LOCATED, CONFIGURED, DETAILED, AND INFILLED IN A MANNER THAT
ALTERS NEITHER THE STRENGTH OF THE STRUCTURAL FRAMING NOR THE STRENGTH OF
CONNECTIONS. INFILL ALL BLOCKOUTS AND TEMPORARY OPENINGS USING THE
MATERIALS SPECIFIED FOR THE FRAMING AT THE LOCATIONS WHERE THE BLOCKOUTS
AND OPENINGS OCCUR. SUBMIT DRAWINGS INDICATING THE LOCATIONS, DIMENSIONS,
AND DETAILS OF ALL PROPOSED BLOCKOUTS AND OPENINGS AND DETAILS INDICATING
THE MANNER IN WHICH THE BLOCKOUTS AND OPENINGS WILL BE INFILLED.
14.
NO HOLES, NOTCHES, BLOCK-OUTS, ETC. ARE ALLOWED IN STRUCTURAL ELEMENTS
UNLESS SPECIFICALLY DETAILED ON THE STRUCTURAL DRAWINGS OR APPROVED BY THE
STRUCTURAL ENGINEER.
15.
BEFORE SUBMITTING A PROPOSAL FOR THIS WORK, CONTRACTOR SHALL VISIT THE
PREMISES AND BECOME FULLY ACQUAINTED WITH FIELD CONDITIONS, TEMPORARY
CONSTRUCTION REQUIRED, QUANTITIES AND TYPE OF EQUIPMENT, ETC. THE PROPOSAL
SHALL INCLUDE ALL SUMS REQUIRED TO DO THE WORK.
16.
ELEMENTS SUCH AS NON-BEARING PARTITIONS, ETC. ATTACHED TO AND/OR SUPPORTED
BY THE STRUCTURE SHALL TAKE INTO ACCOUNT DEFLECTIONS AND OTHER STRUCTURAL
MOVEMENTS. THE STRUCTURAL FRAMING WAS DESIGNED TO LIMIT DRIFT AND
DEFLECTION OF THE STRUCTURAL SYSTEM TO LESS THAN THE MAXIMUM PERMITTED
DEFLECTIONS LISTED IN THE BUILDING CODE. THE CONTRACTOR SHALL COORDINATE THE
WORK OF OTHER TRADES TO ACCOMMODATE THESE DEFLECTIONS AND TO
ACCOMMODATE CONSTRUCTION TOLERANCES.
17.
FIRE PROTECTION FOR ALL STRUCTURAL PARTS SHALL BE PROVIDED AS SPECIFIED BY
THE ARCHITECTURAL DRAWINGS. UL FIRE RESISTANCE RATING RESTRAINT
CLASSIFICATION AS FOLLOWS:
18.
a. "PRIMARY STRUCTURAL FRAME", AS DEFINED BY IBC SECTION 202 IS "RESTRAINED"
EXCEPT AS INDICATED IN FOLLOWING NOTE.
SUBMITTALS
SUBMITTALS ARE:1.
a.
b.
c.
d.
e.
CONCRETE MIX DESIGNS
MATERIAL PRODUCT DATA FOR STRUCTURAL MATERIALS
STEEL FABRICATION AND MISCELLANEOUS METALS
STEEL DECK
COLD FORMED STEEL FRAMING AND CONNECTIONS
SUBMITTALS SHALL BE REVIEWED AND COORDINATED PRIOR TO SUBMITTING TO THE
ARCHITECT. EACH SHOP DRAWING SUBMITTED SHALL BE STAMPED INDICATING REVIEW
BY THE CONSTRUCTION MANAGER/GENERAL CONTRACTOR AND REVIEW BY THE
ARCHITECT SHALL NOT BEGIN UNTIL THIS IS COMPLETE. WORK SHALL NOT BEGIN
WITHOUT REVIEW BY THE DESIGN PROFESSIONALS.
2.
SUBMITTALS SHALL BE REVIEWED BY THE DESIGN PROFESSIONALS FOR GENERAL
CONFORMANCE WITH DESIGN CONCEPT ONLY. NOTATIONS MADE BY THE DESIGN
PROFESSIONALS ON THE SHOP DRAWINGS DO NOT RELIEVE THE CONTRACTOR FROM
COMPLYING WITH THE REQUIREMENTS OF THE DRAWINGS.
3.
FOR ADDITIONAL INFORMATION ON REQUIRED SUBMITTALS, SEE INDIVIDUAL MATERIAL
SECTIONS.
4.
DELEGATED DESIGN
DELEGATED DESIGNS PER SECTION 107.3.4.1 SHALL BE SUBMITTED TO THE BUILDING
OFFICIAL AND THE DESIGN PROFESSIONALS AND REVIEWED PRIOR TO INSTALLATION.
1.
DELEGATED DESIGNS ARE:2.
a.
b.
c.
d.
STRUCTURAL STEEL CONNECTIONS
EXTERIOR WALL SYSTEMS
COLD FORMED STEEL FRAMING AND CONNECTIONS
STAIRS, ACCESS LADDERS, HANDRAILS, GUARDRAILS, AND GRATING
ALL DELEGATED DESIGNS SHALL BE SIGNED AND SEALED BY AN ENGINEER LICENSED IN
THE PROJECT'S JURISDICTION RESPONSIBLE FOR THE PREPARATION OF THESE
DOCUMENTS.
3.
STAIRS:4.
a.
b.
c.
STEEL STAIRS IN STEEL FRAMED STRUCTURES SHALL BE CONFIGURED SO THE
STAIR STRINGERS CONNECT TO THE WEBS OF SUPPORTING STRUCTURAL STEEL
FLOOR FRAMING MEMBERS. STAIR STRINGERS MAY NOT CONNECT TO SLABS ON
DECK. STAIR STRINGER AND HANGER CONNECTIONS SHALL BE CONFIGURED SO
THEY CONNECT TO THE SUPPORTING STRUCTURAL STEEL IN A MANNER THAT
IMPOSES NO TORSION UPON THE SUPPORTING STRUCTURAL MEMBER. WHERE
STAIR HANGERS MUST FRAME ECCENTRIC TO THE SUPPORTING STEEL,
SUPPLEMENTAL FRAMING SHALL BE PROVIDED AS INDICATED ON THE CONTRACT
DOCUMENTS TO PREVENT TORSION ON THE SUPPORTING STEEL FRAMING.
DESIGN FRAMING MEMBERS IN COMMUNICATING STAIRS AND MONUMENTAL
STAIRS TO LIMIT LIVE LOAD DEFLECTION TO THE SMALLER OF L/600 OR 1/4". SIZE
STAIR FRAMING MEMBERS TO PROVIDE A STAIR ASSEMBLY WITH A NATURAL
FREQUENCY > 5 HERTZ AND PEAK ACCELERATION, ap/g = 0.015, AS COMPUTED PER
AISC DESIGN GUIDE 11 EQUATION 2.3 USING INDOOR FOOTBRIDGE CRITERIA.
SEE ARCHITECTURAL DRAWINGS FOR STEEL STAIR DETAILS. DESIGN OF FRAMING
MEMBERS AND CONNECTIONS TO BE BY SPECIALTY ENGINEER, WORKING
DIRECTLY WITH THE STAIR DETAILER AND FABRICATOR. WHERE SUPPORT POSTS
ARE REQUIRED, PROVIDE 3'-0" SQUARE x 1'-0" THICKENED SLAB WITH (4)#5 BOTTOM
AT BASE OF STAIR.
FACADE:5.
a.
1.
2.
3.
4.
5.
DESIGN AND DETAILING OF THE FACADE SYSTEM AND CONNECTIONS TO THE
STRUCTURE SHALL TAKE INTO CONSIDERATION THE FOLLOWING MOVEMENTS:
±1/2" VERTICAL DIFFERENTIAL DEFLECTION OF SLAB EDGES ON ADJACENT
FLOORS
±1/2" HORIZONTAL DIFFERENTIAL DEFLECTION BETWEEN ADJACENT FLOORS
DIFFERENTIAL THERMAL EXPANSION / CONTRACTION BETWEEN FACADE
SYSTEM AND SUPPORTING PRIMARY STRUCTURAL SYSTEM
THE FACADE SHALL NOT BE INSTALLED UNTIL AFTER THE SUPERSTRUCTURE
HAS BEEN PLUMBED, ALL FRAMING CONNECTIONS HAVE BEEN INSTALLED, AND
ALL SHORES AND RESHORES HAVE BEEN REMOVED.
WHERE STRUCTURAL STEEL HORIZONTAL GIRTS ARE PROVIDED, THOSE GIRTS
MAY BE USED ONLY TO RESIST LATERAL LOADS FROM THE FACADE. VERTICAL
LOADS MAY NOT BE IMPOSED BY THE FACADE UPON THE GIRT FRAMING
UNLESS THE SECTIONS AND DETAILS ON THE STRUCTURAL DRAWINGS
SPECIFICALLY INDICATE THAT FACADE GRAVITY LOAD CONNECTIONS MAY BE
MADE TO THE GIRTS.
EXISTING CONDITIONS / DEMOLITION
EXISTING CONDITIONS:1.
a.
b.
EXISTING STRUCTURAL INFORMATION SHOWN WAS OBTAINED FROM EXISTING
DRAWINGS DATED MAY 1ST, 1956 PROVIDED BY VETERAN AFFAIRS.
ALL INFORMATION SHOWN ON THE DRAWINGS RELATIVE TO EXISTING CONDITIONS
IS GIVEN AS THE BEST PRESENT KNOWLEDGE. CONTRACTOR TO VERIFY EXISTING
INFORMATION, DIMENSIONS, AND SIZES AS REQUIRED TO COMPLETE THEIR WORK.
WHERE ACTUAL CONDITIONS CONFLICT WITH THE DRAWINGS, THEY SHALL BE
REPORTED TO THE ARCHITECT SO CLARIFICATION MAY BE MADE. MODIFICATION
OF CONSTRUCTION DETAILS SHALL NOT BE MADE WITHOUT WRITTEN APPROVAL
OF THE ARCHITECT.
EXISTING BUILDING MATERIAL PROPERTIES:2.
a.
b.
c.
EXISTING STRUCTURE IS STEEL ENCASED IN CONCRETE
EXISTING STEEL ASSUMED TO HAVE MINIMUM YIELD STRENGTH OF 36KSI
EXISTING CONCRETE ASSUMED TO HAVE MINIMUM f'c=4KSI
ALL DEMOLITION SHALL BE CARRIED OUT IN SUCH A WAY TO PREVENT DAMAGE TO
EXISTING ELEMENTS WHICH ARE TO REMAIN.
3.
ALL ELEMENTS WHICH ARE TO REMAIN AND WHICH ARE DAMAGED DURING DEMOLITION
WORK SHALL BE REPLACED AT NO ADDED COST. CONTRACTOR SHALL PROVIDE AND BE
RESPONSIBLE FOR THE PROTECTION AND REPAIR OF ADJACENT EXISTING SURFACES AND
AREAS WHICH MAY BE DAMAGED AS A RESULT OF NEW WORK.
4.
CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS AND CONDITIONS OF EXISTING
STRUCTURE AND SITES THAT ARE AFFECTED BY NEW WORK BEFORE PROCEEDING WITH
FABRICATION AND CONSTRUCTION.
5.
ALL CONSTRUCTION IS NEW UNLESS IDENTIFIED AS EXISTING, "(E)". THE CONTRACTOR
SHALL VERIFY ALL EXISTING BUILDING INFORMATION AND SHALL NOTIFY THE ARCHITECT
OF ANY DISCREPANCIES PRIOR TO FABRICATION OF ANY STRUCTURAL COMPONENT. NEW
SLABS ARE TO BE AT THE SAME ELEVATIONS AS ADJACENT EXISTING SLABS UON.
FOUNDATION ELEVATIONS OR COLUMN LENGTHS SHALL BE ADJUSTED WITH THE
APPROVAL OF THE STRUCTURAL ENGINEER TO ACHIEVE MATCHING SLAB ELEVATIONS.
6.
REINFORCING STEEL IN EXISTING CONCRETE SHALL BE LOCATED PRIOR TO INSTALLATION
OF NEW OPENINGS OR CORING OF HOLES IN THE CONCRETE. REINFORCING STEEL MAY
NOT BE CUT WITHOUT APPROVAL FROM THE ENGINEER.
7.
CAST-IN-PLACE CONCRETE
CONCRETE MATERIALS SHALL CONFORM TO:1.
PORTLAND LIMESTONE CEMENT ASTM C595, TYPE IL
PORTLAND CEMENT ASTM C150, TYPE I
FLY ASH ASTM C618, TYPE C OR F
SLAG CEMENT ASTM C989
FINE AND COARSE AGGREGATE ASTM C33
LIGHTWEIGHT AGGREGATE ASTM C330
WATER POTABLE
AIR-ENTRAINING ADMIXTURE ASTM C260
WATER REDUCING ADMIXTURE ASTM C494
ALL CONCRETE WORK SHALL CONFORM TO THE REQUIREMENTS OF ACI 318, BUILDING
CODE REQUIREMENTS FOR STRUCTURAL CONCRETE, AND ACI 301, SPECIFICATIONS FOR
STRUCTURAL CONCRETE UON.
2.
AIR ENTRAINMENT:3.
NOMINAL MAXIMUM
AGGREGATE SIZE
REQUIRED AIR CONTENT PER EXPOSURE CATEGORY
F1 F2
3/8" 6% 7.5%
1/2" 5.5% 7%
3/4" 5% 6%
1" 4.5% 6% a.
b.
ALL LIGHTWEIGHT CONCRETE SHALL HAVE 4-7% AIR ENTRAINMENT.
AIR ENTRAINMENT SHALL CONFORM TO UL RATING REQUIREMENTS FOR FIRE
RESISTANCE.
CONCRETE STRENGTHS SHALL CONFORM TO:4.
LOCATION f'c AT 28 DAYS (PSI) MAX PERMITTED
W/C EXPOSURE CLASS
LIGHTWEIGHT SLAB
ON DECK* 3000 0.55
TOPPING SLABS 3000 0.55
* LIGHTWEIGHT CONCRETE SHALL HAVE A 115 PCF DRY UNIT WEIGHT (±3PCF).
LIGHTWEIGHT AGGREGATES SHALL BE PRESOAKED AS REQUIRED IN ACCORDANCE WITH
ACI 301.
REQUIRED NOMINAL MAXIMUM COARSE AGGREGATE SIZE:5.
CONCRETE ELEMENT REQUIRED NOMINAL MAXIMUM COARSE
AGGREGATE SIZE*
ALL CONCRETE UON 1"
TOPPING SLABS LESS THAN 3" THICK 3/8"
* SMALLER NOMINAL MAXIMUM COARSE AGGREGATE SIZE SHALL BE USED WHERE
REQUIRED PER ACI 318.
"ROUGH JOINTS" ARE JOINTS ROUGHENED TO AN AMPLITUDE OF 1/4" AND FREE AND
CLEAN OF LAITANCE. PROVIDE ROUGH JOINTS AT ALL CONSTRUCTION JOINTS UON.
6.
CONSTRUCTION JOINTS IN SLAB ON DECK SHALL BE LOCATED AS FOLLOWS:7.
a.
b.
c.
JOINTS PERPENDICULAR TO THE DECK SPAN SHALL BE LOCATED MIDWAY
BETWEEN ADJACENT PARALLEL BEAMS.
JOINTS PARALLEL TO GIRDERS SHALL BE LOCATED 4 FEET AWAY FROM THE
GIRDERS.
JOINTS PERPENDICULAR TO GIRDERS SHALL BE LOCATED NO FARTHER THAN 'S'/2
FROM ONE END OF THE GIRDER WHERE 'S' IS THE DIMENSION BETWEEN
ADJACENT BEAMS FRAMING TO THE GIRDER.
INSTALLATION OF ELECTRICAL CABLE, CONDUIT, AND PIPING IN OR THROUGH CONCRETE
COLUMNS AND WALLS IS PROHIBITED UNLESS APPROVED BY THE STRUCTURAL ENGINEER
PRIOR TO INSTALLATION. INSTALLATION OF PIPING IN CAST-IN-PLACE CONCRETE IS
PROHIBITED UNLESS APPROVED BY STRUCTURAL ENGINEER PRIOR TO INSTALLATION.
DRAWINGS SHALL BE SUBMITTED FOR REVIEW SHOWING PROPOSED PLACEMENT OF
ELECTRICAL CABLE AND CONDUIT IN SLABS. THOSE DRAWINGS SHALL SHOW SIZES AND
DIMENSIONED LOCATIONS OF ALL CABLE AND CONDUIT.
8.
ELECTRICAL CABLE AND CONDUIT (HEREAFTER REFERRED TO AS CONDUIT) MAY BE
INSTALLED IN SLABS ON DECK SUBJECT TO THE FOLLOWING CONSTRAINTS:
9.
a.
b.
c.
d.
e.
f.
g.
h.
i.
CONDUIT SHALL BE NO LARGER THAN 1 1/2" MAXIMUM OUTSIDE DIAMETER.
PARALLEL CONDUITS SHALL BE INSTALLED IN A SINGLE LAYER AND SHALL BE
SPACED NO CLOSER THAN 3".
CONDUIT RUNNING PERPENDICULAR OR SKEWED TO THE DECK SPAN MAY BE
INSTALLED DIRECTLY ON TOP OF THE DECK. CONDUIT RUNNING PARALLEL TO THE
DECK SPAN SHALL BE INSTALLED 1" CLEAR ABOVE THE TOP OF THE DECK.
REQUIRED MINIMUM CLEAR COVER BETWEEN TOP OF SLAB AND TOP OF CONDUIT
EQUALS 1".
ONLY ONE LAYER OF CONDUIT MAY CROSS OVER ANOTHER LAYER OF CONDUIT AT
ANY LOCATION.
INSTALLATION OF CONDUIT ON TOP OF THE CONTINUOUS WELDED WIRE FABRIC
SLAB REINFORCING STEEL IS NOT PERMITTED.
LOCATIONS WHERE MULTIPLE CONDUITS EXIST VERTICALLY FROM THE SLAB
SHALL BE TREATED AS A MULTIPLE SLAB OPENING AND ADDITIONAL REINFORCING
STEEL SHALL BE PROVIDED AROUND THE EFFECTIVE SLAB OPENING AS
REQUIRED.
COORDINATED DRAWINGS SHALL BE SUBMITTED FOR REVIEW SHOWING THE
PROPOSED LOCATIONS OF ALL SLAB-EMBEDDED ELECTRICAL CONDUIT. THESE
DRAWINGS SHALL SHOW "DRAWN TO SCALE" CONDUIT RUNS, LOCATIONS, AND
DIMENSIONS WHERE GROUPED CONDUITS EXIT THE SLABS ALONG WITH
LOCATIONS AND DIMENSIONS OF SLAB-EMBEDDED ELECTRICAL BOXES.
INSTALLATION OF CONDUIT IN PARKING LEVEL SLABS AND SLABS EXPOSED TO
WEATHER IS NOT PERMITTED.
NO LOADS SHALL BE PLACED ON STRUCTURAL CONCRETE SLABS ON DECK WITHIN 7 DAYS
AFTER CONCRETE IS PLACED.
10.
AFTER CONCRETE IS PLACED, IN NO CASE SHALL THE SUPERIMPOSED CONSTRUCTION
LOADS BE GREATER THAN SPECIFIED DESIGN LIVE LOADS UNLESS THE WORK IS SHORED.
11.
NOTIFY THE ARCHITECT 48 HOURS MINIMUM PRIOR TO ALL POURS.12.
CONTRACTOR SHALL SURVEY ALL CONCRETE WORK WITHIN 48 HOURS OF PLACING
CONCRETE TO ENSURE PLACEMENT IS IN ACCORDANCE WITH PROJECT REQUIREMENTS.
13.
CORING OF CONCRETE IS NOT PERMITTED UNLESS APPROVED BY THE STRUCTURAL
ENGINEER. SUBMIT LOCATIONS OF PROPOSED CONCRETE CORES.
14.
REINFORCING STEEL SHALL NOT BE DAMAGED WHEN DRILLING CONCRETE.15.
ADHERE TO ACI 305R AND ACI 306R FOR HOT AND COLD WEATHER CONCRETE
CONSTRUCTION.
16.
DRYPACK AND GROUT SHALL HAVE A MINIMUM 28-DAY STRENGTH OF 7000 PSI.17.
THE PROPOSED MATERIALS AND MIX DESIGN SHALL BE FULLY DOCUMENTED AND
REVIEWED BY THE TESTING AND INSPECTION AGENCY. RESPONSIBILITY FOR OBTAINING
THE REQUIRED DESIGN STRENGTH IS THE CONTRACTOR'S. SUBMIT TEST DATA ON EACH
PROPOSED MIX FOR REVIEW IN ACCORDANCE WITH THE APPLICABLE CODE. MIX DESIGNS
SUBMITTED WITHOUT THE REQUIRED TEST DATA WILL BE RETURNED WITHOUT REVIEW.
18.
SEE ARCHITECTURAL DRAWINGS FOR DIMENSIONS, LOCATIONS, AND DETAILS OF ALL
ARCHITECTURAL FEATURES IN THE CONCRETE. SEE ARCHITECTURAL DRAWINGS AND
PROJECT SPECIFICATIONS FOR REQUIREMENTS FOR ALL CONCRETE FINISHES.
19.
STEEL
STRUCTURAL STEEL SHALL BE DETAILED IN ACCORDANCE WITH THE AMERICAN INSTITUTE
OF STEEL CONSTRUCTION (AISC) "DETAILING FOR STEEL CONSTRUCTION" AND
FABRICATED AND ERECTED IN ACCORDANCE WITH THE "SPECIFICATION FOR STRUCTURAL
STEEL BUILDINGS".
1.
STRUCTURAL STEEL SHALL CONFORM TO ASTM STANDARDS AS NOTED BELOW:2.
WIDE FLANGE SHAPES ASTM A992 Fy=50 KSI
WIDE FLANGE SHAPES,
HIGH-STRENGTH WHERE
NOTED
ASTM A913, GR 65 Fy=65 KSI
OTHER ROLLED SHAPES ASTM A36 Fy=36 KSI
HSS SECTIONS, ROUND ASTM A500, GR C Fy=46 KSI
HSS SECTIONS, SQ/RECT ASTM A500, GR C Fy=50 KSI
BASE AND CONNECTION
PLATES ASTM A36 A572 Fy=36 50 KSI
ANCHOR RODS ASTM F1554, GR 36 55 Fy=36 55 KSI
HIGH STRENGTH BOLTS ASTM F3125, GR A325 A490 Fv=120 150 KSI
HIGH STRENGTH TWIST-OFF
BOLTS ASTM F3125, GR F1852 F2280 Fv=120 150 KSI
HEAVY HEX NUTS ASTM A563
WASHERS ASTM F436
HEADED STUD ANCHORS
(HSA) ASTM A108, TYPE B
ELECTRODES FOR ARC
WELDING AWS 5.1, E70XX
HIGH STRENGTH BOLTS SHALL BE INSTALLED IN ACCORDANCE WITH AISC
"SPECIFICATIONS FOR STRUCTURAL JOINTS USING HIGH-STRENGTH BOLTS". SEE DETAILS
FOR BOLT SIZE AND MATERIAL ASTM DESIGNATION.
3.
ALL BOLTED CONNECTIONS SHALL BE GRADE A325N BEARING TYPE BOLTS UON. ALL
BOLTS SHALL BE INSTALLED TO A MINIMUM SNUG TIGHT CONDITION UON.
4.
FULLY TENSIONED HIGH STRENGTH BOLTS AND SLIP CRITICAL HIGH STRENGTH BOLTS
SHALL USE TENSION-CONTROL "TWIST-OFF" BOLTS OR BE INSTALLED USING THE TURN OF
THE NUT METHOD.
5.
EXCEPT WHERE DETAILED OTHERWISE, FABRICATOR SHALL SELECT LRFD BOLTED (OR
WELDED EQUIVALENT) SIMPLE SHEAR CONNECTIONS PER AISC 360 PART 10 TO SUPPORT
LOADS INDICATED ON THE STRUCTURAL DRAWINGS. WHEN LOADS ARE NOT SHOWN,
CONNECTION SHALL SUPPORT 60% OF THE TOTAL UNIFORM LOAD CAPACITY FOR EACH
GIVEN BEAM SIZE AND SPAN AS LISTED IN AISC 360 TABLE 3-6. FOR COMPOSITE MEMBERS,
CONNECTION SHALL SUPPORT 80% OF THE TOTAL UNIFORM LOAD CAPACITY FOR EACH
BEAM SIZE AND SPAN.
6.
BEAM REACTIONS GIVEN ON THE CONTRACT DOCUMENTS SHALL SUPERSEDE THE
PREVIOUS NOTE. IN NO CASE SHALL THE CONNECTIONS BE DESIGNED FOR AN LRFD END
REACTION LESS THAN 15 KIPS.
7.
FIELD CONNECTIONS SHALL BE WELDED OR BOLTED. SHOP CONNECTIONS SHALL BE
WELDED UON. WELDS INDICATED WITH A SHOP WELD SYMBOL MAY BE MADE IN THE FIELD
WITH THE APPROVAL OF THE STRUCTURAL ENGINEER. LOCATIONS OF ALL FIELD WELDS
SHALL BE CLEARLY SHOWN ON THE SHOP DRAWINGS. WELDS SHALL BE DESIGNED TO BE
FULLY EQUIVALENT IN STRENGTH TO BOLTED CONNECTIONS DETAILED TO MINIMIZE
BENDING IN THE CONNECTION.
8.
WELD LENGTHS INDICATED ON THE DRAWINGS ARE THE NET EFFECTIVE LENGTH
REQUIRED. WHERE WELD LENGTH IS NOT SPECIFIED, PROVIDE WELD ALONG ENTIRE
INTERSECTION OF THE JOINED PARTS. WHERE FILLET WELD SYMBOL IS GIVEN WITHOUT
INDICATION OF SIZE, USE MINIMUM WELD SIZE AS SPECIFIED IN AISC 360, TABLE J2.4.
9.
ALL WELDING OF STRUCTURAL STEEL SHALL BE PERFORMED BY CERTIFIED WELDERS
WITH EXPERIENCE AND CERTIFICATION IN THE TYPES OF WELDING INDICATED. WELDERS
SHALL HAVE BEEN RECENTLY QUALIFIED AS PRESCRIBED IN "QUALIFICATION
PROCEDURES" OF THE AMERICAN WELDING SOCIETY (AWS).
10.
HEADED STUD ANCHORS (HSA): SHALL BE INSTALLED IN ACCORDANCE WITH AWS D1.1
AND SHALL BE AUTOMATICALLY END WELDED IN ACCORDANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS IN SUCH A MANNER AS TO PROVIDE COMPLETE
FUSION BETWEEN THE END OF THE HSA AND THE STEEL SHAPE. THERE SHOULD BE NO
POROSITY OR EVIDENCE OF LACK OF FUSION BETWEEN THE WELDED END OF THE HSA
AND THE STEEL SHAPE. THE HSA SHALL DECREASE IN LENGTH DURING WELDING
APPROXIMATELY 1/8" FOR 5/8"Ø AND SMALLER AND 3/16" FOR LARGER THAN 5/8"Ø.
11.
MINIMUM HORIZONTAL CONCRETE COVER FOR HSA TO BE 2".12.
BEAMS SHALL BE CAMBERED UPWARD WHERE SHOWN ON THE DRAWINGS. WHERE NO
UPWARD CAMBER IS INDICATED, ANY MILL CAMBER SHALL BE DETAILED UPWARD IN THE
BEAMS.
13.
SPLICING OF STEEL MEMBERS WHERE NOT DETAILED ON THE DRAWINGS IS PROHIBITED
WITHOUT THE PRIOR APPROVAL OF THE STRUCTURAL ENGINEER AS TO LOCATION, TYPE
OF SPLICE, AND CONNECTION TO BE MADE.
14.
PROVIDE ONE SHOP COAT OF PAINT ON ALL STRUCTURAL STEEL NOT COVERED WITH
CONCRETE, FIREPROOFING, MASONRY, OR AT CONTACT SURFACES AT HIGH STRENGTH
BOLTS.
15.
ALL STEEL EXPOSED TO WEATHER OR AS NOTED ON PLAN SHALL BE HOT-DIP GALVANIZED
AFTER FABRICATION IN ACCORDANCE WITH ASTM A123 G60. ABRADED AREAS TO BE
TOUCHED UP WITH COLD GALVANIZING COMPOUND IN ACCORDANCE WITH ASTM A780.
16.
ALL GALVANIZED HOLLOW SECTIONS SHALL HAVE WELDED CAP PLATES TO SEAL
EXPOSED ENDS.
17.
CUTS, HOLES, OPENINGS, ETC. REQUIRED IN STRUCTURAL STEEL MEMBERS FOR THE
WORK OF OTHER TRADES SHALL BE SHOWN ON THE SHOP DRAWINGS. BURNING OR
TORCHING OF HOLES, CUTS, AND OTHER FIELD MODIFICATIONS SHALL NOT BE ALLOWED,
EXCEPT BY WRITTEN AUTHORIZATION FROM THE STRUCTURAL ENGINEER.
18.
SEE ARCHITECTURAL, MECHANICAL, ELECTRICAL, ETC. FOR MISCELLANEOUS STEEL NOT
DETAILED SPECIFICALLY ON THE STRUCTURAL DRAWINGS.
19.
GROUT FOR BASE AND BEARING PLATES SHALL BE A NON-SHRINK, NON-METALLIC
PRODUCT. MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS SHALL BE 7000 PSI. INSTALL
GROUT PRIOR TO APPLYING SIGNIFICANT LOADING TO MEMBER.
20.
THE STRUCTURAL STEEL FABRICATOR SHALL FURNISH SHOP DRAWINGS OF ALL
STRUCTURAL STEEL FOR REVIEW AND APPROVAL BEFORE FABRICATION.
21.
ALL WELDING ELECTRODES SHALL BE E70XX UON. 22.
STEEL DECK
MATERIAL, DETAILING, DESIGN, MANUFACTURE, AND ERECTION OF STEEL DECKS SHALL
BE IN ACCORDANCE WITH THE STEEL DECK INSTITUTE (SDI) SPECIFICATION.
1.
DECK SIZE AND GAUGE INDICATED ON THE DRAWINGS ARE BASED ON THE FOLLOWING:2.
a.
b.
CURRENT VERSION OF VULCRAFT VERCO CATALOG FOR GRAVITY DESIGN LOADS
AND UNSHORED CONSTRUCTION SPANS
SDI DIAPHRAGM DESIGN MANUAL 4 FOR DIAPHRAGM LOADS
PROVIDE MINIMUM DECK BEARING AND LAP LENGTHS PER MANUFACTURER'S
RECOMMENDATIONS.
3.
FOR PENETRATIONS LESS THAN OR EQUAL TO 12"Ø OR 12"x12", FRAMING OF OPENINGS
FOR OTHER TRADES SHALL BE THE RESPONSIBILITY OF THE TRADES INVOLVED. HOLES
LOCATED AND DIMENSIONED ON THE DRAWINGS SHALL BE THE RESPONSIBILITY OF THE
DECK ERECTOR. SEE STRUCTURAL FRAMING DETAILS FOR ANY OPENING EXCEEDING
LIMITS NOTED.
4.
SUBMIT SHOP DRAWINGS SHOWING DECKING LAYOUT, DECK GAUGE, DECK DIRECTION,
FASTENERS, AND FASTENING PATTERN FOR REVIEW AND APPROVAL.
5.
FURNISH DECKING IN MINIMUM LENGTHS TO ACHIEVE 3-SPAN CONDITION UON.6.
ROOF DECK:7.
a.
b.
c.
d.
ALL ROOF DECK SHALL BE GALVANIZED TO CONFORM TO ASTM A653 WITH A
MINIMUM COATING OF G60.
ALL ROOF DECK SHALL BE PRIME PAINTED GRAY TO CONFORM TO ASTM A1008.
DO NOT EXCEED 25 LBS PER HANGER AND A MINIMUM SPACING OF 2'-0" ON
CENTER WHEN ATTACHING TO ROOF DECK. THIS 25 LBS LOAD AND 2'-0" SPACING
INCLUDE ADJACENT MECHANICAL, ELECTRICAL, AND ARCHITECTURAL ITEMS
HANGING FROM THE DECK. IF THE HANGER RESTRICTIONS CANNOT BE ACHIEVED,
SUPPLEMENTAL FRAMING SUPPORTED OFF STEEL FRAMING WILL NEED TO BE
ADDED. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING
LOCATION AND WEIGHT OF ALL THE ELEMENTS BEING HUNG WITH STRUCTURAL
ENGINEER UON.
DECK MANUFACTURER SHALL FURNISH ALL RIDGE AND VALLEY PLATES, SUMP
PANS, DRAIN PLATES, AND OTHER ACCESSORIES REQUIRED FOR A COMPLETE
INSTALLATION.
COMPOSITE DECK:8.
a.
b.
c.
d.
e.
ALL FLOOR DECK SHALL BE GALVANIZED TO CONFORM TO ASTM A653 WITH A
MINIMUM COATING OF G60.
CONDUITS SHALL NOT BE PLACED IN SLAB ON DECK WITHOUT COORDINATION
WITH THE STRUCTURAL ENGINEER UON.
COORDINATE ALL PENETRATIONS, EMBEDS, AND RECESSES IN COMPOSITE DECK
WITH THE STRUCTURAL ENGINEER UON.
COMPOSITE DECK HAS BEEN DESIGNED FOR THE UNSHORED CLEAR SPAN.
CONCRETE FILL THICKNESS SHOWN ON FRAMING PLANS AND DETAIL SHEETS IS A
MINIMUM THICKNESS. CONTRACTOR TO PROVIDE CONCRETE FILL REQUIRED TO
COMPENSATE FOR BEAM AND DECK DEFLECTIONS AND TO MAINTAIN SURFACE
TOLERANCES SPECIFIED. DO NOT INSTALL MORE THAN 1" OF ADDITIONAL
CONCRETE WITHOUT NOTIFYING STRUCTURAL ENGINEER.
DECK MANUFACTURER SHALL PROVIDE ALL CLOSURE PLATES AND POUR STOPS
NOT PROVIDED BY THE STEEL FABRICATOR.
POST-INSTALLED ANCHORS
BASIS OF DESIGN ANCHORS:1.
INSTALLATION CONDITION ANCHOR TYPE
EXPANSION ANCHORS INTO CONCRETE HILTI KWIK BOLT TZ2 (ESR-4266)
SCREW ANCHORS > 1/4"Ø INTO CONCRETE HILTI KWIK HUS-EZ (ESR-3027)
ADHESIVE ANCHORS INTO CONCRETE
HILTI SAFE-SET SYSTEM w/ HIT-HY 200 V3 AND HIT-Z ROD (ESR-4868)or HILTI SAFE-SET SYSTEM w/ HIT-HY 200 V3
AND HAS-E THREADED ROD (ESR-4868)
or HILTI SAFE-SET SYSTEM w/ HIT-RE 500 V3
AND HAS-E THREADED ROD (ESR-3814)
FOR ALL ADHESIVE ANCHORS, HOLES
SHALL BE HAMMER DRILLED AND HOLES
MAY BE DRY OR WATER SATURATED.
EXPANSION ANCHORS INTO GROUTED CMU HILTI KWIK TZ2 (ESR-4561)
ADHESIVE DOWELING FOR ANCHORING
REINFORCING BARS INTO (E) CONCRETE
HILTI SAFE-SET SYSTEM w/ HIT-HY 200 V3
ADHESIVE (ESR-4868)
or HILTI SAFE-SET SYSTEM w/ HIT-RE 500 V3
ADHESIVE (ESR-3814)
POWDER-ACTUATED FASTENERS (PAF's) IN
CONCRETE HILTI X-U FASTENERS (ESR-2269)
ALTERNATIVE ANCHORS MAY BE USED IF APPROVED IN WRITING BY THE STRUCTURAL
ENGINEER. THE CONTRACTOR SHALL SUBMIT CALCULATIONS SIGNED AND SEALED BY AN
ENGINEER LICENSED IN THE PROJECT’S JURISDICTION VERIFYING PROPOSED
ALTERNATIVE ANCHORS WILL PROVIDE THE SAME OR GREATER LOAD-CARRYING
CAPACITY AS THE SPECIFIED ANCHORS. THE CONTRACTOR SHALL SUBMIT EVALUATION
REPORTS. EACH ANCHOR CONFIGURATION SHALL BE EVALUATED AND COMPARED TO THE
SPECIFIED ANCHOR.
2.
CRACKED CONCRETE IS ASSUMED FOR ALL ANCHORAGE DESIGN CONDITIONS UNLESS IT
CAN BE DEMONSTRATED THROUGH ENGINEERING ANALYSIS THAT THE CONCRETE
REMAINS UNCRACKED DURING THE GOVERNING ULTIMATE LOAD STATE.
3.
POST-INSTALLED ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
MANUFACTURER’S PRINTED INSTALLATION INSTRUCTIONS.
4.
THE CONTRACTOR SHALL ARRANGE FOR AN ANCHOR MANUFACTURER ’S
REPRESENTATIVE TO PROVIDE ONSITE INSTALLATION TRAINING FOR EACH SPECIFIED
ANCHOR TYPE. THE STRUCTURAL ENGINEER SHALL RECEIVE DOCUMENTATION VERIFYING
ALL OF THE CONTRACTOR’S PERSONNEL WHO INSTALL ANCHORS HAVE BEEN TRAINED
PRIOR TO COMMENCEMENT OF INSTALLING ANCHORS.
5.
INSTALLATION OF ADHESIVE ANCHORS SHALL BE PERFORMED BY PERSONNEL CERTIFIED
BY AN APPROVED CERTIFICATION PROGRAM. CERTIFICATION SHALL INCLUDE WRITTEN
AND PERFORMANCE TESTS IN ACCORDANCE WITH THE ACI/CRSI ADHESIVE ANCHOR
INSTALLER CERTIFICATION PROGRAM OR EQUIVALENT. THE ACCEPTABILITY OF
CERTIFICATIONS OTHER THAN THE ACI/CRSI ADHESIVE INSTALLER CERTIFICATION WILL BE
DETERMINED BY THE STRUCTURAL ENGINEER.
6.
CONCRETE SHALL HAVE ACHIEVED DESIGN STRENGTH PRIOR TO INSTALLING POST-
INSTALLED ANCHORS. ADHESIVE ANCHORS SHALL BE INSTALLED IN CONCRETE THAT HAS
CURED FOR A MINIMUM OF 21 DAYS.
7.
ANCHOR CAPACITY IS DEPENDENT UPON SPACING BETWEEN ANCHORS AND PROXIMITY
OF ANCHORS TO EDGES OF CONCRETE OR MASONRY. INSTALL ANCHORS IN
ACCORDANCE WITH SPACING AND EDGE CLEARANCES INDICATED ON THE DRAWINGS.
8.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
4/
/2
4:
:2
PM
Au to de sk
D oc s:
//5
A7
-2 2-
VA
S yr ac us e
EH
R
M in fra st ru ct ur e
U pg ra de s/
VA
SY
_0
1_
ST
_I M
EG
.rv t
S001
GENERAL NOTES
EB GRB
100% CONSTRUCTION
DOCUMENTS
08/29/2025
528A7-22-700EHRM INFRASTRUCTURE
UPGRADES - SYRACUSE VA
VA NY SYRACUSE
800 IRVING AVE., SYRACUSE, NY 13210
5. REINFORCING STEEL CLEARANCES HAVE BEEN PROVIDED - X AISC 341:
TABLE J9.1
6. COMPOSITE STEEL MEMBERS HAVE REQUIRED SIZE - X AISC 341:
TABLE J9.1
7. REINFORCING BAR WELDING:
a. VERIFY WELDABILITY OF REINFORCING BARS OTHER THAN ASTM
A706
- X AWS D1.4 -
b. INSPECT SINGLE-PASS FILLET WELDS, MAXIMUM 5/16”; AND - X ACI 318: 26.6.4 -
c. INSPECTS ALL OTHER WELDS X - - -
8. INSPECT ANCHORS CAST IN CONCRETE - X ACI 318: 17.8.2 -
9. INSPECT ANCHORS POST-INSTALLED IN HARDENED CONCRETE
MEMBERS:
a. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR UPWARDLY
INCLINED ORIENTATIONS TO RESIST SUSTAINED TENSION LOADS
X - ACI 318:
17.8.2.4
b. MECHANICAL ANCHORS AND ADHESIVE ANCHORS NOT DEFINED IN 4.a
- X ACI 318: 17.8.2 -
10. VERIFY USE OF REQUIRED DESIGN MIX - X ACI 318: CH 19,
26.4.2, 26.4.4
1904.1, 1904.2, 1908.2, 1908.3
11. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR
STRENGTH TESTS, PERFORM SLUMP AND AIR CONTENT TESTS, AND
DETERMINE THE TEMPERATURE OF THE CONCRETE
X - ASTM C172,
ASTM C31, ACI
318: 26.5, 26.12
1907.10
12. INSPECT CONCRETE AND SHOTCRETE PLACEMENT FOR PROPER
APPLICATION TECHNIQUES
X - ACI 318: 26.5 1908.6,
1908.7, 1908.8
13. VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND
TECHNIQUES
- X ACI 318:
26.5.3-26.5.5
1908.9
14. INSPECT PRESTRESSED CONCRETE FOR:
a. APPLICATION OF PRESTRESSING FORCES; AND X - ACI 318:
26.11.2
b. GROUTING OF BONDED PRESTRESSING TENDONS X - - -
15. INSPECT ERECTION OF PRECAST CONCRETE MEMBERS X - ACI 318: 26.9 -
16. VERIFY IN-SITU CONCRETE STRENGTH, PRIOR TO STRESSING OF
TENDONS IN POST-TENSIONED CONCRETE AND PRIOR TO REMOVAL OF
SHORES AND FORMS FROM BEAMS AND STRUCTURAL SLABS
- X ACI 318:
26.11.2
17. INSPECT FORMWORK FOR SHAPE, LOCATION, AND DIMENSIONS OF THE
CONCRETE MEMBER BEING FORMED
- X ACI 318:
26.11.2(b)
VERIFICATION AND INSPECTION TASK QC QA MATERIAL
STD
REFERENCE
STRUCTURAL STEEL - FABRICATION
1. FABRICATION FACILITY - - X
2. CONNECTION ERECTION AND ASSEMBLY X X -
3. PRETENSIONED AND SLIP-CRITICAL BOLTS/JOINTS USING TURN-OF-NUT
METHOD WITHOUT MATCHMAKING OF CALIBRATED WRENCH METHODS
OF INSTALLATION
X X -
4. SINGLE PASS FILLET WELDS 5/16” OR LESS X X X
5. ALL OTHER WELDS INCLUDING COMPLETE AND PARTIAL PENETRATION
WELDS
X X X
6. SHEAR STUD PLACEMENT X X -
VERIFICATION AND INSPECTION TASK QC QA MATERIAL
STD
REFERENCE
STRUCTURAL STEEL - ERECTION
1. STRUCTURAL STEEL ERECTION X X -
2. CONNECTION ERECTION AND ASSEMBLY X X -
3. PRETENSIONED AND SLIP-CRITICAL BOLTS/JOINTS USING TURN-OF-NUT
METHOD WITHOUT MATCHMAKING OF CALIBRATED WRENCH METHODS
OF INSTALLATION
X X -
4. SINGLE PASS FILLET WELDS 5/16” OR LESS X X X
5. ALL OTHER WELDS INCLUDING COMPLETE AND PARTIAL PENETRATION
WELDS
X X X
6. SHEAR STUD PLACEMENT X X -
7. BEAM CAMBER (IN-PLACE) X - -
VERIFICATION AND INSPECTION TASK QC QA MATERIAL
STD
REFERENCE
AWS D1.1
CLAUSES
STRUCTURAL STEEL PRIOR TO BOLTING - MINIMUM INSPECTION
1. MANUFACTURER’S CERTIFICATIONS AVAILABLE FOR FASTENER
MATERIALS
O P TABLE C-
N5.6-1 2.1, 9.1
2. FASTENERS MARKED IN ACCORDANCE WITH ASTM REQUIREMENTS O O TABLE C-
N5.6-1
6.5.1
3. CORRECT FASTENERS SELECTED FOR THE JOINT DETAIL (GRADE,
TYPE, BOLT LENGTH IF THREADS ARE TO BE EXCLUDED FROM THE
SHEAR PLANE)
O O TABLE C-
N5.6-1
2.3.2, 2.7.2, 9.1
4. CORRECT BOLTING PROCEDURE SELECTED FOR JOINT DETAIL O O TABLE C-
N5.6-1
4, 8
5. CONNECTING ELEMENTS, INCLUDING THE APPROPRIATE FAYING
SURFACE CONDITION AND HOLE PREPARATION, IF SPECIFIED, MEET
APPLICABLE REQUIREMENTS
O O TABLE C-
N5.6-1
TABLE
6.1(2)
6. PRE-INSTALLATION VERIFICATION TESTING BY INSTALLATION
PERSONNEL OBSERVED AND DOCUMENTED FOR FASTENER
ASSEMBLIES AND METHODS USED
P1 O1 TABLE C-
N5.6-1
3, 9.1, 9.3
7. PROTECTION STORAGE PROVIDED FOR BOLTS, NUTS, WASHERS, AND
OTHER FASTENER COMPONENTS
O O TABLE C-
N5.6-1
2.2, 8, 9.1
1 DOCUMENT - THE INSPECTOR SHALL PREPARE REPORTS INDICATING THE WORK HAS
BEEN PERFORMED IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. THE REPORTS
NEED NOT PROVIDE DETAILED MEASUREMENTS FOR JOINT FIT-UPS, WPS SETTINGS,
COMPLETED WELDS, OR OTHER INDIVIDUAL ITEMS LISTED IN THE TABLES. FOR SHOP
FABRICATION, THE REPORT SHALL INDICATE THE PIECE MARK OF THE PIECE INSPECTED.
FOR FIELD WORK, THE REPORT SHALL INDICATE THE REFERENCE GRID LINES AND
FLOOR OR ELEVATION INSPECTED. WORK NOT IN COMPLIANCE WITH THE CONTRACT
DOCUMENTS AND WHETHER THE NONCOMPLIANCE HAS BEEN SATISFACTORILY
REPAIRED SHALL BE NOTED IN THE INSPECTION.
VERIFICATION AND INSPECTION TASK QC QA MATERIAL
STD
REFERENCE
AWS D1.1
CLAUSES
STRUCTURAL STEEL AFTER BOLTING - MINIMUM INSPECTION
1. DOCUMENT ACCEPTANCE OR REJECTION OF BOLTED CONNECTIONS P P TABLE C-
N5.6-3 N/A
VERIFICATION AND INSPECTION TASK QC QA MATERIAL
STD
REFERENCE
AWS D1.1
CLAUSES
STRUCTURAL STEEL PRIOR TO WELDING - MINIMUM INSPECTION
1. WELDING PROCEDURE SPECIFICATIONS (WPS) AVAILABLE P P TABLE C-
N5.4-1 6.3
2. MANUFACTURER CERTIFICATES FOR WELDING CONSUMABLES
AVAILABLE
P P TABLE C-
N5.4-1
6.2
3. MATERIAL IDENTIFICATION O O TABLE C-
N5.4-1
6.2
4. WELDER IDENTIFICATION O O TABLE C-
N5.4-1
6.4
(WELDER
QUALIFICA
TION)
5. FIT-UP OF GROOVE WELDS (INCLUDING JOINT GEOMETRY) O O TABLE C-
N5.4-1
a. JOINT PREPARATION O O TABLE C- N5.4-1
6.5.2
b. DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL) O O TABLE C- N5.4-1
5.22
c. CLEANLINESS (CONDITION OF STEEL SURFACE) O O TABLE C- N5.4-1
5.14
d. TACKING (TACK WELD QUALITY AND LOCATION) O O TABLE C- N5.4-1
5.17
e. BACKING TYPE AND FIT (IF APPLICABLE) O O TABLE C- N5.4-1
5.9, 5.21.1.1
6. FIT-UP OF CJP GROOVE WELDS OF HSS T-, Y- & K--JOINTS WITHOUT
BACKING (INCLUDING JOINT GEOMETRY)
P/O1 O TABLE C-
N5.4-1
9.11.2
a. JOINT PREPARATION P/O1 O TABLE C- N5.4-1
9.11.2
b. DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL) P/O1 O TABLE C- N5.4-1
9.11.2
c. CLEANLINESS (CONDITION OF STEEL SURFACE) P/O1 O TABLE C- N5.4-1
9.11.2
d. TACKING (TACK WELD QUALITY AND LOCATION) P/O1 O TABLE C- N5.4-1
9.11.2
7. CONFIGURATION AND FINISH OF ACCESS HOLES O - TABLE C-
N5.4-1
6.5.2, 5.16
(& SEE
AISC 360
SECT. J1.6)
8. FIT-UP OF FILLET WELDS P/O1 O TABLE C-
N5.4-1
a. DIMENSIONS (ALIGNMENT, GAPS AT ROOT) P/O1 O TABLE C- N5.4-1
5.21.1
b. CLEANLINESS (CONDITION OF STEEL SURFACES) P/O1 O TABLE C- N5.4-1
5.14
c. TACKING (TACK WELD QUALITY AND LOCATION) P/O1 O TABLE C- N5.4-1
5.17
9. CHECK WELDING EQUIPMENT O O TABLE C-
N5.4-1
6.2, 5.10
VERIFICATION AND INSPECTION TASK QC QA MATERIAL
STD
REFERENCE
AWS D1.1
CLAUSES
STRUCTURAL STEEL DURING WELDING - MINIMUM INSPECTION
1. USE OF QUALIFIED WELDERS O O TABLE C-
N5.4-2 6.4
2. CONTROL AND HANDLING OF WELDING CONSUMABLES O O TABLE C-
N5.4-2
6.2
a. PACKAGING O O TABLE C- N5.4-2
5.3.1
b. EXPOSURE CONTROL O O TABLE C- N5.4-2
5.3.2 (FOR
SMAW),
5.3.3 (FOR
SAW)
3. ENVIRONMENT CONDITIONS O O TABLE C-
N5.4-2
a. WIND SPEED WITHIN LIMITS O O TABLE C- N5.4-2
5.11.1
b. PRECIPITATION AND TEMPERATURE O O TABLE C- N5.4-2
5.11.2
4. WPS FOLLOWED O O TABLE C-
N5.4-2
6.3.3, 6.5.2, 5.5, 5.20
a. SETTINGS ON WELDING EQUIPMENT O O TABLE C- N5.4-2
b. TRAVEL SPEED O O TABLE C- N5.4-2
c. SELECTED WELDING MATERIALS O O TABLE C- N5.4-2
d. SHIELDING GAS TYPE/FLOW RATE O O TABLE C- N5.4-2
e. PREHEAT APPLIED O O TABLE C- N5.4-2
5.6, 5.7
f. INTERPASS TEMPERATURE MAINTAINED (MIN/MAX) O O TABLE C- N5.4-2
g. PROPER POSITION (F, V, H, OH) O O TABLE C- N5.4-2
h. INTERMIX OF FILLER METALS AVOIDED UNLESS APPROVED O O TABLE C- N5.4-2
5. WELDING TECHNIQUES O O TABLE C-
N5.4-2
6.5.2, 6.5.3, 5.23
a. INTERPASS AND FINAL CLEANING O O TABLE C- N5.4-2
5.29.1
b. EACH PASS WITHIN PROFILE LIMITATIONS O O TABLE C- N5.4-2
c. EACH PASS MEETS QUALITY REQUIREMENTS O O TABLE C- N5.4-2
VERIFICATION AND INSPECTION TASK QC QA MATERIAL
STD
REFERENCE
AWS D1.1
CLAUSES
STRUCTURAL STEEL AFTER WELDING - MINIMUM INSPECTION
1. WELDS CLEANED O O TABLE C-
N5.4-3 5.29.1
2. SIZE, LENGTH AND LOCATION OF WELDS P P TABLE C-
N5.4-3
6.5.1
3. WELDS MEET VISUAL ACCEPTANCE CRITERIA P2 P2 TABLE C-
N5.4-3
6.5.3
a. CRACK PROHIBITION P2 P2 TABLE C- N5.4-3
TABLE
6.1(1)
b. WELD/BASE-METAL FUSION P2 P2 TABLE C- N5.4-3
TABLE
6.1(2)
c. CRATER CROSS-SECTION P2 P2 TABLE C- N5.4-3
TABLE
6.1(3)
d. WELD PROFILES P2 P2 TABLE C- N5.4-3
TABLE
6.1(4), 5.24
e. WELD SIZE P2 P2 TABLE C- N5.4-3
TABLE
6.1(6)
f. UNDERCUT P2 P2 TABLE C- N5.4-3
TABLE
6.1(7)
g. POROSITY P2 P2 TABLE 6.1(8)
4. ARC STRIKES P P TABLE C-
N5.4-3
5.28
5. K-AREA3 P2 P2 TABLE C-
N5.4-3
N/A
6. WELD ACCESS HOLES IN ROLLED HEAVY SHAPES AND BUILT-UP HEAVY
SHAPES
P P TABLE C-
N5.4-3
5.16, 6.5.2
(& SEE
AISC 360
SECT. J1.6)
7. BACKING REMOVED AND WELD TABS REMOVED (IF REQUIRED) P2 P2 TABLE C-
N5.4-3
5.9, 5.30
8. REPAIR ACTIVITIES P P2 TABLE C-
N5.4-3
6.5.3, 5.25
9. DOCUMENT ACCEPTANCE OR REJECTION OF WELDED JOINT OR
MEMBER
P P TABLE C-
N5.4-3
6.5.4, 6.5.5
10. PLACEMENT OF REINFORCING OR CONTOURING FILLET WELDS (IF
REQUIRED)
P2 P2 TABLE C-
N5.4-3
6.5.4, 6.5.5
1 FOLLOWING PERFORMANCE OF THIS INSPECTION TASK FOR TEN WELDS TO BE MADE
BY A GIVEN WELDER, WITH THE WELDER DEMONSTRATING UNDERSTANDING OF
REQUIREMENTS AND POSSESSION OF THE SKILLS TO VERIFY THESE ITEMS, THE
PERFORM DESIGNATION OF THIS TASK SHALL BE REDUCED TO OBSERVE, AND THE
WELDER SHALL PERFORM THIS TASK. SHOULD THE INSPECTOR DETERMINE THE WELDER
HAS DISCONTINUED PERFORMANCE OF THIS TASK, THE TASK SHALL BE RETURNED TO
PERFORM UNTIL SUCH TIME AS THE INSPECTOR HAS RE-ESTABLISHED ADEQUATE
ASSURANCE THE WELDER WILL PERFORM THE INSPECTION TASKS LISTED.
2 DOCUMENT - THE INSPECTOR SHALL PREPARE REPORTS INDICATING THE WORK HAS
BEEN PERFORMED IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. THE REPORT
NEED NOT PROVIDE DETAILED MEASUREMENTS FOR JOINT FIT-UPS, WPS SETTINGS,
COMPLETED WELDS, OR OTHER INDIVIDUAL ITEMS LISTED IN THE TABLES. FOR SHOP
FABRICATION, THE REPORT SHALL INDICATE THE PIECE MARK OF THE PIECE INSPECTED.
FOR FIELD WORK, THE REPORT SHALL INDICATE THE REFERENCE GRID LINES AND
FLOOR OR ELEVATION INSPECTED. WORK NOT IN COMPLIANCE WITH THE CONTRACT
DOCUMENTS AND WHETHER THE NONCOMPLIANCE HAS BEEN SATISFACTORILY
REPAIRED SHALL BE NOTED IN THE INSPECTION.
3 WHEN WELDING OF DOUBLER PLATES, CONTINUITY PLATES OR STIFFENERS HAS BEEN
PERFORMED IN THE K-AREA, VISUALLY INSPECT THE WEB K-AREA FOR CRACKS WITHIN 3 ”
OF THE WELD. THE VISUAL INSPECTION SHALL BE PERFORMED NO SOONER THAN 48
HOURS FOLLOWING COMPLETION OF THE WELDING.
VERIFICATION AND INSPECTION TASK QC QA MATERIAL
STD
REFERENCE
STRUCTURAL STEEL - OTHER INSPECTION TASKS REQUIRED BY AISC 341
1. RBS REQUIREMENTS, IF APPLICABLE P1 P1 -
2. CONTOUR AND FINISH P1 P1 -
3. DIMENSIONAL TOLERANCES P1 P1 -
4. PROTECTED ZONE - NO HOLES AND UNAPPROVED ATTACHMENTS MADE
BY FABRICATOR OR ERECTOR, AS APPLICABLE
P1 P1 -
1 DOCUMENT - THE INSPECTOR SHALL PREPARE REPORTS INDICATING THE WORK HAS
BEEN PERFORMED IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. THE REPORTS
NEED NOT PROVIDE DETAILED MEASUREMENTS FOR JOINT FIT-UPS, WPS SETTINGS,
COMPLETED WELDS, OR OTHER INDIVIDUAL ITEMS LISTED IN THE TABLES. FOR SHOP
FABRICATION, THE REPORT SHALL INDICATE THE PIECE MARK OF THE PIECE INSPECTED.
FOR FIELD WORK, THE REPORT SHALL INDICATE THE REFERENCE GRID LINES AND
FLOOR OR ELEVATION INSPECTED. WORK NOT IN COMPLIANCE WITH THE CONTRACT
DOCUMENTS AND WHETHER THE NONCOMPLIANCE HAS BEEN SATISFACTORILY
REPAIRED SHALL BE NOTED IN THE INSPECTION.
VERIFICATION AND INSPECTION TASK CONTINUOU
S
PERIODI
C
MATERIAL
STD
REFERENCE
IBC
REFERENCE
STRUCTURAL DECKING
1. DECK PLACEMENT AND ATTACHMENT X X - -
Revisions: Date:
TESTING, INSPECTIONS, AND OBSERVATIONS
1.
2.
3.
THE STRUCTURAL ENGINEER DOES NOT PROVIDE INSPECTIONS OF
CONSTRUCTION. STRUCTURAL ENGINEER MAY MAKE PERIODIC OBSERVATIONS OF
THE CONSTRUCTION. SUCH OBSERVATIONS SHALL NOT REPLACE REQUIRED
INSPECTIONS BY THE GOVERNING AUTHORITIES OR SERVE AS “SPECIAL
INSPECTIONS” AS MAY BE REQUIRED BY CHAPTER 17 OF THE INTERNATIONAL
BUILDING CODE.
SEE ARCHITECTURAL, CIVIL, MECHANICAL, PLUMBING, AND ELECTRICAL
DRAWINGS OR SPECIFICATIONS FOR TESTING AND INSPECTION REQUIREMENTS
OF NON-STRUCTURAL COMPONENTS.
DUTIES OF THE INSPECTION AGENCY PER IBC CHAPTER 17:
a.
b.
c.
d.
SUBMIT A PROPOSED TESTING AND INSPECTION PROGRAM TO THE OWNER,
THE ARCHITECT AND THE STRUCTURAL ENGINEER FOR REVIEW AND
APPROVAL AT LEAST TWO WEEKS PRIOR TO COMMENCEMENT OF WORK.
PERFORM ALL TESTING AND INSPECTION REQUIRED PER APPROVED
TESTING AND INSPECTION PROGRAM.
FURNISH INSPECTION REPORT TO THE BUILDING OFFICIAL, THE OWNER,
THE ARCHITECT, STRUCTURAL ENGINEER AND THE GENERAL
CONTRACTOR. THE REPORTS SHALL BE COMPLETED AND FURNISHED
WITHIN 48 HOURS OF INSPECTED WORK.
SUBMIT A FINAL SIGNED REPORT STATING WHETHER THE WORK REQUIRING
SPECIAL INSPECTION WAS, TO THE BEST OF THE SPECIAL INSPECTION
AGENCY’S KNOWLEDGE, IN CONFORMANCE WITH THE APPROVED PLANS
AND SPECIFICATIONS.
4. SPECIAL INSPECTIONS AND TESTS ARE REQUIRED FOR MATERIALS AND SYSTEMS
REQUIRED TO BE INSTALLED IN ACCORDANCE WITH ADDITIONAL
MANUFACTURER’S INSTRUCTIONS THAT PRESCRIBE REQUIREMENTS NOT
CONTAINED IN CHAPTER 17 OF THE IBC OR IN STANDARDS REFERENCED BY THE
IBC. THESE ITEMS INCLUDE:
a. POST-INSTALLED ANCHORS - INSPECTION
5. THE FOLLOWING WORK SHALL BE INSPECTED BY THE SPECIAL INSPECTOR
UNLESS SPECIFICALLY WAIVED BY THE BUILDING OFFICIAL.
VERIFICATION AND INSPECTION TASK
CONTINUOUS PERIODIC
MATERIAL
STD
REFERENCE
IBC
REFERENCE
CONCRETE CONSTRUCTION
1. INSPECT REINFORCEMENT, AND VERIFY
PLACEMENT
- X ACI 318: CH 20,
25.2, 25.3, 26.2.1-26.6.3
1908.4
2. MATERIAL IDENTIFICATION OF REINFORCING
(TYPE/GRADE)
- X AISC 341:
TABLE J9.1
3. REINFORCING STEEL HAS NOT BEEN REBENT
IN THE FIELD
- X AISC 341:
TABLE J9.1
4. REINFORCING STEEL HAS BEEN TIED AND
SUPPORTED AS REQUIRED
- X AISC 341:
TABLE J9.1
L P Q
19.1
'-0
12'-0"
30'-0"
1.
2.
KEYNOTES:
62 PSF DRIFT SNOW LOAD.
57 PSF DRIFT SNOW LOAD.
1.
2.
LOAD SHEET NOTES:
MINIMUM BALANCE SNOW LOADING:
46 PSF ENTIRE ROOF
RAMP UP TO PEAK DRIFT LOAD OVER
DISTANCE SHOWN ON PLAN.
ROOF LIVE LOAD: 20 PSF (REDUCIBLE)
STRUCTURAL ABBREVIATION KEY
ABBR: DESCRIPTION: ABBR: DESCRIPTION:
KSF
KSI
L
LBS
LL
LLH
LLV
LONG.
LSH
LSV
LT WT
MAX
MECH
MANUF
MIN
NIC
NTS
OC
OH
OPNG
OSB
PCF
P.H.
PJP
PL
PLF
PSF
PSI
PT
R
REINF
REQD
RTU
SC
SCHED
SFRS
SIM
SL
S.M.S.
SP
SPECS
SQ
STIFF
STL
SYM
T&B T.O.
TC
TEMP
tf
THK
TRANS
TYP
UON
VERT
VIF
W/
WP
WT
WWR
(E) A.B.
ARCH
B.O.
bf
BF
BM
B.N.
BOTT
BTWN
CFSF
CGS
CJP
CLR
CL
CMU
COL
CONC
CONN
CONST
CONT
COORD
DIA
DL
DET
DWG
DWL
EA
EF
EFF
EL
ELEC
EMBED
E.N.
EOD
EOS
EQ
EQUIP
ETC
EW
EXP
EXT
f 'c
FDN
F.N.
FT
FTG
Fy
GA
GALV
GLB
GT
HORIZ
HSA
HSB
JT
K, KIP
NUMBER OR POUNDS
AT
DEGREE
DIAMETER
EXISTING
ANCHOR BOLT
ARCHITECT, -URE, -URAL
BOTTOM OF
BEAM FLANGE WIDTH
BRACE FRAME
BEAM
BOUNDARY NAILING
BOTTOM
BETWEEN
COLD FORM STEEL FRAMING
CENTER OF GRAVITY OF THE TENDON
COMPLETE JOINT PENETRATION WELD
CLEAR
CENTERLINE
CONCRETE MASONRY UNIT
COLUMN
CONCRETE
CONNECTION
CONSTRUCTION
CONTINUOUS
COORDINATION
DIAMETER
DEAD LOAD
DETAIL
DRAWING
DOWEL
EACH
EACH FACE
EFFECTIVE
ELEVATION
ELECTRICAL
EMBEDMENT
EDGE NAILING
EDGE OF DECK
EDGE OF SLAB
EQUAL
EQUIPMENT
ETCETERA
EACH WAY
EXPANSION
EXTERIOR
CONCRETE COMPRESSIVE STRENGTH
FOUNDATION
FIELD NAILING
FOOT
FOOTING
YIELD STRESS
GAGE OR GAUGE
GALVANIZED
GLULAM BEAM
GIRDER TRUSS
HORIZONTAL
HEADED STUD ANCHOR
HIGH STRENGTH BOLT
JOINT
KILOPOUND (1,000 POUNDS)
KIPS PER SQUARE FOOT
KIPS PER SQUARE INCH
LENGTH
POUNDS
LIVE LOAD
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LONGITUDINAL
LONG SIDE HORIZONTAL
LONG SIDE VERTICAL
LIGHTWEIGHT
MAXIMUM
MECHANICAL
MANUFACTURER
MINIMUM
NOT IN CONTRACT
NOT TO SCALE
ON CENTER
OPPOSITE HAND
OPENING
ORIENTED STRAND BOARD
POUNDS PER CUBIC FOOT
PENTHOUSE
PARTIAL JOINT PENETRATION WELD
PLATE
POUNDS PER LINEAR FOOT
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
POST-TENSION, -ED, -ING
RADIUS
REINFORCING, -MENT, -ED
REQUIRED
ROOF TOP UNIT
SLIP CRITICAL
SCHEDULE
SEISMIC FORCE-RESISTING SYSTEM
SIMILAR
SNOW LOAD
SHEET METAL SCREW
SPACE(S)
SPECIFICATION(S)
SQUARE
STIFFENER
STEEL
SYMMETRICAL
TOP AND BOTTOM
TOP OF
PRE-TENSIONED BOLT
TEMPERATURE
BEAM FLANGE THICKNESS
THICK
TRANSVERSE
TYPICAL
UNLESS OTHERWISE NOTED
VERTICAL
VERIFY IN FIELD
WITH
WORK POINT
WEIGHT
WELDED WIRE REINFORCING
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
4/
/2
4:
:2
PM
Au to de sk
D oc s:
//5
A7
-2 2-
VA
S yr ac us e
EH
R
M in fra st ru ct ur e
U pg ra de s/
VA
SY
_0
1_
ST
_I M
EG
.rv t
S002
PLAN NOTES & LOAD SCHEDULE
EB GRB
100% CONSTRUCTION
DOCUMENTS
08/29/2025
528A7-22-700EHRM INFRASTRUCTURE
UPGRADES - SYRACUSE VA
VA NY SYRACUSE
800 IRVING AVE., SYRACUSE, NY 13210
BASEMENT FL HOSPITAL (LAB & OFFICE ) 100 Y
GROUND FL CANTEEN / DINNING HALL 100 N
1ST FL HOSPITAL (PATIENT ROOM & OFFICE) 100 Y
2ND FL HOSPITAL (LAB & OFFICE ) 100 Y
3RD FL HOSPITAL (LAB) 100 Y
4TH FL HOSPITAL (LAB & OFFICE ) 100 Y
5TH FL OPEN TO BELOW N/A N/A
LOW ROOF NO OCCUPANCY 20 Y
LOWER MCR FLOOR UPS ROOM/MECHANICAL/PLATFORM 300/100/40 N/N/Y
MCR FLOOR (6TH FL) DATA CENTER 250 N
MCR ROOF ROOF 20PSF ROOF LL/SNOW LOAD Y
LEVEL CURRENT USAGE (AREA UNDER DATA CENTER) ASSUMED LIVE LOAD (PSF) REDUCIBLE? (Y/N)
1/8" = 1'-0"
SNOW DRIFT MAP2
NO SCALE
EXISTING FLOOR LOAD SCHEDULE4
Revisions: Date:
1 : 1
ABBREVIATIONS3
3D VIEW1
K L L.1 M N P Q
17.1
16.1
19.1
K.9
6'-6" Ø (-15'-0") 5'-6" Ø (-15'-0")
5'-9" Ø (-15'-0")5'-3" Ø (-15'-0")
5'-9" Ø (-15'-0") 5'-3" Ø (-15'-0")5'-6" Ø (-15'-0")
5'-3" Ø (-15'-0")
5'-6" Ø (-15'-0")
6'-9" Ø (-15'-0")
6'-6" Ø (-15'-0")
8'-6" Ø (-15'-0") 7'-0" Ø (-15'-0") 7'-0" Ø (-15'-0") 6'-0" Ø (-15'-0")
A: 650k B: 595k C: 61k D: 656k
A: 396k B: 371k C: 115k D: 486k
A: 434k B: 415k C: 100k D: 515k
A: 510k B: 482k C: 69k D: 551k
A: 466k B: 414k C: 81k D: 495k
A: 405k B: 361k C: 103k D: 464k
A: 398k B: 346k C: 76k D: 422k
A: 578k B: 519k C: 56k D: 575k
A: 413k B: 363k C: 109k D: 472k
A: 409k B: 346k C: 130k D: 476k
A: 466k B: 416k C: 76k D: 492k
A: 447k B: 421k C: 49k D: 470k
A: 611k B: 585k C: 107k D: 692k
A: 670k B: 644k C: 99k D: 743k
A: 934k B: 903k C: 32k D: 935k
A: EX LOAD (LL UNREDUCED):
B: EX LOAD (LL REDUCED):
C: DATA CENTER LOAD:
D: TOTAL (EX LL REDUCED):
15'-4" 19'-6" 19'-6" 19'-6" 19'-6"
12'-10" 6'-0"
2' -1
/2
'-4
9' -8
'-4
'-2
3' -0
6'
-8
3' -0
'-4
6' -0
'-2
3'-6" Ø
3'-0" Ø 3'-0" Ø…
This is the start of the file's text. The full file is on GovTribe.