This document is a technical specification section (Section 10 73 16) for prefabricated aluminum canopies to be installed at the VA Medical Center in Providence, Rhode Island as part of an MRI space expansion and renovation project. The specification details requirements for a Mapes Cantilever Super Lumideck, Flat Soffit (PERP) Canopy system, including material specifications, fabrication standards, and installation guidelines.

Key technical requirements include using aluminum framing with ASTM standards, extruded aluminum decking with 3-inch by 6-inch flat profile, 8-inch J-style aluminum fascia, and a rear gutter with downspout. The canopy must have a high-performance organic finish complying with AAMA 2605 standards, with a custom color to match aluminum composite wall panels. Installation specifications mandate precise welding techniques, corrosion protection, and coordination with other construction elements. The project includes a five-year warranty for the canopy components and a ten-year warranty for the finish, with specific performance requirements for structural integrity and thermal movement.

View the file

Other files

File Type Posted
36C77625R0047 0004.pdf PDF
36C77625R0047_r2.pdf PDF
E2-02.1-001 SECTION Reg Roll in 5113 Pkt Tile Support 1.pdf PDF
261116 - Secondary Unit Substations 1.pdf PDF
E2-01.1-003 SECTION Regular Roll with Fascia Wall Moun 1.pdf PDF
19026-VA Medical Center Geotech Rpt 1.pdf PDF
Magnetom Sola Tech Specs 1.pdf PDF
19.0158 - RGB - VAMC - MRI 3-24-23-SKC-1 1.pdf PDF
36C77625R0047_r1.pdf PDF
00 Rescue SR frame 1.pdf PDF
Sola 1.PDF PDF
Vida XT Typical Final Drawings 1.PDF PDF
Sola XQ Typical Final Drawings 1.PDF PDF
36C77625R0047 0003.pdf PDF
Technical Questions and Answers - Volume 1.docx DOCX document
E1-01.1-00220Regular20with20Wall 20 Mount.pdf PDF
190316.01 - VAMC Providence - MRI Expan-Add - 04.03.2023 1.pdf PDF
Technical Questions and Answers - Volume 2.docx DOCX document
Vida 1.PDF PDF
MagnetomVida Tech Specs 1.pdf PDF
S06 - 36C77625R0047 0002.pdf PDF
S06 - Attachment 01 - Site Visit Sign in Sheet - Original.pdf PDF
S06 - Attachment 02 - Site Visit Sign in Sheet - VA Reproduced.pdf PDF
S06 - Attachment 01 - Providence Campus Map.pdf PDF
S06 - 36C77625R0047 0001.pdf PDF
100 VAMC MRI - Full Set IFC 1 of 5.pdf PDF
100 VAMC MRI - Full Set IFC 2 of 5.pdf PDF
Limitations on Subcontracting - Construction.docx DOCX document
Specifications.pdf PDF
100 VAMC MRI - Full Set IFC 3 of 5.pdf PDF
100 VAMC MRI - Full Set IFC 5 of 5.pdf PDF
19026-VA Medical Center Geotech Rpt.pdf PDF
S02 - Solicitation - 36C77625R0047.pdf PDF
100 VAMC MRI - Full Set IFC 4 of 5.pdf PDF
Wage Rates - Providence County.pdf PDF
650-345 Expand and Renovate MRI SOW Synopsis-FINAL.doc DOC document
Contractor Safety - Environmental Form.docx DOCX document
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

JULY 18, 2025 - ADDENDUM ## VAMC PROVIDENCE

VA Project No. 650-345 EXPAND AND RENOVATE SPACE FOR NEW MRI

PROVIDENCE, RI

10 73 16 - 1

SECTION 107316

CANOPIES

PART 1 - GENERAL

1.1 DESCRIPTION OF WORK

A. Section Includes: Provide labor, materials and equipment necessary to complete the work of this Section, including but not limited to the following:

1. Prefabricated aluminum canopy system.

1.2 RELATED WORK

A. Section 07 60 00, FLASHING AND SHEET METAL: for counterflashing at exterior wall assembly.

B. Division 26, ELECTRICAL: for electrical heat trace within downspouts.

1.3 APPLICABLE PUBLICATIONS

A. Comply with references to extent specified in this Section.

B. ASTM International (ASTM):

A 53/A 53M-22 .........Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless

B 209/B 209M-21a ......Aluminum and Aluminum-Alloy Sheet and Plate

B 210/B 210M-19a ......Aluminum and Aluminum-Alloy Drawn Seamless

Tubes

B 221-21 ..............Aluminum and Aluminum-Alloy Extruded Bards, Rods, Wire, Profiles, and Tubes

B 429/B 429M-20 .......Aluminum-Alloy Extruded Structural Pipe and

Tube

D 1187/D 1187M-97(2024) Asphalt-Base Emulsions for Use as Protective

Coatings for Metal

C. American Architecture Manufacturers Association (AAMA):

2605-22 ...............Superior Performing Organic Coatings on

Aluminum Extrusions and Panels

D. American Welding Society (AWS):

AWS D1.2/D1.2M ........Structural Welding Code - Aluminum

E. National Association of Architectural Metal Manufacturers (NAAMM)

AMP 500-06 ............Metal Finishes Manual for Architectural and

Metal Products

1.4 SUBMITTALS

A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT

DATA, AND SAMPLES

10 73 16 - 2

B. Product Data: For each type of product.

1. Include styles, material descriptions, construction details, fabrication details, dimensions of individual components and profiles, hardware, fittings, mounting accessories, features, and finishes for canopies.

2. Include rated capacities, and furnished specialties and accessories.

C. Shop Drawings:

1. Include plans, elevations, sections, mounting heights, and attachment details.

2. Show locations for blocking, reinforcement, and supplementary structural support.

D. Delegated-Design Submittal: For aluminum canopy system indicated to comply with performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.

E. Samples for Verification: For each type of exposed finish in manufacturer's standard sizes.

F. Operation and Maintenance Data: For canopies to include in operation and maintenance manuals.

1.5 QUALITY ASSURANCE

A. Engineering Responsibility: Preparation of Shop Drawings, design calculations, and other structural data by a qualified professional engineer.

B. Professional Engineer Qualifications: A professional structural engineer who is legally qualified to practice in the State of Rhode

Island, and who is experienced in providing engineering services of the kind indicated. Engineering services are defined as those performed for installations of aluminum canopy systems that are similar to those indicated for this Project in material, design, and extent.

C. Fabricator Qualifications: Shop that employs skilled workers who custom-fabricate products similar to those required for this Project and whose products have a record of successful in-service performance.

1. Fabricator's responsibilities include fabricating and installing canopies and providing professional engineering services needed to assume engineering responsibility.

10 73 16 - 3

D. Installer Qualifications: Minimum three years' experience in erecting canopies of the type specified.

E. Welding Qualifications: Qualify procedures and personnel according to the following:

1. AWS D1.2/D1.2M, "Structural Welding Code - Aluminum."

1.6 FIELD CONDITIONS

A. Weather Limitations: Proceed with installation only when existing and forecasted weather conditions permit installation of canopies in exterior locations to be performed according to manufacturers' written instructions and warranty requirements.

B. Field Measurements: Where canopy installation is indicated to fit to other work, verify dimensions of other work by field measurements before fabrication and indicate measurements on Shop Drawings. Allow clearances for fenestration operation throughout the entire operating range. Notify Architect of discrepancies. Coordinate fabrication schedule with construction progress to avoid delaying the Work.

1.7 WARRANTY

A. Construction Warranty: Comply with FAR clause 52.246-21, “Warranty of

Construction”.

B. Special Warranty: Manufacturer and fabricator agree to repair or replace components of canopies that fail in materials or workmanship within specified warranty period.

1. Failures include, but are not limited to, the following:

a. Structural failures including framework.

b. Deterioration of metals, metal finishes, and other materials beyond normal weathering.

2. Canopy Warranty Period: Five years from date of Substantial

Completion.

C. Special Finish Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components on which finishes fail within specified warranty period. Warranty does not include normal weathering.

1. Warranty Period: Ten years from date of Substantial Completion.

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Delegated Design: Design aluminum canopy systems, including comprehensive engineering analysis by a qualified professional

10 73 16 - 4 engineer, using performance requirements and design criteria indicated.

B. Structural Performance: Canopies shall withstand the following loads and stresses within limits and under conditions indicated according to

ASCE/SEI 7:

1. Design Loads: As indicated on Structural Drawings.

C. Thermal Movements: Allow for thermal movements from ambient and surface temperature changes.

1. Temperature Change: 120 deg F, ambient; 180 deg F, material surfaces.

2.2 MANUFACTURERS

A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

1. Austin Mohawk & Co., Inc.

2. Mapes Industries, Inc.

3. Panel Built and Company, Inc.

4. Perfection Architectural Systems, Inc.

B. Basis-of-Design Product:

1. Mapes; Super Lumideck, Flat Soffit Hanger Rod Canopy.

2.3 CANOPY FRAMING

A. Aluminum Framing: Alloy and temper recommended by canopy manufacturer for type of use and finish indicated and with not less than the strength and durability properties of alloy and temper required by structural loads.

1. Aluminum Plate and Sheet: ASTM B 209.

2. Aluminum Extrusions: ASTM B 221.

3. Extruded Structural Pipe and Round Tubing: ASTM B 429/B 429M, standard weight (Schedule 40) unless another weight is indicated or required by structural loads.

4. Drawn Seamless Tubing: ASTM B 210.

5. Aluminum Finish: Manufacturer's standard decorative paint finish complying with finish manufacturer's written instructions for surface preparation including pretreatment, application, baking, and minimum dry film thickness.

Cantilever Super Lumideck, Flat Soffit (PERP) Canopy.

10 73 16 - 5

B. Hanger Rods: Galvanized steel pipe, size as required for compliance with performance requirements. Provide with eye bolt, clevis, and steel threaded rod for adjustment

C. Anchors, Fasteners, Fittings, Hardware, and Installation Accessories:

Complying with performance requirements indicated and suitable for exposure conditions, supporting structure, anchoring substrates, and installation methods indicated. Corrosion-resistant or noncorrodible units; weather-resistant, compatible, nonstaining materials. Provide as required for canopy assembly, mounting, and secure attachment.

Number as needed to comply with performance requirements and to maintain uniform appearance; evenly spaced. Where exposed to view, provide finish and color as selected by Architect from manufacturer's full range.

D. Bituminous Paint: Cold-applied asphalt emulsion complying with

ASTM D 1187.

2.4 CANOPY DECK

A. Decking: Manufacturer's standard extruded aluminum decking, self-flashing, interlocking sections.

1. Profile: 3-inch by 6-inch wide, flat.

2. Thickness: As required by design, but not less than 0.078-inch.

B. Fascia: Manufacturer's standard J-style extruded aluminum fascia sections

1. Depth: 8-inch.

2. Thickness: As required by design, but not less than 0.125-inch

C. Drainage: Manufacturer's standard J-style extruded aluminum rear gutter with 2-inch drain hole, downspout stub, roll formed aluminum downspout.

2.5 CANOPY FABRICATION

A. Framing: Preassemble canopy framing in the shop to greatest extent possible. Disassemble units only as necessary for shipping and handling limitations. Use connections that maintain structural value of joined pieces. Clearly mark units for reassembly and coordinated installation.

1. Form bent-metal corners to smallest radius possible without causing grain separation or otherwise impairing work.

2. Form exposed work true to line and level with accurate angles and surfaces and straight edges.

10 73 16 - 6

3. Form exposed connections with hairline joints, flush and smooth, using concealed fasteners where possible. Fabricate slip-fit connections that will be exposed to weather in a manner to exclude water. Provide weep holes where water may accumulate.

4. Weld corners and connections continuously. Obtain fusion without undercut or overlap. Remove welding flux immediately. At exposed corners and connections, finish exposed welds and surfaces smooth and blended so no roughness shows after finishing and contour of welded surface matches that of adjacent surface.

5. Provide for anchorage of type indicated; coordinate with supporting structure. Space anchoring devices to secure metal fabrications in place and to properly transfer loads.

2.6 ALUMINUM FINISHES

A. General: Comply with NAAMM's "Metal Finishes Manual for Architectural and Metal Products" for recommendations for applying and designating finishes.

B. Finish designations prefixed by AA comply with the system established by the Aluminum Association for designating aluminum finishes.

C. High-Performance Organic Finish (2-Coat Fluoropolymer): AA-C12C40R1x

(Chemical Finish: cleaned with inhibited chemicals; Chemical Finish:

conversion coating; Organic Coating: manufacturer's standard 2-coat, thermocured system consisting of specially formulated inhibitive primer and fluoropolymer color coat, with color coat containing not less than 70 percent polyvinylidene fluoride resin by weight).

Prepare, pretreat, and apply coating to exposed metal surfaces to comply with AAMA 2605 and with coating and resin manufacturers' written instructions.

1. Color and Gloss: Custom color to match aluminum composite material wall panels.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates, areas, and conditions, with Installer present, for compliance with requirements for supporting members, blocking, inserts, installation tolerances, lighting, and other conditions affecting performance of the Work.

B. Proceed with installation only after unsatisfactory conditions have been corrected.

10 73 16 - 7

3.2 INSTALLATION

A. General: Install canopies at locations and in position indicated, securely connected to supports, free of rack, and in proper relation to adjacent construction. Use mounting methods of types described and in compliance with Shop Drawings and fabricator's written instructions.

B. Install canopies after other finishing operations, including joint sealing and painting, have been completed.

C. Weld frame connections that are not to be left as exposed joints but cannot be shop welded because of shipping size limitations.

1. Field Welding: Comply with the following requirements:

a. Use materials and methods that minimize distortion and develop strength and corrosion resistance of base metals.

b. Obtain fusion without undercut or overlap.

c. Remove welding flux immediately.

d. At exposed connections, finish exposed welds and surfaces smooth and blended so no roughness shows after finishing and contour of welded surface matches that of adjacent surface.

D. Anchoring to In-Place Construction: Use anchors, fasteners, fittings, hardware, and installation accessories where necessary for securing canopies to structural support and for properly transferring load to in-place construction.

E. Corrosion Protection: Coat concealed surfaces of aluminum that come in contact with grout, concrete, masonry, wood, or dissimilar metals with a heavy coat of bituminous paint.

F. Coordinate canopy installation with flashing and joint-sealant installation so these materials are installed in sequence and in a manner that prevents exterior moisture from passing through completed exterior wall and roof assemblies.

3.3 CLEANING AND PROTECTION

A. Touchup Painting: Immediately after erection, clean field welds, connections, and abraded areas. Paint uncoated and abraded areas with same or compatible material as used for shop-applied finish painting.

1. Apply by brush or spray to provide a minimum 2.0-mil dry film thickness.

B. Protect finished aluminum surfaces from damage due to subsequent construction operations.

10 73 16 - 8

END OF SECTION