This document provides notification of an upcoming solicitation for Project 501-17-105: Upgrade Energy Plant Equipment Infrastructure at the New Mexico VA Healthcare System located in Albuquerque, New Mexico. The purpose of the project is to provide renovations, new construction, equipment replacements, and utility modifications to address deficiencies at Building 43, the Central Utility Plant, related to mechanical, plumbing, accessibility, electrical, life safety, structure, and cooling. The work includes general construction, alterations, mechanical and electrical work, utility systems, necessary demolition and removal of existing structures. The solicitation will be issued on or around July 15, 2023 via SAM.gov as a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses listed in VetCert with a NAICS code of 236220 and project value between $10-20 million. The point of contact is Maria Cruz-Thompson, Contracting Specialist, Network Contracting Office 22 who can be reached at maria.cruz-thompson@va.gov.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GG
LPLP
ELECTRICAL SYMBOL LEGEND
ELECTRICAL ABBREVIATIONS
A,2,a
LABEL LEGEND
A = TYPE
2 = BRANCH CIRCUIT NUMBER
a = SWITCH NUMBER OR 'NL' (NIGHT LIGHT)
TROFFER, REFER TO BRANCH POWER LEGEND FOR POWER SOURCE. TYPICAL
DOWNLIGHT, CEILING
DOWNLIGHT, WALL
GROUND/FLOOR
WALL WASHER
TRACK
STRIP
LINEAR
EMERGENCY LIGHTING UNIT, BATTERY PACK ON LIFE SAFETY/EMERGENCY POWER.
UON.
EXIT SIGNS, SINGLE FACE WITH DIRECTIONAL ARROWS AS INDICATED
EXIT SIGNS, DOUBLE FACE WITH DIRECTIONAL ARROWS AS INDICATED
POLE LIGHT, SINGLE HEAD.
POLE LIGHT, DOUBLE HEAD.
NOTES:
1. REFER TO FLOORPLANS AND ELECTRICAL SPECIFICATIONS FOR DEVICE/EQUIPMENT TYPES AND REQUIREMENTS.
2. NOT ALL SYMBOLS INDICATED APPLY TO THIS PROJECT.
3. DIMESIONS INDICATED ARE TO THE TOP OF DEVICE, UON.
NURSE CALL
D
O
O
L
L
SWITCHES
LIGHT SWITCH, SINGLE POLE, . ADJACENT TEXT INDICATES TYPE:
a = ID, LOWER CASE
2 = 2 POLE
3 = 3-WAY
4 = 4-WAY
A = TIMER
K = KEYED
P = PILOT LIGHT
M = MOMENTARY CONTACT
DIMMER SWITCH, WALL , .
OCCUPANCY SENSOR, WALL
OCCUPANCY SENSOR, CEILING
AMBIENT LIGHT LEVEL SENSOR, WALL
AMBIENT LIGHT LEVEL SENSOR,CEILING
LIGHTING CONTACTOR
PHOTOCELL
(WALL MOUNTED DEVICES MOUNTED 48" AFF TO TOP OF BOX, UON.)
(REFER TO THE LUMINAIRE SCHEDULE FOR TYPES AND REQUIREMENTS)
C
P
RECEPTACLES AND WIRING
(WALL MOUNTED DEVICES MOUNTED 18" AFF TO TOP, UON.)
DUPLEX RECEPTACLE, NORMAL & EMERGENCY
DUPLEX RECEPTACLE, 2" ABOVE BACKSPLASH. TYPICAL FOR ALL RECEPTACLES WITH
VERTICAL STRIKETHROUGH LINE.
DUPLEX - CEILING, NORMAL & EMERGENCY
DUPLEX - FLOOR, NORMAL & EMERGENCY. REFER TO FLOORPLANS FOR DEVICE TYPE.
DUPLEX RECEPTACLE - GFCI. NORMAL & EMERGENCY
DOUBLE DUPLEX, SINGLE BACKBOX
TWO DUPLEX RECEPTACLES, NORMAL AND EMERGENCY, INSTALLED IN SEPERATE
BACKBOXES AND A TWO GANG FACEPLATE
SIMPLEX
SPECIAL TYPE - WALL , NORMAL & EMERGENCY. NEMA CONFIGURATION PER
FLOORPLANS
SPECIAL TYPE - CEILING, NORMAL & EMERGENCY
FIXED EQUIPMENT CONNECTION - WALL, NORMAL & EMERGENCY
FIXED EQUIPMENT CONNECTION, NORMAL & EMERGENCY. LOCATION PER FLOORPLANS
PUSHBUTTON
SURFACE MOUNTED WIREWAY WITH RECEPTACLES LENGTH AS INDICATED ON
DRAWINGS, SPACING AS INDICATED:
A = 6" ON CENTER
B = 12" ON CENTER
C = 24" ON CENTER
JUNCTION BOX, FLUSH WALL
JUNCTION BOX - FLUSH MOUNTED
JUNCTION BOX, SURFACE MOUNTED
PANEL DIVISION ARROW
PANEL DIVISION LINE
HOMERUN, 2#12, 1#12G, 3/4"C. UNO.
LABEL INDICATES PANEL-CIRCUIT NO.'S
GROUNDING COUNTERPOISE WITH BOND, REFER TO SPECIFICATIONS FOR SIZE AND
BONDING REQUIREMENTS.
LIGHTNING PROTECTION PERIMETER CONDUCTOR, WITH BOND, REFER TO
SPECIFICATIONS FOR CONDUCTOR SIZE AND BONDING REQUIREMENTS.
BRANCH POWER LEGEND:
NORMAL
CRITICAL / EMERGENCY
LIFE SAFETY
LIGHTING
J
J
J
EQUIPMENT
PANELBOARD, SURFACE, NORMAL POWER
PANELBOARD, SURFACE, CRITICAL / EMERGENCY POWER - TYPICAL ALL EQUIPMENT
PANELBOARD, SURFACE, LIFE SAFETY - TYPICAL ALL EQUIPMENT
PANELBOARD, SURFACE, EQUIPMENT POWER - TYPICAL EQUIPMENT
PANELBOARD, SURFACE >42 CIRCUITS, SINGLE ENCLOSURE
PANELBOARD, FLUSH
CABINET, SURFACE, TYPE AS INDICATED ON FLOORPLANS
CABINET, FLUSH, TYPE AS INDICATED ON FLOORPLANS
SWITCHBOARD, MOTOR CONTROL CENTER OR AS INDICATED.
TRANSFORMER
NON-FUSED DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
BREAKER DISCONNECT SWITCH
MAGNETIC MOTOR STARTER
COMBINATION MOTOR STARTER
MANUAL STARTER W/THERMAL OVERLOADS
MOTOR
DISTRIBUTION EQUIPMENT LABELS
EXAMPLES:
8EPSB1A (BUILDING 8, EMERGENCY, 277/480V, SWITCHBOARD, LEVEL 1, SEQUENCE A)
8USS1A (BUILDING 8, NORMAL, OTHER VOLTAGE, UNIT SUBSTATION 1, LEVEL 1, SECTION A) 8SP1A(E) (BUILDING 8, LIFE SAFETY, 277/480V, PANELBOARD, LEVEL 1, SEQUENCE A, EXISTING)
8 = BUILDING NUMBER
E = SOURCE
BLANK = NORMAL
E = EMERGENCY
C = CRITICAL
S = LIFE SAFETY
Q = EQUIPMENT
U = UNINTERRUPTIBLE POWER SUPPLY
I = ISOLATION POWER (HEALTHCARE)
G = ISOLATED GROUND
P = VOLTAGE
BLANK = OTHER VOLTAGE, REFER TO ONE LINE DIAGRAM
L = 120/208V P = 277/480V
SB = EQUIPMENT TYPE
BLANK = BRANCH PANELBOARD
DP = DISTRIBUTION PANELBOARD
SB = SWITCHBOARD
SG = SWITCHGEAR
MC = MOTOR CONTROL CENTER
TX = TRANSFORMER
AT = AUTOMATIC TRANSFER SWITCH
BD = BUSDUCT
UP = UNINTERRUPTIBLE POWER SUPPLY
US = UNIT SUBSTATION
2 = FLOOR
A = SEQUENCE AND/OR SECTION (A,B,C, etc.)
(E) = EXISTING
F
B
T
T
ONE LINE DIAGRAM
MOLDED CASE CIRCUIT BREAKER
LOW VOLTAGE, DRAW OUT CIRCUIT BREAKER
DISCONNECT SWITCH
DISCONNECT SWITCH, DRAW OUT TYPE
FUSE
FUSE, DRAW OUT TYPE
MEDIUM VOLTAGE VACUUM BREAKER
MEDIUM VOLTAGE VACUUM BREAKER, DRAW OUT TYPE
MEDIUM VOLTAGE SWITCH
TRANSFORMER DELTA-WYE
TRANSFER SWITCH
BUSS DUCT
BUSS DUCT PLUG-IN UNIT
CURRENT TRANSFORMER
METER WITH CURRENT TRANSFORMER
PROTECTIVE RELAYS
MOTOR CONNECTION
GROUND
DIODE
N.O. CONTACT
N.C. CONTACT
INVERTER
VFD, BY DIVISION 23
KIRK KEY INTERLOCK
ELECTRICALLY OPERATED CIRCUIT BREAKER
PANELBOARD, NORMAL POWER
PANELBOARD, CRITICAL / EMERGENCY POWER
PANELBOARD, LIFE SAFETY POWER
PANELBOARD, EQUIPMENT POWER
ENGINE GENERATOR SET
ONE LINE DIAGRAM - FEEDER SIZE
M M
M
PNL
100A
PNL
100A
PNL
100A
PNL
100A
NCM
ANN
FIRE ALARM
F
FACP
FANN
H
S
B
R
FS
D
TS
MANUAL PULLSTATION
FIRE ALARM CONTROL PANEL, 6'-0" AFF TO TOP
FIRE ALARM REMOTE ANNUNCIATOR, 6'-0" AFF TO TOP
NACP, NOTIFICATION APPLIANCE POWER, 6'-0" AFF TO TOP
HEAT DETECTOR, CEILING
SMOKE DETECTOR, CEILING
BEAM TRANSMITTER, WALL 12" BELOW CEILING OBSTRUCTION
BEAM RECEIVER, WALL 12" BELOW CEILING OBSTRUCTION
MAGNETIC DOOR HOLDER, WALL. COORDINATE WITH DOOR HARDWARE.
ELECTRIC DOOR CLOSER. COORDINATE WITH DOOR OPENER.
FLOW SWITCH
TAMPER SWITCH
PRESSURE SWITCH
DUCT MOUNTED SMOKE DETECTOR. LABEL INDICATES 'S' SUPPLY OR 'R' RETURN AIR
SYSTEM.
SMOKE DAMPER
COMBINATION FIRE/SMOKE DAMPER
FIRE ALARM SPEAKER AND STROBE, CEILING OR WALL +82" AFF FLOOR NUMBER
INDICATES CANDELLA RATING.
FIRE ALARM CHIME AND STROBE, CEILING OR WALL +82" AFF FLOOR. NUMBER
INDICATES RATING.
FIRE ALARM STROBE, CEILING OR WALL +82" AFF FLOOR. NUMBER INDICATES
CANDELLA RATING.
NACP
F
F
PS
1H1A-2
J
COMMUNICATIONS / SECURITY
(WALL MOUNTED DEVICES MOUNTED 18" AFF TO TOP, UON.)
S
S
VOICE/DATA, WALL, NUMBER OF PORTS INDICATED
VOICE/DATA, FLOOR
PHONE
WALL PHONE, +48" AFF
CEILING SPEAKER
WALL SPEAKER, +80" AFF, UNO.
TELEPHONE TERMINAL CABINET
TELEPHONE TERMINAL BOARD
CARD READER
ELECTRIC STRIKE
DOOR CONTACT
REQUEST TO EXIT
DOOR OPENER POWER CONNECTOR, NORMAL & EMERGENCY
PUSHPLATE, +48" AFF TO TOP
KEYPAD, +48" AFF TO TOP
INTERCOM, +48" AFF TO TOP
PANIC BUTTON, +48" AFF TO TOP
MONITOR
MOTION DETECTOR
GLASS BREAK DETECTOR
SECURITY ACCESS BUZZER
CAMERA, CEILING. TYPE INDICATED; PTZ, 360, ETC.
ALARM STROBE, REFER TO PLANS FOR ASSOCIATED SYSTEM.
W
CR
ES
DC
RE
DO
PP
KP
IC
PB
K
DO
S/R
SD
CD
M
D
N
N
(WALL MOUNTED DEVICES MOUNTED 60" AFF TO TOP, UON.)
R
N E
PATIENT BED STATION, SINGLE BED
PATIENT BED STATION, DOUBLE BED
PATIENT BED RECEPTACLE, 20" AFF
EMERGENCY CALL:
TOILETS: W/PULL CORD. 84" AFF IN SHOWERS, +54" AFF IN TUBS AND 36" AFF
AT TOILETS.
TREATEMENT ROOMS: 84" AFF.
CODE BLUE
STAFF STATION
DUTY STATION
PSYCHIATRIC COORIDOR STATION
CABLE TV INTERFACE
DOME LIGHT, CEILING OR WALL +80" AFF FLOOR OR 6" BELOW CEILING.
ZONE LIGHT, CEILING OR WALL +80" AFF FLOOR OR 6" BELOW CEILING.
NURSE CALL MASTER
NURSE CALL ANNUNCIATOR
NURSE CALL TERMINAL CABINET
N C
N S
N D
N T
N
Z
N P
NCT
TTC
TTB
SM
MD
GB
SB
(WALL MOUNTED DEVICES MOUNTED 48" AFF, UON.)
A
N
TB
PR
V
45kVA
100-4
EG-1
PB
A
F
E
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
B
IM
/5
-1
-1
O p ti m iz e B
E n e rg y P la n t
/5
V A
A B
Q B
E L
E C
.r v t
/2 /2
:2
:2
A M
E-001
ELECTRICAL SYMBOL LEGEND AND
ABBREVIATIONS
TRIPLE C THE A/E GROUP
1839 S. Alma School Rd., Ste.
Mesa, AZ 85210
307-460-2054
Mat Perkins
UPGRADE ENERGY PLANT
EQUIPMENT INFRASTRUCTURE
(BLDG. 43 & 43A)
1501 SAN PEDRO SE ALBUQUERQUE, NM 87108
501-17-105
11-01-2019 M.PERKINS F.CLARK
100% CONSTRUCTION
DOCUMENTS
A AMPERES MGAS MEDICAL GAS PANEL
AC ALTERNATING CURRENT KW KILOWATTS
ADO AUTOMATIC DOOR OPENER MCB MAIN CIRCUIT BREAKER
AF AMPERE FRAME LGT LIGHT
AFF ABOVE FINISHED FLOOR LTG LIGHTING
AHU AIR HANDLING UNIT LTS LIGHTS
AIC AMP INTERRUPTING CAPACITY LV LOW VOLTAGE
ALT ALTERNATE MATV MASTER ANTENNA TELEVISION
ARCH ARCHITECTURAL NC NORMALLY CLOSED
ASC ABOVE SUSPENDED CEILING MCC MOTOR CONTROL CENTER
AT AMPERE TRIP MDP MAIN DISTRIBUTION PANEL
ATS AUTOMATIC TRANSFER SWITCH LAN LOCAL AREA NETWORK
BATS BYPASS AUTOMATIC TRANSFER
SWITCH
MGHT MOUNTING HEIGHT
BCG BARE COPPER GROUND MH MANHOLE
BKR BREAKER MLO MAIN LUGS ONLY
BLDG BUILDING MTD MOUNTED
C CONDUIT MTG MOUNTING
CB CIRCUIT BREAKER MTR MOTOR/METER
CCT CIRCUIT NA NOT APPLICABLE
CCTV CLOSED CIRCUIT TELEVISION NAC FA NOTIFICATION APPLIANCE POWER
SUPPLY
CFCI CONTRACTOR FURNISHED,
CONTRACTOR INSTALLED
NEC NATIONAL ELECTRICAL CODE
CLG CEILING NFD NON-FUSED DISCONNECT
CONTR CONTRACTOR NFSS NON-FUSED SAFETY SWITCH
CORR CORRIDOR NIC NOT IN CONTRACT
CT CURRENT TRANSFORMER NO NORMALLY OPEN
CTRL CONTROL NTS NOT TO SCALE
DB DIRECT BURIAL OC ON CENTER
DC DIRECT CURRENT OFCI OWNER FURNISHED CONTRACTOR
INSTALLED
DED DEDICATED OFOI OWNER FURNISHED OWNER INSTALLED
DET DETAIL PA PUBLIC ADDRESS
DIA DIAMETER PBB PRIMARY BONDING BUSBAR
DISC DISCONNECT PC PHOTOCELL
DN DOWN PDU POWER DISTRIBUTION UNIT
DS DISCONNECT SWITCH PF POWER FACTOR
EC EMPTY CONDUIT/ELECTRICAL
CONTRACTOR
PH PHASE
EG EQUIPMENT GROUND PLBG PLUMBING
EGS ENGINE GENERATOR SET PNL PANEL
ELEC ELECTRIC/ELECTRICAL PT POTENTIAL TRANSFORMER
EMER EMERGENCY PWR POWER
EMI ELECTROMAGNETIC INTERFERENCE REC RECEPTACLE
EMT ELECTRICAL METALLIC TUBING RECD RECESSED
EPO EMERGENCY POWER OFF REQD REQUIRED
EQUIP EQUIPMENT RMC RIGID METAL CONDUIT
ETR EXISTING TO REMAIN SBB SECONDARY BONDING BUSBAR
FA FIRE ALARM SECT SECTION
FACP FIRE ALARM CONTROL PANEL SHT SHEET
FCU FAN COIL UNIT SIG SIGNAL
FDR FEEDER SIM SIMILAR
FIXT FIXTURE SPD SURGE PROTECTIVE DEVICE
FLA FULL LOAD AMPERES SPEC SPECIFICATION
FLEX FLEXIBLE SS SAFETY SWITCH
FLR FLOOR STR STARTER
FLUOR FLUORESCENT SW SWITCH
FS FLOW SWITCH SWGR SWITCHGEAR
FVNR FULL VOLTAGE NON-REVERSING TBB TELECOMMUNICATIONS BONDING
BACKBONE
GC GENERAL CONTRACTOR TBC TELECOMMUICATIONS BONDING
CONDUCTOR
GCP GENERATOR CONTROL PANEL MCR MAIN COMPUTER ROOM
GE GROUNDING EQUALIZER TEBC TELECOMMUNICATIONS EQUIP BONDING
CONDUCTOR
GEC GROUNDING ELECTRODE
CONDUCTOR
TEL TELEPHONE
GEN GENERATOR TS TAMPER SWITCH/TIME SWITCH
GES GROUNDING ELECTRODE SYSTEM TTB TELEPHONE TERMINAL BOARD
GFCI GROUND FAULT CIRCUIT
INTERRUPTER
TTC TELEPHONE TERMINAL CABINET
GFI GROUND FAULT INTERRUPTER TV TELEVISION
GFP GROUND FAULT PROTECTION TVSS TRANSIENT VOLTAGE SURGE
SUPPRESSION
GND GROUND TYP TYPICAL
HH HANDHOLE UC UNDER COUNTER
HOA HAND OFF AUTOMATIC UG UNDER GROUND
HP HORSE POWER UNO UNLESS NOTED OTHERWISE
HV HIGH VOLTAGE UPS UNINTERRUPTED POWER SUPPLY
IMC INTERMEDIATE METAL CONDUIT VFD VARIABLE FREQUENCY DRIVE
IT INFORMATION TECHNOLOGY W WIRE
JB JUNCTION BOX W/ WITH
KV KILOVOLT X EXISTING
KVA KILOVOLT-AMPERES XFMR TRANSFORMER
IDENTIFICATION SIGNS PER SPECIFICATION 260511, 1.11. FOR NORMAL
POWER SYSTEM EQUIPMENT SHALL BE LAMINATED BLACK PHENOLIC RESIN
WITH A WHITE CORE WITH ENGRAVED LETTERING. IDENTIFICATION SIGNS
FOR ESSENTIAL ELECTRICAL SYSTEM (EES) EQUIPMENT, AS DEFINED IN THE
NEC, SHALL BE LAMINATED RED PHENOLIC RESIN WITH A WHITE CORE WITH
ENGRAVED LETTERING. LETTERING SHALL BE A MINIMUM OF 12 MM (1/2
INCH) HIGH. IDENTIFICATION SIGNS SHALL INDICATE EQUIPMENT
DESIGNATION, RATED BUS AMPERAGE, VOLTAGE, NUMBER OF PHASES,
NUMBER OF WIRES, AND TYPE OF EES POWER BRANCH AS APPLICABLE.
SECURE NAMEPLATES WITH SCREWS.
43P1B 400A
480Y/277V-3P-4W
SERVED FROM 43PSB2
EQUIPMENT LABELING STANDARD
NAME
SIZE (AMPS, HP, ETC.)
VOLTAGE
SERVICE SOURCE
Revisions: Date:
11-25-2019
7/20/2022
MATHEW PERKINS
NO.005843
07/20/2022
DN
F
FF
F F
EPO
PB
EPO
PB
V VV V V V
F
F
F
F
F
F
F F P
B P
B
T
1 2 3 4
E
D
C
B
A
MCCEQ(E)
1500kVA
TRANSFORMER
MAIN
SWBD
NDPP
1750kW
EMERGENCY
GENERATOR
ATS
WCH2
ATS
MCCEP
ATS-1
ATS-2
ATS
WCH3
ECLA(E)
ECPA(E)
A(E)
EQHA(E)
NLSS(E)
BFD-43-ML (E)
CST-43-ML (E)
WATER
TREATMENT
(E)
F
E
D B
F
E
D B
C1
ED101A
A1
ED101A
C2
ED101A
BOILER
PLANT
MA-105
STAIRS
MA-209
VESTIBULE
MA-120
ELECTRICAL
ROOM
MA-107
GENERATOR
ROOM
MA-106
NC26FHR(E)
B56(E)
EQTD(E)
EDSB(E) EPDS(E)
12 12
FL-2
FL-1
PULLBOX(E)
PULLBOX(E)
NORT
H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
KEY PLAN
A
B
IM
/5
-1
-1
O p ti m iz e B
E n e rg y P la n t
/5
V A
A B
Q B
E L
E C
.r v t
/2 /2
:2
:5
A M
ED101A
ELECTRICAL DEMO PLAN - LEVEL 1 - AREA A
TRIPLE C THE A/E GROUP
1839 S. Alma School Rd., Ste.
Mesa, AZ 85210
307-460-2054
Mat Perkins
UPGRADE ENERGY PLANT
EQUIPMENT INFRASTRUCTURE
(BLDG. 43 & 43A)
1501 SAN PEDRO SE ALBUQUERQUE, NM 87108
501-17-105
11-01-2019 M.PERKINS F.CLARK
100% CONSTRUCTION
DOCUMENTS
1/4" = 1'-0" F2
ELECTRICAL DEMO PLAN - LEVEL 1 - AREA A
GENERAL SHEET NOTES
KEYNOTES
A ALL EQUIPMENT INDICATED HALFTONE IS EXISTING TO REMAIN, UNO.
B ALL EQUIPMENT SHOWN DASHED AND BOLD SHALL BE REMOVED IN THEIR ENTIRETY. UNO
C THE DEMOLITION OF EQUIPMENT AND DEVICES SHALL INCLUDE ALL ASSOCIATED CONDUIT
AND WIRE BACK TO THE NEAREST POINT OF SERVICE.
D MAINTAIN CIRCUIT CONTINUITY TO DEVICES THAT REMAIN.
E CONTRACTOR SHALL AVOID ALL ELECTRICAL, FIRE ALARM, CONTROL, INFORMATION
TECHNOLOGY SYSTEMS SHUTDOWNS, INSTALL NEW EQUIPMENT PRIOR TO THE RENOVATION
OF EXISTING EQUIPMENT; PROVIDE TEMPORARY UTILITIES (LIGHTING AND POWER) AS
REQUIRED TO MEET THIS REQUIREMENT.
F REFER TO THE 'SEQUENCE OF RENOVATION' SCHEDULE ON SHEET E-601 FOR ELECTRICAL
DISTRIBUTION EQUIPMENT DEMOLITION SEQUENCE REQUIREMENTS.
G CONTRACTOR SHALL REMOVE ALL FEEDERS (WIRE AND RACEWAY) INCLUDING ASSOCIATED
JBOXES AND COMPONENTS FOUND TO BE ABANDONED OR NO LONGER DUE TO DEMOLITION
IN USE IN THEIR ENTIRETY.
1 DISCONNECT AND REMOVE EXISTING SWITCHBOARD IN IT'S ENTIRETY.
REFER TO SHEET E-601 FOR ADDITIONAL INFORMATION.
2 DISCONNECT AND REMOVE EXISTING 1500kVA TRANSFORMER IN IT'S
ENTIRETY. REFER TO SHEET E-601 FOR ADDITIONAL INFORMATION.
3 DISCONNECT AND REMOVE EXISTING 15kV SWITCH IN IT'S ENTIRETY. REFER
TO SHEET E-601 FOR ADDITIONAL INFORMATION.
4 DISCONNECT AND REMOVE EXISTING AUTOMATIC TRANSFER SWITCH. REFER
TO ONE LINE DIAGRAM, SHEET E-601 FOR ADDITIONAL INFORMATION.
5 EXISTING 48" SQUARE PULLBOX FOR NORMAL POWER SERVICE TO BUILDING
10 TO REMAIN. REFER TO ONE LINE DIAGRAM FOR WORK TO BE PERFORMED
TO RE-FEED BUILDING 10.
6 EXISTING 18" SQUARE PULLBOX FOR ATS CONTROL WIRES TO BUILDING 10
TO REMAIN.
7 DISCONNECT AND REMOVE WALL MOUNTED DEVICES LOCATED IN WALL
DESIGNATED TO BE REMOVED.
8 DISCONNECT AND REMOVE CEILING MOUNTED DEVICES, LIGHTING, CEILING
FANS, FIRE ALARM DEVICE LOCATED IN CEILINGS INDICATED TO BE
REMOVED. REFER TO ARCHITECTURAL RCP FOR ADDITIONAL INFORMATION.
9 DISCONNECT AND REMOVE ELECTRICAL SERVICE TO UNIT HEATER IN IT'S
ENTIRETY BACK TO NEAREST POINT OF SERVICE. SERVICE PANEL
INDICATED, CONTRACTOR SHALL FIELD VERIFY PRIOR TO DEMOLITION.
10 DISCONNECT AND REMOVE EXISTING LIGHT FIXTURE IN IT'S ENTIRETY BACK
TO NEAREST POINT OF SERVICE.
11 DISCONNECT AND REMOVE EXTERIOR LIGHTING CONTROL CONTACTOR AND
BY-PASS SWITCH.
12 DISCONNECT AND REMOVE EXISTING SWITCHBOARD AFTER THE EXISTING
LOADS PRESENTLY SERVED FOR THE SWITCHBOARD HAVE BEEN RE-FED
FROM NEW DISTRUBTION EQUIPMENT. REFER TO ONE LINE DIAGRAM, SHEET
E-601 FOR ADDITIONAL INFORMATION.
13 ELECTRICAL CONTRACTOR SHALL RE-LOCATE, SECURE AND RE-ANCHOR ALL
CONDUITS, J-BOXES, LIGHTING AND ELECTRICAL EQUIPMENT THAT ARE
CURRENTLY SECURED TO THIS WALL
NTS
A1
EXISTING MOTOR CONTROL CENTER
(MCCEQ)- BOILER ROOM
NTS
C1
EXISTING ELECTRICAL PANEL - EQHA
NTS
C2
EXISTING PULLBOXES - ELECTRICAL
ROOM
11-01-2019Revisions: Date:
11-25-2019
7/20/2022
MATHEW PERKINS
NO.005843
F
E P
O
PB
F
4 4
S
F
F
F F
PBPBA
PBPBA
P B
P B
F
F
F
H
4 5 6
E
D
C
B
A
ELPA(E)
ELLA(E)
NPP(E)
NLP(E)
43-P12 (E)
43-P11 (E)43-P10 (E)
43-P8 (E)
43-P7 (E)
43-WCCH-1 (E)
43-WCCH-2 (E)
43-P13 (E)
43-WCCH-3 (E)
WATER
TREATMENT
(E)
43-P14 (E)
43-P9 (E)
HE-2 (E)
F
E
D A
F
E
D A
/F2 ED101A
43-P6 (E)
G1
ED101B
E1
ED101B
I1
ED101B
B2
ED101B
A1
ED101B
C1
ED101B
D2
ED101B
H2
ED101B
J1
ED101B
K1
ED101B
43PX(E)
CONTROL
PANEL 'A'
CONTROL
PANEL 'B'
MCCNP(E)
NDPP
MCCEP(E)
BLDG 43A
43A
SHOWER/CHANGE
VESTIBULE
5MCCEP
MCCEP
8 43-PX
7 NDPP
43A-P2 (E)
43A-P1 (E)
D E
D U
C T
A L
T N
O . 2
GEN-2
MEDG-
FA-3 FA-2 FA-1
FL-2
FL-1
(E)
(E)
CHILLER ROOM
MA-109
LP1(E)
PP1(E)
ELLA ELLA ELLA
NORT
H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
KEY PLAN
B
B
B
IM
/5
-1
-1
O p ti m iz e B
E n e rg y P la n t
/5
V A
A B
Q B
E L
E C
.r v t
/2 /2
:2
:0
A M
ED101B
ELECTRICAL DEMO PLAN - LEVEL 1 - AREA B
TRIPLE C THE A/E GROUP
1839 S. Alma School Rd., Ste.
Mesa, AZ 85210
307-460-2054
Mat Perkins
UPGRADE ENERGY PLANT
EQUIPMENT INFRASTRUCTURE
(BLDG. 43 & 43A)
1501 SAN PEDRO SE ALBUQUERQUE, NM 87108
501-17-105
11-01-2019 M.PERKINS F.CLARK
100% CONSTRUCTION
DOCUMENTS
1/4" = 1'-0" F4
ELECTRICAL DEMO PLAN - LEVEL 1 - AREA B
GENERAL SHEET NOTES
KEYNOTES
A ALL EQUIPMENT INDICATED HALFTONE IS EXISTING TO REMAIN, UNO.
B ALL EQUIPMENT SHOWN DASHED AND BOLD SHALL BE REMOVED IN THEIR ENTIRETY. UNO
C THE DEMOLITION OF EQUIPMENT AND DEVICES SHALL INCLUDE ALL ASSOCIATED CONDUIT
AND WIRE BACK TO THE NEAREST POINT OF SERVICE.
D MAINTAIN CIRCUIT CONTINUITY TO DEVICES THAT REMAIN.
E CONTRACTOR SHALL AVOID ALL ELECTRICAL, FIRE ALARM, CONTROL, INFORMATION
TECHNOLOGY SYSTEMS SHUTDOWNS, INSTALL NEW EQUIPMENT PRIOR TO THE RENOVATION
OF EXISTING EQUIPMENT; PROVIDE TEMPORARY UTILITIES (LIGHTING AND POWER) AS
REQUIRED TO MEET THIS REQUIREMENT.
F REFER TO THE 'SEQUENCE OF RENOVATION' SCHEDULE ON SHEET E-601 FOR ELECTRICAL
DISTRIBUTION EQUIPMENT DEMOLITION SEQUENCE REQUIREMENTS.
G CONTRACTOR SHALL REMOVE ALL FEEDERS (WIRE AND RACEWAY) INCLUDING ASSOCIATED
JBOXES AND COMPONENTS FOUND TO BE ABANDONED OR NO LONGER DUE TO DEMOLITION
IN USE IN THEIR ENTIRETY.
1 REMOVE ELECTRICAL SERVICE TO CHILLER IN IT'S ENTIRETY BACK TO
NEAREST POINT OF SERVICE. REFER TO THE ONE LINE DIAGRAM FOR
ADDITIONAL INFORMATION.
2 REMOVE WALL MOUNTED DEVICES LOCATED IN WALL INDICATED TO BE DEMO.
RELOCATE WALL MOUNTED DEVICES TO NEW ENGINEERING CONTROL CENTER
3 REMOVE ALL CEILING MOUNTED DEVICES LOCATED IN CEILINGS INDICATED TO
BE REMOVED INCLUDING ALL LIGHTING, EXHUAST FAN, FIRE ALARM DEVICES.
REFER TO ARCHITECTURAL RCP FOR ADDITIONAL INFORMATION.
4 REMOVE REFRIGERANT ALARM PUSHBUTTONS AND STROBE AND RELOCATE
PER SHEET EP101B.
5 REMOVE ELECTRICAL SERVICE TO PUMP IN IT'S ENTIRETY BACK TO NEAREST
POINT OF SERVICE. SERVICE PANEL INDICATED, CONTRACTOR SHALL FIELD
VERIFY PRIOR TO DEMOLITION.
6 REMOVE ELECTRICAL SERVICE TO PUMP IN IT'S ENTIRETY BACK TO POINT OF
SERVICE. PROVIDE NEW SERVICE FROM 43PSB1. AS-BUILT DOCUMENTS
INDICATE THE PUMP IS SERVED FROM MCCNP, CONTRACTOR SHALL FIELD
VERIFY PRIOR TO DEMOLITION.
7 REMOVE ELECTRICAL SERVICE TO CHILLER IN IT'S ENTIRETY BACK TO
NEAREST POINT OF SERVICE. REFER TO THE ONE LINE DIAGRAM FOR
ADDITIONAL INFORMATION.
8 REMOVE ELECTRICAL SERVICE TO PUMP IN IT'S ENTIRETY BACK TO NEAREST
POINT OF SERVICE. PROVIDE NEW SERVICE FROM 43PSB1, CONTRACTOR
SHALL FIELD VERIFY POINTS OF SERVICE PRIOR TO DEMOLITION.
9 REMOVE ELECTRICAL SERVICE TO PUMP (PUMPS ARE EXISTING TO REMAIN)
BACK TO MCCNP. PROVIDE NEW SERVICE FROM 43PSB1.
10 REMOVE EXISTING LIGHT FIXTURES AND ELCTRICAL SERVICE IN IT'S ENTIRETY
BACK TO NEAREST POINT OF SERVICE.
11 ELECTRICAL CONTRACTOR SHALL RE-LOCATE, SECURE AND RE-ANCHOR ALL
CONDUITS, J-BOXES, LIGHTING AND ELECTRICAL EQUIPMENT THAT ARE
CURRENTLY SECURED TO THIS WALL
12 ALL LIVE LOADS ON "MCCNP" SHALL BE REWIRED TO NEW DISTRIBUTION
BOARD "43DPB2". CONTRACTOR SHALL COORDINATE WITH VA TO PREVENT ANY
DISRUPTION IN OPERATIONS DURING CONSTRUCTION. AFTER ALL LOADS HAVE
BEEN TRANSFERED TO "43DPSB2" DEMO "MCCNP"
13 DISCONNECT POWER FROM PUMP "43-P14(E) AND REMOVE PUMP TO MAKE
SPACE TO INSTALL NEW CHILLER. REINSTALL PUMP "43-P14(E) IN ORIGINAL
LOCATION AND SUPPLY NEW SERVICE FROM "43DPSB2"
NTS
G1
EXISTING FIRE ALARM CONTROL
PANEL DIGITAL CONTROLLER & N.A.
WALL
NTS
E1
EXISTING BAS DSC CONTROL PANEL
CHILLER ROOM
NTS
H2
EXISTING BRANCH PANELBOARDS -
ELLA
NTS
B2
EXISTING GENERATOR CONTROL
INDICATOR
NTS
A1
EXISTING VEEDER ROOT CONTROL
SYSTEM
NTS
D2
EXISTNG POWER GROUND FAULT
ALARM PANEL
NTS
C1
EXISTING GAS ALARM PANEL
NTS
I1
EXISTING BRANCH PANEL BOARDS -
ELPA
NTS
J1
EXISTING BRANCH PANEL BOARDS -
NPP
NTS
K1
EXISTING BRANCH PANEL BOARDS -
NLP
11-01-2019Revisions: Date:
11-25-2019
7/20/2022
MATHEW PERKINS
NO.005843
S
S
S
F
F
1 2 3 4
E
D
C
B
A
F
E
D B
F
E
D B
43-UH-6
43-UH-7
43-UH-3
43-UH-4
43-UH-5
NLP
NLP
43-DWBP-1
43-DWBP-1
NORT
H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
KEY PLAN
A
B
IM
/5
-1
-1
O p ti m iz e B
E n e rg y P la n t
/5
V A
A B
Q B
E L
E C
.r v t
/2 /2
:2
:1
A M
ED102A
ELECTRICAL DEMO PLAN - LEVEL 2 - AREA A
TRIPLE C THE A/E GROUP
1839 S. Alma School Rd., Ste.
Mesa, AZ 85210
307-460-2054
Mat Perkins
UPGRADE ENERGY PLANT
EQUIPMENT INFRASTRUCTURE
(BLDG. 43 & 43A)
1501 SAN PEDRO SE ALBUQUERQUE, NM 87108
501-17-105
11-01-2019 M.PERKINS F.CLARK
100% CONSTRUCTION
DOCUMENTS
A ALL EQUIPMENT INDICATED HALFTONE IS EXISTING TO REMAIN, UNO.
B ALL EQUIPMENT SHOWN DASHED AND BOLD SHALL BE REMOVED IN THEIR ENTIRETY. UNO
C THE DEMOLITION OF EQUIPMENT AND DEVICES SHALL INCLUDE ALL ASSOCIATED CONDUIT
AND WIRE BACK TO THE NEAREST POINT OF SERVICE.
D MAINTAIN CIRCUIT CONTINUITY TO DEVICES THAT REMAIN.
E CONTRACTOR SHALL AVOID ALL ELECTRICAL, FIRE ALARM, CONTROL, INFORMATION
TECHNOLOGY SYSTEMS SHUTDOWNS, INSTALL NEW EQUIPMENT PRIOR TO THE RENOVATION
OF EXISTING EQUIPMENT; PROVIDE TEMPORARY UTILITIES (LIGHTING AND POWER) AS
REQUIRED TO MEET THIS REQUIREMENT.
F REFER TO THE 'SEQUENCE OF RENOVATION' SCHEDULE ON SHEET E-601 FOR ELECTRICAL
DISTRIBUTION EQUIPMENT DEMOLITION SEQUENCE REQUIREMENTS.
G CONTRACTOR SHALL REMOVE ALL FEEDERS (WIRE AND RACEWAY) INCLUDING ASSOCIATED
JBOXES AND COMPONENTS FOUND TO BE ABANDONED OR NO LONGER DUE TO DEMOLITION
IN USE IN THEIR ENTIRETY.
1/4" = 1'-0" F3
ELECTRICAL DEMO PLAN - LEVEL 2 - AREA A
GENERAL SHEET NOTES
KEYNOTES
1 DISCONNECT AND REMOVE EXISTING FIRE ALARM DEVICE.
2 DISCONNECT AND REMOVE EXISTING LIGHT FIXTURES IN THEIR ENTIRETY
BACK TO NEAREST POINT OF SERVICE. TYPICAL THIS ROOM.
3 DISCONNECT AND REMOVE ELECTRICAL SERVICE TO UNIT HEATER IN IT'S
ENTIRETY BACK TO NEAREST POINT OF SERVICE. SERVICE PANEL INDICATED,
CONTRACTOR SHALL FIELD VERIFY PRIOR TO DEMOLITION.
4 DISCONNECT AND REMOVE ELECTRICAL SERVICE TO WATER HEATER IN IT'S
ENTIRETY BACK TO NEAREST POINT OF SERVICE. CONTRACTOR TO FIELD
VERIFY PANEL PERIOR TO DEMO
5 DISCONNECT AND REMOVE EXISTING LIGHT FIXTURES IN THIS SPACE
INCLUDING WIRING BACK TO LIGHT SWITCH. THE EXISTING JBOX AND
RACEWAY WILL BE REUSED WITH NEW LIGHT FIXTURES. SEE SHEET EL102A.
6 DISCONNECT AND REMOVE ELECTRICAL SERVICE TO EXISTING CHILLER #3
FEEDER PULLBOX IN IT'S ENTIRETY. THE PULLBOX LOCATED ABOVE
ATS-WCH3, ~18'-6" AFF.
7 DISCONNECT ELECTRICAL SERVICE TO PUMP SKID. EXTEND RACEWAY AND
WIRING TO NEW LOCATION. SEE SHEET EP102A.
8 DISCONNECT AND REMOVE ELECTRICAL SERVICE TO SIDE STREAM FILTER
SKID BACK TO NEAREST POINT OF SERVICE. REFER TO LEVEL 1 POWER PLAN
FOR NEW EQUIPMENT CONNECTION REQUIREMENTS.
9 REMOVE UNIT HEATER "43-UH-7" AND REPLACE WITH NEW UNIT OF THE SAME
TYPE AND SIZE. SEE MECHCANICAL SCHEDULE FOR MORE INFORMATION.
11-01-2019Revisions: Date:
11-25-2019
7/20/2022
MATHEW PERKINS
NO.005843
4 5 6
E
D
C
B
A
43-UH-2
F
E
D A
F
E
D A
43-FCU-1
43-UH-1
VESTIBULE
103SHOWER/CHANGE
NORT
H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
KEY PLAN
B
B
B
IM
/5
-1
-1
O p ti m iz e B
E n e rg y P la n t
/5
V A
A B
Q B
E L
E C
.r v t
/2 /2
:2
:1
A M
ED102B
ELECTRICAL DEMO PLAN - LEVEL 2 - AREA B
TRIPLE C THE A/E GROUP
1839 S. Alma School Rd., Ste.
Mesa, AZ 85210
307-460-2054
Mat Perkins
UPGRADE ENERGY PLANT
EQUIPMENT INFRASTRUCTURE
(BLDG. 43 & 43A)
1501 SAN PEDRO SE ALBUQUERQUE, NM 87108
501-17-105
11-01-2019 M.PERKINS F.CLARK
100% CONSTRUCTION
DOCUMENTS
A ALL EQUIPMENT INDICATED HALFTONE IS EXISTING TO REMAIN, UNO.
B ALL EQUIPMENT SHOWN DASHED AND BOLD SHALL BE REMOVED IN THEIR ENTIRETY BACK
TO NEAREST POINT OF SERVICE, UNO.
C PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED OUTDOORS.
D PROVIDE EQUIPMENT CONNECTIONS SIZED PER THE HOMERUN.
E COORDINATE FINAL EQUIPMENT CONNECTIONS REQUIREMENTS WITH EQUIPMENT SUPPLIER
PRIOR TO ROUGH-IN.
F COORDINATE THE REQUIRED SHORT CIRCUIT RATING OF NEW EQUIPMENT WITH THE
ELECTRICAL STUDIES PER SPECIFICATIONS 260527.
G NEW SWITCHBOARDS SHALL HAVE MINIMUM 50,000 AIC BRACING.
H NEW LV SWITCHGEAR SHALL HAVE 100,000 AIC BRACING.
I CIRCUIT BREAKERS 250A AND LARGER SHALL BE FULLY ELECTRONIC TYPE WITH AT LEAST
FIVE (5) LEVELS OF ADJUSTMENT.
J CIRCUIT BREAKERS 800A AND LARGER SHALL BE 100% RATED.
K NEW EQUIPMENT RATED 600A OR GREATER SHALL BE SWITCHBOARDS.
L NEW SWITCHBOARDS AND NEW CIRCUIT BREAKERS 400A AND GREATER SHALL BE METERED.
M METERING EQUIPMENT SHALL HAVE THE CAPABILITY OF READING KWH, KVA, KVARS, VOLTS, CURRENT, THD VOLTAGE, THD CURRENT, FREQUENCY AND POWER FACTOR IN THE SAME
SYSTEM WITH THE CAPABILITY OF TRANSMITTING THAT DATA TO THE EXISTING CENTRAL
SYSTEM WHERE THAT DATA CAN BE READ AT A CENTRAL CONTROL STATION.
N PROVIDE THE ELECTRICAL STUDIES, AS REQUIRED BY SPECIFICATION 260527 PRIOR TO
SUBMITTING DISTRIBUTION EQUIPMENT SUBMITTALS.
O CONTRACTOR SHALL ROUTE ALL NEW FEEDERS FROM SOURCES TO EXISTING EQUIPMENT
PRIOR TO DISCONNECTING THE EXISTING EQUIPMENT AND WIRING NEW FEEDERS.
P CONTRACTOR SHALL PROVIDE LABELS FOR ALL EQUIPMENT, NEW AND EXISTING PER THE
EXAMPLE INDICATED ON SHEET E-001.
Q PROVIDE A 4" HOUSEKEEPING PAD FOR FLOOR MOUNTED EQUIPMENT.
R ALL OVERCURRENT PROTECTION DEVICES ARE THREE POLE, UNO.
GENERAL SHEET NOTES
KEYNOTES
1/4" = 1'-0" F4
ELECTRICAL POWER SECOND FLOOR - PHASE 2
1 DISCONNECT AND REMOVE EXISTING LIGHT FIXTURES IN THIS SPACE
INCLUDING WIRE BACK TO LIGHT SWITCH.
2 DEMO FAN COIL "43-FCU-1" AND ELECTRICAL SERVICE BACK TO PANEL "NLP"
THE SERVICE PANEL IS INDICATED, CONTRACTOR SHALL FIELD VERIFY PRIOR
TO DEMOLITION.
3 DISCONNECT AND REMOVE RECEPTACLE IN IT'S ENTIRETY BACK TO NEAREST
POINT OF SERVICE.
4 DISCONNECT AND REMOVE LIGHT SWITCH.
5 DISCONNECT AND REMOVE CEILING MOUNTED CAMERA IN IT'S ENTIRETY BACK
TO NEAREST POINT OF SERVICE.
6 DISCONNECT AND REMOVE EXISTING TELECOM/I.T. EQUIPMENT IN THEIR
ENTIRETY BACK TO POINT OF SERVICE. MOVE EQUIPMENT TO NEW
TELECOMMUNICATIONS ROOM MA-219.
7 DISCONNECT AND REMOVE EXISTING LIGHT FIXTURES IN THIS SPACE
INCLUDING WIRING BACK TO LIGHT SWITCH. THE EXISTING JBOX AND
RACEWAY WILL BE REUSED WITH NEW LIGHT FIXTURES. SEE SHEET EL102B.
8 DISCONNECT POWER TO UNIT HEATERS "43-UH-1 AND 43-UH-2 AND REMOVE
AND REPLACE UNIT HEATERS WITH NEW UNIT HEATERS OF THE SAME TYPE
AND LOADS. SERVICE PANEL INDICATED, CONTRACTOR SHALL FIELD VERIFY
PRIOR TO DEMOLITION.
9 ELECTRICAL CONTRACTOR SHALL RE-LOCATE, SECURE AND RE-ANCHOR ALL
CONDUITS, J-BOXES, LIGHTING AND ELECTRICAL EQUIPMENT THAT ARE
CURRENTLY SECURED TO THIS WALL.
2 NLP
4 4
11-01-2019Revisions: Date:
11-25-2019
7/20/2022
MATHEW PERKINS
NO.005843
1 2 3 4
D
C
B
A
43-RTU-1
43-EF-7
43-GH-6(E)
43-EF-8
43-GH-7(E)
43-EF-9
43-EF-3
FGE-431RF(E)
43-EF-4
43-EF-5
43-EF-10
43-REF-4(E)
43-REF-5(E)
43-EAC-2
43-EAC-1
43-EAC-3
43-BIH-1(E)
43-EF-6
F
E
D B
F
E
D B
MCCEQ
NLP
ECLA
ECLA
ECLA
FGE-433RF(E)
FGE-432RF(E)
MCCEQ
MCCEQ
MCCEQ
NLP
MCCNP
NLP
NLP
MCCNP
NLP
MCCNP
43-BIH-2(E)
43-BIH-3(E)
NORT
H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
KEY PLAN
A
B
IM
/5
-1
-1
O p ti m iz e B
E n e rg y P la n t
/5
V A
A B
Q B
E L
E C
.r v t
/2 /2
:2
:4
A M
ED103A
ELECTRICAL DEMO PLAN - ROOF LEVEL -
AREA A
TRIPLE C THE A/E GROUP
1839 S. Alma School Rd., Ste.
Mesa, AZ 85210
307-460-2054
Mat Perkins
UPGRADE ENERGY PLANT
EQUIPMENT INFRASTRUCTURE
(BLDG. 43 & 43A)
1501 SAN PEDRO SE ALBUQUERQUE, NM 87108
501-17-105
11-01-2019 M.PERKINS F.CLARK
100% CONSTRUCTION
DOCUMENTS
1/4" = 1'-0" F3
ELECTRICAL DEMO PLAN - ROOF LEVEL - AREA A
GENERAL SHEET NOTES
KEYNOTES
1 DISCONNECT AND REMOVE ELECTRICAL SERVICE TO MECHANICAL
EQUIPMENT. SOURCE ELECTRICAL EQUIPMENT INDICATED, CONTRACTOR
SHALL FIELD VERIFY PRIOR TO DEMOLITON.
2 EXISTING TO REMAIN.
3 DISCONNECT POWER TO REFRIGERANT UNITS "43-REF-4" AND 43-REF-5 AND
REMOVE AND RETAIN UNITS FOR RE-INSTALLATION. CONTRACTOR SHALL
FIELD VERIFY PRIOR TO DEMOLITION.
A ALL EQUIPMENT INDICATED HALFTONE IS EXISTING TO REMAIN, UNO.
B ALL EQUIPMENT SHOWN DASHED AND BOLD SHALL BE REMOVED IN THEIR ENTIRETY. UNO
C THE DEMOLITION OF EQUIPMENT AND DEVICES SHALL INCLUDE ALL ASSOCIATED CONDUIT
AND WIRE BACK TO THE NEAREST POINT OF SERVICE.
D MAINTAIN CIRCUIT CONTINUITY TO DEVICES THAT REMAIN.
E CONTRACTOR SHALL AVOID ALL ELECTRICAL, FIRE ALARM, CONTROL, INFORMATION
TECHNOLOGY SYSTEMS SHUTDOWNS, INSTALL NEW EQUIPMENT PRIOR TO THE RENOVATION
OF EXISTING EQUIPMENT; PROVIDE TEMPORARY UTILITIES (LIGHTING AND POWER) AS
REQUIRED TO MEET THIS REQUIREMENT.
F REFER TO THE 'SEQUENCE OF RENOVATION' SCHEDULE ON SHEET E-601 FOR ELECTRICAL
DISTRIBUTION EQUIPMENT DEMOLITION SEQUENCE REQUIREMENTS.
G CONTRACTOR SHALL REMOVE ALL FEEDERS (WIRE AND RACEWAY) INCLUDING ASSOCIATED
JBOXES AND COMPONENTS FOUND TO BE ABANDONED OR NO LONGER DUE TO DEMOLITION
IN USE IN THEIR ENTIRETY.
11-01-2019Revisions: Date:
11-25-2019
7/20/2022
MATHEW PERKINS
NO.005843
D
C
B
A
43-EAC-1
43-OAH-6
43-GH-1(E)
F
E
D A
F
E
D A
NLP
43-GH-2(E)
NORT
H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
KEY PLAN
B
B
B
IM
/5
-1
-1
O p ti m iz e B
E n e rg y P la n t
/5
V A
A B
Q B
E L
E C
.r v t
/2 /2
:2
:1
A M
ED103B
ELECTRICAL DEMO PLAN - ROOF LEVEL -
AREA B
TRIPLE C THE A/E GROUP
1839 S. Alma School Rd., Ste.
Mesa, AZ 85210
307-460-2054
Mat Perkins
UPGRADE ENERGY PLANT
EQUIPMENT INFRASTRUCTURE
(BLDG. 43 & 43A)
1501 SAN PEDRO SE ALBUQUERQUE, NM 87108
501-17-105
11-01-2019 M.PERKINS F.CLARK
100% CONSTRUCTION
DOCUMENTS
GENERAL SHEET NOTES
KEYNOTES
1/4" = 1'-0" F4
ELECTRICAL DEMO PLAN - ROOF LEVEL - AREA B
1 DISCONNECT AND REMOVE ELECTRICAL SERVICE TO MECHANICAL EQUIPMENT.
SOURCE ELECTRICAL EQUIPMENT INDICATED, CONTRACTOR SHALL FIELD
VERIFY PRIOR TO DEMOLITON.
2 CONTRACTOR SHALL RELOCATE OR REPLACE HEAT TRACE EQUIPMENT AS
NECESSARY TO MAINTAIN ACCESSABLITY, COORDINATE LOCATIONS WITH COR.
A ALL EQUIPMENT INDICATED HALFTONE IS EXISTING TO REMAIN, UNO.
B ALL EQUIPMENT SHOWN DASHED AND BOLD SHALL BE REMOVED IN THEIR ENTIRETY. UNO
C THE DEMOLITION OF EQUIPMENT AND DEVICES SHALL INCLUDE ALL ASSOCIATED CONDUIT
AND WIRE BACK TO THE NEAREST POINT OF SERVICE.
D MAINTAIN CIRCUIT CONTINUITY TO DEVICES THAT REMAIN.
E CONTRACTOR SHALL AVOID ALL ELECTRICAL, FIRE ALARM, CONTROL, INFORMATION
TECHNOLOGY SYSTEMS SHUTDOWNS, INSTALL NEW EQUIPMENT PRIOR TO THE RENOVATION
OF EXISTING EQUIPMENT; PROVIDE TEMPORARY UTILITIES (LIGHTING AND POWER) AS
REQUIRED TO MEET THIS REQUIREMENT.
F REFER TO THE 'SEQUENCE OF RENOVATION' SCHEDULE ON SHEET E-601 FOR ELECTRICAL
DISTRIBUTION EQUIPMENT DEMOLITION SEQUENCE REQUIREMENTS.
G CONTRACTOR SHALL REMOVE ALL FEEDERS (WIRE AND RACEWAY) INCLUDING ASSOCIATED
JBOXES AND COMPONENTS FOUND TO BE ABANDONED OR NO LONGER DUE TO DEMOLITION
IN USE IN THEIR ENTIRETY.
11-01-2019Revisions: Date:
11-25-2019
7/20/2022
MATHEW PERKINS
NO.005843
O
H
1 2 3 4
E
D
C
B
A
BOILER
PLANT
MA-105
STORAGE
MA-121
GENERATOR
ROOM
MA-106
STAIRS
MA-209
VESTIBULE
MA-120
ELECTRICAL
ROOM
MA-107
L1, 43UP1- 2,
L1, 43UP1- 2,
L1, 43UP1- 2,
L1E, 43UP1- 2, L1E, 43UP1- 2,
L1E, 43UP1- 2, L1E, 43UP1- 2,
L1E, 43UP1- 2, L1E, 43UP1- 2,
L1E, 43UP1- 2, L1E, 43UP1- 2,
L1E, 43UP1- 2, L1E, 43UP1- 2,
W1, 43UP1- 6,
W1, 43UP1- 6,
X1, 43UP1- 2,
L1E, 43UP1- 2, L1E, 43UP1- 2,
L1E, 43UP1- 2,
L1E, 43UP1- 2,L1E, 43UP1- 2,
F
E
L B
F
E
L B
/E3 EL101C
X1, 43UP1- 2,
L2, 43UP1- 2,
L2, 43UP1- 2, L2, 43UP1- 2,
L2, 43UP1- 2,
L2, 43UP1- 2,
7 7
L1, 43UP1- 2,
43LCP
43UP1- 2,
W1, 43UP1- 6,
43UP1- 6,
W1, 43UP1- 6,
43UP1- 2,
X1, 43UP1- 2,
43UP1- 2,
BOILER
PLANT
MA-108
EXISTING EXTERIOR LIGHTS
EXISTING EXTERIOR WALL LIGHTS
BOILER ROOM LIGHTS
CHILLER ROOM LIGHTS
SPARE
SPARE
SPARE
SPARE
REFER TO
FLOORPLANS
FOR CIRCUIT
NUMBERS
NORT
H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
KEY PLAN
A
B
IM
/5
-1
-1
O p ti m iz e B
E n e rg y P la n t
/5
V A
A B
Q B
E L
E C
.r v t
/2 /2
:2
:3
A M
EL101A
ELECTRICAL LIGHTING PLAN - LEVEL 1 - AREA
A
TRIPLE C THE A/E GROUP
1839 S. Alma School Rd., Ste.
Mesa, AZ 85210
307-460-2054
Mat Perkins
UPGRADE ENERGY PLANT
EQUIPMENT INFRASTRUCTURE
(BLDG. 43 & 43A)
1501 SAN PEDRO SE ALBUQUERQUE, NM 87108
501-17-105
11-01-2019 J. LOHL J. HALPIN
100% CONSTRUCTION
DOCUMENTS
GENERAL SHEET NOTES
KEYNOTES
1/4" = 1'-0" F3
LIGHTING PLAN - LEVEL 1 - AREA A
1 WIRE LIGHT FIXTURE TO CIRCUIT INDICATED. THE EXISTING ROOM CONTROL
SCHEME SHALL REMAIN THE SAME, WIRE AS REQURED.
2 WIRE FIXTURE INTO THE NEW EXTERIOR LIGHTING CIRCUIT INDICATED. LIGHTS
ARE CONTROLLED THROUGH THE LIGHTING CONTROL PANEL '43LCP'.
3 PROVIDE A NEW 4-WAY SWITCH AND WIRE INTO THE EXISTING LIGHTING
CONTROL CIRCUIT SERVING THE ELECTRICAL ROOM.
4 WIRE NEW EXIT SIGN INTO UNSWITCHED LIGHTING CIRCUIT SERVING THIS
ROOM.
5 EXISTING TO REMAIN, CONTRACTOR TO KEEP CONNECTIVITY DURING
CONSTRUCTION
6 REPLACE THE EXISTING LIGHT SWITCH WITH LIKE TYPE OF SWITCH. REPLACE
THE EXISTING WIRING WITH #12 AWG; MATCH EXISTING QUANTITY. RACEWAYS
SHALL BE REUSED WHERE APPLICABLE.
7 SURFACE MOUNT THE LIGHT FIXTURE TO WALL AT 10'0" AFF. WIRE TO THE
SWITCHED LIGHTS ABOVE, REFER TO LEVEL 2 LIGHTING PLAN.
8 REFER TO THE LIGHTING CONTROL DETAIL FOR ADDITIONAL INFORMATION.
9 LIGHTING CONTROL PANEL '43LCP'. 8 CHANNEL, ONE 2-POLE CONTACT, SEVEN
1-POLE CONTACTS, 120VAC INPUT, ASTRONOMIC TIMECLOCK, NORMALLY
CLOSED CONTACTS (CLOSED ON FAIL). WATTSTOPPER #LC8 OR APPROVED
EQUAL.
10 ONE 2-POLE CONTACT WITH THE REMAINING CONTACTS SINGLE POLE.
11 MOVE EXISTING LIGHTING CIRCUITS TO NEW LIGHTING CONTROL PANEL.
WHERE REQUIRED EXTEND WIRE FROM THE NEAREST LIGHTING J-BOX TO NEW
LIGHTING CONTROL PANEL.
A ALL EQUIPMENT AND DEVICES SHOWN HALFTONE ARE EXISTING TO REMAIN, UNO.
B ALL LIGHTS ARE CONTROLLED BY THE LIGHT SWITCH(ES) OR OCCUPANCY SENSOR(S) LOCATED
IN THE ROOM, UNO.
C ALL LUMINAIRES NOTATED AS 'NL' ARE UNSWITCHED NIGHT LIGHTS, WIRED TO AN UNSWITCHED, 277VA LIGHTING BRANCH CIRCUIT.
D ALL SINGLE FACE EXIT SIGNS ARE TYPE 'X1' AND SHALL BE WIRED TO THE NEAREST
UNSWITCHED LIGHTING BRANCH CIRCUIT.
E ALL DOUBLE FACED EXIT SIGNS ARE TYPE 'X2' AND SHALL BE WIRED TO THE NEAREST
UNSWITCHES LIGHTING BRANCH CIRCUIT.
F ALL 277VAC LIGHTING BRANCH CIRCUITS ARE PROVIDED FROM PANEL '43UP1', CIRCUIT NUMBER
AS INDICATED, UNO.
G ALL 277VAC POWER BRANCH CIRCUITS ARE PROVIDED FROM PANEL '43P1A', CIRCUIT NUMBER
AS INDICATED, UNO.
H ALL 120VAC POWER BRANCH CIRCUITS ARE PROVIDED FROM PANEL '43L1A', CIRCUIT NUMBER
AS INDICATED, UNO.
I HOMERUNS SHALL CONTAIN NO MORE THAN (3) THREE BRANCH CIRCUITS.
J THE MINIMUM WIRING SIZE FOR LEVEL 1 BRANCH CIRCUITS IS 2#12, 1#12G. IN 3/4"C.
K THE MINIMUM WIRING SIZE FOR LEVEL 2 BRANCH CIRCUITS IS 2#10, 1#10G. IN 3/4"C.
M THE MINIMUM WIRING SIZE FOR ROOF LEVEL BRANCH CIRCUITS IS 2#8, 1#8G. IN 3/4"C.
N ALL WALL MOUNTED OCCUPANCY SENSOR SHALL BE DUAL TECHNOLOGY, PROGRAM FOR AUTO
ON/AUTO OFF CONTROL. WATTSTOPPER #DW300 SERIES OR EQUAL
O PROVIDE EQUIPMENT LABELS PER SPECIFICATIONS 260511, 1.11 INCLUDING ALL UTILIZATION
EQUIPMENT, FACEPLATES AND JBOX COVERS.
OPEN TO
ABOVE
OPEN TO
ABOVE
NTS
F2
LIGHTING CONTROL PANEL DETAIL
11-01-2019Revisions: Date:
11-25-2019
7/20/2022
MATHEW PERKINS
NO.005843
E
D
C
B
A
TOILET,
STAFF
SHOWER/CHANGE
VESTIBULE
L2, 43UP1- 8,
L2, 43UP1- 8,
L2, 43UP1- 8,
L2, 43UP1- 8,
X1, 43UP1- 8,
D1, 43UP1- 9, D1, 43UP1- 9,
G2, 43UP1- 9,
G2, 9, NL
X1, 43UP1- 9, X1, 43UP1- 9,
/E3 EL101C
F
E
L A
F
E
L A
OPEN TO
ABOVE
L2, 43UP1- 8,
43UP1- 8,
43UP1- 9,
43UP1- 6,
43UP1- 8,
W1, 43UP1- 6,
43UP1- 6,
BLDG 43
43A
CHILLER
ROOM
MA-109
NORT
H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
KEY PLAN
B
B
B
IM
/5
-1
-1
O p ti m iz e B
E n e rg y P la n t
/5
V A
A B
Q B
E L
E C
.r v t
/2 /2
:2
:3
A M
EL101B
ELECTRICAL LIGHTING PLAN - LEVEL 1 - AREA
B
TRIPLE C THE A/E GROUP
1839 S. Alma School Rd., Ste.
Mesa, AZ 85210
307-460-2054
Mat Perkins
UPGRADE ENERGY PLANT
EQUIPMENT INFRASTRUCTURE
(BLDG. 43 & 43A)
1501 SAN PEDRO SE ALBUQUERQUE, NM 87108
501-17-105
11-01-2019 J. LOHL J. HALPIN
100% CONSTRUCTION
DOCUMENTS
GENERAL SHEET NOTES
KEYNOTES
1 EXISTING LIGHT FIXTURE (SHOWN HALFTONE), WIRE TO SWITCHED CIRCUIT
INDICATED, TYPICAL.
2 SURFACE MOUNT THE LIGH FIXTURE TO STRUCTURAL STEEL IN THIS GENERAL
LOCATION. TYPICAL THIS ROW.
3 WIRE LIGHTS TO CHILLER ROOM LIGHTING.
4 WIRE LIGHT FIXTURE INTO THE NEW EXTERIOR LIGHTING CIRCUIT INDICATED.
LIGHTS ARE CONTROLLER THROUGH THE LIGHTING CONTROL PANEL '43LCP'.
5 EXISTING LIGHT FIXTURE (SHOWN HALFTONE) TO REMAIN.
6 WIRE NEW EXIT SIGN INTO UNSWITCHED LIGHTING CIRCUIT SERVING THIS
ROOM.
1/4" = 1'-0" F4
LIGHTING PLAN - LEVEL 1 - AREA B
A ALL EQUIPMENT AND DEVICES SHOWN HALFTONE ARE EXISTING TO REMAIN, UNO.
B ALL LIGHTS ARE CONTROLLED BY THE LIGHT SWITCH(ES) OR OCCUPANCY SENSOR(S) LOCATED
IN THE ROOM, UNO.
C ALL LUMINAIRES NOTATED AS 'NL' ARE UNSWITCHED NIGHT LIGHTS, WIRED TO AN UNSWITCHED, 277VA LIGHTING BRANCH CIRCUIT.
D ALL SINGLE FACE EXIT SIGNS ARE TYPE 'X1' AND SHALL BE WIRED TO THE NEAREST
UNSWITCHED LIGHTING BRANCH CIRCUIT.
E ALL DOUBLE FACED EXIT SIGNS ARE TYPE 'X2' AND SHALL BE WIRED TO THE NEAREST
UNSWITCHES LIGHTING BRANCH CIRCUIT.
F ALL 277VAC LIGHTING BRANCH CIRCUITS ARE PROVIDED FROM PANEL '43UP1', CIRCUIT NUMBER
AS INDICATED, UNO.
G ALL 277VAC POWER BRANCH CIRCUITS ARE PROVIDED FROM PANEL '43P1A', CIRCUIT NUMBER
AS INDICATED, UNO.
H ALL 120VAC POWER BRANCH CIRCUITS ARE PROVIDED FROM PANEL '43L1A', CIRCUIT NUMBER
AS INDICATED, UNO.
I HOMERUNS SHALL CONTAIN NO MORE THAN (3) THREE BRANCH CIRCUITS.
J THE MINIMUM WIRING SIZE FOR LEVEL 1 BRANCH CIRCUITS IS 2#12, 1#12G. IN 3/4"C.
K THE MINIMUM WIRING SIZE FOR LEVEL 2 BRANCH CIRCUITS IS 2#10, 1#10G. IN 3/4"C.
M THE MINIMUM WIRING SIZE FOR ROOF LEVEL BRANCH CIRCUITS IS 2#8, 1#8G. IN 3/4"C.
N ALL WALL MOUNTED OCCUPANCY SENSOR SHALL BE DUAL TECHNOLOGY, PROGRAM FOR AUTO
ON/AUTO OFF CONTROL. WATTSTOPPER #DW300 SERIES OR EQUAL
O PROVIDE EQUIPMENT LABELS PER SPECIFICATIONS 260511, 1.11 INCLUDING ALL UTILIZATION
EQUIPMENT, FACEPLATES AND JBOX COVERS.
11-01-2019Revisions: Date:
11-25-2019
7/20/2022
MATHEW PERKINS
NO.005843
O O
L
L
L
LO
3 4 5 6
E
HOUSEKEEPING
AIDS
CLOSET
CHEMICAL
TESTING
ROOM
CORRIDOR
MA-122
TOILET,
STAFF
TOILET,
STAFF
LOUNGE
ENGINEERING
CONTROL
CENTER
CORRIDOR
G2, 43UP1- 9, a
G2, 43UP1- 9, a
G2, 43UP1- 9, a
G2, 43UP1- 9, a
G2, 43UP1- 9, aG2, 43UP1- 9, a
G2, 43UP1- 9,
G2, 43UP1- 9,
G2, 43UP1- 9,
W1, 43UP1- 6,
F
E
L B
F
E
L A
W1, 43UP1- 6,
W1, 43UP1- 6,
W1, 43UP1- 6,
a a a
G3, 43UP1- 9,
G1, 43UP1- 9, a
G3, 43UP1- 9,
b b 23
G2, 43UP1- 4, b
G2, 43UP1- 4, b
G2, 43UP1- 4, b
G2, 43UP1- 4, b
G1, 43UP1- 9, a
G1, 43UP1- 9, a
G1, 43UP1- 9, a
X1, 43UP1- 4,
X1, 43UP1- 4,
NORT
H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
KEY PLAN
C
B
IM
/5
-1
-1
O p ti m iz e B
E n e rg y P la n t
/5
V A
A B
Q B
E L
E C
.r v t
/2 /2
:2
:4
A M
EL101C
ELECTRICAL LIGHTING PLAN - LEVEL 1 - AREA
C
TRIPLE C THE A/E GROUP
1839 S. Alma School Rd., Ste.
Mesa, AZ 85210
307-460-2054
Mat Perkins
UPGRADE ENERGY PLANT
EQUIPMENT INFRASTRUCTURE
(BLDG. 43 & 43A)
1501 SAN PEDRO SE ALBUQUERQUE, NM 87108
501-17-105
11-01-2019 J. LOHL J. HALPIN
100% CONSTRUCTION
DOCUMENTS
GENERAL SHEET NOTES
KEYNOTES
1 WIRE LIGHT FIXTURE INTO THE NEW EXTERIOR LIGHTING CIRCUIT INDICATED.
LIGHTS ARE CONTROLLER THROUGH THE LIGHTING CONTROL PANEL '43LCP'.
2 CEILING MOUNTED, AMBIENT LIGHT LEVEL SENSOR FOR CONTROL OF AREA
LIGHTING, SWITCH ID AND AMBIENT LIGHT LEVEL INDICATED. SENSOR SHALL
AUTOMATICALLY DIM THE LIGHTS WHEN THE AMBIENT LIGHT LEVEL MEETS THE
INDICATED LIGHT LEVEL. nLIGHT #nCMA SERIES WITH ALL REQUIRED
ACCESSORES OR APPROVED EQUAL.
3 CEILING MOUNTED, DUAL TECHNOLOGY OCCUPANCY SENSOR. SHALL
AUTOMATICALLY TURN LIGHTS ON/OFF DEPENDING UPON OCCUPANCY. THE
OCCUPANCY SENSOR IS WIRE UPSTREAM OF THE AMBIENT LIGHT LEVEL
SENSOR IN ROOM WHICH WILL DIM THE LIGHTS ACCORDINGLY WHILE THE
ROOM IS OCCUPIED. nLIGHT #nCM SERIES OR APPROVED EQUAL.
4 WIRE NEW EXIT SIGN INTO UNSWITCHED LIGHTING CIRCUIT SERVING THIS
ROOM.
1/4" = 1'-0" E3
LIGHTING PLAN - LEVEL 1 - AREA C
A ALL EQUIPMENT AND DEVICES SHOWN HALFTONE ARE EXISTING TO REMAIN, UNO.
B ALL LIGHTS ARE CONTROLLED BY THE LIGHT SWITCH(ES) OR OCCUPANCY SENSOR(S) LOCATED
IN THE ROOM, UNO.
C ALL LUMINAIRES NOTATED AS 'NL' ARE UNSWITCHED NIGHT LIGHTS, WIRED TO AN UNSWITCHED, 277VA LIGHTING BRANCH CIRCUIT.
D ALL SINGLE FACE EXIT SIGNS ARE TYPE 'X1' AND SHALL BE WIRED TO THE NEAREST
UNSWITCHED LIGHTING BRANCH CIRCUIT.
E ALL DOUBLE FACED EXIT SIGNS ARE TYPE 'X2' AND SHALL BE WIRED TO THE NEAREST
UNSWITCHES LIGHTING BRANCH CIRCUIT.
F ALL 277VAC LIGHTING BRANCH CIRCUITS ARE PROVIDED FROM PANEL '43UP1', CIRCUIT NUMBER
AS INDICATED, UNO.
G ALL 277VAC POWER BRANCH CIRCUITS ARE PROVIDED FROM PANEL '43P1A', CIRCUIT NUMBER
AS INDICATED, UNO.
H ALL 120VAC POWER BRANCH CIRCUITS ARE PROVIDED FROM PANEL '43L1A', CIRCUIT NUMBER
AS INDICATED, UNO.
I HOMERUNS SHALL CONTAIN NO MORE THAN (3) THREE BRANCH CIRCUITS.
J THE MINIMUM WIRING SIZE FOR LEVEL 1 BRANCH CIRCUITS IS 2#12, 1#12G. IN 3/4"C.
K THE MINIMUM WIRING SIZE FOR LEVEL 2 BRANCH CIRCUITS IS 2#10, 1#10G. IN 3/4"C.
M THE MINIMUM WIRING SIZE FOR ROOF LEVEL BRANCH CIRCUITS IS 2#8, 1#8G. IN 3/4"C.
N ALL WALL MOUNTED OCCUPANCY SENSOR SHALL BE DUAL TECHNOLOGY, PROGRAM FOR AUTO
ON/AUTO OFF CONTROL. WATTSTOPPER #DW300 SERIES OR EQUAL
O PROVIDE EQUIPMENT LABELS PER SPECIFICATIONS 260511, 1.11 INCLUDING ALL UTILIZATION
EQUIPMENT, FACEPLATES AND JBOX COVERS.
11-01-2019Revisions: Date:
11-25-2019
7/20/2022
MATHEW PERKINS
NO.005843
OO
1 2 3 4
E
D
C
B
A
NEW
ELECTRICAL
MA-211
NEW OFFICE
MA-204
NEW OFFICE
MA-218
W1, 43UP1- 6,
W1, 43UP1- 6,
X1, 43P1A- 1, X1, 43P1A- 1, X1
X1, 43P1A- 1, G1, 43UP1- 10,
G1, 43UP1- 10, G1, 43UP1- 10,
F
E
L B
F
E
L B
L2E, 43P1A- 1, L2E, 43P1A- 1, L2E, 43P1A- 1, L2E, 43P1A- 1, L2E, 43P1A- 1, L2E, 43P1A- 1, L2E, 43P1A- 1, L2E, 43P1A- 1, L2E, 43P1A- 1, L2E, 43P1A- 1,L2E, 1, OPEN TO
BELOW
43PSB2A
43TUSS
2OPEN TO
BELOW
L2E, 43P1A- 1, H1, 43UP1- 7, H1, 43UP1- 7, H1, 43UP1- 7,
H1, 43UP1- 7, H1, 43UP1- 7, H1, 43UP1- 7,
H1, 43UP1- 7, H1, 43UP1- 7, H1, 43UP1- 7,
H1, 43UP1- 7, H1, 43UP1- 7,
H1, 43UP1- 7,
43UP1- 2,
43UP1- 2,
43UP1- 2,
43UP1- 2,
BOILER
PLANT
MA-108
BOILER
PLANT
MA-105
BOILER
ROOM -
MEZZANINE
MA-200
L1, 43UP1- 7,
L1, 43UP1- 7,
L1, 43UP1- 7,
L1, 43UP1- 7,
X1, 43UP1- 10,
L1, L1, NC26FHR-18 NC26FHR-18
G1, 43UP1- 10,
NORT
H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
KEY PLAN
A
B
IM
/5
-1
-1
O p ti m iz e B
E n e rg y P la n t
/5
V A
A B
Q B
E L
E C
.r v t
/2 /2
:2
:4
A M
EL102A
ELECTRICAL LIGHTING PLAN - LEVEL 2 - AREA
A
TRIPLE C THE A/E GROUP
1839 S. Alma School Rd., Ste.
Mesa, AZ 85210
307-460-2054
Mat Perkins
UPGRADE ENERGY PLANT
EQUIPMENT INFRASTRUCTURE
(BLDG. 43 & 43A)
1501 SAN PEDRO SE ALBUQUERQUE, NM 87108
501-17-105
11-01-2019 J. LOHL J. HALPIN
100% CONSTRUCTION
DOCUMENTS
GENERAL SHEET NOTES
KEYNOTES
1/4" = 1'-0" F4
LIGHTING PLAN - LEVEL 2 - AREA A
1 WIRE NEW LIGHTS TO CIRCUIT INDICATED. THE EXISTING ROOM CONTROL
SCHEME SHALL REMAIN THE SAME, WIRE AS REQURED.
2 COORDINATE THE FINAL LOCATION OF PENDANT MOUNTING LIGHTS WITH
MECHANICAL DUCTWORK AND PIPING, TYPICAL.
3 PENDANT MOUNT THE LIGHTS IN THIS ROOM AT 11'-6" AFF.
4 WIRE LIGHT FIXTURE INTO THE NEW EXTERIOR LIGHTING CIRCUIT INDICATED.
LIGHTS ARE CONTROLLER THROUGH THE LIGHTING CONTROL PANEL '43LCP'.
5 INSTALL NEW OCCUPANCY SENSOR ON EXITING BACKBOX AND WIRE TO
CONTROL ROOM LIGHTING.
6 LIGHTING IN THIS ROOM IS CONTROLLED THROUGH THE LIGHTING CONTROL
PANEL '43LCP.
7 MEZZANINE LIGHTING IS CONTROLLED WITH THE CHILLER ROOM LIGHTING.
11 WIRE NEW EXIT SIGN INTO UNSWITCHED LIGHTING CIRCUIT SERVING THIS
ROOM.
A ALL EQUIPMENT AND DEVICES SHOWN HALFTONE ARE EXISTING TO REMAIN, UNO.
B ALL LIGHTS ARE CONTROLLED BY THE LIGHT SWITCH(ES) OR OCCUPANCY SENSOR(S) LOCATED
IN THE ROOM, UNO.
C ALL LUMINAIRES NOTATED AS 'NL' ARE UNSWITCHED NIGHT LIGHTS, WIRED TO AN UNSWITCHED, 277VA LIGHTING BRANCH CIRCUIT.
D ALL SINGLE FACE EXIT SIGNS ARE TYPE 'X1' AND SHALL BE WIRED TO THE NEAREST
UNSWITCHED LIGHTING BRANCH CIRCUIT.
E ALL DOUBLE FACED EXIT SIGNS ARE TYPE 'X2' AND SHALL BE WIRED TO THE NEAREST
UNSWITCHES LIGHTING BRANCH CIRCUIT.
F ALL 277VAC LIGHTING BRANCH CIRCUITS ARE PROVIDED FROM PANEL '43UP1', CIRCUIT NUMBER
AS INDICATED, UNO.
G ALL 277VAC POWER BRANCH CIRCUITS ARE PROVIDED FROM PANEL '43P1A', CIRCUIT NUMBER
AS INDICATED, UNO.
H ALL 120VAC POWER BRANCH CIRCUITS ARE PROVIDED FROM PANEL '43L1A', CIRCUIT NUMBER
AS INDICATED, UNO.
I HOMERUNS SHALL CONTAIN NO MORE THAN (3) THREE BRANCH CIRCUITS.
J THE MINIMUM WIRING SIZE FOR LEVEL 1 BRANCH CIRCUITS IS 2#12, 1#12G. IN 3/4"C.
K THE MINIMUM WIRING SIZE FOR LEVEL 2 BRANCH CIRCUITS IS 2#10, 1#10G. IN 3/4"C.
M THE MINIMUM WIRING SIZE FOR ROOF LEVEL BRANCH CIRCUITS IS 2#8, 1#8G. IN 3/4"C.
N ALL WALL MOUNTED OCCUPANCY SENSOR SHALL BE DUAL TECHNOLOGY, PROGRAM FOR AUTO
ON/AUTO OFF CONTROL. WATTSTOPPER #DW300 SERIES OR EQUAL
O PROVIDE EQUIPMENT LABELS PER SPECIFICATIONS 260511, 1.11 INCLUDING ALL UTILIZATION
EQUIPMENT, FACEPLATES AND JBOX COVERS.
11-01-2019Revisions: Date:
11-25-2019
7/20/2022
MATHEW PERKINS
NO.005843
O O O
4 5 6
E
D
C
B
A
CORRIDOR
MA-202
TELECOM
MA-219
OFFICE
MA-205
OFFICE
MA-203
G2, 43UP1- 10,
G2, 43UP1- 10,
G2, 43UP1- 10,
G2, 43UP1- 10,
G2, 43UP1- 10,
G2, 43UP1- 10,
G2, 43UP1- 10, G2, 43UP1- 10, G2, 43UP1- 10,
F
E
L A
F
E
L A
2 2 2
OPEN TO
BELOW
H1, 43UP1- 8, H1, 43UP1- 8,
H1, 43UP1- 8, H1, 43UP1- 8,
H1, 43UP1- 8, H1, 43UP1- 8,
H1, 43UP1- 8,
H1, 43UP1- 8,
1 1 1
W1, 43UP1- 6,
X1, 43UP1- 10, X1, 43UP1- 10,
W1, 43UP1- 6,
NORT
H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
KEY PLAN
B
B
B
IM
/5
-1
-1
O p ti m iz e B
E n e rg y P la n t
/5
V A
A B
Q B
E L
E C
.r v t
/2 /2
:2
:5
A M
EL102B
ELECTRICAL LIGHTING PLAN - LEVEL 2 - AREA
B
TRIPLE C THE A/E GROUP
1839 S. Alma School Rd., Ste.
Mesa, AZ 85210
307-460-2054
Mat Perkins
UPGRADE ENERGY PLANT
EQUIPMENT INFRASTRUCTURE
(BLDG. 43 & 43A)
1501 SAN PEDRO SE ALBUQUERQUE, NM 87108
501-17-105
11-01-2019 J. LOHL J. HALPIN
100% CONSTRUCTION
DOCUMENTS
GENERAL SHEET NOTES
KEYNOTES
1/4" = 1'-0" F4
LIGHTING PLAN - LEVEL 2 - AREA B
A ALL EQUIPMENT AND DEVICES SHOWN HALFTONE ARE EXISTING TO REMAIN, UNO.
B ALL LIGHTS ARE CONTROLLED BY THE LIGHT SWITCH(ES) OR OCCUPANCY SENSOR(S) LOCATED
IN THE ROOM, UNO.
C ALL LUMINAIRES NOTATED AS 'NL' ARE UNSWITCHED NIGHT LIGHTS, WIRED TO AN UNSWITCHED, 277VA LIGHTING BRANCH CIRCUIT.
D ALL SINGLE FACE EXIT SIGNS ARE TYPE 'X1' AND SHALL BE WIRED TO THE NEAREST
UNSWITCHED LIGHTING BRANCH CIRCUIT.
E ALL DOUBLE FACED EXIT SIGNS ARE TYPE 'X2' AND SHALL BE WIRED TO THE NEAREST
UNSWITCHES LIGHTING BRANCH CIRCUIT.
F ALL 277VAC LIGHTING BRANCH CIRCUITS ARE PROVIDED FROM PANEL '43UP1', CIRCUIT NUMBER
AS INDICATED, UNO.
G ALL 277VAC POWER BRANCH CIRCUITS ARE PROVIDED FROM PANEL '43P1A', CIRCUIT NUMBER
AS INDICATED, UNO.
H ALL 120VAC POWER BRANCH CIRCUITS ARE PROVIDED FROM PANEL '43L1A', CIRCUIT NUMBER
AS INDICATED, UNO.
I HOMERUNS SHALL CONTAIN NO MORE THAN (3) THREE BRANCH CIRCUITS.
J THE MINIMUM WIRING SIZE FOR LEVEL 1 BRANCH CIRCUITS IS 2#12, 1#12G. IN 3/4"C.
K THE MINIMUM WIRING SIZE FOR LEVEL 2 BRANCH CIRCUITS IS 2#10, 1#10G. IN 3/4"C.
M THE MINIMUM WIRING SIZE FOR ROOF LEVEL BRANCH CIRCUITS IS 2#8, 1#8G. IN 3/4"C.
N ALL WALL MOUNTED OCCUPANCY SENSOR SHALL BE DUAL TECHNOLOGY, PROGRAM FOR AUTO
ON/AUTO OFF CONTROL. WATTSTOPPER #DW300 SERIES OR EQUAL
O PROVIDE EQUIPMENT LABELS PER SPECIFICATIONS 260511, 1.11 INCLUDING ALL UTILIZATION
EQUIPMENT, FACEPLATES AND JBOX COVERS.
1 WIRE NEW LIGHTS TO CIRCUIT INDICATED. THE EXISTING ROOM CONTROL
SCHEME SHALL REMAIN THE SAME, WIRE AS REQURED.
2 REPLACE EXISTING SINGLE POLE LIGHT SWITCH WITH A WALL MOUNTED
OCCUPANCY SENSOR. DEVICE WIRING SHALL REMAIN UNCHANGED.
3 COORDINATE THE FINAL LOCATION OF PENDANT MOUNTING LIGHTS WITH
MECHANICAL DUCTWORK AND PIPING, TYPICAL.
4 LIGHTING IN THIS ROOM IS CONTROLLED THROUGH THE LIGHTING CONTROL
PANEL '43LCP.
5 WIRE LIGHT FIXTURE INTO THE NEW EXTERIOR LIGHTING CIRCUIT INDICATED.
LIGHTS ARE CONTROLLER THROUGH THE LIGHTING CONTROL PANEL '43LCP'.
6 WIRE NEW EXIT SIGN INTO UNSWITCHED LIGHTING CIRCUIT SERVING THIS
ROOM.
11-01-2019Revisions: Date:
11-25-2019
7/20/2022
MATHEW PERKINS
NO.005843
F
T
EPO
PB
EPO
PB
V VV V V V
P B
P B
T
T
F
F
1 2 3 4
E
D
C
B
A
ECLA(E)
ECPA(E)
A(E)
GENERATOR
ROOM
MA-106
ELECTRICAL
ROOM
MA-107
Unoccupied
Unoccupied
VESTIBULE
MA-120
1750kW
EG-1(E)
43L1A
43P1A
EQHA(E)
F
E
P B
F
E
P B
MANOLE #16 (E)
PADMOUNT
SWITCH(E)
PADMOUNT
SWITCH(E)
GCP
43UL1
43L1A- 17
MCCNP(E)
NC26FHR(E)
BFD-43-ML (E)
CST-43-ML (E)
NLSS(E)
WATER
TREATMENT
(E)
43T1A 43TU1
43UP1
43L1A- 19 43L1A- 19
43L1A- 19
43L1A- 19
FCU-121
43L1A- 2
43L1A- 4
43L1A- 4
43-SWHX-1
MV_ATS
8FT CLEARANCE
CONTROL
PANEL 'B'
CONTROL
PANEL 'A'
43L1A- 19
43-SWHX-1
43L1A- 36
FCU-100
NORT
H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
KEY PLAN
A
B
IM
/5
-1
-1
O p ti m iz e B
E n e rg y P la n t
/5
V A
A B
Q B
E L
E C
.r v t
/2 /2
:2
:5
A M
EP101A
ELECTRICAL POWER PLAN - LEVEL 1 - AREA A
TRIPLE C THE A/E GROUP
1839 S. Alma School Rd., Ste.
Mesa, AZ 85210
307-460-2054
Mat Perkins
UPGRADE ENERGY PLANT
EQUIPMENT INFRASTRUCTURE
(BLDG. 43 & 43A)
1501 SAN PEDRO SE…