This solicitation is for a Multiple Award Task Order Contract for construction services within the Minnesota region for the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 23. The solicitation will make multiple awards for indefinite-delivery indefinite-quantity contracts ranging in value from $2,000 to $10,000,000 per task order, with a maximum total contract value of $70,000,000. The period of performance for task orders issued against the contracts will be five years from date of award. Services will cover facilities including the Minneapolis and St. Cloud VA Health Care Systems and their associated clinics. The solicitation is designated as a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses. A bid bond will be required and contractors must be able to provide payment and performance bonds for individual task orders valued over $150,000. Interested parties should monitor the Federal Business Opportunities website for release of the solicitation and any subsequent amendments.
36C26318R0688 0002 656-16-277 For Reference Only Drawings (14 pages).pdf
View the file
Other files
Show all 47
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT NO.
PLOT SCALE
PROJECT TITLE
DRAWN
DRAWING NO.DATE:
DATE: BUILDING No
VA MEDICAL CENTER
ST.CLOUD, MN 56303
CHECKED BY
DATE:
DATE:
DATE:
APPROVED: PATIENT SAFETY
APPROVED: INFECTION CONTROL NURSEDATE:
DATE:
DATE:
APPROVED: SERVICE LINE DIRECTOR
APPROVED: PROJECTS SECTION MANAGER
APPROVED: GEMS COORDINATOR
DATE:APPROVED: SAFETY MANAGERDATE:APPROVED: DIRECTOR FMS
APPROVED: CHIEF OF POLICE
APPROVED: MEDICAL CENTER DIRECTOR
APPROVED: CHIEF OF STAFF
DRAWING TITLE
REVISIONNo
S1430
DATE
PROJECT NO.
PLOT SCALE
PROJECT TITLE
DRAWN
DRAWING NO.DATE:
DATE: BUILDING No
VA MEDICAL CENTER
ST.CLOUD, MN 56303
CHECKED BY
DATE:
DATE:
DATE:
APPROVED: PATIENT SAFETY
APPROVED: INFECTION CONTROL NURSEDATE:
DATE:
DATE:
APPROVED: SERVICE LINE DIRECTOR
APPROVED: PROJECTS SECTION MANAGER
APPROVED: GEMS COORDINATOR
DATE:APPROVED: SAFETY MANAGERDATE:APPROVED: DIRECTOR FMS
APPROVED: CHIEF OF POLICE
APPROVED: MEDICAL CENTER DIRECTOR
APPROVED: CHIEF OF STAFF
DRAWING TITLE
DATE
S1430 St. Cloud VA Health Care System
CES CONSULTANTS, LLC
CIVIL ENGINEERING
201 West Travelers Trail, Suite 200 Burn sville, MN 55337
763-274-4405 www.cesminn.com
01-03-2013
CONSTRUCTION DOCUMENTS
REHABILITATION CENTER
656-332
ADDENDUM NO. 1 08/16/131
RECORD SET 09/30/162
http://www.cesminn.com/
GENERATOR
BUILDING
PROJECT NO.
PLOT SCALE
PROJECT TITLE
DRAWN
DRAWING NO.DATE:
DATE: BUILDING No
VA MEDICAL CENTER
ST.CLOUD, MN 56303
CHECKED BY
DATE:
DATE:
DATE:
APPROVED: PATIENT SAFETY
APPROVED: INFECTION CONTROL NURSEDATE:
DATE:
DATE:
APPROVED: SERVICE LINE DIRECTOR
APPROVED: PROJECTS SECTION MANAGER
APPROVED: GEMS COORDINATOR
DATE:APPROVED: SAFETY MANAGERDATE:APPROVED: DIRECTOR FMS
APPROVED: CHIEF OF POLICE
APPROVED: MEDICAL CENTER DIRECTOR
APPROVED: CHIEF OF STAFF
DRAWING TITLE
S1430
01-03-2013
St. Cloud VA Health Care System
DATE
PROJECT NO.
PLOT SCALE
PROJECT TITLE
DRAWN
DRAWING NO.DATE:
DATE: BUILDING No
VA MEDICAL CENTER
ST.CLOUD, MN 56303
CHECKED BY
DATE:
DATE:
DATE:
APPROVED: PATIENT SAFETY
APPROVED: INFECTION CONTROL NURSEDATE:
DATE:
DATE:
APPROVED: SERVICE LINE DIRECTOR
APPROVED: PROJECTS SECTION MANAGER
APPROVED: GEMS COORDINATOR
DATE:APPROVED: SAFETY MANAGERDATE:APPROVED: DIRECTOR FMS
APPROVED: CHIEF OF POLICE
APPROVED: MEDICAL CENTER DIRECTOR
APPROVED: CHIEF OF STAFF
DRAWING TITLE
CONSTRUCTION DOCUMENTS
S1430
St. Cloud VA Health Care System
REHABILITATION CENTERCES CONSULTANTS, LLC
CIVIL ENGINEERING
201 West Travelers Trail, Suite 200 Burn sville, MN 55337
763-274-4405 www.cesminn.com
656-332
REVISION DATENo REVISION DATENo
ADDENDUM NO. 1 08/16/131
PR #14 06/12/142
3 PR #29 05/13/15
4 RFI #160 08/19/15
5 ASI #17 09/09/15
6 RFI #169 09/15/15
7 RECORD SET 09/30/16
PROJECT NO.
PLOT SCALE
PROJECT TITLE
DRAWN
DRAWING NO.DATE:
DATE: BUILDING No
VA MEDICAL CENTER
ST.CLOUD, MN 56303
CHECKED BY
DATE:
DATE:
DATE:
APPROVED: PATIENT SAFETY
APPROVED: INFECTION CONTROL NURSEDATE:
DATE:
DATE:
APPROVED: SERVICE LINE DIRECTOR
APPROVED: PROJECTS SECTION MANAGER
APPROVED: GEMS COORDINATOR
DATE:APPROVED: SAFETY MANAGERDATE:APPROVED: DIRECTOR FMS
APPROVED: CHIEF OF POLICE
APPROVED: MEDICAL CENTER DIRECTOR
APPROVED: CHIEF OF STAFF
DRAWING TITLE
REVISION DATENo
S1430 St. Cloud VA Health Care System
DATE
PROJECT NO.
PLOT SCALE
PROJECT TITLE
DRAWN
DRAWING NO.DATE:
DATE: BUILDING No
VA MEDICAL CENTER
ST.CLOUD, MN 56303
CHECKED BY
DATE:
DATE:
DATE:
APPROVED: PATIENT SAFETY
APPROVED: INFECTION CONTROL NURSEDATE:
DATE:
DATE:
APPROVED: SERVICE LINE DIRECTOR
APPROVED: PROJECTS SECTION MANAGER
APPROVED: GEMS COORDINATOR
DATE:APPROVED: SAFETY MANAGERDATE:APPROVED: DIRECTOR FMS
APPROVED: CHIEF OF POLICE
APPROVED: MEDICAL CENTER DIRECTOR
APPROVED: CHIEF OF STAFF
DRAWING TITLE
REVISION DATENo
S1430 St. Cloud VA Health Care System
CES CONSULTANTS, LLC
CIVIL ENGINEERING
201 West Travelers Trail, Suite 200 Burn sville, MN 55337
763-274-4405 www.cesminn.com
01-03-2013
CONSTRUCTION DOCUMENTS
REHABILITATION CENTER
656-332
ADDENDUM NO. 1 08/16/131
CONSTRUCTION AREA
PROJECT NO.
PLOT SCALE
PROJECT TITLE
DRAWN
DRAWING NO.DATE:
DATE: BUILDING No
VA MEDICAL CENTER
ST.CLOUD, MN 56303
CHECKED BY
DATE:
DATE:
DATE:
APPROVED: PATIENT SAFETY
APPROVED: INFECTION CONTROL NURSEDATE:
DATE:
DATE:
APPROVED: SERVICE LINE DIRECTOR
APPROVED: PROJECTS SECTION MANAGER
APPROVED: GEMS COORDINATOR
DATE:APPROVED: SAFETY MANAGERDATE:APPROVED: DIRECTOR FMS
APPROVED: CHIEF OF POLICE
APPROVED: MEDICAL CENTER DIRECTOR
APPROVED: CHIEF OF STAFF
DRAWING TITLE
REVISION DATENo
S1430 St. Cloud VA Health Care System
DATE
PROJECT NO.
PLOT SCALE
PROJECT TITLE
DRAWN
DRAWING NO.DATE:
DATE: BUILDING No
VA MEDICAL CENTER
ST.CLOUD, MN 56303
CHECKED BY
DATE:
DATE:
DATE:
APPROVED: PATIENT SAFETY
APPROVED: INFECTION CONTROL NURSEDATE:
DATE:
DATE:
APPROVED: SERVICE LINE DIRECTOR
APPROVED: PROJECTS SECTION MANAGER
APPROVED: GEMS COORDINATOR
DATE:APPROVED: SAFETY MANAGERDATE:APPROVED: DIRECTOR FMS
APPROVED: CHIEF OF POLICE
APPROVED: MEDICAL CENTER DIRECTOR
APPROVED: CHIEF OF STAFF
DRAWING TITLE
REVISION DATENo
S1430 St. Cloud VA Health Care System
CES CONSULTANTS, LLC
CIVIL ENGINEERING
201 West Travelers Trail, Suite 200 Burn sville, MN 55337
763-274-4405 www.cesminn.com
01-03-2013
CONSTRUCTION DOCUMENTS
REHABILITATION CENTER
656-332
ADDENDUM NO. 1 08/16/131
PROJECT NO.
PLOT SCALE
PROJECT TITLE
DRAWN
DRAWING NO.DATE:
DATE: BUILDING No
VA MEDICAL CENTER
ST.CLOUD, MN 56303
CHECKED BY
DATE:
DATE:
DATE:
APPROVED: PATIENT SAFETY
APPROVED: INFECTION CONTROL NURSEDATE:
DATE:
DATE:
APPROVED: SERVICE LINE DIRECTOR
APPROVED: PROJECTS SECTION MANAGER
APPROVED: GEMS COORDINATOR
DATE:APPROVED: SAFETY MANAGERDATE:APPROVED: DIRECTOR FMS
APPROVED: CHIEF OF POLICE
APPROVED: MEDICAL CENTER DIRECTOR
APPROVED: CHIEF OF STAFF
DRAWING TITLE
REVISION DATENo
S1430
DATE
PROJECT NO.
PLOT SCALE
PROJECT TITLE
DRAWN
DRAWING NO.DATE:
DATE: BUILDING No
VA MEDICAL CENTER
ST.CLOUD, MN 56303
CHECKED BY
DATE:
DATE:
DATE:
APPROVED: PATIENT SAFETY
APPROVED: INFECTION CONTROL NURSEDATE:
DATE:
DATE:
APPROVED: SERVICE LINE DIRECTOR
APPROVED: PROJECTS SECTION MANAGER
APPROVED: GEMS COORDINATOR
DATE:APPROVED: SAFETY MANAGERDATE:APPROVED: DIRECTOR FMS
APPROVED: CHIEF OF POLICE
APPROVED: MEDICAL CENTER DIRECTOR
APPROVED: CHIEF OF STAFF
DRAWING TITLE
REVISION DATENo
S1430
CES CONSULTANTS, LLC
CIVIL ENGINEERING
201 West Travelers Trail, Suite 200 Burn sville, MN 55337
763-274-4405 www.cesminn.com
St. Cloud VA Health Care System
01-03-2013
CONSTRUCTION DOCUMENTS
REHABILITATION CENTER
656-332
ADDENDUM NO. 1 08/16/131
RESPONSE TO RFI 012 02/05/142
ASI #2 02/19/143
4 PR #14 06/12/14
5 PR #29 05/13/15
6 PR #29 - AMENDMENT #1 05/21/15
7 RFI #160 08/19/15
8 RECORD SET 09/30/16
PROJECT NO.
PLOT SCALE
PROJECT TITLE
DRAWN
DRAWING NO.DATE:
DATE: BUILDING No
VA MEDICAL CENTER
ST.CLOUD, MN 56303
CHECKED BY
DATE:
DATE:
DATE:
APPROVED: PATIENT SAFETY
APPROVED: INFECTION CONTROL NURSEDATE:
DATE:
DATE:
APPROVED: SERVICE LINE DIRECTOR
APPROVED: PROJECTS SECTION MANAGER
APPROVED: GEMS COORDINATOR
DATE:APPROVED: SAFETY MANAGERDATE:APPROVED: DIRECTOR FMS
APPROVED: CHIEF OF POLICE
APPROVED: MEDICAL CENTER DIRECTOR
APPROVED: CHIEF OF STAFF
DRAWING TITLE
REVISION DATENo
S1430
DATE
PROJECT NO.
PLOT SCALE
PROJECT TITLE
DRAWN
DRAWING NO.DATE:
DATE: BUILDING No
VA MEDICAL CENTER
ST.CLOUD, MN 56303
CHECKED BY
DATE:
DATE:
DATE:
APPROVED: PATIENT SAFETY
APPROVED: INFECTION CONTROL NURSEDATE:
DATE:
DATE:
APPROVED: SERVICE LINE DIRECTOR
APPROVED: PROJECTS SECTION MANAGER
APPROVED: GEMS COORDINATOR
DATE:APPROVED: SAFETY MANAGERDATE:APPROVED: DIRECTOR FMS
APPROVED: CHIEF OF POLICE
APPROVED: MEDICAL CENTER DIRECTOR
APPROVED: CHIEF OF STAFF
DRAWING TITLE
REVISION DATENo
S1430
CES CONSULTANTS, LLC
CIVIL ENGINEERING
201 West Travelers Trail, Suite 200 Burn sville, MN 55337
763-274-4405 www.cesminn.com
St. Cloud VA Health Care System
01-03-2013
CONSTRUCTION DOCUMENTS
REHABILITATION CENTER
656-332
ADDENDUM NO. 1 08/16/131
PR #14 06/12/142
RECORD SET 09/30/163
PROJECT NO.
PLOT SCALE
PROJECT TITLE
DRAWN
DRAWING NO.DATE:
DATE: BUILDING No
VA MEDICAL CENTER
ST.CLOUD, MN 56303
CHECKED BY
DATE:
DATE:
DATE:
APPROVED: PATIENT SAFETY
APPROVED: INFECTION CONTROL NURSEDATE:
DATE:
DATE:
APPROVED: SERVICE LINE DIRECTOR
APPROVED: PROJECTS SECTION MANAGER
APPROVED: GEMS COORDINATOR
DATE:APPROVED: SAFETY MANAGERDATE:APPROVED: DIRECTOR FMS
APPROVED: CHIEF OF POLICE
APPROVED: MEDICAL CENTER DIRECTOR
APPROVED: CHIEF OF STAFF
DRAWING TITLE
REVISION DATENo
S1430
DATE
PROJECT NO.
PLOT SCALE
PROJECT TITLE
DRAWN
DRAWING NO.DATE:
DATE: BUILDING No
VA MEDICAL CENTER
ST.CLOUD, MN 56303
CHECKED BY
DATE:
DATE:
DATE:
APPROVED: PATIENT SAFETY
APPROVED: INFECTION CONTROL NURSEDATE:
DATE:
DATE:
APPROVED: SERVICE LINE DIRECTOR
APPROVED: PROJECTS SECTION MANAGER
APPROVED: GEMS COORDINATOR
DATE:APPROVED: SAFETY MANAGERDATE:APPROVED: DIRECTOR FMS
APPROVED: CHIEF OF POLICE
APPROVED: MEDICAL CENTER DIRECTOR
APPROVED: CHIEF OF STAFF
DRAWING TITLE
REVISION DATENo
S1430
1. CHAMBERS SHALL BE STORMTECH MC-3500 OR APPROVED EQUAL.
2. CHAMBERS SHALL BE MADE FROM VIRGIN, IMPACT-MODIFIED POLYPROPYLENE COPOLYMERS.
3. CHAMBER ROWS SHALL PROVIDE CONTINUOUS, UNOBSTRUCTED INTERNAL SPACE WITH NO
INTERNAL SUPPORT PANELS THAT WOULD IMPEDE FLOW OR LIMIT ACCESS FOR INSPECTION.
4. THE STRUCTURAL DESIGN OF THE CHAMBERS, THE STRUCTURAL BACKFILL AND THE
INSTALLATION REQUIREMENTS SHALL ENSURE THAT THE LOAD FACTORS SPECIFIED IN THE
AASHTO LRFD BRIDGE DESIGN SPECIFICATIONS, SECTION 12.12 ARE MET FOR: 1) LONG-DURATION DEAD LOADS AND 2) SHORT-DURATION LIVE LOADS, BASED ON THE AASHTO DESIGN TRUCK WITH
CONSIDERATION FOR IMPACT AND MULTIPLE VEHICLE PRESENCES.
5. CHAMBERS SHALL CONFIRM TO THE REQUIREMENTS OF ASTM F 2418, "STANDARD
SPECIFICATIONS FOR POLYPROPYLENE (PP) CORRUGATED WALL STORMWATER COLLECTION
CHAMBERS.
6. CHAMBERS SHALL CONFIRM TO THE REQUIREMENTS OF ASTM F 2787, "STANDARD PRACTICE FOR
STRUCTURAL DESIGN OF THERMOPLASTIC CORRUGATED WALL STORMWATER COLLECTION
CHAMBERS.
7. ONLY CHAMBERS THAT ARE APPROVED BY THE ENGINEER WILL BE ALLOWED. THE CONTRACTOR
SHALL SUBMIT (3 SETS) OF THE FOLLOWING TO THE ENGINEER FOR APPROVAL BEFORE
DELIVERING CHAMBERS TO THE PROJECT SITE:
a. A STRUCTURAL EVALUATION BY A REGISTERED STRUCTURAL ENGINEER THAT
DEMONSTRATES THAT THE LOAD FACTORS SPECIFIED IN THE AASHTO LRFD BRIDGE
DESIGN SPECIFICATIONS, SECTION 12.12 ARE MET.
b. STRUCTURAL CROSS SECTION DETAIL ON WHICH THE STRUCTURAL CROSS SECTION IS
BASED.
8. THE INSTALLATION OF CHAMBERS SHALL BE IN ACCORDANCE WITH THE MANUFACTURER'S LATEST
INSTALLATION INSTRUCTIONS.
MC-3500 STORMWATER CHAMBER SPECIFICATIONS
THE DESIGN ENGINEER SHALL REVIEW THIS DRAWING PRIOR TO CONSTRUCTION.
IT IS THE ULTIMATE RESPONSIBILITY OF THE DESIGN ENGINEER TO ENSURE THAT
THE PRODUCT(S) DEPICTED AND ALL ASSOCIATED DETAILS MEET ALL APPLICABLE
LAWS, REGULATIONS, AND PROJECT REQUIREMENTS.
ADVANCED DRAINAGE SYSTEMS, INC.
70 INWOOD ROAD, SUITE 3 | ROCKY HILL, CT 06067
PHONE: 888-892-2694 | FAX: 866-328-8401
WWW.STORMTECH.COM
DRAWN BY:
SCALE:
DATE:
CHECKED:
STORMWATER CHAMBER SPECIFICATIONS
KLJ
NTS
3/29/10
NOTE: ALL DIMENSIONS ARE NOMINAL
NOMINAL MC-3500 CHAMBER SPECIFICATIONS
SIZE (L x W x H) 90" x 77" x 45" [2286 mm x 1956 mm x 1143 mm] CHAMBER STORAGE 113.0 ft³ [3.20 m³] MINIMUM INSTALLED STORAGE 176.8 ft³ [5.01 m³] WEIGHT 124 lbs. [56.2 kg]
PART# STUB B C
MC3500TEPE12T 12" [300 mm] 26.36" (670 mm) N/A MC3500TEPE12B 12" [300 mm] N/A 1.35" [34 mm] MC3500TEPE15T 15" [375 mm] 23.39" [594 mm] N/A MC3500TEPE15B 15" [375 mm] N/A 1.50" [38 mm] MC3500TEPE18T 18" [450 mm] 20.03" [509 mm] N/A MC3500TEPE18B 18" [450 mm] N/A 1.77" [45 mm]
24" TOP STUB CORED ENDCAP NOT AVAILABLE
MC3500TEPE24B 24" [600 mm] N/A 2.06" [52 mm]
NOMINAL MC-3500 END CAP SPECIFICATIONS
SIZE (L x W x H) 26.5" x 71" x 45.1" [673 mm x 1803 mm x 1145 mm] ENDCAP STORAGE 15.6 ft³ [0.44 m³] MINIMUM INSTALLED STORAGE 45.6 ft³ [1.29 m³] WEIGHT 43 lbs. [19.5 kg]
26.5" [673 mm]
22.6" [574 mm]
INSTALLED
45.1" [1145 mm]
71.0" [1803 mm]
77.0" [1956 mm]
45.0" [1143 mm]
HANDLE
SHELL
BUILD ROW IN THIS DIRECTION
90.0" [2286 mm]
CREST STIFFENING RIB
VALLEY STIFFENING RIB
VALLEY
CREST
LOWER JOINT
CORRUGATION
UPPER JOINT
CORRUGATION
WEB
HANDLING PORT
(4 LOCATIONS)
FOOT
86.0" [2184 mm] INSTALLED
STORMTECH INVENTORIED MANIFOLDS AND PRECORED END CAPS INCLUDE
24" [600 MM] BOTTOM (MC3500TEPE24B), 18" [450 MM] BOTTOM (MC3500TEPE18B)
AND 15" [375 MM] TOP (MC3500TEPE15T). OTHER PIPE SIZES AND PRECORED
END CAPS ARE AVAILABLE UPON SPECIAL ORDER.
PART NUMBERS ENDING WITH "B" ARE FOR STUBS AT BOTTOM OF END CAP.
PART NUMBERS ENDING WITH "T" ARE FOR STUBS AT TOP OF END CAP.
A
B
A
C
THE DESIGN ENGINEER SHALL REVIEW THIS DRAWING PRIOR TO CONSTRUCTION.
IT IS THE ULTIMATE RESPONSIBILITY OF THE DESIGN ENGINEER TO ENSURE THAT
THE PRODUCT(S) DEPICTED AND ALL ASSOCIATED DETAILS MEET ALL APPLICABLE
LAWS, REGULATIONS, AND PROJECT REQUIREMENTS.
ADVANCED DRAINAGE SYSTEMS, INC.
70 INWOOD ROAD, SUITE 3 | ROCKY HILL, CT 06067
PHONE: 888-892-2694 | FAX: 866-328-8401
WWW.STORMTECH.COM
DRAWN BY:
SCALE:
DATE:
CHECKED:
MC-3500 TECHNICAL SPECIFICATIONS
KLJ
NTS
3/29/10
STORMTECH GENERAL NOTES
1. STORMTECH LLC ("STORMTECH") REQUIRES INSTALLING
CONTRACTORS TO USE AND UNDERSTAND STORMTECH'S
LATEST MC-3500 INSTALLATION INSTRUCTIONS PRIOR TO
BEGINNING SYSTEM INSTALLATION.
2. STORMTECH OFFERS INSTALLATION CONSULTATIONS TO
INSTALLING CONTRACTORS. CONTACT OUR TECHNICAL
SERVICE DEPARTMENT OR LOCAL STORMTECH
REPRESENTATIVE AT LEAST 30 DAYS PRIOR TO SYSTEM
INSTALLATION TO ARRANGE A PRE-INSTALLATION
CONSULTATION. OUR REPRESENTATIVES CAN THEN ANSWER
QUESTIONS OR ADDRESS COMMENTS ON THE STORMTECH
CHAMBER SYSTEM AND INFORM THE INSTALLING CONTRACTOR
OF THE MINIMUM INSTALLATION REQUIREMENTS BEFORE
BEGINNING THE SYSTEM'S CONSTRUCTION. CALL 860-529-8188
TO SPEAK TO A TECHNICAL SERVICE REPRESENTATIVE OR VISIT
WWW.STORMTECH.COM TO RECEIVE A COPY OF OUR
INSTALLATION INSTRUCTIONS.
3. STORMTECH REQUIREMENTS FOR SYSTEMS WITH PAVEMENT
DESIGN (ASPHALT, CONCRETE PAVERS, ETC.): MINIMUM COVER
IS 24" [610 mm] NOT INCLUDING PAVEMENT; MAXIMUM COVER IS 6.5' [1.98 m] INCLUDING PAVEMENT. FOR INSTALLATIONS THAT
DO NOT INCLUDE PAVEMENT, WHERE RUTTING FROM VEHICLES
MAY OCCUR, MINIMUM REQUIRED COVER IS 30" [762 mm], MAXIMUM COVER IS 6.5' [1.98 m].
4. THE CONTRACTOR MUST REPORT ANY DISCREPANCIES WITH
THE BEARING CAPACITY OF THE CHAMBER FOUNDATION
MATERIALS TO THE DESIGN ENGINEER.
5. AASHTO M288 CLASS 2 NON-WOVEN GEOTEXTILE (FILTER
FABRIC) MUST BE USED AS INDICATED IN THE PROJECT PLANS.
6. STONE PLACEMENT BETWEEN CHAMBERS ROWS AND AROUND
PERIMETER MUST FOLLOW INSTRUCTIONS AS INDICATED IN THE
MOST CURRENT VERSION OF STORMTECH MC-3500
INSTALLATION INSTRUCTIONS.
7. BACKFILLING OVER THE CHAMBERS MUST FOLLOW
REQUIREMENTS AS INDICATED IN THE MOST CURRENT VERSION
OF STORMTECH MC-3500 INSTALLATION INSTRUCTIONS.
8. THE CONTRACTOR MUST REFER TO STORMTECH MC-3500
INSTALLATION INSTRUCTIONS FOR A TABLE OF ACCEPTABLE
VEHICLE LOADS AT VARIOUS DEPTHS OF COVER. THIS
INFORMATION IS ALSO AVAILABLE ON THE STORMTECH
WEBSITE: WWW.STORMTECH.COM . THE CONTRACTOR IS
RESPONSIBLE FOR PREVENTING VEHICLES THAT EXCEED
STORMTECH REQUIREMENTS FROM TRAVELING ACROSS OR
PARKING OVER THE STORMWATER SYSTEM. TEMPORARY
FENCING, WARNING TAPE AND APPROPRIATELY LOCATED SIGNS
ARE COMMONLY USED TO PREVENT UNAUTHORIZED VEHICLES
FROM ENTERING SENSITIVE CONSTRUCTION AREAS.
9. THE CONTRACTOR MUST APPLY EROSION AND SEDIMENT
CONTROL MEASURES TO PROTECT THE STORMWATER SYSTEM
DURING ALL PHASES OF SITE CONSTRUCTION PER LOCAL
CODES AND DESIGN ENGINEER'S SPECIFICATIONS.
10. STORMTECH PRODUCT WARRANTY IS LIMITED. CONTACT
STORMTECH FOR WARRANTY INFORMATION.
DRAWN BY:
SCALE:
DATE:
CHECKED:
THE DESIGN ENGINEER SHALL REVIEW THIS DRAWING PRIOR TO
CONSTRUCTION. IT IS THE ULTIMATE RESPONSIBILITY OF THE DESIGN
ENGINEER TO ENSURE THAT THE PRODUCT(S) DEPICTED AND ALL
ASSOCIATED DETAILS MEET ALL APPLICABLE LAWS, REGULATIONS, AND
PROJECT REQUIREMENTS.ADVANCED DRAINAGE SYSTEMS, INC.
70 INWOOD ROAD, SUITE 3 | ROCKY HILL, CT 06067
PHONE: 888-892-2694 | FAX: 866-328-8401
WWW.STORMTECH.COM
STORMTECH GENERAL NOTES
NTS
3/29/10
KLJ
FILL MATERIAL FOR LAYER 'D' STARTS FROM THE
TOP OF THE 'C' LAYER TO THE BOTTOM OF
FLEXIBLE PAVEMENT OR UNPAVED FINISHED
GRADE ABOVE. NOTE THAT PAVEMENT SUBBASE
MAY BE PART OF THE 'D' LAYER.
FILL MATERIAL FOR LAYER 'C' STARTS FROM THE
TOP OF THE EMBEDMENT STONE ('B' LAYER) TO
24" [610 mm] ABOVE THE TOP OF THE CHAMBER.
NOTE THAT PAVEMENT SUBBASE MAY BE A PART
OF THIS LAYER.
EMBEDMENT STONE SURROUNDING THE
CHAMBERS FROM THE FOUNDATION STONE
TO THE 'C' LAYER ABOVE.
FOUNDATION STONE BELOW CHAMBERS FROM
THE SUBGRADE UP TO THE FOOT (BOTTOM) OF
THE CHAMBER.
ANY SOIL/ROCK MATERIALS, NATIVE SOILS,
OR PER ENGINEER'S PLANS. CHECK PLANS
FOR PAVEMENT SUBGRADE REQUIREMENTS.
GRANULAR WELL-GRADED SOIL/AGGREGATE
MIXTURES, < 35% FINES. MOST PAVEMENT
SUBBASE MATERIALS CAN BE USED IN LIEU OF
THIS LAYER.
N/A
3, 357, 4, 467, 5, 56, 57, 6, 67, 68, 7, 78, 8, 89, 9, 10
3, 357, 4, 467, 5, 56, 57
3, 35, 4, 467, 5, 56, 57
PREPARE PER ENGINEER'S PLANS. PAVED
INSTALLATIONS MAY HAVE STRINGENT MATERIAL
AND PREPARATION REQUIREMENTS.
BEGIN COMPACTION AFTER 24" [610 mm] OF MATERIAL
OVER THE CHAMBERS IS REACHED. COMPACT ADD-
ITIONAL LAYERS IN 6" [152 mm] MAX LIFTS TO A MIN.
95% STANDARD PROCTOR DENSITY.
NO COMPACTION REQUIRED.
PLATE COMPACT OR ROLL TO ACHIEVE A 95%
STANDARD PROCTOR DENSITY ²
MATERIAL LOCATION DESCRIPTION COMPACTION/DENSITY REQUIREMENTAASHTO M43
DESIGNATION¹
PLEASE NOTE:
1. THE LISTED AASHTO DESIGNATIONS ARE FOR GRADATIONS ONLY. THE STONE MUST ALSO BE CLEAN, CRUSHED, ANGULAR. FOR EXAMPLE, A SPECIFICATION FOR #4 STONE WOULD STATE:
“CLEAN, CRUSHED, ANGULAR NO. 4 (AASHTO M43) STONE”.
2. AS AN ALTERNATE TO PROCTOR TESTING AND FIELD DENSITY MEASUREMENTS ON OPEN GRADED STONE, STORMTECH COMPACTION REQUIREMENTS ARE MET FOR 'A' LOCATION MATERIALS WHEN PLACED AND COMPACTED IN 9” [229 mm] (MAX) LIFTS USING TWO FULL COVERAGES WITH AN APPROPRIATE COMPACTOR.
ACCEPTABLE FILL MATERIALS: STORMTECH MC-3500 CHAMBER SYSTEMS
A
B
C
D
CLEAN, CRUSHED, ANGULAR STONE,
NOMINAL SIZE DISTRIBUTION BETWEEN
3/4 - 2 INCH [19 - 51 mm]
CLEAN, CRUSHED, ANGULAR STONE,
NOMINAL SIZE DISTRIBUTION BETWEEN
3/4 - 2 INCH [19 - 51 mm]
PAVEMENT AND SUBBASE DESIGN (BY
ENGINEER) MOST PAVEMENT SUBGRADE
MATERIALS CAN BE USED IN LIEU OF
REQUIREMENTS FOR LAYERS 'C' & 'D')
6" [152 mm] MIN. 77" [1956 mm] 12" [305 mm] MIN.
6.5' [1.98 m]
MAX.
12"
45" [1143 mm]
ONCE LAYER 'C' IS PLACED ANY
SOIL/MATERIAL CAN BE PLACED IN
LAYER 'D' UP TO THE FINISHED
GRADE. MOST PAVEMENT
SUBBASE SOILS CAN BE USED TO
REPLACE THE MATERIALS
REQUIREMENTS OF LAYERS 'C'
OR 'D' AT THE DESIGN
ENGINEER'S DISCRETION.
24" [610 mm]
MIN.*
ADS 601 NON-WOVEN
GEOTEXTILE (OR EQUAL) ALL
AROUND ANGULAR STONE
DRAWN BY:
SCALE:
DATE:
CHECKED:
THE DESIGN ENGINEER SHALL REVIEW THIS DRAWING PRIOR TO
CONSTRUCTION. IT IS THE ULTIMATE RESPONSIBILITY OF THE DESIGN
ENGINEER TO ENSURE THAT THE PRODUCT(S) DEPICTED AND ALL
ASSOCIATED DETAILS MEET ALL APPLICABLE LAWS, REGULATIONS, AND
PROJECT REQUIREMENTS.ADVANCED DRAINAGE SYSTEMS, INC.
70 INWOOD ROAD, SUITE 3 | ROCKY HILL, CT 06067
PHONE: 888-892-2694 | FAX: 866-328-8401
WWW.STORMTECH.COM
STORMTECH MC-3500 ACCEPTABLE FILL
NTS
09/22/10
KLJ
*TO BOTTOM OF FLEXIBLE PAVEMENT.
FOR UNPAVED INSTALLATIONS, WHERE
RUTTING FROM VEHICLES MAY OCCUR,
INCREASE COVER TO 30" [762 mm].
DRAWN BY:
SCALE:
DATE:
CHECKED:
THE DESIGN ENGINEER SHALL REVIEW THIS DRAWING PRIOR TO
CONSTRUCTION. IT IS THE ULTIMATE RESPONSIBILITY OF THE DESIGN
ENGINEER TO ENSURE THAT THE PRODUCT(S) DEPICTED AND ALL
ASSOCIATED DETAILS MEET ALL APPLICABLE LAWS, REGULATIONS, AND
PROJECT REQUIREMENTS.ADVANCED DRAINAGE SYSTEMS, INC.
70 INWOOD ROAD, SUITE 3 | ROCKY HILL, CT 06067
PHONE: 888-892-2694 | FAX: 866-328-8401
WWW.STORMTECH.COM
MC-3500 TYPICAL CROSS-SECTION
NTS
09/22/10
KLJ
DESIGN ENGINEER RESPONSIBLE FOR
ENSURING THE REQUIRED BEARING
CAPACITY OF SUBGRADE SOILS
GRANULAR WELL GRADED SOIL/AGGREGATE MIXTURES,
<35% FINES. COMPACT IN 6" [152 mm] LIFTS TO 95%
STANDARD PROCTOR DENSITY. SEE THE TABLE OF
ACCEPTABLE FILL MATERIALS
PAVEMENT DESIGN (PER
ENGINEER'S DRAWINGS)
ADS 601 NON-WOVEN
GEOTEXTILE (OR EQUAL) ALL
AROUND ANGULAR STONE
NOMINAL 3/4 - 2 INCH [19 mm - 51 mm]
CLEAN, CRUSHED, ANGULAR STONE
THE INSTALLED CHAMBER SYSTEM SHALL PROVIDE THE
LOAD FACTORS SPECIFIED IN THE AASHTO LRFD BRIDGE
DESIGN SPECIFICATIONS SECTION 12.12 FOR EARTH AND
LIVE LOADS, WITH CONSIDERATION FOR IMPACT AND
MULTIPLE VEHICLE PRESENCES.
6" [152 mm] MIN. 77" [1956 mm] 12" [305 mm] MIN.
45" [1143 mm]
MC-3500 ENDCAP
6.5' [1.98 m]
MAX.
MC-3500 CHAMBER
*TO BASE OF FLEXIBLE PAVEMENT.
FOR UNPAVED INSTALLATIONS, WHERE RUTTING FROM
VEHICLES MAY OCCUR, INCREASE COVER TO 30" [762 mm].
16"
6" MIN.
[152 mm]
CHAMBERS SHALL MEET ASTM F 2418 "STANDARD
SPECIFICATION FOR POLYPROPYLENE (PP) CORRUGATED
WALL STORMWATER COLLECTION CHAMBERS"
DRAWN BY:
SCALE:
DATE:
CHECKED:
THE DESIGN ENGINEER SHALL REVIEW THIS DRAWING PRIOR TO
CONSTRUCTION. IT IS THE ULTIMATE RESPONSIBILITY OF THE DESIGN
ENGINEER TO ENSURE THAT THE PRODUCT(S) DEPICTED AND ALL
ASSOCIATED DETAILS MEET ALL APPLICABLE LAWS, REGULATIONS, AND
PROJECT REQUIREMENTS.ADVANCED DRAINAGE SYSTEMS, INC.
70 INWOOD ROAD, SUITE 3 | ROCKY HILL, CT 06067
PHONE: 888-892-2694 | FAX: 866-328-8401
WWW.STORMTECH.COM
MC-3500 ISOLATOR ROW PROFILE
NTS
6/15/11
KLJ
SUMP DEPTH
TBD BY
DESIGN ENGINEER
CATCH
BASIN
OR
MANHOLE
24" [600 mm] HDPE ACCESS PIPE REQUIRED.
USE FACTORY PRE-CORED END CAPS.
2 LAYERS OF ADS 315ST WOVEN GEOTEXTILE
BETWEEN FOUNDATION STONE AND CHAMBERS.
MC-3500 - 8.25' [2.51 m] WIDE STRIPS
MC-3500 END CAP
COVER ENTIRE ROW WITH ADS 601
NON-WOVEN GEOTEXTILE (OR EQUAL)
MC-3500 - 12.5' [3.81 m] WIDE STRIP
NOTE: FOR MANY APPLICATIONS, THE ADS 601 NON-WOVEN GEOTEXTILE OVER THE MC-3500 CHAMBERS CAN BE ELIMINATED OR SUBSTITUTED WITH ADS 315ST WOVEN GEOTEXTILE. CONTACT YOUR STORMTECH REPRESENTATIVE FOR ASSISTANCE.
ELEV. 1036.00
ELEV. 1036.75
ELEV. 1041.83
9"
NOTE
DETAILS SHOWN ARE FOR THE ADS STORMTECH © SYSTEM TO
PROVIDE A BASIS FOR COMPARISON TO OTHER SYSTEMS.
SUBMIT OTHER SYSTEMS FOR APPROVAL PRIOR TO
SUBMITTING A BID.
9"
CES CONSULTANTS, LLC
CIVIL ENGINEERING
201 West Travelers Trail, Suite 200 Burn sville, MN 55337
763-274-4405 www.cesminn.com
St. Cloud VA Health Care System
01-03-2013
CONSTRUCTION DOCUMENTS
REHABILITATION CENTER
656-332
24" [610 mm]
MIN.*
ADDENDUM NO. 1 08/16/131
RECORD SET 09/30/162
http://WWW.STORMTECH.COM/ http://WWW.STORMTECH.COM/ http://WWW.STORMTECH.COM/ http://WWW.STORMTECH.COM/ http://WWW.STORMTECH.COM/ http://WWW.STORMTECH.COM/ http://WWW.STORMTECH.COM/ http://WWW.STORMTECH.COM/
ND
GENERAL STRUCTURAL NOTES
DESIGN CODES:
2007 MINNESOTA STATE BUILDING CODE (2006 IBC AS AMENDED)
ASCE 7--05 - MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER
STRUCTURES.
DESIGN LOADS:
50 PSF ------GROUND SNOW LOAD (P,I
C.= 1.0 Ct= 1.0 TYP. UNO
= 1.1 AT LINK LIGHT GAGE STEEL TRUSSES
= 1.2 AT CANOPY AND LIGHT GAGE STEEL
TRUSSES OVER PRECAST PLANK ROOF
I = 1.0
35 PSF -------ROOF SNOW LOAD TYP. UNO (PLUS SNOW
DRIFTING)
38.5 PSF ------ROOF SNOW LOAD AT LINK LIGHT GAGE STEEL
TRUSSES
42 PSF-------ROOF SNOW LOAD AT CANOPY AND LIGHT GAGE
STEEL TRUSSES OVER PRECAST PLANK ROOF.
80 PSF ------ROOF LIVE LOAD (FUTURE SECOND FLOOR)
80 PSF ------FLOOR LIVE LOAD TYP. UNO
100 PSF ------FLOOR LIVE LOAD AT LOBBIES, STAIRS AND
CORRIDORS
125 PSF ------FLOOR LIVE LOAD AT MECHANICAL AND
STORAGE ROOMS
90 MPH BASIC WIND SPEED (EXPOSURE C)
1.0 --------WIND IMPORTANCE FACTOR, I
0.18 INTERNAL PRESSURE COEFFICIENT
5000 PSF ALLOWABLE SOIL BEARING PRESSURE
48 PSF/FT. -----LATERAL (AT REST) SOIL EQUIVALENT FLUID
PRESSURE
NOTES:
1. IT IS THE CONTRACTOR"S SOLE RESPONSIBILITY TO DESIGN AND
PROVIDE ADEQUATE TEMPORARY SHORING AND LATERAL BRACING
FOR ALL STRUCTURAL ELEMENTS INCLUDING WALLS, COLUMNS,
BEAMS, LINTELS, ETC. FOR WIND, SOIL. AND CONSTRUCTION
LATERAL AND GRAVITY LOADS. THE BRACING MUST REMAIN IN
PLACE UNTIL PERMANENT STRUCTURAL SUPPORTS, INCLUDING
ROOF AND FLOOR DIAPHRAGMS. ARE INSTALLED AND HAVE
REACHED THEIR ALLOWABLE SERVICE STRESSES.
2. IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO ENSURE THAT
CONSTRUCTION CONFORMS TO THE LATEST OSHA SAFETY
REQUIREMENTS. NOTIFY THE ARCHITECT AND ENGINEER
IMMEDIATELY IF ANY REVISIONS ARE REQUIRED TO THE DRAWINGS
DUE TO OSHA SAFETY REQUIREMENTS.
3. GEOTECHNICAL ENGINEER SHALL FIELD VERIFY SOIL BEARING
CAPACITY. NOTIFY ARCHITECT AND ENGINEER IF ANY
DISCREPANCIES ARE FOUND.
4. THIS PROJECT IS DESIGNED FOR A FUTURE SECOND FLOOR. SEE
DESIGN LOADS ABOVE.
SUBMITTALS:
ALL SUBMITTED STRUCTURAL SHOP DRAWINGS WILL BE REVIEWED FOR
GENERAL CONFORMANCE WITH THE INFORMATION GIVEN AND DESIGN
CONCEPTS EXPRESSED IN THE CONTRACT DOCUMENTS. REVIEW OF
SUCH SUBMITTALS IS NOT CONDUCTED FOR THE PURPOSE OF
DETERMINING THE ACCURACY AND COMPLETENESS OF DETAILS SUCH
AS DIMENSIONS AND QUANTITIES AS REQUIRED BY THE CONTRACT
DOCUMENTS.
NEW CONST. IN CONJUNCTION WI EXIST. STRUCTURE:
1. THE CONTRACTOR SHALL FIELD VERIFY ALL SIZES, DIMENSIONS,
ELEVATIONS, LOCATIONS. ETC. OF ELEMENTS OF THE EXISTING
CONSTRUCTION RELEVANT TO NEW CONSTRUCTION.
2. ALL DIMENSIONS INVOLVING NEW CONSTRUCTION ADJACENT TO OR
GOVERNED BY EXISTING CONSTRUCTION SHALL BE FIELD CHECKED
BY THE CONTRACTOR AND NOTED ON THE FIRST SHOP DRAWING
SUBMITTED.
3. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT/ENGINEER
IMMEDIATELY OF ANY DISCREPANCIES BETWEEN CONSTRUCTION
DOCUMENTS AND ACTUAL FIELD CONDITIONS.
4. ALL HOLES THROUGH EXIST. CONSTRUCTION MUST BE CORE
DRILLED OR SAW CUT. DO NOT OVERCUT WHEN SAW CUTTING.
5. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE PROTECTION
OF THE EXISTING BUILDING DURING ALL PHASES OF
CONSTRUCTION.
SOILS AND FOUNDATIONS:
1. FOUNDATIONS, BASEMENT WALLS, SLABS ON GRADE AND OTHER
ITEMS RELATED TO THE SOILS ARE DESIGNED AND SHALL BE
CONSTRUCTED IN ACCORDANCE WITH THE RECOMMENDATIONS OF
NORTHERN TECHNOLOGIES, INC.- GEOTECHNICAL EVALUATION
REPORT NO. 11.50654.100 DATED AUGUST 24, 2011.
2. MINIMUM DEPTH FROM EXTERIOR GRADE TO BOTTOM OF BUILDING
PERIMETER FOOTINGS SHALL BE 42".
3. MINIMUM DEPTH FROM EXTERIOR GRADE TO BOTTOM OF FOOTINGS
AT UNHEATED STRUCTURES SHALL BE 80"'.
4. ALL FOOTINGS ARE CENTERED UNDER WALLS, PILASTERS AND
COLUMNS ABOVE UNO.
5. ALL FOUNDATION WALLS SHALL BE LATERALLY BRACED BEFORE
BACKFILLING AND COMPACTING.
6. DO NOT BACKFILL AROUND STEEL COLUMNS UNTIL CORROSION
RESISTANT ASPHAL TIC COATING HAS BEEN INSTALLED BY THE
STRUCTURAL STEEL ERECTOR
7. COORDINATE ALL UNDERGROUND PIPING OR DUCTWORK
LOCATIONS AND ELEVATIONS WITH THE MECHANICAL CONTRACTOR.
ADJUST FOOTING ELEVATIONS AND PROVIDE SLEEVES PER WALL
FOOTING AT UNDERGROUND LINES DETAIL. FOR PIPING OR
DUCTWORK PARALLEL TO FOOTING. BOTTOM OF FOOTING
ELEVATION SHOULD BE NO HIGHER THAN TI,E PIPE OR DUCTWORK
INVERT ELEVATION PLUS THE HORIZONTAL DISTANCE BETWEEN
EDGE OF FOOTING AND EDGE OF PIPING OR DUCTWORK.
CONTRACTOR SHALL NOTIFY ARCHITECT & ENGINEER FOR
APPROVAL OF ANY DEVIATIONS PRIOR TO COMMENCING WORK
RECORD SET 9/30/H
Horty
CAST-IN-PLACE CONCRETE:
1. DESIGN CODE: IBC CHAPTER 19 &ACI 318-05. BUILDING CODE
REQUIREMENTS FOR STRUCTURAL CONCRETE & ACI DETAILING
MANUALS LATEST EDITION.
2. MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS:
TYPE STRENGTH LOCATION
A-- f'c = 3000 PSI -- MASONRY CORE FILL AND BOND BEAMS W/ ~'ii" MAX. AGGREGATE
SIZE AND 8" TO 11• SLUMP.
B f 'c = 4000 PSI INTERIOR SLABS ON GRADE W/ ti"
MAX. AGGREGATE SIZE AND 3" TO
5"SLUMP.
C f 'c = 3000 PSI FOOTINGS
D f 'c = 4000 PSI PIERS, FOUNDATION WALLS AND
COLUMNS
E -- f'c = 4000 PSI -- EXPOSED EXTERIOR CONCRETE
AIR ENTRAINED 6% ± 1%
F -- f'c = 4000 PSI -- CONCRETE TOPPING OVER STEEL
DECK OR PRECAST STRUCTURAL
SYSTEMS.
G f 'c = 4000 PSI ALL OTHER CONCRETE W/ %." MAX.
AGGREGATE SIZE.
3. REINFORCING STEEL PROPERTIES:
A. DEFORMED BARS -ASTM A615 GRADE 60 UNO. USE ASTM
A706 GRADE 60 FOR WELDABLE REBAR.
B. WELDED WIRE FABRIC -ASTM A185.
4. ALL REINFORCING SHALL BE DETAILED. FABRICATED AND PLACED IN
ACCORDANCE WITH THE LATEST ACI MANUALS.
5. SHOP DRAWINGS FOR REINFORCING STEEL AND CONCRETE MIX
DESIGNS SHALL BE SUBMITTED FOR APPROVAL.
6. PLACE ALL ITEMS PER APPROVED SHOP DRAWINGS AND APPROVED
MIX DESIGNS.
7. PROVIDE ALL ACCESSORIES, CHAIRS, SPACER BARS AND SUPPORTS
NECESSARY TO SECURE REINFORCING PER "ACI DETAILING
MANUAL." NO OTHER METHODS OR MATERIALS WILL BE ACCEPTABLE.
8. PROVIDE PLASTIC CHAIRS AND SUPPORTS IN ALL AREAS OF
EXPOSED CONCRETE.
9. PROVIDE MINIMUM CONCRETE COVER FOR ALL REINFORCING AS
FOLLOWS UNO:
A. CONCRETE CAST AGAINST AND
PERMANENTLY EXPOSED TO EARTH. --- 3'"
B. CONCRETE EXPOSED TO EARTH OR
WEATHER: #6 THROUGH #18 BARS---- 2"'
#5 BARS AND SMALLER 111/
C. CONCRETE NOT EXPOSED TO WEATHER
OR IN CONTACT WITH GROUND:
SLABS, WALLS, JOISTS:
#14AND#18BARS 11'::!"
#11 BARS AND SMALLER --- 3//
BEAMS. COLUMNS:
PRIMARY REINFORCEMENT.
TIES, STIRRUPS, SPIRALS 1 1/" ,,
10. PROVIDE 6x6-W1.4xW1.4 WWF IN ALL INTERIOR AND EXTERIOR
SLABS ON GRADE UNO.
11. PROVIDE 100% VIRGIN POLYPROPYLENE FIBER REINFORCING IN ALL
TOPPING OVER PRECAST PLANK UNO (FIBERMESH 300. GENESIS
FIBER, MASTER FIBER F70 OR APPROVED EQUAL).
12. PROVIDE FOOTING DOWELS FOR CONCRETE OR MASONRY WALLS
AND COLUMNS. DOWELS SHALL BE SAME SIZE AND SPACING AS
WALL AND COLUMN VERTICAL REINFORCING AND SHALL PROJECT
FROM FOOTINGS TO PROVIDE LAP SPLICES AS INDICATED BELOW
OR IN THE MASONRY NOTES. PROVIDE 90 DEGREE STANDARD HOOK
IN COLUMN AND FREE STANDING WALL FOOTING DOWELS UNO.
13. LAP SPLICES FOR ALL CONCRETE REINFORCING SHALL BE 36 BAR
DIAMETERS OR 24•, WHICHEVER IS GREATER, UNO ON PL.ANS.
14. PROVIDE MINIMUM CONCRETE WALL REINFORCING AS FOLLOWS
UNO:
WALL THICKNESS
6" ANDB"
10" 12" 14"
16" AND 18"
VERT. REINF. HORIZ. REINF.
#4@ 16" O.C. CTRD #4@ 12"' O.C. CTRD
#4@ 16"' O.C. EF #4@ 16'" O.C. EF
#4@ 12"' O.C. EF #4@ 12'" O.C. EF
#S@ 16" O.C. EF #4@ 12" O.C. EF
#S@ 16" O.C. EF #5@ 16" O.C. EF
15. PROVIDE EXTRA REINFORCING ON ALL SIDES OF ALL CONCRETE
WALL AND SLAB OPENINGS EQUAL TO ONE HALF THE INTERRUPTED
REINFORCING IN EACH DIRECTION. UNO ON THE DRAWINGS. A
MINIMUM OF 1-#5 SHALL BE PROVIDED FOR EACH LAYER OF
REINFORCEMENT. EXTEND BARS PAST EDGE OF OPENING THE LAP
SPLICE NOTED ABOVE. PROVIDE AN ADDITIONAL #4x4'-0" DIAGONAL
BAR AT EACH CORNER FOR EACH LAYER OF REINFORCING.
16. HOT WEATHER AND COLD WEATHER CONCRETE PROVISIONS OF ACI
305 AND ACI 306 SHALL BE FOLLOWED.
17. PROVIDE CONCRETE WALL VERTICAL CONTROL JOINTS AS FOLLOWS
UNO:
WALL THICKNESS MAX. CONTROL JOINT SPACING
8"-10" 12"-16.
Elving"'
24'-0" o.c.
30'-0" O.C.
Planning Architecture Engineering Interior Design Construction Management
505 East Grant Street, Minneapolis, MN 55404-1490 Design Build
REVISION DATE T 612.332-4422 F 612.344.1282 hortyelving.com Horty Elving & Associates, Inc.
PRECAST, PRESTRESSED CONCRETE:
1. DESIGN CODE: PRECAST PRESTRESSED CONCRETE SHALL BE
DESIGNED, FABRICATED AND ERECTED PER ACI 318--05. BUILDING
CODE REQUIREMENT FOR STRUCTURAL CONCRETE AND PCI DESIGN
HANDBOOK - PRECAST AND PRESTRESSED CONCRETE. LATEST
EDITION.
2.
3.
4, 5.
6.
PRECAST. PRESTRESSED CONCRETE SHALL BE DESIGNED.
FABRICATED AND ERECTED PERACI 318 AND PCI •DESIGN HANDBOOK
- PRECAST AND PRESTRESSED CONCRETE" LATEST EDITIONS.
PRECAST MANUFACTURER SHALL PROVIDE AND DESIGN FOR ALL
OPENINGS LARGER THAN 8" SQUARE OR 8" IN DIAMETER THRU ALL
PRECAST UNITS. THE MANUFACTURER SHALL DESIGN FOR ALL
OTHER SMALLER OPENINGS TO BE FIELD CUT BY THE TRADE
REQUIRING THEM. THE FIELD CUT OPENING SIZE AND LOCATION
MUST BE APPROVED BY THE PRECAST MANUFACTURER PRIOR TO
INSTALLATION. THE PRECAST MANUFACTURER SHALL VERIFY ALL
OPENING QUANTITIES. SIZES AND LOCATIONS WITH MECH .• ELEC.
AND ARCH. DRAWINGS AND ALL CONCERNED CONTRACTORS.
PRECAST MANUFACTURER SHALL DESIGN AND PROVIDE ALL
HEADERS AT OPENINGS THRU PRECAST UNITS. ADJACENT PRECAST
UNITS SHALL BE DESIGNED FOR HEADER LOADS.
ALL PRECAST UNITS SHALL BE POURED A MINIMUM OF 28 DAYS
PRIOR TO ERECTION.
PRECAST UNITS SHALL BE ERECTED SIMULTANEOUSLY ON EACH
SIDE OF ALL SUPPORTING BEAMS OR WALLS. THE BEAMS SHALL BE
BRACED TO PREVENT ROTATION UNTIL ALL OF THE PRECAST UNITS
ARE INSTALLED AND CONNECTED.
7. LIMIT CAMBER TO ONE HALF THE NORMAL CAMBER AT ALL PRECAST
UNITS ADJACENT AND PARALLEL TO EXTERIOR AND INTERIOR WALLS.
8. PRECAST MANUFACTURER SHALL SHOW ALL FIELD CONNECTION
REQUIREMENTS, INCLUDING WELDING ON THE SHOP DRAWINGS.
9. SEE ARCH. DRAWINGS AND DETAILS FOR ALL RECESSES OR FLOOR
SLOPES OVER PRECAST UNITS.
10. THE DESIGN OF ALL MEMBERS AND ELEMENTS SHOWN ON THE
DRAWINGS ARE FOR THE IN-PLACE COMPLETED BUILDING. ALL
LOADING CRITERIA AND VERIFICATION OF DESIGN FOR LOADING
SUCH AS STRIPPING, HANDLING. TRANSPORTATION AND ERECTION
ARE TI,E SOLE RESPONSIBILITY OF THE PRECAST SUPPLIER.
11. DESIGN DEVIATIONS WILL NOT BE PERMITTED WITHOUT THE
ARCHITECrs APPROVAL. DESIGN DEVIATIONS SHALL BE SUBMITTED
WITH COMPLETE CALCULATIONS AND DRAWINGS CERTIFIED BY A
PROFESSIONAL ENGINEER REGISTERED IN THE STATE WHERE THE
PROJECT IS LOCATED. DESIGN DEVIATIONS SHALL PROVIDE AN
INSTALLATION EQUIVALENT TO THE ORIGINAL INTENT WITHOUT
INCURRING ADDITIONAL COST TO THE OWNER.
12. CONTRACT DRAWINGS INDICATE NOMINAL STRUCTURAL TOPPING
THICKNESS. THE PRECAST MANUFACTURER SHALL DESIGN THE
UNITS FOR THE ACTUAL TOPPING THICKNESS WHICH IS DETERMINED
BY THE UNITS CAMBER. FLOORS ARE POURED LEVEL UNO.
13. ROUGHEN SURFACES OF PRECAST UNITS TO RECEIVE A CONCRETE
TOPPING TO ENSURE A SUFFICIENT BOND FOR COMPOSITE ACTION
BETWEEN PRECAST AND TOPPING.
14. THE PRECAST MANUFACTURER SHALL DESIGN ALL PRECAST,
PRESTRESSED CONCRETE MEMBERS FOR ALL APPLICABLE GRAVITY.
SOIL AND WIND LOADS INDICATED ON THE DRAWINGS. IN ADDITION,
THE PRECAST MANUFACTURER SHALL DESIGN THE FOLLOWING:
A. ALL EMBEDDED ITEMS IN PRECAST UNITS SUCH AS PLATES.
ANCHORS. ETC.
B. LOOSE SHEAR PLATES STRUCTURALLY ATTACHED TO
EMBEDDED ITEMS IN PRECAST UNITS.
PRECAST MANUFACTURER SHALL SUPPLY ALL ABOVE LISTED ITEMS
AND COORDINATE LOCATIONS WITH ALL CONCERNED CONTRACTORS.
15. SUBMIT SHOP DRAWINGS AND DESIGN CALCULATIONS CERTIFIED BY
A PROFESSIONAL ENGINEER REGISTERED IN THE STATE WHERE THE
PROJECT IS LOCATED.
MASONRY:
1. DESIGN CODES: IBC CHAPTER 21 & ACI 530-05. MSJC-BUILDING CODE
REQUIREMENTS AND SPECIFICATION FOR MASONRY STRUCTURES.
2. SEE ARCHITECTURAL DRAWINGS FOR MASONRY WALL FIRE RATINGS.
3. HOLLOW CONCRETE MASONRY UNITS SHALL BE NORMAL WEIGHT
UNITS PER ASTM C90 REQUIREMENTS. F'm = 2000 PSI.
4. ALL MORTAR FOR LOAD BEARING WALLS BELOW GRADE SHALL BE
TYPE 'M' MORTAR. MORTAR FOR LOAD BEARING WALLS ABOVE
GRADE SHALL BE TYPE'S'. TYPE "N" MORTAR WILL BE ALLOWED FOR
INTERIOR ABOVE GRADE NON-LOAD BEARING PARTITIONS.
5. MORTAR PER ASTM C270. MINIMUM 28 DAY COMPRESSIVE
STRENGTH: TYPE 'M' = 2500 PSI., TYPE'S'= 1800 PSI., TYPE 'N' = 750
PSI.
6. COARSE GROUT PER ASTM C476. MINIMUM 28 DAY COMPRESSIVE
STRENGTH = 3000 PSI. NO GROUT IS TO BE HAND MIXED ON SITE.
7. WHEN REQUIRED BY THE ARCHITECT, ENGINEER, OR BUILDING
OFFICIAL, MASONRY COMPRESSIVE STRENGTH SHALL BE TESTED
PER IBC 2105.3.
8. MASONRY CEMENT SHALL NOT BE USED IN MORTAR OR GROUT.
9. REINFORCING STEEL:
A. DEFORMED BARS: ASTM GRADE 60.
B. JOINT REINFORCEMENT: ASTM A82.
10. SUBMIT MORTAR AND GROUT DESIGN MIXES FOR APPROVAL.
11. SUBMIT SHOP DRAWINGS FOR REINFORCING STEEL.
12. PROVIDE MINIMUM 8" FULL DEPTH AND WIDTH BEARING FOR ALL
MASONRY LINTELS.
13. WIRE JOINT REINFORCING FOR CONCRETE BLOCK WALLS SHALL BE
STANDARD CORROSION RESISTANT 9 GAGE LADDER TYPE (PROVIDE
TRI-ROD LADDER FOR MUL Tl WYTHE WALLS). INSTALL JOINT
REINFORCING PER MANUFACTURER'S RECOMMENDATIONS AT A
MAXIMUM SPACING OF 16" O.C. UNO ON DRAWINGS OR PROJECT
SPECIFICATIONS.
14. INSTALL MASONRY VERTICAL AND HORIZONTAL REINFORCING PER
IBC REQUIREMENTS AND AS FOLLOWS:
A. SEE PLANS. DETAILS. AND SCHEDULES FOR REQUIRED
REINFORCING.
B. PROVIDE FULL MORTAR BEDDED FACE SHELLS AND WEBS
AROUND ALL GROUTED CELLS FOR BEARING AND TO
PREVENT LEAKAGE INTO ADJACENT CELLS.
C. PLACE VERTICAL REINFORCING PRIOR TO PLACING GROUT.
D. PROVIDE REINFORCEMENT POSITIONERS TO HOLD VERTICAL
REINFORCEMENT IN PROPER POSITION AT TOP AND BOTTOM OF
ALL LIFTS. LENGTI, OF REINFORCING BARS TO BE COORDINATED
WITH CONCRETE AND MASONRY CONTRACTORS.
E. GROUT ALL CORES CONTAINING REINFORCING SOLID.
F. MASONRY WALL CELLS TO BE GROUTED WITH CONCRETE
SHALL BE FILLED IN MAXIMUM 4'-0" LIFTS. REMOVE ALL
OVERHANGING OBSTRUCTIONS AND DEBRIS FROM THE
CELLS PRIOR TO GROUTING.
G. CONSOLIDATE ALL GROUT BY RODDING OR VIBRATING.
H. REINFORCEMENT SPLICES AT ALL FOOTING DOWELS,
VERTICAL WALL REINFORCING, HORIZONTAL WALL
REINFORCING, AND BOND BEAM REINFORCING SHALL BE A
MINIMUM OF 48 BAR DIAMETERS FOR TENSION SPLICES AND
48 BAR DIAMETERS FOR COMPRESSION SPLICES.
J. PROVIDE CORNER BAR WITH 2'-0" + 2'--0" LEGS FOR EACH
HORIZONTAL BOND BEAM BAR AT CORNERS AND
INTERSECTING WALLS.
15. PROVIDE CONTINUOUS BOND BEAMS WITH 2-#5 CONTINUOUS AT THE
TOP OF ALL BEARING AND END WALLS.
16. PROVIDE CONTINUOUS 811 HIGH x WALL THICKNESS BOND BEAM WITH
2-#5 CONTINUOUS AT ALL MASONRY WALL BRICK LEDGE ELEVATIONS.
17. GROUT SOLID BELOW ALL STEEL BEARINGS A MINIMUM OF FIVE
COURSES DOWN FOR 16" LENGTH OF WALL, UNO ON DRAWINGS. ALL
STEEL BEAMS SHALL BEAR A MINIMUM OF 8- ON SOLID GROUTED
MASONRY UNITS, UNO.
18. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SHORE AND
BRACE. AS NECESSARY. ALL BEAMS SUPPORTING MASONRY ABOVE
TO PREVENT MOVEMENT OF BEAMS DURING WALL CONSTRUCTION.
SHORING AND BRACING MAY BE REMOVED ONLY AFTER WALLS ARE
ATTACHED TO ROOF OR FLOOR STRUCTURE ABOVE.
19. STEEL BEAMS SUPPORTED ON MASONRY SHALL BEAR EACH END ON
h:" STEEL PLATE x 12• LONG x NOMINAL WALL WIDTH MINUS 2"WITH 2-%" DIAMETER x 5" LONG HEADED STUDS. FASTEN ONE END OF
BEAM TO PLATE WITH KEEPER BARS WHICH WILL PROVIDE LATERAL
SUPPORT FOR BEAM AND ALLOW LONGITUDINAL MOVEMENT. SEE
DRAWINGS FOR KEEPER BAR CONNECTION DETAILS.
20. INSTALL LINTELS FOR ALL MASONRY WALL OPENINGS AS FOLLOWS,
UNO ON PLANS, DETAILS, AND SCHEDULES:
A. PROVIDE ONE 8" HIGH COURSE LINTEL W/ 2-#5 BOTTOM FOR
ALL 2'-0" WIDE OR LESS OPENINGS IN LOAD BEARING
MASONRY WALLS AND ALL 4'--0" WIDE OR LESS OPENINGS IN
NON-LOAD BEARING MASONRY WALLS. PROVIDE TWO a•
HIGH COURSE LINTEL W/ 2-#5 BOTTOM FOR SPANS UP TO
6'-4" IN NON-LOAD BEARING WALL.
B. VERIFY SIZE AND LOCATIONS OF ALL MECHANICAL LOUVERS,
DUCTS, AND ALL OTHER OPENINGS WITH MECHANICAL
CONTRACTOR AND OTHER CONCERNED DISCIPLINES.
C. SEE PLANS, SCHEDULES, AND DETAILS FOR LINTEL TYPES
AND LOCATIONS. CONTACT ARCHITECT FOR LINTEL TYPE
AND SIZE FOR ALL REQ'D OPENINGS GREATER THAN 2'--0"
WIDE IN LOAD BEARING WALLS NOT SHOWN ON STRUCTURAL
PLANS. DETAILS AND SCHEDULES.
21. MASONRY VERTICAL CONTROL JOINTS:
A. COORDINATE JOINTS AND CONSTRUCTION DETAILS Wini
ARCHITECT. MAXIMUM SPACING IS 24'-0".
B. LOCATE JOINTS 2'-0" FROM ALL CORNERS AND EDGE OF ALL
OPENINGS EXCEPT AS NOTED PER SECTIONS AND DETAILS.
C. FOR LOAD BEARING MASONRY, CONTINUE BOND BEAM
REINFORCING AND GROUT THROUGH CONTROL JOINTS.
D. FORM CONTROL JOINTS IN BLOCK WITH JAMB BLOCK WITH
NEOPRENE INSERTS, OR ROD AND CAULK. CONTRACTOR
OPTION: USE STANDARD BLOCK, LINE ONE SIDE WITH
BUILDING PAPER, AND GROUT SOLID TO FORM KEYWAY.
E. PROVIDE CONTROL JOINTS AT INTERSECTIONS OF BEARING
AND NON-BEARING WALLS.
STEEL - STRUCTURAL:
1. DESIGN CODES: IBC CHAPTER 22 & AISC 360--05, SPECIFICATION FOR
STRUCTURAL STEEL BUILDINGS.
2. STEEL PROPERTIES:
A. ASTM A992 (f,=50 KSI) FOR WIDE FLANGE SHAPES B. ASTM A500 GRADE B (f,=46 KSI) FOR TUBULAR MEMBERS
C. ASTM A36 STEEL (1,=36 KSI) FOR ALL OTHER MEMBERS UNO
D. CONNECTION BOLTS= ASTM A325
E. WELDS= AMERICAN WELDING SOCIETY (AWS.J A5.1 OR A5.5 &
E70XX ELECTRODES
F. HEADED STUDS= ASTM A307
G. EXPANSION ANCHORS= HIL Tl KWIK BOLT 3 OR APPROVED EQUAL
3. PROVIDE CORROSION RESISTANT ASPHAL TIC COATING OR EQUAL
AROUND ALL STRUCTURAL STEEL BELOW GRADE.
4. ALL WELDS SHALL BE MADE BY CERTIFIED WELDERS AND IN
ACCORDANCE WITH AMERICAN WELDING SOCIETY (AWS.) - D1.1
LATEST EDITION.
5. STRUCTURAL STEEL FABRICATOR SHALL FURNISH ALL PLATES AND
ANGLES CAST IN CONCRETE AND MASONRY FOR CONNECTING
STEEL JOISTS, BEAMS, COLUMNS, DECK, ETC. UNO. SEE APPLICABLE
NOTES ON THIS SHEET AND COORDINATE WITH MASONRY AND
CONCRETE CONTRACTORS.
6. ALL STEEL BEAMS AND LINTELS TO BEAR A MINIMUM OF 8" UNO.
7. ALL COLUMN BASE AND CAP PLATES TO BE WELDED AROUND ALL
SIDES.
8. PRIME PAINT PER AISC SECTION 6.5, UNO ON ANY CONSTRUCTION
DOCUMENTS.
9. STRUCTURAL STEEL FABRICATOR SHALL SUBMIT SHOP DRAWINGS
FOR APPROVAL.
10. MISCELLANEOUS METALS SUPPLIER SHALL SUBMIT DRAWINGS AND
DESIGN CALCULATIONS FOR STAIR SYSTEMS, INCLUDING STAIRS.
STRINGERS, LANDINGS, RAILINGS AND CONNECTIONS. DESIGN
CALCULATIONS SHALL BE CERTIFIED BY A PROFESSIONAL ENGINEER
REGISTERED IN THE STATE WHERE THE PROJECT IS LOCATED.
11. PROVIDE BEAM CONNECTIONS AS SHOWN BELOW. ALTERNATE
CONNECTIONS WILL BE ALLOWED PROVIDED THAT CONNECTION
DESIGN CALCULATIONS, CERTIFIED BY A PROFESSIONAL ENGINEER
REGISTERED IN THE STATE WHERE THE PROJECT IS LOCATED, ARE
SUBMITTED BY THE FABRICATOR FOR REVIEW.
BOLTED/WELDED BEAM CONNECTION REQUIREMENTS
BEAM SIZE
NO. OF ~-:t0 H.S. CONN. ANGLES WELD
(A325N) BOLTS E.S. ITHICKNESS LENGTH SIZE
W36 10 ~-.:.• 2•-5J,;,• h" W33 9 ~.:.- 2•-2k• 1-'" 4 W30 8 3,-. 1'-111'2" 1/" ,, ,4
W27 7 3_,,. 1'-BJ-;:,• 1-'" Jo 4 W24 6 %· 1•-5%• ]/" ,4
W21 5 ~,,,. 1'-2%- )4" W18 4 %· o·-11h" 1/H ,4
W16 4 5/16" o·-11!--::." t,"
W14 3 5/16" 0'-81-:!" %" W12 3 5/16" 0'-8%" t," ,4
W10 2 5/16" 0'-5\i" 1'4'' W8 2 5/16" 0'-5%"
1,-11 ,4
W6 1 5/16" 0'-4" 3/16"
NOTES:1. USE E70XX ELECTRODES.
2. OUTSTANDING LEGS OF CONNECTION ANGLES MAY BE
REDUCED TO 3- WHEN BEAM FRAMES INTO W8 COLUMN
WEB.
3. SEE TABLE FOR CONNECTION ANGLES, NUMBER OF
BOLTS AND WELD SIZES.
4. BOLTS SHALL BE TIGHTENED IN PROPERLY ALIGNED
HOLES TO A SNUG-TIGHT CONDITION AS DEFINED BY THE
LA TEST EDITION OF AISC "SPECIFICATION FOR
STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS•
UNO.
I hemby certify that this plm, speclllcallon, or report was pmpsred by me er under my di-eel •upervlslon anti that I an a APPROVED: SERVICE LINE DIRECTOR duly lic:enlll!d Profeuicnal Engiieer under 1h11 laws of the Slab, cf MinnEcla.
Robert Hul!:hlnMn Rl!glll1mllon No. 26828
I APPROVED: GEMS COORDINATOR
I APPROVED: PROJECTS SECTION MANIU,ER
OCOl'YRIGHT This drawing Is lhe copflti,rte,d work prOliJct of Ardttect ind reue, modlflallan or reproduction ,;lthne d-1111 wltb1111t eipraa wrlfll=n c;anlelll of An:hlled la prohibited. The i11Chlle&tural or lellled Rnl= perftmned orfunnhed by the An:hbd forttk pnijel:I n I APPROVED: DIRECTOR FMS prvvldtd1ijijtd m th, i;a11!1and llilll or,1m1111y mrRIOd by 111111111111!1111"11111 tn:11111!:lural plllllnlon pm;tl;m11111dli'" almll1r i;i~._ at 1111 ..mt&n~ •rid ii lhl Afflf loc:dty. Archilltl m1ktt no vrel'l"llriiH, PprtN or ,.a;lld, ii comtetion with ill Hl'Yittl.
DATE:
STEEL - DECK:
1. DESIGN CODE: STEEL DECK INSTITUTE (SDI.): "DESIGN MANUAL FOR
COMPOSITE DECKS, FORM DECKS AND ROOF DECKS" LATEST EDITION.
2. STEEL DECK SHALL CONFORM TO ASTM A-611 ORA-448 AND HAVE A
MINIMUM YIELD STRENGTH OF 33,000 PSI. DECK SIZE. TYPE AND
GAUGE TO BE AS INDICATED ON PLANS.
3. FIELD WELD STEEL ROOF DECK AT CANOPY AND VESTIBULE TO ALL
INTERIOR STEEL SUPPORTS AS SHOWN ON PLANS. PROVIDE
WELDS@6" O.C. TO PLATE, ANGLE OR BEAM AT BUILDING
PERIMETER UNO. SI DELAP FASTENING SHALL BE AS INDICATED ON
PLANS.
4. SEE ROOF FRAMING PLAN NOTES FOR FASTENING REQUIREMENTS
FOR STEEL DECK OVER LIGHT GAGE STEEL ROOF TRUSSES.
5. SPAN DECK SECTION MINIMUM 3 SPANS CONTINUOUS. UNO.
6. THE STEEL DECK FABRICATOR SHALL SUBMIT SHOP DRAWINGS FOR
APPROVAL.
7. STEEL DECK TO BE SHOP PRIMED W/ STANDARD GREY PRIMER UNO.
ON ARCHITECTURAL DRAWINGS.
LIGHT GAGE STEEL TRUSSES:
1. DESIGN CODE: IBC CHAPTER 22, SECTION 2209-COLD FORMED
STEEL. SEE PLANS FOR SIZE AND GAUGE OF STUDS.
2. ALL STEEL STUDS SHALL BE DESIGNATED CSJ PER "DIETRICH
INDUSTRIES" OR EQUAL.
3. ALL STEEL STUD FASTENERS SHALL BE WELDED CONNECTIONS, OR
SHALL BE "TEKS" SCREWS, MANUFACTURED BY "ITW BUILDEX" OR
APPROVED EQUAL.
4. STUDS SHALL HAVE FULL BEARING AGAINST INSIDE TRACK WEB
PRIOR TO STUD AND TRACK ATTACHMENT.
5. ALL FRAMING COMPONENTS SHALL BE CUT SQUARELY FOR
ATTACHMENT TO PERPENDICULAR MEMBERS. MEMBERS SHALL BE
HELD POSITIVELY IN PLACE UNTIL PROPERLY FASTENED.
6. STUDS SHALL BE PLUMBED. ALIGNED AND SECURELY ATTACHED TO
THE FLANGE OR WEBS OF BOTH UPPER AND LOWER TRACKS.
7. SEE PLANS AND STEEL DECK NOTES FOR SHEATHING
REQUIREMENTS AND FASTENING.
8. TRUSS SYSTEM BRIDGING AND BRACING SHALL BE SPACED AND
CONNECTED ACCORDING TO THE CERTIFIED 054000 SHOP DRAWINGS.
9. CONTINUOUS BOTTOM RUNNER TRACK FOR ALL PITCHED ROOF
TRUSSES SHALL BE ANCHORED TO PRECAST ROOF PLANK WITH
POWER DRIVEN FASTENERS AS PER THE CERTIFIED 054000 SHOP
DRAWINGS. (MAXIMUM SPACING TO BE 16" O.C.)
10. THE INFORMATION SHOWN ON THE STRUCTURAL DRAWINGS IS
ONLY CONCEPTUAL AND IS INTENDED TO EXPRESS MINIMUM LIGHT
GAGE STEEL SYSTEM MATERIAL, DESIGN, AND CONSTRUCTION
PERFORMANCE CRITERIA. THE LIGHT GAGE STEEL TRUSS SUPPLIER
SHALL PROVIDE AND SUBMIT FOR APPROVAL THE FINAL
STRUCTURAL ENGINEERING DESIGN WHICH INCLUDES DETAILED
SHOP DRAWINGS AND CALCULATIONS OF THE MEMBER SIZES, GAGE
THICKNESS. SPACING, AND ALL CONNECTIONS. ALL SUBMITTALS
MUST BE CERTIFIED BY A PROFESSIONAL ENGINEER REGISTERED IN
THE STATE OF MINNESOTA.
SPECIAL INSPECTION AND TESTING:
1. SPECIAL INSPECTION AND TESTING IS REQUIRED IN ACCORDANCE
WITH THE LATEST EDITION OF IBC. CHAPTER 17. FOR THE FOLLOWING
PORTIONS OF CONSTRUCTION:
A. CONCRETE
B. CAST-IN-PLACE ANCHORS IN CONCRETE
C. POST-INSTALLED ANCHORS IN CONCRETE (PER PRODUCT
ICC-ESR REQUIREMENTS)
D. REINFORCING STEEL IN CONCRETE
E. CAST-IN-PLACE ANCHORS IN MASONRY
F. POST-INSTALLED ANCHORS IN MASONRY (PER PRODUCT
ICC-ESR REQUIREMENTS)
G. REINFORCING STEEL IN MASONRY - LEVEL 1
H. STRUCTURAL WELDING -VISUAL TESTING (UNO)
J. HIGH STRENGTH BOLTING
2. THE GENERAL CONTRACTOR SHALL SUBMIT A COMPLETED •SPECIAL
STRUCTURAL TESTING AND INSPECTION - PROGRAM SUMMARY
SCHEDULE" TO TI,E BUILDING OFFICIAL, ARCHITECT AND ENGINEER
PRIOR TO THE START OF CONSTRUCTION.
3. THE TESTING/INSPECTION AGENCY SHALL SUBMIT A FINAL
CERTIFIED REPORT AT SUBSTANTIAL COMPLETION. INDICATING
THAT ALL WORK REQUIRING SPECIAL INSPECTIONS AND TESTING
HAS BEEN CONSTRUCTED IN ACCORDANCE WITH THE CONTRACT
DOCUMENTS. A LIST OF ANY UNRESOLVED DEFICIENCIES SHALL BE
INCLUDED IN THIS REPORT.
APPROVED: INFECTION CONTROL NLRSE DATE: DRAWING TITLE
GENERAL
DATE: 11 APPROVED: PATIENT SAFETY DATIC I STRUCTURAL NOTES
DATE: 11 APPROVED: CHIEF OF Pct.ICE DATIC I I APPROVED: CHIEF OF STAFF DATIC I
DATE: 11 APPROVED: SAFETY MANAGER DATIC I I APPROVED: MEDICAL CENTER DIRECTOR DATIC I
STRUCTURAL ABBREVIATIONS
CL
A A.B.
A.D.
ADDM.
ADD'L.
ADJ.
A.F.F.
ALT.
APPROX.
ARCH.
B BROG.
BFE
BIT.
BLDG.
BLK.
BLKG.
BM.
BT.
BOT.
BRG.
BSMT.
BTWN.
C CANT.
C.I.P C.J.
CLR.
c.o.
COL.
COMB.
COMP.
CONG.
CONN.
CONST.
CONT.
CONTR.
CMU
COORD.
CTR.
CU. FT.
C.Y.
D TT, DBL TEE
DP.
DEPT.
DIAJ0
DIAG.
DIM.
DEAD LD., D.L.
DTL./DET.
DN.
DO.
DWG.
OWLS.
DR
E EA.
E.F.
EL.
ELEC.
ELEV.
ED .• =
EMBED.
EQUIP.
ERECT.
E.W.
EXIST.
EXP.
E.J., EXP. JT.
EXT.
F FAB.
FD
FON.
FIN.
FLR
FLG.
FP
FRMG.
FTG.
FFE
FT., I
FV
G GA.
GALV.
G.C.
GEN'L.
GLU-LAM, G.L.
GR BM.
H H. H.
HT.
HD.
HDR.
HK
HORIZ.
H.V.A.C.
I.E.
I.F.
IN.,•
INFO.
INSUL.
INT.
INV.
J JBE
JST.
JT .• JNT.
PROJECT TITLE
AND K K. KIPS
AT (CL TO CL SPACING) K.O. KNOCKOUT
CENTERLINE KSI KIPS PER SQUARE INCH
ROUND OR DIAMETER
POUND OR NUMBER L LB. OR# POUND (WEIGHT)
L.F. LINEAL FOOT
ANCHOR BOLT LG., LGT LENGTH, LONG
AREA DRAIN LIN. LINEAR
ADDENDUM LIVE LD., L.L. LIVE LOAD
ADDITIONAL LLH LONG LEG HORIZONTAL
ADJUST/ADJUSTABLE LLV LONG LEG VERTICAL
ABOVE FINISH FLOOR LOC. LOCATION OR LOCATE
ALTERNATE LONG. LONGITUDINAL
APPROXIMATE LT.WT. LIGHT WEIGHT
ARCHITECT/ARCHITECTURAL LD. LOAD
BRIDGING M MAN. MANUAL
BOTTOM FOOTING ELEVATION MAS. MASONRY
BITUMINOUS MAX. MAXIMUM
BUILDING MAT'L. MATERIAL
BLOCK MECH. MECHANICAL
BLOCKING MEMB. MEMBRANE
BEAM MTL. METAL
BENT MEZZ. MEZZANINE
BOTTOM MFR. MANUFACTURER
BEARING MIN. MINIMUM
BASEMENT MISC. MISCELLANEOUS
BETWEEN M.O. MECHANICAL OPENING
CANTILEVER N N.A. NOT APPLICABLE
CAST IN PLACE N.I.C. NOT IN CONTRACT
CONTROL JOINT NO .• # NUMBER
CLEAR NOM. NOMINAL
CLEAN OUT N.T.S. NOTTO SCALE
COLUMN
COMBINATION/COMBINED 0 o.c. ON CENTER
COMPOSITE O.F. OUTSIDE FACE
CONCRETE OD OVERFLOW DRAIN
CONNECT/-ED/-ION OPNG. OPENING
CONSTRUCT/-ION OPP. OPPOSITE
CONTINUE/-OUS/-ION O.H.DR OVERHEAD DOOR
CONTRACT/-OR
CONCRETE MASONRY UNIT p P&J PAN AND JOIST
COORDINATE PART. PARTITION
CENTER P/C PRECAST CONCRETE
CUBIC FEET PLBG. PLUMBING
CUBIC YARD PL. PLATE
PLF POUNDS PER LINEAR FOOT
DOUBLE TEE PNL. PANEL
DEPTH OR DEEP PRELIM. PRELIMINARY
DEPARTMENT PREP. PREPARATION
DIAMETER PROJ. PROJECTION
DIAGONAL PSF POUNDS PER SQUARE FOOT
DIMENSION PSI POUNDS PER SQUARE INCH
DEAD LOAD P.T. POST TENSION
DETAIL
DOWN Q QUAN.,QTY. QUANTITY
DITTO
DRAWING R R. RISER OR RADIUS
DOWELS RD ROOF DRAIN
DOOR REC. RECESSED
REF. REFERENCE
EACH REINF. REINFORCE/-ED/-ING
EACH FACE RET. RETAINING
ELEVATION REQ"D. REQUIRED
ELECTRICAL REV. REVISION
ELEVATOR R.O. ROUGH OPENING
EQUAL
EMBEDMENT.EMBEDDED s SCHED. SCHEDULE
EQUIPMENT SEC.,SECT. SECTION
ERECTION S.F., SQ. FT. SQUARE FOOT
EACH WAY SHT. SHEET
EXISTING SIM. SIMILAR
EXPANSION SJI STEEL JOIST INSTITUTE
EXPANSION JOINT SL SNOW LOAD
EXTERIOR SPA. SPACES
SPEC. SPECIFICATIONS
FABRICATE SQ. SQUARE
FLOOR DRAIN SQ.YD. SQUARE YARD
FOUNDATION STD. STANDARD
FINISH STIFF. STIFFENERS
FLOOR STL STEEL
FLANGE STIR. STIRRUPS
FIREPROOFING STL JST. STEEL JOIST
FRAMING STOR STORAGE
FOOTING STR,STRT. STRAIGHT
FINISH FLOOR ELEVATION STRUC(T). STRUCTURAL
FOOT SYM. SYMMETRICAL
FIELD VERIFY
T TBE TOP BEAM ELEVATION
GAUGE TGE TOP GIRDER ELEVATION
GALVANIZED T&B TOP AND BOTTOM
GENERAL CONTRACTOR TPE TOP OF PLANK ELEVATION
GENERAL TEMP. TEMPERATURE
GLUE LAMINATED WOOD THRU THROUGH
GRADE BEAM T&G TONGUE AND GROOVE
TRANS(V). TRANSVERSE
HIGH TSE TOP OF SLAB ELEVATION
HEIGHT TDE TOP STEEL DECK ELEVATION
HEADED TYP. TYPICAL
HEADER TFE TOP FOOTING ELEVATION
HOOK TWE TOP WALL ELEVATION
HORIZONTAL
HEATING, VENTILATION, u UNFIN. UNFINISHED
& AIR CONDITIONING UNO UNLESS NOTED OTHERWISE
INVERT ELEVATION V VERT. VERTICAL
INSIDE FACE
INCH/-ES WWI WITH
INFORMATION W,W. WIDE/WIDE FLANGE
INSULATION WD. WOOD
INTERIOR WOW. WINDOW
INVERT W/0 WITHOUT
W.PT.,WP WORK POINT
JOIST BEARING ELEVATION WT. WEIGHT
JOIST W.W.F. WELDED WIRE FABRIC
JOINT
STRUCTURAL DRAWING SHEET INDEX
S001 GENERAL STRUCTURAL NOTES
S101 LOWER LEVEL AND TRASH ENCLOSURE
FOUNDATION PLANS
S201 MAIN LEVEL FRAMING PLAN AND GENERATOR
BUILDING PLANS
S301 ROOF FRAMING PLAN
S401 SECTIONS AND DETAILS
S402 SECTIONS AND DETAILS
S403 SECTIONS AND DETAILS
DA TIC
I 01/03/2013
REHABILITATION CENTER PLOT SCALE
I St. Cloud VA PROJECT #656-332
St. Cloud VA Health Care System PROJECT NO.
S1430 Health Care System Brainerd I Montevideo I Alexandri a
BUILDING No CHECKED BY
~ 116 RSH M
LLC~I JLIN DRAWING NO.
I
VA MEDICAL CENTER S001 ST.CLOUD, MN 56303
4" CONC. SLAB ON GRADE
W/ 6x6-W1.4xW1.4 WWF
FFE=88'-0" (SEE MECH. FOR
CONC. PAD REQUIREMENTS)
T/O GRADE EL.
= 93'-0"
T/O GRADE EL.
= 91'-7"
T/O GRADE EL.= 91'-7"+/-
(MATCH EXIST.)
DRAIN TILE
D R
A
IN
T
ILE
D R
A
IN
T
ILE
DRAIN TILE
DRAIN TILE
D R
A
IN
T
IL
E
DRAIN TILE
DRAIN TILE
DRAIN TILE
D R
A
IN
T
IL
E
DRAIN TILE
DRAIN TILE
DRAIN TILE
C.O.
C.O.
C.O.
C.O.
C.O.
C.O. C.O.
C.O.
C.O.
C.O.
C.O.
C.O.
SEE 3/S401 FOR TYP.
CONTROL/CONST.
JT. DETAIL
S401
TYP. 2
LOC.
S401
SIM.
S S
SS
S S
S
S
S S
S S
S S
S S
11' - 4 1/2"
S401
SIM.
S401
S401
S401 8
S401
SIM.
SIM.
SIM.
S401
S401
S401
S401
S401 8
S401 8
S401
S401
S401
S401
S401
S401
S401
S401
S401
S401
S401
S401
S401
SIM.
SIM.
SIM.
SIM.
SIM.
SIM.
S401
SIM.
S401
SIM.
SIM.
SIM.
SIM.
SIM.
SIM.
SIM.
SIM. SIM.
S401SIM.
TYP.
S401
S401
S401
S401 9
S401
S401
S401
S401
S401
S401
S401
S401
TYP.
2 LOC.
SIM.
SIM.
SIM.
TYP.
SIM.
SIM.
SIM.
SIM.
OPP.
HAND
SIM.
TYP.
SIM.
TYP.
SIM.
TYP.
SIM.
SIM.
OPP.
HAND
SIM.
TYP.
SIM.
A
A
S
S
S
S
T F
E
'-0
TFE
88'-0"
TFE
87'-0"
T F
E
'-0
T F
E
'-0
TFE
87'-0"
T F
E
'-0
T F
E
'-0
T F
E
'-0
S
S
T F
E
'-0
SS
TFE
88'-0"
TFE
90'-0"
TFE
92'-0"
/2
1'
2'
1'
8"
S401
SIM.
S401
S401
SIM.
S401
S401SIM.
S401
S401
SIM.
SIM.
/4
2'
/4
5'
/2
8"
2'
8'
1"
2'
EXIST. PIPE
SPACE
FFE=91'-7"+/-
EXIST…