02 82 11.01 - Addendum 01.pdf
PDF 8 MB Posted
- Solicitation number
- 36C77626B0001
About this file
This document is an Asbestos Containing Materials and Lead Based Paints Assessment for the West Texas VA Health Care Hospital in Big Spring, Texas. The assessment was conducted by ECS Southwest on December 5, 2023, focusing on rooms #95, 96A, 96B, 96C, 96D, 96E, and 98. The survey involved sampling and analyzing various materials including floor tiles, mastics, joint compounds, drywall, and ceiling tiles for the presence of asbestos and lead-based paint.
Laboratory analysis by Southeastern Environmental Microbiology Laboratories found no asbestos-containing materials (ACMs) in the sampled materials, with all samples testing below the 1% asbestos threshold. Similarly, the lead-based paint survey using X-Ray Fluorescence (XRF) spectrometry did not identify any lead-based paints in the examined surfaces. The report recommends that if additional suspect materials are discovered during future construction activities, they should be sampled or presumed to contain asbestos and handled accordingly. The assessment was performed by licensed professionals, including Jose De Los Reyes, a Texas Department of State Health Services Asbestos Inspector, and followed EPA and OSHA guidelines.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ASBESTOS CONTAINING MATERIALS AND LEAD
BASED PAINTS ASSESSMENT
WEST TEXAS VA HEALTH CARE HOSPITAL
300 WEST VETERANS BLVD
ROOMS #95, 96A, 96B, 96C, 96D, 96E, AND 98
BIG SPRING, TEXAS 75460
ECS PROJECT NO. 51:3784
FOR: AGRACEL, INC.
DECEMBER 15, 2023
December 15, 2023 Mr. Brady Cauthen Agracel, Inc.
15 South Main Street, Suite 701 Greenville, South Carolina 29601
ECS Project No. 51:3784
Reference: Asbestos Containing Materials and Lead Based Paints Assessment, West Texas VA Health Care Hospital, 300 West Veterans Blvd,Rooms #95, 96A, 96B, 96C, 96D, 96E, and 98 Big Spring, Texas, 75460
Dear Mr. Cauthen:
ECS Southwest, LLP (ECS) is pleased to provide Agracel, Inc. with the results of the above referenced Asbestos Containing Materials and Lead Based Paints Assessment performed at West Texas VA Health Care Hospital located at 300 West Veterans Blvd in Big Spring, Texas 75460. This report summarizes our observations, analytical results, findings, and recommendations related to the work performed. The work described in this report was performed by ECS in general accordance with the Scope of Services described in ECS Proposal Number 51:5622 and the terms and conditions of the agreement authorizing those services.
ECS appreciates this opportunity to provide Agracel, Inc. with our services. If we can be of further assistance to you, please do not hesitate to contact us.
Sincerely, ECS Southwest, LLP
Jose De Los Reyes Katherine Moore, P.G.
Environmental Staff Project Manager Environmental Principal JDLReyes@ECSLimited.com klmoore@ecslimited.com 713-955-1980 210-428-1530
3033 Kellway Drive, Carrollton, Texas 75006 • T:972-392-3222
TDSHS Asbestos Consultant Agency No. 100592 TDLR Mold Assessment Company No. ACO1212 TDSHS Lead Firm No. 2110759
ECS Florida, LLC • ECS Mid-Atlantic LLC • ECS Midwest, LLC • ECS Southeast, LLC • ECS Southwest, LLP • ECS Pacific, Inc.
ecslimited.com
EXECUTIVE SUMMARY
The subject property consists of of rooms 95, 96A, 96B, 96C, 96D, 96E, and 98 inside a six-story hospital located at 300 West Veterans Blvd, in Big Spring, Howard County, Texas 75460. The structure consists of approximately 150,000 square feet and was reportedly originally constructed in 1979. At the time of our survey, the subject building was occupied and is currently scheduled to have select areas renovated.
The purpose of the survey was to determine if asbestos-containing materials (ACMs), or Lead-Based Paints (LBPs), are present in the pre-discussed targeted scope of rooms #95, 96A, 96B, 96C, 96D, 96E, and 98. The survey was performed within those select interior areas of the subject building.
ECS performed it's survey of the pre-discussed area of identified rooms on December 05, 2023. Jose De Los Reyes a State of Texas Department of State Health Services (TDSHS) Asbestos Inspector License No. 604052, performed the survey on December 05, 2023. Bulk samples were submitted to Southeastern Environmental Micriobiology Laboratories (SEEML) in North Carolina for analysis via Polarized Light Microscopy (PLM) in accordance with the current EPA-600 methodology
A total of 27 bulk samples from nine (9) homogeneous areas were submitted to the laboratory. Based on the laboratory analysis of the bulk samples collected during the survey, none of the materials were reported to contain one (1) percent or greater asbestos-containing materials.
The lead-based paint survey was performed by a State of Texas licensed Lead Risk Assessor. Painted and/or glazed surfaces were assessed for lead content using a Direct-Read X-ray fluorescence (XRF) Spectrometer, SciAps S500. Lead-based paint was not identified inside the subject buildings.
The executive summary is an integral portion of this report, however, ECS recommends the report be read in its entirety.
ii
PAGETABLE OF CONTENTS
1.0 SITE DESCRIPTION
2.0 PURPOSE
3.0 METHODOLOGY
3.1 Asbestos-Containing Materials
3.2 Lead in Paint and Surface Coatings
4.0 RESULTS
4.1 Asbestos Sampling
4.2 Suspect or Assumed Asbestos-Containing Materials
4.3 Lead in Paint and Surface Coatings
5.0 RECOMMENDATIONS AND REGULATORY REQUIREMENTS
5.1 Asbestos-Containing Materials
5.2 Lead in Paint and Surface Coatings
6.0 LIMITATIONS
iii
TABLE OF APPENDICES
Appendix I: Site Photographs
Appendix II: XRF Lead-Based Paint Readings
Appendix III: Laboratory Report(s)
Appendix IV: Certifications/Licenses iv
1.0 SITE DESCRIPTION
The subject property consists of rooms 95, 96A, 96B, 96C, 96D, 96E, and 98 within a six-story hospital located at 300 West Veterans Blvd in Big Spring, Texas 75460. The building was occupied at the time of the survey. The six-story consists of stucco/plaster walls with a slab foundation and a flat roofing system.
2.0 PURPOSE
The purpose of the Asbestos Containing Materials and Lead Based Paints Assessment was to identify asbestos-containing materials (ACM), and lead-based paint (LBP), which require special handling and/ or disposal if disturbed during construction activities. The identification of ACMs requires trained labor, regulated work practices, and special disposal. The identification of LBP or other lead hazards requires disclosure to contractors and monitoring of lead exposure. The removal of other regulated materials such as universal waste may require personal protective equipment, training, special handling, packaging, and disposal.
3.0 METHODOLOGY
ECS performed the authorized Scope of Services in general accordance with our proposal, standard industry practice(s) and methods specified by regulation(s) for the identification of ACMs, and LBPs.
3.1 Asbestos-Containing Materials
The suspect asbestos sampling was performed by an EPA-accredited asbestos inspector who has met the requirements of Title 40, Part 763, Part III, Subpart E, Appendix C of the Code of Federal Regulations; and is currently licensed by the Texas Department of State Health Services to perform Asbestos sampling. Mr. Jose De Los Reyes, an EPA accredited and State of Texas Department of State Health Services Asbestos Inspector License No. 604052, who performed the survey on December 05, 2023. This scope is intended to generally meet the requirements of the Occupational Safety and Health Administration (OSHA) Standard 29 CFR 1926.1101 Inspection Protocol.
Samples of suspect ACMs were collected utilizing hand tools and placed into individual, labeled plastic bags. Unique bulk suspect ACM samples were submitted to Southeastern Environmental Micriobiology Laboratories in Greenville, North Carolina for analysis via Polarized Light Microscopy (PLM) in accordance with the current EPA-600 methodology. Materials consisting of additional layers were analyzed separately. SEEML is listed as an accredited laboratory by the National Voluntary Laboratory Accreditation Plan (NVLAP) managed by the National Institute of Standards and Technology (NIST) and Texas Department of State Health Services (TDSHS) Laboratory license #300474 for bulk sample analysis by currently approved EPA methodology by PLM Method.
During the survey, ECS attempted to identify suspect ACMs in readily accessible areas. However, due to the destructive means required to identify some materials, certain areas were deemed inaccessible (i.e. behind walls or sub grade materials) and were not surveyed for suspect ACMs. Unidentified suspect ACMs may be located in these and/or other inaccessible areas including but not limited to the interior and exterior of the subject building.
December 15, 2023
ECS Project # 51:3784
Samples were collected in general accordance with EPA Standard 40 CFR 763 Subpart E, Asbestos Hazard Emergency Response Act (AHERA) and OSHA Standard 29 CFR 1926.1101 Inspection Protocol.
Multiple samples of each unique material were submitted.Samples were analyzed using the “Positive Stop” methodology. If one sample of homogeneous material is reported to contain asbestos, the remaining samples of that material are not analyzed. EPA regulations stipulate that if one sample contains asbestos the entire quantity of that material contains asbestos, regardless of additional analysis.
3.2 Lead in Paint and Surface Coatings
The Lead-Based Paint (LBP) survey was performed by a State of Texas Lead Risk Assessor No 2071314 using an X-Ray Fluorescence (XRF) Spectrometer to identify lead concentrations in painted and glazed surfaces.
The survey was conducted utilizing the U.S. EPA definition of LBP. Under this definition, painted surfaces that contain lead in concentrations equal to or greater than 1.0 milligrams per square centimeter (≥ 1.0 mg/cm2) are classified as coated with LBP. Paints with concentrations of lead detectable by the XRF are considered lead-containing paints. Additionally, fixtures or components that are manufactured with a factory-applied glazing (i.e., sinks, toilets, ceramic tiles, etc.) are tested as these factory-applied finishes often contain lead. Activities that disturb lead-containing paints and glazing (while not lead-based paints by the U.S. EPA definition) are regulated by OSHA (29 CFR 1926.62).
Because the current or proposed use of the property is not residential or child-occupied, the scope of the LBP survey was not conducted in accordance with HUD Chapter 7 requirements. This representative survey included taking readings from walls, windows, doors, and miscellaneous components. Walls are listed by letter with wall “A” being the entrance of the subject building, proceeding clockwise to “B, C, D”, etc.
4.0 RESULTS
The following is a summary of laboratory results, findings and observations.
4.1 Asbestos Sampling
An Asbestos-Containing Material (ACM) is defined as any material containing more than one percent (>1%) asbestos as determined using the method specified in Appendix E, Subpart E, 40 CFR Part 763, Section 1, PLM. Materials are categorized by the U.S. EPA in the following categories:
• Friable ACMs are defined as any ACM that, when dry, can be crumbled, pulverized or reduced to powder by hand pressure. Non-friable ACMs are defined as any ACM that, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.
• Category I non-friable ACM are listed as following: packings, gaskets, resilient floor coverings, and asphalt roofing products containing more than one percent (>1%) asbestos.
• Category II non-friable ACM are listed as any material, excluding Category I non-friable ACM, containing more than one percent (>1%) asbestos.
December 15, 2023
Regulated Asbestos Containing Materials (RACM) are friable ACM or non-friable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading or has crumbled, been pulverized, or reduced to powder in the course of renovation and/or demolition operations.
Based on the laboratory analysis performed by Southeastern Environmental Micriobiology Laboratories of the bulk samples collected during the survey on December 05, 2023. None of the sampled materials were reported to contain 1% or greater asbestos content and therefore none were found to be asbestos-containing materials. The survey addressed only the pre-discussed of rooms #95, 96A, 96B, 96C, 96D, 96E, and 98. The survey was performed by Jose De Los Reyes, an EPA-accredited Asbestos Inspector, and State of Texas Department of State Health Services Asbestos Inspector License 604052. A detailed summary of the samples collected, locations, and results can be found in the appendix.
An Asbestos-Containing Material (ACM) is defined as any material containing more than one percent (>1%) asbestos as determined using the method specified in Appendix E, Subpart E, 40 CFR Part 763, Section 1, PLM.
4.2 Suspect or Assumed Asbestos-Containing Materials
Due to the inaccessibility or the destructive means that asbestos sampling requires, additional suspect ACMs may remain within the building hidden behind inaccessible areas that include but are not limited to, sub-grade walls, structural members, topping slabs, sub-grade sealants, flooring located below underlayments, areas behind exterior walls, pipe trenches, and subsurface utilities, etc.
These areas were deemed inaccessible and were not assessed.
• Pipe Chases behind and above restrooms and sinks
• Exterior
• Mirror Mastic
• Roof
• Crawlspaces
If these materials are discovered during construction activities, they should be presumed to contain asbestos and be treated as ACMs or be sampled immediately upon discovery and prior to the disturbance for asbestos content by a certified asbestos inspector in accordance with 29 CFR 1926.1101.
4.3 Lead in Paint and Surface Coatings
Paint and surface coatings which contain detectable concentrations of lead are considered lead-containing paints. Since OSHA has no specific action level for lead in paint, all paint on the site found to have a measurable concentration of lead should be assumed to be lead-containing. Work performed which may disturb lead-containing paint is regulated under OSHA as referenced under 29
CFR 1926.62.
A total of 68 readings were collected during the survey, including calibration readings. Lead was not detected in the XRF readings and/or paint chip samples analyzed.
December 15, 2023
5.0 RECOMMENDATIONS AND REGULATORY REQUIREMENTS
Based on our understanding of the purpose of the Asbestos Containing Materials and Lead Based Paints Assessment, the results of laboratory analysis, and our findings and observations, ECS presents the following recommendations.
5.1 Asbestos-Containing Materials
Based on the asbestos-containing materials survey and laboratory results, None of the bulk samples submitted to Southeastern Environmental Micriobiology Laboratories were reported to contain detectable concentrations of asbestos. If additional suspect asbestos-containing materials are uncovered which were not accessible during this sampling event, it is recommended that these materials be sampled or tested immediately upon discovery for asbestos content by an asbestos inspector in accordance with 29 CFR 1926.1101.
Additional suspect ACMs may remain within inaccessible areas that include but are not limited to, sub-grade walls, structural members, topping slabs, exterior areas, sub-grade sealants, flooring located below underlayments, vapor barriers, pipe trenches, pipe chases and other subsurface utilities, etc. If additional suspect ACMs are uncovered which were not accessible during this survey, it is recommended that these materials either be assumed to contain asbestos or be sampled prior to disturbance upon discovery for asbestos content by an EPA-accredited and TDSHS-licensed asbestos inspector in accordance with 29 CFR 1926.1101 and Texas Asbestos Health Protection Rules (TAHPR).
An Asbestos Abatement Specification is required be prepared to delineate and quantify known and suspect hazardous and regulated materials in the buildings and to outline proper procedures for the abatement. This is a TDSHS requirement prior to demolition or renovation activities which may disturb the identified asbestos containing material in the path of construction. This will help protect the owner’s liability in better defining the scope of work and contractors’ roles and responsibilities in the abatement process and holding the contractor accountable for the performance of the project.
The specification typically defines the Contractor’s scope of work and outlines requirements and procedures that must be followed for the project. The intent of the specification is to give performance requirements for the Contractor so that the project can be completed safely and in compliance with applicable federal and state regulations. Typically, the asbestos abatement specification document serves as part of the site owner’s contract with the contractor.
5.2 Lead in Paint and Surface Coatings
The results of the lead-based paint survey did not identify detectable concentrations of lead in the surfaces analyzed by ECS using a XRF. Should future activities disturb building materials which were not tested for the presence of lead additional testing should be performed or the materials should be assumed to contain lead.
6.0 LIMITATIONS
The conclusions and recommendations presented within this report are based upon a reasonable level of assessment within normal bounds and standards of professional practice for a site in this particular geographic setting. ECS is not responsible or liable for the discovery and elimination of hazards that may potentially cause damage, accidents, or injuries.
December 15, 2023
The observations, conclusions, and recommendations pertaining to environmental conditions at the subject site are necessarily limited to conditions observed, and/or materials reviewed at the time this study was undertaken. No warranty, expressed or implied, is made with regard to the conclusions and recommendations presented within this report. This report is provided for the exclusive use of the client. This report is not intended to be used or relied upon in connection with other projects or by other unidentified third parties without the written consent of ECS and the client.
This survey is not intended to represent an exhaustive research of every potential hazard or condition that may exist, nor does it claim to represent indoor conditions or events that arise after the survey.
This report has been prepared in accordance with generally accepted environmental practices. Our conclusions and findings are based, in part, upon information provided to us by others and our site observations. We have not verified the completeness or accuracy of the information provided by others. The scope of services performed was limited to those requested by the Client and does not constitute a full microbial assessment of the site or a comprehensive moisture survey of the site. The data provided in this study is only indicative of conditions sampled at the immediate time of the study. The work performed in conjunction with this assessment and the data developed is intended as a description of available information at the dates and locations given. This report does not warrant against future operations or conditions, nor does it warrant against extant, or future, conditions of a type or at a location not investigated. Because of the nature of this type of work and the difficulties involved in conducting remediation work, ECS cannot guarantee that the methods or recommendations described in this report will eliminate all potential indoor air quality issues.
Since performance of the remediation work is also beyond ECS scope of services, ECS also cannot be held responsible for the execution of the remediation work. The reported microbial levels are only reflective of conditions at the time of this test and that microbial populations can vary over time, depending upon a number of conditions, including environmental factors (i.e., temperature and relative humidity). The work performed in conjunction with this assessment and the data developed is intended as a description of available information at the dates and locations given.
Our recommendations are in part based on federal, state, and local regulations and guidelines. ECS does not assume the responsibility of the person(s) in charge of the site, or otherwise undertake responsibility for reporting to any local, state, or federal public agencies, any conditions at the site that may present a potential danger to public health, safety, or the environment. Under this scope of services, ECS assumes no responsibility regarding any response actions initiated as a result of these findings. General compliance with regulations and response actions are the sole responsibility of the Client and should be conducted in accordance with local, state, and/or federal requirements.
December 15, 2023
Appendix I: Site Photographs
1 - MAIN ENTRY TO HOSPITAL
2 - CORRIDOR WITH ROOMS IN SCOPE OF WORK
ECS Project No. 51:3784
3 - RESTROOMS
4 - CORRIDOR WITH ROOMS IN SCOPE
5 - ENTRY TO ROOM 96
6 - ROOM 96D INTERIOR VIEW
7 - ROOM 96D INTERIOR
8 - MULTILAYERED FLOORING IN ROOM 96D
9 - CLOSET 96E INTEIOR
10 - DETAIL VIEW OF MULTILAYERED FLOORING
11 - INTERIOR OF 96A
12 - INTERIOR OF 96A
13 - 96B INTERIOR GENERAL VIEW
14 - FLOORING DETAIL VIEW IN ROOM 96C
15 - 96C INTERIOR GENERAL VIEW
16 - ROOM 95 INTERIOR GENERAL VIEW
17 - RESIDUAL MASTIC IN ROOM 95
18 - ABOVE CEILING IN ROOM 95
19 - ABOVE CEILING IN ROOM 95
20 - ROOM 96 INTERIOR GENERAL VIEW
21 - ROOM 96 INTERIOR GENERAL VIEW
22 - ROOM 96 INTERIOR GENERAL VIEW
23 - ABOVE CEILING IN ROOM 96D
24 - FLOORING DETAIL VIEW IN ROOM 96
25 - FLOORING DETAIL VIEW IN ROOM 96A
26 - FLOORING DETAIL VIEW IN ROOM 98
27 - FLORING DETAIL VIEW IN ROOM 98
28 - YELLOW MASTIC IN ROOM 98
29 - ABOVE CEILING IN ROOM 95
Appendix II: XRF Lead-Based Paint Readings
West Texas VA Health Care Center
300 West Veterans Blvd
BIg Spring, Texas 75460
Test # Serial # Pass/Fail Unit type Calibration Model/Matrix ID Pb Pb +/- Pb P/F 1 X550-02215 Pass mg/cm2 PCS Cal 1.1 0.1 Positive 2 X550-02215 Pass mg/cm2 PCS Cal 1.1 0.1 Positive 3 X550-02215 Pass mg/cm2 PCS Cal 1.1 0.1 Positive 4 X550-02215 Pass mg/cm2 PCS Cal 1.1 0.1 Positive 5 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 6 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 7 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 8 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 9 X550-02215 Pass mg/cm2 LeadPaint 0.1 0.1 Negative
10 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 11 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 12 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 13 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 14 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 15 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 16 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 17 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 18 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 19 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 20 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 21 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 22 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 23 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 24 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 25 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 26 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 27 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 28 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 29 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 30 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 31 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 32 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 33 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 34 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 35 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 36 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 37 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 38 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 39 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 40 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 41 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative
West Texas VA Health Care Center
300 West Veterans Blvd
BIg Spring, Texas 75460
Test # Serial # Pass/Fail Unit type Calibration Model/Matrix ID Pb Pb +/- Pb P/F 42 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 43 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 44 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 45 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 46 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 47 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 48 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 49 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 50 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 51 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 52 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 53 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 54 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 55 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 56 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 57 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 58 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 59 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 60 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 61 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 62 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 63 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 64 X550-02215 Pass mg/cm2 LeadPaint 0 0.1 Negative 65 X550-02215 Pass mg/cm2 PCS Cal 1.2 0.1 Positive 66 X550-02215 Pass mg/cm2 PCS Cal 1.1 0.1 Positive 67 X550-02215 Pass mg/cm2 PCS Cal 1.1 0.1 Positive 68 X550-02215 Pass mg/cm2 PCS Cal 1.1 0.1 Positive
Appendix III: Laboratory Report(s)
Asbestos Analytical Report By: Polarized Light Microscopy
Client Project Name: Big Spring Va Hospital
The Following report was prepared using this test method(s) contained within this document.
Thank you for choosing SEEML Labs. We strive to provide superior quality testing, analytical data and customer service. SEEML is accredited through the National Institute of Standards and Technology (NIST) National
Voluntary Accreditation Program (NVLAP) for bulk asbestos analysis NVLAP # 201031-0 and licensed by the
Texas Department of State Health Services (License Number: 300474). This report must not be used to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the US government.
Date Issued: 12/11/2023
Southeast Environmental Microbiology Laboratories 102 Edinburgh Court
Greenville, SC 29607
Phone: (864) 233-3770
Fax: (864) 233-6589
SEEML Reference Number:
G-231206043
This report has been prepared for ECS Southwest the information and data has been checked for thoroughness and accuracy. The results reported apply only to the materials as received.
The documents(s) contained herein are confidential and privileged information intended for the exclusive use of the individual or entity named above. This report shall not be reproduced except in full without SEEML’s approval.
Approved By : Andrea Berrios
PLM Bulk Asbestos Fiber Analysis: EPA 600/R-93/116
PLM 400 Point Count (<0.25%) EPA 600/R-93/116
PLM 1000 Point Count (<0.1%) EPA 600/R-93/116
PLM Carb 435 Level A Reporting Limit (<0.25%)
PLM Carb 435 Level B (Reporting limit <0.1%)
PLM by EPA/600/R-93/116 with Milling Prep 400 Point Count
PLM Vermiculite Initial Screening EPA 600R-93/116
PLM Cincinnati Method 600/R-04/004 (Amphibole Only)
PLM Vermiculite Method SOF-V 198.8 (Step 1 Chrysotile & Prep)
PLM Vermiculite Method SOF-V 198.8 (Step 2 (Amphibole)
Form 16 Rev. 7 05/11/20 Page 1 of 7
Texas Lic: 300474
Client:
Lab No.:
Client No.:
175A
175B
176A
176B
177A
177B
178A
178B
178C
Form 8.0 Rev. 8 04/29/20
95% Organic Matrix
(Black) Mastic/96E
Big Springs, TX
300 W Veterans Blvd
95% Organic Matrix
100% Organic Matrix (White) Floor Tile/96D
100% Organic Matrix
G-231206043SEEML Ref#:
95% Organic Matrix
Description/Location
(White) Floor Tile/96D
(Black) Mastic/96D
(White) Floor Tile/96E
100% Organic Matrix
% Non-Fibrous Material
EPA/600/R-93/116 Without Gravimetry
Project No:
Analyzed by: Andrea Berrios City, State. ZIP:
Project Address:
% Asbestos Type % Fibrous Non-
Asbestos Material Type
Methodology:
None Detected
None Detected
5% Cellulose
None Detected
None Detected
5% Cellulose
None Detected
None Detected
None Detected
None Detected
Southeast Environmental Microbiology Laboratories - Asbestos Division
102 Edinburgh Court Greenville, SC 29607
Phone: 864-233-3770, Fax: 864-233-6589 , www.seeml.com
Date Sampled:
Date Received:
ECS Southwest
PLM Asbestos Bulk Sample Summary
12/05/2023
12/06/2023100 Post OakRoad #240
NVLAP Lab ID:201031-0
Approved By: Andrea Berrios Disclaimer:
The results in this report only apply to the samples as received.
NOB samples are tested as a preliminary analysis. We highly recommend for Negative NOB samples resulting in less than 1% Asbestos to be verified by TEM or Point Analysis.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. NAD means no asbestos fibers were detected. When detected the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
Guidelines for Interpretation:
Any opinions/interpretations expressed in this report are outside the scope of this laboratory's accreditation. Interpretation of the data and information within this document is left to the company, consultant, and/or persons who conducted the fieldwork. A material is considered regulated asbestos containing material (ACM) where the asbestos content is determined to be one percent or greater. Several organizations, including the
American Conference of Government Industrial Hygienists (ACGIH); the American Industrial Hygiene Association (AIHA); the Indoor Air Quality Association (IAQA); the United States Environmental Protection Agency (USEPA);
the Centers for Disease Control (CDC) as well as the California Department of Health Services (CADHS) have published guidelines for assessment and interpretation of analytical data indicating a tested material is ACM.
5% Cellulose
(White) Joint Compound-Layer 2/96E
None Detected
None Detected 100% Binder/Filler (White) Joint Compound-Layer 1/96E
100% Binder/Filler
None Detected
None Detected
None Detected
None Detected None Detected
(Black) Mastic/96D
(White) Texture/96E100% Binder/Filler
Date Revised:
Houston,TX,77055
(281)814-2502/mak@seeml.com
12/11/2023Date Analyzed:
Date Reported:
Project Name:
12/11/2023
Big Spring Va Hospital
51-3784
Lab No.:
Client No.:
178D
179A
179B
179C
179D
180A
180B
180C
180D
None Detected 10% Cellulose,5%
Fiberglass 85% Gypsum (White) Drywall/98
Approved By: Andrea Berrios Disclaimer:
The results in this report only apply to the samples as received.
NOB samples are tested as a preliminary analysis. We highly recommend for Negative NOB samples resulting in less than 1% Asbestos to be verified by TEM or Point Analysis.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. NAD means no asbestos fibers were detected. When detected the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
Guidelines for Interpretation:
Any opinions/interpretations expressed in this report are outside the scope of this laboratory's accreditation. Interpretation of the data and information within this document is left to the company, consultant, and/or persons who conducted the fieldwork. A material is considered regulated asbestos containing material (ACM) where the asbestos content is determined to be one percent or greater. Several organizations, including the
American Conference of Government Industrial Hygienists (ACGIH); the American Industrial Hygiene Association (AIHA); the Indoor Air Quality Association (IAQA); the United States Environmental Protection Agency (USEPA);
the Centers for Disease Control (CDC) as well as the California Department of Health Services (CADHS) have published guidelines for assessment and interpretation of analytical data indicating a tested material is ACM.
None Detected None Detected 100% Binder/Filler (White) Joint Compound-Layer 1/98
None Detected None Detected 100% Binder/Filler (White) Joint Compound-Layer 2/98
None Detected 10% Cellulose,5%
Fiberglass 85% Gypsum (White) Drywall/96C
None Detected 10% Cellulose 90% Organic Matrix (Tan) Vinyl Covering/98
None Detected None Detected 100% Binder/Filler (White) Joint Compound-Layer 1/96C
None Detected None Detected 100% Binder/Filler (White) Joint Compound-Layer 2/96C
None Detected 10% Cellulose,5%
Fiberglass 85% Gypsum (White) Drywall/96E
None Detected 10% Cellulose 90% Organic Matrix (Tan) Vinyl Covering/96C
Methodology: EPA/600/R-93/116 Without Gravimetry SEEML Ref#: G-231206043
% Asbestos Type % Fibrous Non-
Asbestos Material Type % Non-Fibrous Material Description/Location
Analyzed by: Andrea Berrios Project Address: 300 W Veterans Blvd
City, State. ZIP: Big Springs, TX
Project Name: Big Spring Va Hospital
Project No: 51-3784
(281)814-2502/mak@seeml.com Date Reported: 12/11/2023
Date Revised:
100 Post OakRoad #240 Date Received: 12/06/2023
Houston,TX,77055 Date Analyzed: 12/11/2023
Southeast Environmental Microbiology Laboratories - Asbestos Division
102 Edinburgh Court Greenville, SC 29607
Phone: 864-233-3770, Fax: 864-233-6589 , www.seeml.com
NVLAP Lab ID:201031-0
PLM Asbestos Bulk Sample Summary
ECS Southwest Date Sampled: 12/05/2023
Lab No.:
Client No.:
181A
181B
182A
182B
183A
183B
184A
185A
186A
20% Min Wool,60%
Cellulose 20% Perlite (Tan) Ceiling Tile/98
Approved By: Andrea Berrios Disclaimer:
The results in this report only apply to the samples as received.
NOB samples are tested as a preliminary analysis. We highly recommend for Negative NOB samples resulting in less than 1% Asbestos to be verified by TEM or Point Analysis.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. NAD means no asbestos fibers were detected. When detected the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
Guidelines for Interpretation:
Any opinions/interpretations expressed in this report are outside the scope of this laboratory's accreditation. Interpretation of the data and information within this document is left to the company, consultant, and/or persons who conducted the fieldwork. A material is considered regulated asbestos containing material (ACM) where the asbestos content is determined to be one percent or greater. Several organizations, including the
American Conference of Government Industrial Hygienists (ACGIH); the American Industrial Hygiene Association (AIHA); the Indoor Air Quality Association (IAQA); the United States Environmental Protection Agency (USEPA);
the Centers for Disease Control (CDC) as well as the California Department of Health Services (CADHS) have published guidelines for assessment and interpretation of analytical data indicating a tested material is ACM.
None Detected 20% Min Wool,60%
Cellulose 20% Perlite (Tan) Ceiling Tile/96
None Detected 20% Min Wool,60%
Cellulose 20% Perlite (Tan) Ceiling Tile/96E
None Detected None Detected 100% Organic Matrix (Brown) Cove Base/N/A
None Detected None Detected 100% Organic Matrix (Yellow) Mastic/N/A
None Detected None Detected 100% Organic Matrix (Brown) Cove Base/N/A
None Detected None Detected 100% Organic Matrix (Yellow) Mastic/N/A
None Detected None Detected 100% Organic Matrix (Brown) Cove Base/N/A
None Detected None Detected 100% Organic Matrix (Yellow) Mastic/N/A
Methodology: EPA/600/R-93/116 Without Gravimetry SEEML Ref#: G-231206043
% Asbestos Type % Fibrous Non-
Asbestos Material Type % Non-Fibrous Material Description/Location
Analyzed by: Andrea Berrios Project Address: 300 W Veterans Blvd
City, State. ZIP: Big Springs, TX
Project Name: Big Spring Va Hospital
Project No: 51-3784
(281)814-2502/mak@seeml.com Date Reported: 12/11/2023
Date Revised:
100 Post OakRoad #240 Date Received: 12/06/2023
Houston,TX,77055 Date Analyzed: 12/11/2023
Southeast Environmental Microbiology Laboratories - Asbestos Division
102 Edinburgh Court Greenville, SC 29607
Phone: 864-233-3770, Fax: 864-233-6589 , www.seeml.com
NVLAP Lab ID:201031-0
PLM Asbestos Bulk Sample Summary
Lab No.:
Client No.:
187A
187B
188A
188B
189A
189B
190A
190B
191A
None Detected None Detected 100% Organic Matrix (Gray) Vinyl Floor Tile/98
Approved By: Andrea Berrios Disclaimer:
The results in this report only apply to the samples as received.
NOB samples are tested as a preliminary analysis. We highly recommend for Negative NOB samples resulting in less than 1% Asbestos to be verified by TEM or Point Analysis.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. NAD means no asbestos fibers were detected. When detected the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
Guidelines for Interpretation:
Any opinions/interpretations expressed in this report are outside the scope of this laboratory's accreditation. Interpretation of the data and information within this document is left to the company, consultant, and/or persons who conducted the fieldwork. A material is considered regulated asbestos containing material (ACM) where the asbestos content is determined to be one percent or greater. Several organizations, including the
American Conference of Government Industrial Hygienists (ACGIH); the American Industrial Hygiene Association (AIHA); the Indoor Air Quality Association (IAQA); the United States Environmental Protection Agency (USEPA);
the Centers for Disease Control (CDC) as well as the California Department of Health Services (CADHS) have published guidelines for assessment and interpretation of analytical data indicating a tested material is ACM.
None Detected None Detected 100% Organic Matrix (Gray) Vinyl Floor Tile/98
None Detected None Detected 100% Organic Matrix (Yellow) Mastic/98
None Detected None Detected 100% Organic Matrix (White) Vinyl Floor Tile/Restroom 96B
None Detected 5% Cellulose 95% Organic Matrix (Black) Mastic/Restroom 96B
None Detected None Detected 100% Organic Matrix (White) Vinyl Floor Tile/96
None Detected 5% Cellulose 95% Organic Matrix (Black) Mastic/96
None Detected None Detected 100% Organic Matrix (White) Vinyl Floor Tile/96A
None Detected 5% Cellulose 95% Organic Matrix (Black) Mastic/96A
Methodology: EPA/600/R-93/116 Without Gravimetry SEEML Ref#: G-231206043
% Asbestos Type % Fibrous Non-
Asbestos Material Type % Non-Fibrous Material Description/Location
Analyzed by: Andrea Berrios Project Address: 300 W Veterans Blvd
City, State. ZIP: Big Springs, TX
Project Name: Big Spring Va Hospital
Project No: 51-3784
(281)814-2502/mak@seeml.com Date Reported: 12/11/2023
Date Revised:
100 Post OakRoad #240 Date Received: 12/06/2023
Houston,TX,77055 Date Analyzed: 12/11/2023
Southeast Environmental Microbiology Laboratories - Asbestos Division
102 Edinburgh Court Greenville, SC 29607
Phone: 864-233-3770, Fax: 864-233-6589 , www.seeml.com
NVLAP Lab ID:201031-0
PLM Asbestos Bulk Sample Summary
Lab No.:
Client No.:
191B
192A
192B
193A
193B
194A
194B
195A
195B
25% Fiberglass,75% Min
Wool None Detected (Yellow) Insulation/96
Approved By: Andrea Berrios Disclaimer:
The results in this report only apply to the samples as received.
NOB samples are tested as a preliminary analysis. We highly recommend for Negative NOB samples resulting in less than 1% Asbestos to be verified by TEM or Point Analysis.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. NAD means no asbestos fibers were detected. When detected the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
Guidelines for Interpretation:
Any opinions/interpretations expressed in this report are outside the scope of this laboratory's accreditation. Interpretation of the data and information within this document is left to the company, consultant, and/or persons who conducted the fieldwork. A material is considered regulated asbestos containing material (ACM) where the asbestos content is determined to be one percent or greater. Several organizations, including the
American Conference of Government Industrial Hygienists (ACGIH); the American Industrial Hygiene Association (AIHA); the Indoor Air Quality Association (IAQA); the United States Environmental Protection Agency (USEPA);
the Centers for Disease Control (CDC) as well as the California Department of Health Services (CADHS) have published guidelines for assessment and interpretation of analytical data indicating a tested material is ACM.
None Detected 25% Fiberglass,75% Min
Wool None Detected (Yellow) Insulation/96
None Detected 15% Cellulose 85% Organic Matrix (White) TSI/96
None Detected 25% Fiberglass,75% Min
Wool None Detected (Yellow) Insulation/96
None Detected 15% Cellulose 85% Organic Matrix (White) TSI/96
None Detected None Detected 100% Organic Matrix (Yellow) Mastic/98
None Detected 25% Cellulose 75% Organic Matrix (White) TSI/96
None Detected None Detected 100% Organic Matrix (Yellow) Mastic/98
None Detected None Detected 100% Organic Matrix (Gray) Vinyl Floor Tile/98
Methodology: EPA/600/R-93/116 Without Gravimetry SEEML Ref#: G-231206043
% Asbestos Type % Fibrous Non-
Asbestos Material Type % Non-Fibrous Material Description/Location
Analyzed by: Andrea Berrios Project Address: 300 W Veterans Blvd
City, State. ZIP: Big Springs, TX
Project Name: Big Spring Va Hospital
Project No: 51-3784
(281)814-2502/mak@seeml.com Date Reported: 12/11/2023
Date Revised:
100 Post OakRoad #240 Date Received: 12/06/2023
Houston,TX,77055 Date Analyzed: 12/11/2023
Southeast Environmental Microbiology Laboratories - Asbestos Division
102 Edinburgh Court Greenville, SC 29607
Phone: 864-233-3770, Fax: 864-233-6589 , www.seeml.com
NVLAP Lab ID:201031-0
PLM Asbestos Bulk Sample Summary
Lab No.:
Client No.:
196A
196B
197A
197B
198A
198B
199A
200A
201A
None Detected 2% Synthetic 98% Organic Matrix (Tan) Mastic/95
Approved By: Andrea Berrios Disclaimer:
The results in this report only apply to the samples as received.
NOB samples are tested as a preliminary analysis. We highly recommend for Negative NOB samples resulting in less than 1% Asbestos to be verified by TEM or Point Analysis.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. NAD means no asbestos fibers were detected. When detected the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
Guidelines for Interpretation:
Any opinions/interpretations expressed in this report are outside the scope of this laboratory's accreditation. Interpretation of the data and information within this document is left to the company, consultant, and/or persons who conducted the fieldwork. A material is considered regulated asbestos containing material (ACM) where the asbestos content is determined to be one percent or greater. Several organizations, including the
American Conference of Government Industrial Hygienists (ACGIH); the American Industrial Hygiene Association (AIHA); the Indoor Air Quality Association (IAQA); the United States Environmental Protection Agency (USEPA);
the Centers for Disease Control (CDC) as well as the California Department of Health Services (CADHS) have published guidelines for assessment and interpretation of analytical data indicating a tested material is ACM.
None Detected 3% Synthetic 97% Organic Matrix (Tan) Mastic/95
None Detected 3% Synthetic 97% Organic Matrix (Tan) Mastic/95
None Detected None Detected 100% Carbon/Quartz (Brown) Ceramic Tile/96B
None Detected None Detected 100% Organic Matrix (Yellow) Mastic/96B
None Detected None Detected 100% Carbon/Quartz (Brown) Ceramic Tile/96C
None Detected None Detected 100% Organic Matrix (Yellow) Mastic/96C
None Detected None Detected 100% Carbon/Quartz (Brown) Ceramic Tile/96B
None Detected None Detected 100% Organic Matrix (Yellow) Mastic/96B
Methodology: EPA/600/R-93/116 Without Gravimetry SEEML Ref#: G-231206043
% Asbestos Type % Fibrous Non-
Asbestos Material Type % Non-Fibrous Material Description/Location
Analyzed by: Andrea Berrios Project Address: 300 W Veterans Blvd
City, State. ZIP: Big Springs, TX
Project Name: Big Spring Va Hospital
Project No: 51-3784
(281)814-2502/mak@seeml.com Date Reported: 12/11/2023
Date Revised:
100 Post OakRoad #240 Date Received: 12/06/2023
Houston,TX,77055 Date Analyzed: 12/11/2023
Southeast Environmental Microbiology Laboratories - Asbestos Division
102 Edinburgh Court Greenville, SC 29607
Phone: 864-233-3770, Fax: 864-233-6589 , www.seeml.com
NVLAP Lab ID:201031-0
PLM Asbestos Bulk Sample Summary
Appendix IV: Certifications/ Licenses
| Title Page |
| Cover Letter |
| Executive Summary |
| 1.0 Site Description |
| 2.0 Purpose |
| 3.0 Methodology |
| 3.1 Asbestos-Containing Materials |
| 3.2 Lead in Paint and Surface Coatings |
| 4.0 Results |
| 4.1 Asbestos Sampling |
| 4.2 Suspect or Assumed Asbestos-Containing Materials |
| 4.3 Lead in Paint and Surface Coatings |
| 5.0 Recommendations and Regulatory Requirements |
| 5.1 Asbestos-Containing Materials |
| 5.2 Lead in Paint and Surface Coatings |
| 6.0 Limitations |
| Site Photographs |
| XRF Lead-Based Paint Readings |
| Laboratory Report(s) |
| Certifications/Licenses |
File details come from the government source that posted it. Updated .