This document provides details for a federal construction Multiple Award Task Order Contract (MATOC) opportunity. The Department of Veterans Affairs Veterans Integrated Services Network 23 intends to award indefinite-delivery, indefinite-quantity contracts valued up to $70 million total to a minimum of eight Service-Disabled Veteran Owned Small Businesses. The contracts will be for maintenance, repair, alteration, and new construction services for facilities in Minneapolis and St. Cloud, Minnesota. Task orders will range from $2,000 to $10 million. The period of performance is five years from award. Interested parties must register in the System for Award Management and ORCA databases. A pre-solicitation notice, solicitation, and subsequent amendments will be posted at FBO.gov. The pre-bid site visit date will be announced with the solicitation.

36C26318R0688 ATTACHMENT 11f--Drawings Original Revised 656-16-277 Relocate Rehab Functions (6 pages).pdf

View the file

Other files

File Type Posted
36C26319D0094-000.docx DOCX document
36C26319D0093-000.docx DOCX document
36C26319D0092-000.docx DOCX document
36C26319D0091-000.docx DOCX document
36C26319D0090-000.docx DOCX document
36C26319D0089-002.docx DOCX document
36C26319D0088-001.docx DOCX document
36C26318R0688-0003000.docx DOCX document
36C26318R0688-0002002.pdf PDF
36C26318R0688-0002000.docx DOCX document
36C26318R0688-0002003.pdf PDF
36C26318R0688-0002001.pdf PDF
36C26318R0688-0001000.docx DOCX document
36C26318R0688-0001003.pdf PDF
36C26318R0688-0001005.pdf PDF
36C26318R0688-0001004.pdf PDF
36C26318R0688-0001001.pdf PDF
36C26318R0688-0001002.pdf PDF
36C26318R0688-0001006.pdf PDF
36C26318R0688-0001007.pdf PDF
36C26318R0688-072.docx DOCX document
36C26318R0688-090.pdf PDF
36C26318R0688-088.pdf PDF
36C26318R0688-071.docx DOCX document
36C26318R0688-078.pdf PDF
36C26318R0688-077.pdf PDF
36C26318R0688-076.pdf PDF
36C26318R0688-075.pdf PDF
36C26318R0688-064.docx DOCX document
36C26318R0688-066.docx DOCX document
36C26318R0688-069.docx DOCX document
36C26318R0688-086.pdf PDF
36C26318R0688-087.pdf PDF
36C26318R0688-082.pdf PDF
36C26318R0688-084.pdf PDF
36C26318R0688-068.docx DOCX document
36C26318R0688-067.docx DOCX document
36C26318R0688-081.pdf PDF
36C26318R0688-079.pdf PDF
36C26318R0688-070.docx DOCX document
36C26318R0688-085.pdf PDF
36C26318R0688-073.xls XLS spreadsheet
36C26318R0688-074.pdf PDF
36C26318R0688-065.docx DOCX document
36C26318R0688-089.pdf PDF
36C26318R0688-080.pdf PDF
36C26318R0688.docx DOCX document
Show all 47

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RELOCATE REHAB

SERVICES 656-16-277

12/03/2018

AREA OF

WORK

N.I.C.

N.I.C.

N.I.C.

RELOCATE REHAB

AREA OF WORK

N.I.C.

N.I.C.

N.I.C.

RELOCATE REHAB

RELOCATE REHAB

PANELBOARD SCHEDULE PANEL: XX-EQ1-1

LOCATION: ELECTRICAL 113 MAIN: 100A MCB

VOLTAGE: 120/208V PH: 3 WIRE: 4 MOUNTING: SURFACE SOURCE: MAIN SWITCHBOARD

CKT. DESCRIPTION EQP. MTR. REC. LTG. C.B. KW / PHASE C.B. LTG. REC. MTR. EQP. DESCRIPTION CKT.

NO. KW KW KW KW A/P - A - - B - - C - A/P KW KW KW KW NO.

1 SPARE 20/1 0.5 20/1 0.5 DOMESTIC WATER HEATER 2

3 SPARE 20/1 0 20/1 METER POWER 4

5 SPARE 20/1 0.5 20/1 0.5 BAS CONTROL 6

7 SPARE 20/1 0.5 20/1 0.5 BAS CONTROL 8

9 SPACE 0 SPACE 10

11 SPACE 0 SPACE 12

13 SPACE 0 SPACE 14

15 SPACE 0 SPACE 16

17 SPACE 0 SPACE 18

19 SPACE 0 SPACE 20

21 SPACE 0 SPACE 22

23 SPACE 0 SPACE 24

25 SPACE 0 SPACE 26

27 SPACE 0 SPACE 28

29 SPACE 0 SPACE 30

31 SPACE 0 SPACE 32

33 SPACE 0 SPACE 34

35 SPACE 0 SPACE 36

37 SPACE 0 SPACE 38

39 SPACE 0 SPACE 40

41 SPACE 0 SPACE 42

CONNECTED KW 0 0 0 0 1 0 0.5 0 0 0 1.5

DEMAND 0.8 0.8 0.7 1.25 1.25 0.7 0.8 0.8

DEMAND KW 0 0 0 0 0 0 0 1.2

TOTAL KW WITH DEMAND 1.2

TOTAL 3 PHASE AMPS 3.33

NOTES:

PANELBOARD SCHEDULE PANEL: ZZ-ES1-1

LOCATION: GENERATOR BUILDING 180 MAIN: 150A MCB

VOLTAGE: 120/208V PH: 3 WIRE: 4 MOUNTING: SURFACE SOURCE: LS SECTION

CKT. DESCRIPTION EQP. MTR. REC. LTG. C.B. KW / PHASE C.B. LTG. REC. MTR. EQP. DESCRIPTION CKT.

NO. KW KW KW KW A/P - A - - B - - C - A/P KW KW KW KW NO.

1 GENERATOR SPACE HEATER 1 15/2 1.7 20/1 0.7 LIGHTS 2

3 1 - 1.4 20/1 0.4 RECEPTACLES 4

5 GEN. WATER JACKET HTR 5.2 60/2 5.7 20/1 0.5 OMNTEC MONITOT 6

7 5.2 - 5.7 20/1 0.5 ASCO ANNUNCIATOR 8

9 GEN. BATTERY CHARGER 0.5 20/1 1 20/1 0.5 ELECTRIC METER 10

11 TRAMONT FUEL DAY TANK 0.5 20/1 0.5 20/1 SPARE 12

13 FUEL MONITOR 0.2 15/1 0.2 SPACE 14

15 DAY TANK PUMPS 1 15/2 1 SPACE 16

17 1 - 1 SPACE 18

19 ELECTRIC UNIT HEATER 1.6 20/3 1.6 SPACE 20

21 1.6 - 1.6 SPACE 22

23 1.6 - 1.6 SPACE 24

25 ELECTRIC UNIT HEATER 1.6 20/3 1.6 SPACE 26

27 1.6 - 1.6 SPACE 28

29 1.6 - 1.6 SPACE 30

31 LOUVER MOTORS 0.8 20/1 0.8 SPACE 32

33 LOUVER MOTORS 0.8 20/1 0.8 SPACE 34

35 SPACE 0 SPACE 36

37 SPACE 0 SPACE 38

39 SPACE 0 SPACE 40

41 SPACE 0 SPACE 42

CONNECTED KW 23.2 3.6 0 0 11.6 7.4 10.4 0.7 0.4 0 1.5

DEMAND 0.8 0.8 0.7 1.25 1.25 0.7 0.8 0.8

DEMAND KW 18.56 2.88 0 0 0.875 0.28 0 1.2

TOTAL KW WITH DEMAND 23.8

TOTAL 3 PHASE AMPS 66.1

NOTES:

PANELBOARD SCHEDULE PANEL: XX-ES1-1

LOCATION: HALLWAY 116 MAIN: 50A MLO

VOLTAGE: 208/120 PH: 3 WIRE: 4 MOUNTING: RECESSED SOURCE: LS SECTION

CKT. DESCRIPTION EQP. MTR. REC. LTG. C.B. KW / PHASE C.B. LTG. REC. MTR. EQP. DESCRIPTION CKT.

NO. KW KW KW KW A/P - A - - B - - C - A/P KW KW KW KW NO.

1 EGRESS LIGHTS 0.8 20/1 1.3 20/1 0.5 FA SMOKE DAMPERS 2

3 EGRESS LIGHTS 1.0 20/1 1 20/1 SPARE 4

5 EGRESS LIGHTS 1.3 20/1 1.3 20/1 SPARE 6

7 EGRESS LIGHTS 0.9 20/1 0.9 20/1 SPARE 8

9 EGRESS LIGHTS 1.1 20/1 1.1 20/1 SPARE 10

11 SPARE 20/1 0 20/1 SPARE 12

13 SPACE 0 SPACE 14

15 SPACE 0 SPACE 16

17 SPACE 0 SPACE 18

19 SPACE 0 SPACE 20

21 SPACE 0 SPACE 22

23 SPACE 0 SPACE 24

25 SPACE 0 SPACE 26

27 SPACE 0 SPACE 28

29 SPACE 0 SPACE 30

31 SPACE 0 SPACE 32

33 SPACE 0 SPACE 34

35 SPACE 0 SPACE 36

37 SPACE 0 SPACE 38

39 SPACE 0 SPACE 40

41 SPACE 0 SPACE 42

CONNECTED KW 0 0 0 5.1 2.2 2.1 1.3 0 0 0.5 0

DEMAND 0.8 0.8 0.7 1.25 1.25 0.7 0.8 0.8

DEMAND KW 0 0 0 6.375 0 0 0.4 0

TOTAL KW WITH DEMAND 6.78

TOTAL 3 PHASE AMPS 18.8

NOTES:

PANELBOARD SCHEDULE PANEL: XX-EC1-1

LOCATION: ELECTRICAL 113 MAIN: 250 MLO

VOLTAGE: 480/277 PH: 3 WIRE: 4 MOUNTING: SURFACE SOURCE: MAIN SWITCHBOARD

CKT. DESCRIPTION EQP. MTR. REC. LTG. C.B. KW / PHASE C.B. LTG. REC. MTR. EQP. DESCRIPTION CKT.

NO. KW KW KW KW A/P - A - - B - - C - A/P KW KW KW KW NO.

1 SPACE 0 SPACE 2

3 SPACE 0 SPACE 4

5 SPACE 0 SPACE 6

7 SPACE 0 SPACE 8

9 SPACE 0 SPACE 10

11 SPACE 0 SPACE 12

13 SPACE 0 SPACE 14

15 SPACE 0 SPACE 16

17 SPACE 0 SPACE 18

19 SPACE 0 SPACE 20

21 SPACE 0 SPACE 22

23 SPACE 0 SPACE 24

25 SPACE 0 SPACE 26

27 SPACE 0 SPACE 28

29 SPACE 0 SPACE 30

31 SPACE 0 SPACE 32

33 SPACE 0 SPACE 34

35 SPACE 0 SPACE 36

37 SPACE 6.8 100/3 1.2 3.2 1.2 1.2 PANEL XX-EC1-2 38

39 SPACE 8 - 0.7 3.8 1.4 2.1 - 40

41 SPACE 6.4 - 0.7 3.2 1.2 1.3 - 42

CONNECTED KW 0 0 0 0 6.8 8 6.4 2.6 10.2 3.8 4.6

DEMAND 0.8 0.8 0.7 1.25 1.25 0.7 0.8 0.8

DEMAND KW 0 0 0 0 3.25 7.14 3.04 3.68

TOTAL KW WITH DEMAND 17.1

TOTAL 3 PHASE AMPS 20.6

NOTES:

PANELBOARD SCHEDULE PANEL: XX-EC1-2

LOCATION: HALLWAY 116 MAIN: 100A MLO

VOLTAGE: 208/120 PH: 3 WIRE: 4 MOUNTING: RECESSED SOURCE: XX-EC1-1

CKT. DESCRIPTION EQP. MTR. REC. LTG. C.B. KW / PHASE C.B. LTG. REC. MTR. EQP. DESCRIPTION CKT.

NO. KW KW KW KW A/P - A - - B - - C - A/P KW KW KW KW NO.

1 DOOR OPERATOR 0.8 20/1 1.2 20/3 0.4 RECEPTACLE 2

3 DOOR OPERATOR 0.8 20/1 1.2 - 0.4 RECEPTACLE 4

5 DOOR OPERATOR/AIR CURTAIN 0.8 30/1 1.2 - 0.4 RECEPTACLE 6

7 DOOR OPERATOR 0.8 20/1 1.2 20/3 0.4 RECEPTACLE 8

9 DOOR OPERATOR/AIR CURTAIN 0.8 30/1 1.6 - 0.8 REFRIG RECEPTACLE 10

11 DOOR OPERATOR 0.8 20/1 1.4 - 0.6 RECEPTACLE 12

13 DOOR OPERATOR 0.8 20/1 1.6 20/3 0.8 RECEPTACLE 14

15 RECEPTACLE 0.6 20/3 1.4 - 0.8 RECEPTACLE 16

17 RECEPTACLE 0.4 - 1.2 - 0.8 RECEPTACLE 18

19 RECEPTACLE 0.4 - 0.8 20/3 0.4 RECEPTACLE 20

21 REFRIG RECEPT 0.8 20/1 1.2 - 0.4 RECEPTACLE 22

23 RECEPTACLE 0.8 20/1 1.6 - 0.8 RECEPTACLE 24

25 LIGHTS 1.2 20/1 2 20/3 0.8 RECEPTACLE 26

27 LIGHTS 0.7 20/1 1.5 - 0.8 RECEPTACLE 28

29 LIGHTS 0.7 20/1 1.5 - 0.8 RECEPTACLE 30

31 BAS CONTROLLER 0.5 20/1 0.9 20/3 0.4 RECEPTACLE 32

33 DOOR OPERATOR 0.8 20/1 1.2 - 0.4 RECEPTACLE 34

35 DOOR OPERATOR 0.8 20/1 1.2 - 0.4 RECEPTACLE 36

37 POWER SUPPLY 0.2 20/1 0.6 20/3 0.4 RECEPTACLE 38

39 NURSE CALL MASTER 1.0 20/1 1.4 - 0.4 RECEPTACLE 40

41 SPARE 20/1 0.4 - 0.4 RECEPTACLE 42

43 SPARE 20/1 0.4 20/1 0.4 RECEPTACLE 44

45 SPARE 20/1 0.8 20/1 0.8 NURSE CALL 46

47 SPARE 20/1 0.5 20/1 0.5 ANNUNCATOR 48

49 SPACE 0.5 0.5 TEMPERATURE CONTROL 50

51 SPACE 0.5 0.5 STEAM METER 52

53 SPACE SPACE 54

CONNECTED KW 2.3 8.6 1 2.6 9 11 9 0 11.4 0 3.1

DEMAND 0.8 0.8 0.7 1.25 1.25 0.7 0.8 0.8

DEMAND KW 1.84 6.88 0.7 3.25 0 7.98 0 2.48

TOTAL KW WITH DEMAND 23.1

TOTAL 3 PHASE AMPS 64.3

NOTES:

PANELBOARD SCHEDULE PANEL: XX-1-1

LOCATION: HALLWAY 116 MAIN: 100A MLO

VOLTAGE: 208/120 PH: 3 WIRE: 4 MOUNTING: RECESSED SOURCE: XX-1-4

CKT. DESCRIPTION EQP. MTR. REC. LTG. C.B. KW / PHASE C.B. LTG. REC. MTR. EQP. DESCRIPTION CKT.

NO. KW KW KW KW A/P - A - - B - - C - A/P KW KW KW KW NO.

1 UNIT HEATERS 0.4 15/1 1 20/3 0.6 RECEPTACLE 2

3 PROP FAN 20/1 0.4 - 0.4 RECEPTACLE 4

5 SPARE 20/1 0.8 - 0.8 RECEPTACLE 6

7 BASEMENT RECEPTACLE 0.4 20/1 0.8 20/3 0.4 RECEPTACLE 8

9 BASEMENT RECEPTACLE 0.6 20/3 1.6 - 1.0 RECEPTACLE 10

11 BASEMENT RECEPTACLE 0.6 - 1.4 - 0.8 RECEPTACLE 12

13 BASEMENT RECEPTACLE 0.6 - 1.6 20/3 1.0 RECEPTACLE 14

15 CUH # 4 0.4 20/3 1.2 - 0.8 RECEPTACLE 16

17 RECEPTACLE 0.8 - 1.6 - 0.8 RECEPTACLE 18

19 RECEPTACLE 0.6 - 1.4 20/3 0.8 RECEPTACLE 20

21 RECEPTACLE 0.4 20/3 1 - 0.6 RECEPTACLE 22

23 RECEPTACLE 0.6 - 1.2 - 0.6 RECEPTACLE 24

25 RECEPTACLE 0.6 - 1 20/3 0.4 RECEPTACLE 26

27 RECEPTACLE 0.6 20/3 1.2 - 0.6 RECEPTACLE 28

29 RECEPTACLE 0.6 - 1.6 - 1.0 RECEPTACLE 30

31 RECEPTACLE 0.4 - 1.4 20/3 1.0 RECEPTACLE 32

33 RECEPTACLE 0.6 20/3 1.2 - 0.6 RECEPTACLE 34

35 SPARE - 0.8 - 0.8 RECEPTACLE 36

37 CUH # 1 0.5 - 1.3 20/3 0.8 RECEPTACLE 38

39 PRV # 1 0.5 20/1 1.1 - 0.6 RECEPTACLE 40

41 DRINKING FOUNTAIN 0.5 20/1 0.9 - 0.4 RECEPTACLE 42

43 SPARE 20/1 0.8 20/1 0.8 ROOFTOP RECEPTACLES 44

45 SPARE 20/1 0 SPACE 46

47 SPARE 20/1 0 SPACE 48

49 SPACE 0 SPACE 50

51 SPACE 0 SPACE 52

53 SPACE 0 SPACE 54

CONNECTED KW 0.5 1.8 7.4 0 9 8 8 0 15.6 0 0

DEMAND 0.8 0.8 0.7 1.25 1.25 0.7 0.8 0.8

DEMAND KW 0.4 1.44 5.18 0 0 10.92 0 0

TOTAL KW WITH DEMAND 17.9

TOTAL 3 PHASE AMPS 49.9

NOTES:

PANELBOARD SCHEDULE PANEL: XX-1-2

LOCATION: HALLWAY 116 MAIN: 100A MLO

VOLTAGE: 208/120 PH: 3 WIRE: 4 MOUNTING: RECESSED SOURCE: XX-1-4

CKT. DESCRIPTION EQP. MTR. REC. LTG. C.B. KW / PHASE C.B. LTG. REC. MTR. EQP. DESCRIPTION CKT.

NO. KW KW KW KW A/P - A - - B - - C - A/P KW KW KW KW NO.

1 RECEPTACLE 0.4 20/3 0.8 20/3 0.4 RECEPTACLE 2

3 RECEPTACLE 0.6 - 1 - 0.4 RECEPTACLE 4

5 RECEPTACLE 0.4 - 0.8 - 0.4 RECEPTACLE 6

7 RECEPTACLE 0.6 20/3 1.2 20/3 0.6 RECEPTACLE 8

9 RECEPTACLE 0.8 - 1.8 - 1.0 RECEPTACLE 10

11 RECEPTACLE 0.8 - 1.4 - 0.6 RECEPTACLE 12

13 RECEPTACLE 0.6 20/3 1.2 20/3 0.6 RECEPTACLE 14

15 RECEPTACLE 0.6 0.6 - 1.8 - 0.6 RECEPTACLE 16

17 RECEPTACLE 0.6 0.6 - 2 - 0.8 RECEPTACLE 18

19 RECEPTACLE 0.4 20/3 1.4 20/3 1.0 RECEPTACLE 20

21 RECEPTACLE 0.4 - 1.6 - 1.0 0.2 CUH # 2/RECEPTACLE 22

23 RECEPTACLE 0.4 - 1.4 - 1.0 RECEPTACLE 24

25 RECEPTACLE 0.4 20/3 1.2 20/3 0.8 RECEPTACLE 26

27 RECEPTACLE 0.8 - 1.6 - 0.8 RECEPTACLE 28

29 RECEPTACLE 0.8 - 1.6 - 0.8 RECEPTACLE 30

31 RECEPTACLE 0.4 20/3 1.2 20/3 0.8 RECEPTACLE 32

33 RECEPTACLE 0.4 - 0.8 - 0.4 RECEPTACLE 34

35 RECEPTACLE 0.4 - 1.2 - 0.8 RECEPTACLE 36

37 RECEPTACLE 0.6 1.4 20/3 0.8 RECEPTACLE 38

39 RECEPTACLE 0.8 20/1 1.4 - 0.6 RECEPTACLE 40

41 RECEPTACLE 0.8 20/1 1.4 - 0.6 RECEPTACLE 42

43 SPARE 20/1 0 20/1 SPARE 44

45 SPARE 20/1 0 SPACE 46

47 SPARE 20/1 0 SPACE 48

49 SPACE 0 SPACE 50

51 SPACE 0 SPACE 52

53 SPACE 0 SPACE 54

CONNECTED KW 8.6 0 4.6 0 8 10 10 0 14.8 0.2 0

DEMAND 0.8 0.8 0.7 1.25 1.25 0.7 0.8 0.8

DEMAND KW 6.88 0 3.22 0 0 10.36 0.16 0

TOTAL KW WITH DEMAND 20.6

TOTAL 3 PHASE AMPS 57.3

NOTES:

PANELBOARD SCHEDULE PANEL: XX-1-3

LOCATION: HALLWAY 116 MAIN: 100 MLO

VOLTAGE: 208/120 PH: 3 WIRE: 4 MOUNTING: RECESSED SOURCE: XX-1-4

CKT. DESCRIPTION EQP. MTR. REC. LTG. C.B. KW / PHASE C.B. LTG. REC. MTR. EQP. DESCRIPTION CKT.

NO. KW KW KW KW A/P - A - - B - - C - A/P KW KW KW KW NO.

1 BASEMENT LIGHTS 1.4 20/3 2 20/3 0.6 RECEPTACLE 2

3 BASEMENT LIGHTS 1.4 - 2 - 0.2 0.4 RECEPTACLE 4

5 BASEMENT LIGHTS 1.3 - 1.7 - 0.4 RECEPTACLE 6

7 FIRST FL LIGHTS 0.9 20/3 2.9 50/2 2 RANGE 8

9 FIRST FL LIGHTS 1.1 - 3.1 - 2 - 10

11 FIRST FL LIGHTS 1.1 - 1.7 20/3 0.6 RECEPTACLE 12

13 FIRST FL LIGHTS 0.9 20/3 1.5 - 0.6 RECEPTACLE 14

15 FIRST FL LIGHTS 1.1 - 1.7 - 0.6 RECEPTACLE 16

17 FIRST FL LIGHTS 0.8 - 1.6 20/3 0.8 RECEPTACLE 18

19 FIRST FL LIGHTS 1.5 20/1 1.9 - 0.4 RECEPTACLE 20

21 FIRST FL LIGHTS 1 20/1 1.4 - 0.4 RECEPTACLE 22

23 AHU LIGHTS 0.8 20/1 0.8 20/3 SPARE 24

25 AHU RECEPTACLES 0.6 20/1 0.6 - SPARE 26

27 AHU RECEPTACLES 0.6 20/1 0.6 - SPARE 28

29 RECEPTACLE 0.4 20/1 1.2 20/1 0.8 SPLINT MACHINE 30

31 RECEPTACLE 0.4 20/1 1.2 20/1 0.8 REFRIG 32

33 RECEPTACLE 0.4 20/1 1.2 20/1 0.8 MICROWAVE 34

35 RECEPTACLE 0.4 20/1 1.2 20/1 0.8 MICROWAVE 36

37 TIMER 0.3 20/1 0.8 20/2 0.5 HOIST CONTROLLER 38

39 LIGHTS 0.6 20/1 1.1 - 0.5 40

41 SPARE 20/1 0 SPACE 42

43 SPARE 20/1 0 SPACE 44

45 SPARE 20/1 0 SPACE 46

47 SPACE 0 SPACE 48

49 SPACE 0 SPACE 50

51 SPACE 0 SPACE 52

53 SPACE 0 SPACE 54

CONNECTED KW 0.3 0 1.2 15.5 11 11 8 0 4 0 9.2

DEMAND 0.8 0.8 0.7 1.25 1.25 0.7 0.8 0.8

DEMAND KW 0.24 0 0.84 19.375 0 2.8 0 7.36

TOTAL KW WITH DEMAND 30.6

TOTAL 3 PHASE AMPS 85.1

NOTES:

PANELBOARD SCHEDULE PANEL: XX-1-4

LOCATION: ELECTRICAL 114 MAIN: 225A MCB

VOLTAGE: 208/120 PH: 3 WIRE: 4 MOUNTING: SURFACE SOURCE: SWBD A

CKT. DESCRIPTION EQP. MTR. REC. LTG. C.B. KW / PHASE C.B. LTG. REC. MTR. EQP. DESCRIPTION CKT.

NO. KW KW KW KW A/P - A - - B - - C - A/P KW KW KW KW NO.

1 XX-1-1 0 0.9 8.4 0 100/3 9.3 SPACE 2

3 - 0 0.9 6.8 0 - 7.7 SPACE 4

5 - 0.5 0 7.8 0 - 8.3 SPACE 6

7 XX-1-2 1.8 0 6.6 0 100/3 8.4 SPACE 8

9 - 3.8 0.2 6 0 - 10 SPACE 10

11 - 3 0 6.8 0 - 9.8 SPACE 12

13 XX-1-3 4.2 0 1.6 5.1 100/3 10.9 SPACE 14

15 - 3.7 0 1.8 5.6 - 11.1 SPACE 16

17 - 1.6 0 1.8 4.8 - 8.2 SPACE 18

19 SPACE 0 SPACE 20

21 SPACE 0 SPACE 22

23 SPACE 0 SPACE 24

25 SPACE 0 SPACE 26

27 SPACE 0 SPACE 28

29 SPACE 0 SPACE 30

31 SPACE 0 SPACE 32

33 SPACE 0 SPACE 34

35 SPACE 0 SPACE 36

37 SPACE 0 SPACE 38

39 SPACE 0 SPACE 40

41 SPACE 0 SPACE 42

43 SPACE 0 SPACE 44

45 SPACE 0 SPACE 46

47 SPACE 0 SPACE 48

49 SPACE 0 SPACE 50

51 SPACE 0 SPACE 52

53 SPACE 0 SPACE 54

CONNECTED KW 18.6 2 47.6 15.5 29 29 26 0 0 0 0

DEMAND 0.8 0.8 0.7 1.25 1.25 0.7 0.8 0.8

DEMAND KW 14.88 1.6 33.32 19.375 0 0 0 0

TOTAL KW WITH DEMAND 69.2

TOTAL 3 PHASE AMPS 192

NOTES:

RELOCATE REHAB

MOTOR & EQUIPMENT SCHEDULE - S1430

MOTOR/ EQUIP NO. DESCRIPTION LOCATION kW HP MCA

MAX

OPD

VOLT/

PHASE FED FROM CONDUIT & REMARKS

BY DIV TYPE BY DIV TYPE/CNTRL WIRE SIZE

A.H.U. #1 AIR HANDLING UNIT MECHANICAL 119

SUPPLY FAN MECHANICAL 119 25 42.5 50 480/3 26 VFD 26 VFD SEE ONE-LINE SEE ONE-LINE PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY DUCT.

RETURN FAN MECHANICAL 119 15 26.3 30 480/3 26 VFD 26 VFD SEE ONE-LINE SEE ONE-LINE PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN DUCT.

PUMP # 1 WELL FIELD PUMP MECH ROOM 001 15 26.3 30 480/3 26 VFD 26 VFD SEE ONE-LINE SEE ONE-LINE

PUMP # 2 WELL FIELD PUMP MECH ROOM 001 15 26.3 30 480/3 26 VFD 26 VFD SEE ONE-LINE SEE ONE-LINE

PUMP # 3 HYDRONIC HEATING PUMP MECH ROOM 001 7 1/2 13.8 20 480/3 26 VFD 26 VFD SEE ONE-LINE SEE ONE-LINE

PUMP # 4 HYDRONIC HEATING PUMP MECH ROOM 001 7 1/2 13.8 20 480/3 26 VFD 26 VFD SEE ONE-LINE SEE ONE-LINE

FUTURE PUMP # 5 HYDRONIC HEATING PUMP MECH ROOM 001 7 1/2 13.8 20 480/3 26 VFD 26 VFD SEE ONE-LINE SEE ONE-LINE

PUMP # 6 CH. WATER PUMP MECH ROOM 001 5 9.5 15 480/3 26 VFD 26 VFD SEE ONE-LINE SEE ONE-LINE

PUMP # 7 CH. WATER PUMP MECH ROOM 001 5 9.5 15 480/3 26 VFD 26 VFD SEE ONE-LINE SEE ONE-LINE

FUTURE PUMP # 8 CH. WATER PUMP MECH ROOM 001 5 9.5 15 480/3 26 VFD 26 VFD SEE ONE-LINE SEE ONE-LINE

PUMP # 9 HEAT PUMP MECH ROOM 001 5 9.5 15 480/3 26 VFD 26 VFD SEE ONE-LINE SEE ONE-LINE

PUMP # 10 HEAT PUMP MECH ROOM 001 5 9.5 15 480/3 26 VFD 26 VFD SEE ONE-LINE SEE ONE-LINE

FUTURE PUMP # 11 HEAT PUMP MECH ROOM 001 5 9.5 15 480/3 26 VFD 26 VFD SEE ONE-LINE SEE ONE-LINE

PUMP # 12 HEAT EXCHANGER MECH ROOM 001 3 6 15 480/3 26 DS 26 COMB SEE ONE-LINE SEE ONE-LINE

PUMP # 13 SNOW MELT MECH ROOM 001 1 3 15 480/3 26 DS 26 COMB SEE ONE-LINE SEE ONE-LINE

PUMP #14 CONDENSATE PUMPS MECH ROOM 001 (2)3/4 4 15 480/3 26 DS 23 FVNR SEE ONE-LINE SEE ONE-LINE

HEAT PUMP 1 HEAT PUMP MECH ROOM 001 70 105 150 480/3 26 FDS - - SEE ONE-LINE SEE ONE-LINE

HEAT PUMP 2 HEAT PUMP MECH ROOM 001 70 105 150 480/3 26 FDS - - SEE ONE-LINE SEE ONE-LINE

FUTURE HEAT PUMP 3 HEAT PUMP MECH ROOM 001 70 105 150 480/3 26 FDS - - SEE ONE-LINE SEE ONE-LINE

C.U.H. # 1 CABINET UNIT HEATER S VESTIBULE 101 1/20 15 120/1 23 MS - - SEE PLAN 3/4"C - 2#12 & 1#12 GND

C.U.H. # 2 CABINET UNIT HEATER N VESTIBULE 137 1/20 15 120/1 23 MS - - SEE PLAN 3/4"C - 2#12 & 1#12 GND

C.U.H. # 3 CABINET UNIT HEATER CORRIDOR 104 1/20 15 120/1 23 MS - - SEE PLAN 3/4"C - 2#12 & 1#12 GND

C.U.H. # 4 CABINET UNIT HEATER LINK TO BLDG 51 176 1/20 15 120/1 23 MS - - SEE PLAN 3/4"C - 2#12 & 1#12 GND

UNIT HEATER # 1 UNIT HEATER CRAWL SPACE 002 1/12 15 120/1 26 MS - - SEE PLAN 3/4"C - 2#12 & 1#12 GND

UNIT HEATER # 2 UNIT HEATER CRAWL SPACE 002 1/12 15 120/1 26 MS - - SEE PLAN 3/4"C - 2#12 & 1#12 GND

UNIT HEATER # 3 UNIT HEATER MECH ROOM 001 1/12 15 120/1 26 MS - - SEE PLAN 3/4"C - 2#12 & 1#12 GND

P.R.V. #1 POWERED ROOTOP VENTILATOR ROOF 1/2 12.3 20 120/1 26 COMB - SEE PLAN 3/4"C - 2#12 & 1#12 GND PROVIIDE SINGLE POLE 120V RELAY WITH 24VAC COIL AND DISCONNECT SWITCH

P.R.V. #2 POWERED ROOTOP VENTILATOR ROOF 1/2 12.3 20 120/1 26 COMB - - SEE PLAN 3/4"C - 2#12 & 1#12 GND PROVIIDE SINGLE POLE 120V RELA YWITH 24VAC COIL AND DISCONNECT SWITCH

PROP. FAN PROPELLER FAN CRAWL SPACE 002 1/4 7.3 15 120/1 23 MS - - SEE PLAN 3/4"C - 2#12 & 1#12 GND

DRAIN TILE PUMPS MECH ROOM 001 (2) 1/2 15 480/3 26 DS 22 FVNR SEE PLAN SEE ONE-LINE

SEWAGE EJECTOR PUMPS MECH ROOM 001 (2) 1/2 15 480/3 26 DS 22 FVNR SEE PLAN SEE ONE-LINE PROVIDE WIRING FOR TWO SOLENOID VALVES AND CONTROLLER.

DOMESTIC WATER HEATER MECH ROOM 001 FRAC 15 120/1 26 MS - - SEE PLAN 3/4"C - 2#12 & 1#12 GND

LEGEND: FDS = FUSED SAFETY SWITCH FVNR = FULL VOLTAGE NON-REVERSING STARTER VFD = VARIABLE FREQUENCY DRIVE

SHUNT = SHUNT TRIP SAFETY SWITCH MRS = MOTOR RATED SWITCH TR = 24V CONTROL TRANSFORMER

COMB = #1 FVNR COMB. STARTER/HOA/AUX/TR HOA = HAND/OFF/AUTO CONTROL DS = NON FUSED SAFETY SWITCH

COMB 1 = #2 FVNR COMB. STARTER/HOA/AUX/TR SS = START/STOP CONTROL CB = CIRCUIT BREAKER

COMB 2 = #3 FVNR COMB STARTER/HOA/AUX/TR AUX = AUXILIARY CONTACTS WP = WEATHER PROOF

TSAT = THERMOSTAT

DISC BY DIV STARTER BY DIV

LUMINAIRE SCHEDULE

TYPE FIXTURE TYPE F

L

U O

R

H

ID

L E

D

IN

C

A N

D

LAMPS VOLTS DESCRIPTION MANUFACTURER/MODEL APPROVED EQUAL NOTES/REMARKS

A1 2' X 4' X (2) 28W T8 120V HIGH PERFORMANCE PARABOLIC LUMINAIRE LITHONIA COLUMBIA, DAYBRIGHT, METALUX, LIGHTOLIER, RECESSED COLD ROLLED STEEL HOUSING, MULTI-VOLT BALLAST, 18-CELL 2PM3N-G-B-2-32-18LD-MVOLT-GEB10IS LUMAX, WILLIAMS, COOPER, LSI, FOCAL POINT OR

PARABOLIC ALUMINUM LOW IRIDESCENT DIFFUSER, LAY-IN GRID. APPROVED EQUAL

A2 2' X 2' X (4) 17W T8 120V HIGH PERFORMANCE PARABOLIC LUMINAIRE LITHONIA COLUMBIA, DAYBRIGHT, METALUX, LIGHTOLIER, RECESSED COLD ROLLED STEEL HOUSING, MULTI-VOLT BALLAST, 9-CELL 2PM3N-G-B-4-17-9LD-MVOLT-GEB10IS LUMAX, WILLIAMS, COOPER, LSI, FOCAL POINT OR

PARABOLIC ALUMINUM LOW IRIDESCENT DIFFUSER, LAY-IN GRID. APPROVED EQUAL

A3 2' X 4' RECESSED X (3) 28W T8 120V RECESSED DIRECT/INDIRECT. MATTE SATIN WHITE FINISH. FOCAL POINT COLUMBIA, DAYBRIGHT, METALUX,LIGHTOLIER, DIRECT/INDIRECT- EXTRUDED ACRYLIC DIFFUSER . SEALED OPTICAL COMPARTMENT. FMA2-24-3-T8-1C-120-E-G LUMAX, WILLIAMS, COOPER, LSI, LITHONIA OR APPROVED

INSTANT START BALLAST. EQUAL

A4 2' X 4' RECESSED X (2) 54W T5HO 120V RECESSED DIRECT/INDIRECT. MATTE SATIN WHITE FINISH. FOCAL POINT COLUMBIA, DAYBRIGHT, METALUX,LIGHTOLIER, DIRECT/INDIRECT- EXTRUDED ACRYLIC DIFFUSER . SEALED OPTICAL COMPARTMENT. FMA2-24-2-T5HO-1C-120-E-G LUMAX, WILLIAMS, COOPER, LSI, LITHONIA OR APPROVED

INSTANT START BALLAST. EQUAL

A5 2' X 4' X (3) 28W T8 120V HIGH PERFORMANCE PARABOLIC LUMINAIRE LITHONIA COLUMBIA, DAYBRIGHT, METALUX, LIGHTOLIER, RECESSED COLD ROLLED STEEL HOUSING, MULTI-VOLT BALLAST, 18-CELL 2PM3N-G-B-3-32-18LD-MVOLT-GEB10IS LUMAX, WILLIAMS, COOPER, LSI, FOCAL POINT OR

PARABOLIC ALUMINUM LOW IRIDESCENT DIFFUSER, LAY-IN GRID. APPROVED EQUAL

B VANITY - 24" X (2) 17W T8 120V TWO-LIGHT BATH BAR IN SATIN NICKEL FINISH WITH WHITE ACRYLIC DIFFUSER. FORECAST

20/277V BALLAST, UL DAMP LISTED. F325236U

4-5/8"H X 25-1/2"L X 4-5/8" D

C1 4' STRIP LIGHT X (2) 28W T8 120V 4' STANDARD INDUSTRIAL STRIP WITH SYMMETRIC REFLECTOR AND WIREGUARD. LITHONIA COLUMBIA, DAYBRIGHT, METALUX,LITHONIA, CHAIN HUNG, MOUNT 8' A.F.F. OR

C-232-MVOLT-GEB10RS-WGCSMR-CSMR48 LUMAX, WILLIAMS, COOPER, LSI OR APPROVED BENEATH DUCTWORK.

EQUAL PROGRAMMED START BALLAST

C2 8' STRIP LIGHT X (4) 28W T8 120V 8' STANDARD INDUSTRIAL STRIP WITH SYMMETRIC REFLECTOR AND WIREGUARD. LITHONIA COLUMBIA, DAYBRIGHT, METALUX,LITHONIA, CHAIN HUNG, MOUNT 8' A.F.F. OR

TANDOM MOUNT TC-232-MVOLT-GEB10RS-WGCSMR LUMAX, WILLIAMS, COOPER, LSI OR APPROVED BENEATH DUCTWORK.

-CSMR96 EQUAL PROGRAMMED START BALLAST

C3 4' STRIP LIGHT X (2) 28W T8 120V 4' STANDARD INDUSTRIAL STRIP WITH WIREGUARD. LITHONIA COLUMBIA, DAYBRIGHT, METALUX,LITHONIA, MOUNT 6" BELOW CEILING.

WALL MOUNTED C-232-MVOLT-GEB10IS-WGCSMR LUMAX, WILLIAMS, COOPER, LSI OR APPROVED

EQUAL

C4 8' STRIP LIGHT X (4) 28W T8 120V 8' STANDARD INDUSTRIAL STRIP WITH SYMMETRIC REFLECTOR AND WIREGUARD. LITHONIA COLUMBIA, DAYBRIGHT, METALUX,LITHONIA, TANDOM MOUNT. 40" LONG SWIVEL STEM HANGER. TC-232-MVOLT-GEB10IS-WGCSMR LUMAX, WILLIAMS, COOPER, LSI OR APPROVED

-CSMR96-SQ40 EQUAL

CL CLOSET LIGHT X (1) 17W T8 120V 2' STANDARD WALL BRACKET. BAKED WHITE ENAMEL FINISH. LITHONIA COLUMBIA, DAYBRIGHT, METALUX,LITHONIA, MOUNT ABOVE CLOSET DOOR.

#12 PATTERN, 0.125" THICK ACRYLIC DIFFUSER WS-1-17-A12125-MVOLT-GEB10IS LUMAX, WILLIAMS, COOPER, LSI OR APPROVED

EQUAL

D RECESSED X (1) 42W TRT 120V 8" RECESSED DOWNLIGHT, CLEAR SEMI-SPECULAR REFLECTOR, LITHONIA INFINITY, LIGHTOLIER, PATHWAYS, PEACHTREE, DOWNLIGHT MULTI-VOLT BALLAST, VERTICAL LAMP 8VF-42TRT-802AZ-MVOLT PORTFOLIO, PRESCOLITE, SURELITE, COOPER, 8-IN OR APPROVED EQUAL

DD RECESSED x (1) 150W 120V 6" RECESSED DOWNLIGHT, CLEAR SPECULAR REFLECTOR, LITHONIA INFINITY, LIGHTOLIER, PATHWAYS, PEACHTREE, DOWNLIGHT LP6N-609A PORTFOLIO, PRESCOLITE, SURELITE, OR APPROVED

6" DIMMING EQUAL

D1 RECESSED X LED 20W 120V 4" RECESSED ROUND LED DOWNLIGHT. CLEAR, WHITE FLANGE. 3000K LIGHTOLIER SOLVANTI, ELITE(ORACLE), JUNO, PMC

DOWNLIGHT LED. C420LEDDL30K CCLW, C420LED1 OR APPROVED EQUAL.

4 INCH

EA EXIT SIGN X LED 120V WHITE THERMOPLASTIC HOUSING WITH RED LITHONIA CHLORIDE, EXITRONICS, LIGHTOLIER, SINGLE FACE LETTERS, UNIVERSAL MOUNTING, SINGLE FACE LQM-S-W-3-R-120/277 EMERGI-LITE, MCPHILBEN, PRESCOLITE, SURELITE

DUAL LITE, KENALL, OR APPROVED EQUAL

EB EXIT SIGN X LED 120V WHITE THERMOPLASTIC HOUSING WITH RED LITHONIA CHLORIDE, EXITRONICS, LIGHTOLIER, DOUBLE FACE LETTERS, UNIVERSAL MOUNTING, COUBLE FACE LQM-S-W-3-R-120/277 EMERGI-LITE, MCPHILBEN, PRESCOLITE, SURELITE

DUAL LITE, KENALL, OR APPROVED EQUAL

EG EMERGENCY X (2) 5.4W KRYPTON 120V WHITE HIGH IMPACT THERMOPLASTIC HOUSING, LEAD CALCIUM LITHONIA CHLORIDE, EXITRONICS, LIGHTOLIER, LIGHTING UNIT BATTERY, SELF-DIAGNOSTICS. ELM2-SD EMERGI-LITE, MCPHILBEN, PRESCOLITE, SURELITE

DUAL LITE, KENALL, OR APPROVED EQUAL

OA EXTERIOR X LED 120V WALLPACK WITH 2 LED ARRAYS, SPECULAR REFLECTOR AND CLEAR FLAT GLASS RAB LIGHTING ALLOWANCE PRICE $211.25 EACH SEE EXTERIOR ELEVATIONS FOR

WALL PACK 20W LENS. BRONZE FINISH. 5000K LEDS. WPLED20Y CONTACT ELECTROTECH INC. MOUNTING HEIGHTS.

(763) 544-4288 FOR INFORMATION

OB EXTERIOR X LED 26W 120V FULL CUTOFF, WALL MOUNTED LED LANTERN WITH TRADITIONAL LOOK. WHITE USA LTG HOLOPHANE, SELUX, KIM, HUBBEL, SEE EXTERIOR ELEVATIONS FOR

LED LANTERN POLYCARBONATE DIFFUSER. DARK BRONZE TEXTURED FINISH. NEUTRAL 4100K WHITE LEDS. MOZART MINI, MOZM-WA-VP-V-24LED-WM-RAL-8019-T-WP LSI, COOPER, OR APPROVED EQUAL MOUNTING HEIGHTS.

TYPE V DISTRIBUTION, 20"W X 26.5"H

OD RECESSED X (1) 100W MH 120V 8" RECESSED OPEN DOWN LIGHT, HORIZONTAL LAMP LITHONIA OMEGA, INFINITY, LIGHTOLIER, PATHWAYS, EXTERIOR LIGHT AHZ-100M-8-AR-120 PRESCOLITE, ATLANTIC OR APPROVED EQUAL.

OE RECESSED X (1) 100W MH 120V 8" RECESSED OPEN DOWN LIGHT, HORIZONTAL LAMP, QUARTZ RESTRIKE LITHONIA OMEGA, INFINITY, LIGHTOLIER, PATHWAYS, EXTERIOR LIGHT AHZ-100M-8-AR-120-QRS PRESCOLITE, ATLANTIC OR APPROVED EQUAL.

QUARTZ RESTRIKE

OP1 EXTERIOR LIGHT X (1) 250W HPS 480V/1P IES TYPE IV FOREWARD THROW HIGH PERFORMANCE REFLECTOR. SUPER CWA PULSE-START. STERNER EXEC-RT25-250HPS-4L-480-C-10-N-FL-BZ OR PRE-APPROVED EQUALS

LIGHT POLE DARK BRONZE FINISH. 30FT 6" ALUMINUM SQUARE POLE. PROVIDE ALUMINUM FRANGIBLE NAFCO 6S30E-DARK POLE POLE WITH VIBRATION DAMPER

1-HEAD "BREAKAWAY" T-BASE. MILLERBERND T-BASE AKRON-TB1-17-BRZ-H

UC UNDER CABINET X (1) 17W T8 120V LOW-PROFILE DESIGN, WHITE FINISH, INTEGRAL LITHONIA N2S-17-MVOLT-GEB10IS-SWR COLUMBIA, DAYBRITE, LIGHTOLIER, LUMAX, HARDWIRE TO LOCAL 120V CIRCUIT

LIGHTS-24" ROCKER SWITCH, MULTI-VOLT, 10% THD BALLAST. MERCURY, METALUX, WILLIAMS, COOPER, OR APPROVED EQUAL.

NOTE THAT ALL LIGHTS SHALL MEET THE "MADE IN AMERICA" VA REQUIREMENTS.

N.I.C.

N.I.C.

N.I.C.

RELOCATE REHAB