This file is an electrical distribution system condition assessment report for the Honolulu Veterans Affairs Medical Center (VAMC), prepared by E.K. Fox & Associates, Ltd. The comprehensive assessment evaluates the condition of the facility's electrical infrastructure, including medium and low voltage distribution systems, grounding systems, emergency/standby electrical systems, and transformer components. The report provides a detailed analysis of equipment conditions using a grading methodology ranging from A (like new) to F (critical), with specific focus on identifying components that require replacement or upgrades.
Key findings include a total recommended correction cost of $261,488 across four buildings (E-Wing, ACC, Parking Garage, and CFA), with priority ratings assigned to various electrical system components. Notable recommendations include replacing generators, automatic transfer switches, circuit breakers, and transformers that are past their service life or have specific technical deficiencies. The assessment highlights that while most of the electrical system is in good condition, several components need attention, particularly around ground fault protection, equipment clearances, and coordination of electrical protective devices. The report provides a systematic breakdown of equipment conditions, useful life remaining, and estimated replacement costs to support future maintenance and upgrade planning.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
110-CB-DPLSH
SIEMENS
FXD6-A Sentron
FXD6-A
Trip 100.0 A Plug 100.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) HI (1200A)
110-CB-DPLSH-1
SIEMENS
BQD
BQD
Trip 30.0 A Plug 30.0 A Settings Phase Fixed
110-CB-DPLSH-2
SIEMENS
BQD
BQD
Trip 100.0 A Plug 100.0 A Settings Phase Fixed
110-CB-DPLSH-3
SIEMENS
BQD
BQD
Trip 50.0 A Plug 50.0 A Settings Phase Fixed
110-CB-DPLSH
SIEMENS
FXD6-A Sentron
FXD6-A
Trip 100.0 A Plug 100.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) HI (1200A)
110-CB-DPLSH-1
SIEMENS
BQD
BQD
Trip 30.0 A Plug 30.0 A Settings Phase Fixed
110-CB-DPLSH-2
SIEMENS
BQD
BQD
Trip 100.0 A Plug 100.0 A Settings Phase Fixed
110-CB-DPLSH-3
SIEMENS
BQD
BQD
Trip 50.0 A Plug 50.0 A Settings Phase Fixed
110-CB-DPLSH
110-BUS-DPLSH
110-CB-DPLSH-1
110-CB-DPLSH-2
110-CB-DPLSH-3
TCC Comments: Replacement of 110-CB-DPLSH-2 suggested for improved coordination.
TCC: 110_DPLSH Current Scale x 1 Reference Voltage: 480 January 27, 2020 VAMC Honolulu (Existing) SKM Systems Analysis, Inc.
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
110-CB-DPLSH
SIEMENS
FXD6-A Sentron
FXD6-A
Trip 100.0 A Plug 100.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) HI (1200A)
110-CB-DPLSH-1
SIEMENS
BQD
BQD
Trip 30.0 A Plug 30.0 A Settings Phase Fixed
110-CB-DPLSH-2
SIEMENS
BQD
BQD
Trip 70.0 A Plug 70.0 A Settings Phase Fixed
110-CB-DPLSH-3
SIEMENS
BQD
BQD
Trip 50.0 A Plug 50.0 A Settings Phase Fixed
110-CB-DPLSH
SIEMENS
FXD6-A Sentron
FXD6-A
Trip 100.0 A Plug 100.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) HI (1200A)
110-CB-DPLSH-1
SIEMENS
BQD
BQD
Trip 30.0 A Plug 30.0 A Settings Phase Fixed
110-CB-DPLSH-2
SIEMENS
BQD
BQD
Trip 70.0 A Plug 70.0 A Settings Phase Fixed
110-CB-DPLSH-3
SIEMENS
BQD
BQD
Trip 50.0 A Plug 50.0 A Settings Phase Fixed
110-CB-DPLSH
110-BUS-DPLSH
110-CB-DPLSH-1
110-CB-DPLSH-2
110-CB-DPLSH-3
TCC Comments: 110-CB-DPLSH-2 replaced with 70A equivalent breaker.
TCC: 110_DPLSH Current Scale x 1 Reference Voltage: 480 January 27, 2020 VAMC Honolulu (Recommended) SKM Systems Analysis, Inc.
110-CBL-NL1 (2)110-CBL-NL1 (2)-1110-CBL-NL1 (2)-2
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
110-CB-NL1 (1)-MAIN
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) 3 (2570A)
110-CB-NL1 (2)-1
SIEMENS
QJH2
QJH2
Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (2650A)
110-CB-NL1 (2)-2
SIEMENS
QJH2
QJH2
Trip 150.0 A Plug 150.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (1750A)
110-CB-NKL1-MAIN
SIEMENS
QJH2
QJH2
Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (2650A)
110-CB-NDL1-MAIN
SIEMENS
QJH2
QJH2
Trip 150.0 A Plug 150.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (1750A)
110-CBL-NL1 (2)
110-CBL-NL1 (2)-1
110-CBL-NL1 (2)-2
110-CB-NL1 (1)-MAIN
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) 3 (2570A)
110-CB-NL1 (2)-1
SIEMENS
QJH2
QJH2
Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (2650A)
110-CB-NL1 (2)-2
SIEMENS
QJH2
QJH2
Trip 150.0 A Plug 150.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (1750A)
110-CB-NKL1-MAIN
SIEMENS
QJH2
QJH2
Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (2650A)
110-CB-NDL1-MAIN
SIEMENS
QJH2
QJH2
Trip 150.0 A Plug 150.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (1750A)
110-CBL-NL1 (2)
110-CBL-NL1 (2)-1
110-CBL-NL1 (2)-2
110-CB-NL1 (1)-MAIN
110-BUS-NL1 (1)
110-CBL-NL1 (2)
110-BUS-NL1 (2)
110-CB-NL1 (2)-1 110-CB-NL1 (2)-2
110-CBL-NL1 (2)-1
110-CB-NKL1-MAIN
110-BUS-NKL1 110-BUS-NDL1
110-CB-NDL1-MAIN
110-CBL-NL1 (2)-2
TCC Comments: Adjustment to 110-CB-NL1 (1)-MAIN trip settings suggested for improved coordination.
TCC: 110_MSB - DPNH - NH1 - NL1 Current Scale x 1 Reference Voltage: 208 January 29, 2020 VAMC Honolulu (Existing) SKM Systems Analysis, Inc.
110-CBL-NL1 (2)110-CBL-NL1 (2)-1110-CBL-NL1 (2)-2
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
110-CB-NL1 (1)-MAIN
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) HI (4000A)
110-CB-NL1 (2)-1
SIEMENS
QJH2
QJH2
Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (2650A)
110-CB-NL1 (2)-2
SIEMENS
QJH2
QJH2
Trip 150.0 A Plug 150.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (1750A)
110-CB-NKL1-MAIN
SIEMENS
QJH2
QJH2
Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (2650A)
110-CB-NDL1-MAIN
SIEMENS
QJH2
QJH2
Trip 150.0 A Plug 150.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (1750A)
110-CBL-NL1 (2)
110-CBL-NL1 (2)-1
110-CBL-NL1 (2)-2
110-CB-NL1 (1)-MAIN
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) HI (4000A)
110-CB-NL1 (2)-1
SIEMENS
QJH2
QJH2
Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (2650A)
110-CB-NL1 (2)-2
SIEMENS
QJH2
QJH2
Trip 150.0 A Plug 150.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (1750A)
110-CB-NKL1-MAIN
SIEMENS
QJH2
QJH2
Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (2650A)
110-CB-NDL1-MAIN
SIEMENS
QJH2
QJH2
Trip 150.0 A Plug 150.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (1750A)
110-CBL-NL1 (2)
110-CBL-NL1 (2)-1
110-CBL-NL1 (2)-2
110-CB-NL1 (1)-MAIN
110-BUS-NL1 (1)
110-CBL-NL1 (2)
110-BUS-NL1 (2)
110-CB-NL1 (2)-1 110-CB-NL1 (2)-2
110-CBL-NL1 (2)-1
110-CB-NKL1-MAIN
110-BUS-NKL1 110-BUS-NDL1
110-CB-NDL1-MAIN
110-CBL-NL1 (2)-2
TCC Comments: 110-CB-NL1 (1)-MAIN adjustments include INST from 3 to HI.
TCC: 110_MSB - DPNH - NH1 - NL1 Current Scale x 1 Reference Voltage: 208 January 29, 2020 VAMC Honolulu (Recommended) SKM Systems Analysis, Inc.
110-CBL-DPNH-1110-CBL-NH1-1
TX Inrush
110-XF-T3110-CBL-NL1 (1)
0.5
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
110-CB-DPNH-1
SIEMENS
JG, ETU 555 GF Mod
NJG
Trip 400.0 A Plug 400.0 A Settings Phase LTPU (Ir) 400A (400A) LTD (tr) 20 STPU (Isd) 8 (3200A) STD (tsd) I2T-OFF 0.1 (I^s T Off) INST (Ii) 11 (4400A)
110-CB-NH1-MAIN
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (2000A)
110-CB-NH1-1
SIEMENS
FD6-A Sentron
FD6-A
Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) 5 (1900A)
110-CB-NL1 (1)-MAIN
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) 3 (2570A)
110-CBL-DPNH-1
110-CBL-NH1-1
110-XF-T3
Pri: 480 V Sec: 208 V
112.5 kVA
110-CBL-NL1 (1)
110-CB-DPNH-1
SIEMENS
JG, ETU 555 GF Mod
NJG
Trip 400.0 A Plug 400.0 A Settings Phase LTPU (Ir) 400A (400A) LTD (tr) 20 STPU (Isd) 8 (3200A) STD (tsd) I2T-OFF 0.1 (I^s T Off) INST (Ii) 11 (4400A)
110-CB-NH1-MAIN
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (2000A)
110-CB-NH1-1
SIEMENS
FD6-A Sentron
FD6-A
Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) 5 (1900A)
110-CB-NL1 (1)-MAIN
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) 3 (2570A)
110-CBL-DPNH-1
110-CBL-NH1-1
110-XF-T3
Pri: 480 V Sec: 208 V
112.5 kVA
110-CBL-NL1 (1)
110-CB-DPNH-1
110-CB-DPNH-12 (GF)
110-CBL-DPNH-1
110-CB-NH1-MAIN
110-BUS-NH1
110-CB-NH1-1
110-CBL-NH1-1
110-BUS-XF T3-PRI
S
P
110-XF-T3
110-BUS-XF T3-SEC
110-CBL-NL1 (1)
110-CB-NL1 (1)-MAIN
110-BUS-NL1 (1)
TCC Comments: Adjustment to 110-CB-DPNH-1, 110-CB-NH1-MAIN, and 110-CB-NL1 (1)-MAIN trip settings suggested for improved coordination.
TCC: 110_MSB - DPNH - NH1 Current Scale x 1 Reference Voltage: 480 January 31, 2020 VAMC Honolulu (Existing) SKM Systems Analysis, Inc.
110-CBL-DPNH-1110-CBL-NH1-1
110-XF-T3110-CBL-NL1 (1)
0.5
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
110-CB-DPNH-1
SIEMENS
JG, ETU 555 GF Mod
HJG
Trip 400.0 A Plug 400.0 A Settings Phase LTPU (Ir) 400A (400A) LTD (tr) 10 STPU (Isd) 6 (2400A) STD (tsd) I2T-OFF 0.1 (I^s T Off) INST (Ii) 11 (4400A)
110-CB-NH1-MAIN
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) 5 (3140A)
110-CB-NH1-1
SIEMENS
FD6-A Sentron
FD6-A
Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) 5 (1900A)
110-CB-NL1 (1)-MAIN
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) HI (4000A)
110-CBL-DPNH-1
110-CBL-NH1-1
110-XF-T3
Pri: 480 V Sec: 208 V
112.5 kVA
110-CBL-NL1 (1)
110-CB-DPNH-1
SIEMENS
JG, ETU 555 GF Mod
HJG
Trip 400.0 A Plug 400.0 A Settings Phase LTPU (Ir) 400A (400A) LTD (tr) 10 STPU (Isd) 6 (2400A) STD (tsd) I2T-OFF 0.1 (I^s T Off) INST (Ii) 11 (4400A)
110-CB-NH1-MAIN
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) 5 (3140A)
110-CB-NH1-1
SIEMENS
FD6-A Sentron
FD6-A
Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) 5 (1900A)
110-CB-NL1 (1)-MAIN
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) HI (4000A)
110-CBL-DPNH-1
110-CBL-NH1-1
110-XF-T3
Pri: 480 V Sec: 208 V
112.5 kVA
110-CBL-NL1 (1)
110-CB-DPNH-1
110-CB-DPNH-12 (GF)
110-CBL-DPNH-1
110-CB-NH1-MAIN
110-BUS-NH1
110-CB-NH1-1
110-CBL-NH1-1
110-BUS-XF T3-PRI
S
P
110-XF-T3
110-BUS-XF T3-SEC
110-CBL-NL1 (1)
110-CB-NL1 (1)-MAIN
110-BUS-NL1 (1)
TCC Comments: 110-CB-DPNH-1 adjustments include LTD from 20 to 10 and STPU from 8 to 6.
110-CB-NH1-MAIN adjustments include INST from LO to 5.
110-CB-NL1 (1)-MAIN adjustments include INST from 3 to HI.
TCC: 110_MSB - DPNH - NH1 Current Scale x 1 Reference Voltage: 480 January 31, 2020 VAMC Honolulu (Recommended) SKM Systems Analysis, Inc.
110-CBL-NL2 (2)110-CBL-NL2 (2)-1110-CBL-NL2 (2)-2
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
110-CB-NL2 (1)-MAIN
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) 3 (2570A)
110-CB-NL2 (2)-1
SIEMENS
BLH, 2 & 3-Pole
BLH
Trip 70.0 A Plug 70.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (675A)
110-CB-NL2A-MAIN
SIEMENS
BLH, 2 & 3-Pole
BLH
Trip 70.0 A Plug 70.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (675A)
110-CB-NL2B-MAIN
SIEMENS
BLH, 2 & 3-Pole
BLH
Trip 70.0 A Plug 70.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (675A)
110-CB-NL2 (2)-2
SIEMENS
BLH, 2 & 3-Pole
BLH
Trip 70.0 A Plug 70.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (675A)
110-CBL-NL2 (2)
110-CBL-NL2 (2)-1
110-CBL-NL2 (2)-2
110-CB-NL2 (1)-MAIN
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) 3 (2570A)
110-CB-NL2 (2)-1
SIEMENS
BLH, 2 & 3-Pole
BLH
Trip 70.0 A Plug 70.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (675A)
110-CB-NL2A-MAIN
SIEMENS
BLH, 2 & 3-Pole
BLH
Trip 70.0 A Plug 70.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (675A)
110-CB-NL2B-MAIN
SIEMENS
BLH, 2 & 3-Pole
BLH
Trip 70.0 A Plug 70.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (675A)
110-CB-NL2 (2)-2
SIEMENS
BLH, 2 & 3-Pole
BLH
Trip 70.0 A Plug 70.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (675A)
110-CBL-NL2 (2)
110-CBL-NL2 (2)-1
110-CBL-NL2 (2)-2
110-CB-NL2 (1)-MAIN
110-BUS-NL2 (1)
110-CBL-NL2 (2)
110-BUS-NL2 (2)
110-CB-NL2 (2)-1
110-CBL-NL2 (2)-1
110-CB-NL2A-MAIN
110-BUS-NL2A 110-BUS-NL2B
110-CB-NL2B-MAIN
110-CBL-NL2 (2)-2
110-CB-NL2 (2)-2
TCC Comments: No adjustments required.
TCC: 110_MSB - DPNH - NH2 - NL2 Current Scale x 1 Reference Voltage: 208
110-CBL-DPNH-2110-CBL-NH2-1
110-XF-T5110-CBL-NL2 (1)
0.5
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
110-CB-DPNH-2
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 350.0 A Plug 350.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (2000A)
110-CB-NH2-MAIN
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 350.0 A Plug 350.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (2000A)
110-CB-NH2-1
SIEMENS
FD6-A Sentron
FD6-A
Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) 5 (1900A)
110-CB-NL2 (1)-MAIN
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) 3 (2570A)
110-CBL-DPNH-2
110-CBL-NH2-1
110-XF-T5
Pri: 480 V Sec: 208 V
112.5 kVA
110-CBL-NL2 (1)
110-CB-DPNH-2
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 350.0 A Plug 350.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (2000A)
110-CB-NH2-MAIN
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 350.0 A Plug 350.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (2000A)
110-CB-NH2-1
SIEMENS
FD6-A Sentron
FD6-A
Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) 5 (1900A)
110-CB-NL2 (1)-MAIN
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) 3 (2570A)
110-CBL-DPNH-2
110-CBL-NH2-1
110-XF-T5
Pri: 480 V Sec: 208 V
112.5 kVA
110-CBL-NL2 (1)
110-CB-DPNH-2
110-CBL-DPNH-2
110-BUS-NH2
110-CB-NH2-MAIN
110-CB-NH2-1
110-CBL-NH2-1
S
P
110-XF-T5
110-BUS-XF T5-PRI
110-BUS-XF T5-SEC
110-CBL-NL2 (1)
110-CB-NL2 (1)-MAIN
110-BUS-NL2 (1)
TCC Comments: Adjustment to 110-CB-NH2-1 trip settings suggested for improved coordination.
TCC: 110_MSB - DPNH - NH2 Current Scale x 1 Reference Voltage: 480
110-CBL-DPNH-2110-CBL-NH2-1
110-XF-T5110-CBL-NL2 (1)
0.5
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
110-CB-DPNH-2
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 350.0 A Plug 350.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (2000A)
110-CB-NH2-MAIN
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 350.0 A Plug 350.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (2000A)
110-CB-NH2-1
SIEMENS
FD6-A Sentron
FD6-A
Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (1100A)
110-CB-NL2 (1)-MAIN
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) 3 (2570A)
110-CBL-DPNH-2
110-CBL-NH2-1
110-XF-T5
Pri: 480 V Sec: 208 V
112.5 kVA
110-CBL-NL2 (1)
110-CB-DPNH-2
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 350.0 A Plug 350.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (2000A)
110-CB-NH2-MAIN
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 350.0 A Plug 350.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (2000A)
110-CB-NH2-1
SIEMENS
FD6-A Sentron
FD6-A
Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (1100A)
110-CB-NL2 (1)-MAIN
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) 3 (2570A)
110-CBL-DPNH-2
110-CBL-NH2-1
110-XF-T5
Pri: 480 V Sec: 208 V
112.5 kVA
110-CBL-NL2 (1)
110-CB-DPNH-2
110-CBL-DPNH-2
110-BUS-NH2
110-CB-NH2-MAIN
110-CB-NH2-1
110-CBL-NH2-1
S
P
110-XF-T5
110-BUS-XF T5-PRI
110-BUS-XF T5-SEC
110-CBL-NL2 (1)
110-CB-NL2 (1)-MAIN
110-BUS-NL2 (1)
TCC Comments: 110-CB-NH2-1 adjustments include INST from 5 to LO.
TCC: 110_MSB - DPNH - NH2 Current Scale x 1 Reference Voltage: 480
110-CBL-NL3 (2)110-CBL-NL3 (2)-1
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
110-CB-NL3 (1)-MAIN
SIEMENS
QJH2
QJH2
Trip 150.0 A Plug 150.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (1750A)
110-CB-NL3 (2)-1
SIEMENS
BLH, 2 & 3-Pole
BLH
Trip 50.0 A Plug 50.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (425A)
110-CB-NL3A-MAIN
GE
THQB
THQB
Trip 50.0 A Plug 50.0 A Settings Phase Fixed
110-CBL-NL3 (2)
110-CBL-NL3 (2)-1
110-CB-NL3 (1)-MAIN
SIEMENS
QJH2
QJH2
Trip 150.0 A Plug 150.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (1750A)
110-CB-NL3 (2)-1
SIEMENS
BLH, 2 & 3-Pole
BLH
Trip 50.0 A Plug 50.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (425A)
110-CB-NL3A-MAIN
GE
THQB
THQB
Trip 50.0 A Plug 50.0 A Settings Phase Fixed
110-CBL-NL3 (2)
110-CBL-NL3 (2)-1
110-CB-NL3 (1)-MAIN
110-BUS-NL3 (1)
110-CBL-NL3 (2)
110-BUS-NL3 (2)
110-CB-NL3 (2)-1
110-CBL-NL3 (2)-1
110-CB-NL3A-MAIN
110-BUS-NL3A
TCC Comments: No adjustments required.
TCC: 110_MSB - DPNH - NH3 - NL3 Current Scale x 1 Reference Voltage: 208
110-CBL-DPNH-3110-CBL-NH3-1
110-XF-T7110-CBL-NL3 (1)
0.5
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
110-CB-DPNH-3
SIEMENS
FXD6 Sentron
FXD6
Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (1100A)
110-CB-NH3-MAIN
SIEMENS
FXD6-A Sentron
FXD6-A
Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (1100A)
110-CB-NH3-1
SIEMENS
BQD
BQD
Trip 70.0 A Plug 70.0 A Settings Phase Fixed
110-CB-NL3 (1)-MAIN
SIEMENS
QJH2
QJH2
Trip 150.0 A Plug 150.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (1750A)
110-CBL-DPNH-3
110-CBL-NH3-1
110-XF-T7
Pri: 480 V Sec: 208 V
45.0 kVA
110-CBL-NL3 (1)
110-CB-DPNH-3
SIEMENS
FXD6 Sentron
FXD6
Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (1100A)
110-CB-NH3-MAIN
SIEMENS
FXD6-A Sentron
FXD6-A
Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (1100A)
110-CB-NH3-1
SIEMENS
BQD
BQD
Trip 70.0 A Plug 70.0 A Settings Phase Fixed
110-CB-NL3 (1)-MAIN
SIEMENS
QJH2
QJH2
Trip 150.0 A Plug 150.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (1750A)
110-CBL-DPNH-3
110-CBL-NH3-1
110-XF-T7
Pri: 480 V Sec: 208 V
45.0 kVA
110-CBL-NL3 (1)
110-CB-DPNH-3
110-CBL-DPNH-3
110-BUS-NH3
110-CB-NH3-MAIN
110-CB-NH3-1
110-CBL-NH3-1
S
P
110-XF-T7
110-BUS-XF T7-PRI
110-BUS-XF T7-SEC
110-CBL-NL3 (1)
110-CB-NL3 (1)-MAIN
110-BUS-NL3 (1)
TCC Comments: No adjustments required.
TCC: 110_MSB - DPNH - NH3 Current Scale x 1 Reference Voltage: 480
110-CBL-MSB-1
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
110-CB-MSB-1
SIEMENS
SHMD6, Sensitrip III
SHMD6
Trip 800.0 A Plug 600.0 A Settings Phase LTPU (20-100% x P) 100 % (600A) LTD (2.2-27 Sec.) 20 STPU (1.5-10 x LTPU) 5 (3000A) STD (0.05-0.5 Sec.) 0.1 Sec. (I^s T Off) INST (2-40 x LTPU) 15 (9000A) INST Override (Max) Max (10000A)
110-CB-DPNH-MAIN
SIEMENS
LXD6-A Sentron
LXD6-A
Trip 600.0 A Plug 600.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (3000A)
110-CB-DPNH-1
SIEMENS
JG, ETU 555 GF Mod
NJG
Trip 400.0 A Plug 400.0 A Settings Phase LTPU (Ir) 400A (400A) LTD (tr) 20 STPU (Isd) 8 (3200A) STD (tsd) I2T-OFF 0.1 (I^s T Off) INST (Ii) 11 (4400A)
110-CB-DPNH-2
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 350.0 A Plug 350.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (2000A)
110-CB-DPNH-3
SIEMENS
FXD6 Sentron
FXD6
Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (1100A)
110-CBL-MSB-1
110-CB-MSB-1
SIEMENS
SHMD6, Sensitrip III
SHMD6
Trip 800.0 A Plug 600.0 A Settings Phase LTPU (20-100% x P) 100 % (600A) LTD (2.2-27 Sec.) 20 STPU (1.5-10 x LTPU) 5 (3000A) STD (0.05-0.5 Sec.) 0.1 Sec. (I^s T Off) INST (2-40 x LTPU) 15 (9000A) INST Override (Max) Max (10000A)
110-CB-DPNH-MAIN
SIEMENS
LXD6-A Sentron
LXD6-A
Trip 600.0 A Plug 600.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (3000A)
110-CB-DPNH-1
SIEMENS
JG, ETU 555 GF Mod
NJG
Trip 400.0 A Plug 400.0 A Settings Phase LTPU (Ir) 400A (400A) LTD (tr) 20 STPU (Isd) 8 (3200A) STD (tsd) I2T-OFF 0.1 (I^s T Off) INST (Ii) 11 (4400A)
110-CB-DPNH-2
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 350.0 A Plug 350.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (2000A)
110-CB-DPNH-3
SIEMENS
FXD6 Sentron
FXD6
Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (1100A)
110-CBL-MSB-1
110-CB-MSB-1
110-CB-MSB-1 (GF)
110-CBL-MSB-1
110-CB-DPNH-MAIN
110-BUS-DPNH
110-CB-DPNH-1
110-CB-DPNH-2
110-CB-DPNH-3
TCC Comments: Adjustment to 110-CB-MSB-1, 110-CB-DPNH-MAIN, and 110-CB-DPNH-1 trip settings suggested for improved coordination.
TCC: 110_MSB - DPNH Current Scale x 1 Reference Voltage: 480
110-CBL-MSB-1
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
110-CB-MSB-1
SIEMENS
SHMD6, Sensitrip III
SHMD6
Trip 800.0 A Plug 600.0 A Settings Phase LTPU (20-100% x P) 100 % (600A) LTD (2.2-27 Sec.) 7 STPU (1.5-10 x LTPU) 6 (3600A) STD (0.05-0.5 Sec.) 0.2 Sec. (I^s T Off) INST (2-40 x LTPU) 10 (6000A) INST Override (Max) Max (10000A)
110-CB-DPNH-MAIN
SIEMENS
LXD6-A Sentron
LXD6-A
Trip 600.0 A Plug 600.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) 7 (5570A)
110-CB-DPNH-1
SIEMENS
JG, ETU 555 GF Mod
HJG
Trip 400.0 A Plug 400.0 A Settings Phase LTPU (Ir) 400A (400A) LTD (tr) 10 STPU (Isd) 6 (2400A) STD (tsd) I2T-OFF 0.1 (I^s T Off) INST (Ii) 11 (4400A)
110-CB-DPNH-2
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 350.0 A Plug 350.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (2000A)
110-CB-DPNH-3
SIEMENS
FXD6 Sentron
FXD6
Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (1100A)
110-CBL-MSB-1
110-CB-MSB-1
SIEMENS
SHMD6, Sensitrip III
SHMD6
Trip 800.0 A Plug 600.0 A Settings Phase LTPU (20-100% x P) 100 % (600A) LTD (2.2-27 Sec.) 7 STPU (1.5-10 x LTPU) 6 (3600A) STD (0.05-0.5 Sec.) 0.2 Sec. (I^s T Off) INST (2-40 x LTPU) 10 (6000A) INST Override (Max) Max (10000A)
110-CB-DPNH-MAIN
SIEMENS
LXD6-A Sentron
LXD6-A
Trip 600.0 A Plug 600.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) 7 (5570A)
110-CB-DPNH-1
SIEMENS
JG, ETU 555 GF Mod
HJG
Trip 400.0 A Plug 400.0 A Settings Phase LTPU (Ir) 400A (400A) LTD (tr) 10 STPU (Isd) 6 (2400A) STD (tsd) I2T-OFF 0.1 (I^s T Off) INST (Ii) 11 (4400A)
110-CB-DPNH-2
SIEMENS
JXD6-A Sentron
JXD6-A
Trip 350.0 A Plug 350.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (2000A)
110-CB-DPNH-3
SIEMENS
FXD6 Sentron
FXD6
Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)
INST (LO-HI) LO (1100A)
110-CBL-MSB-1
110-CB-MSB-1
110-CB-MSB-1 (GF)
110-CBL-MSB-1
110-CB-DPNH-MAIN
110-BUS-DPNH
110-CB-DPNH-1
110-CB-DPNH-2
110-CB-DPNH-3
TCC Comments: 110-CB-MSB-1 adjustments include LTD from 20 to 7, STPU from 5 to 7, STD from 0.1 to 0.2, and INST from 15 to 10.
110-CB-DPNH-MAIN adjustments include INST from LO to 7.
110-CB-DPNH-1 adjustments include LTD from 20 to 10 and STPU from 8 to 6.
TCC: 110_MSB - DPNH Current Scale x 1 Reference Voltage: 480
110-CBL-MSB-3110-CBL-ERNH-1
110-XF-T1110-CBL-ERNL
0.5
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
110-CB-MSB-3
SIEMENS
DG, ETU 555 GF Mod
HDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 14 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.5 (I^s T Off) INST (Ii) 11 (1100A)
110-CB-ERNH-MAIN
SIEMENS
ED6 Sentron, 2 & 3-Pole
ED6
Trip 100.0 A Plug 100.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (800A)
110-CB-ERNH-1
SIEMENS
ED6 Sentron, 2 & 3-Pole
ED6
Trip 20.0 A Plug 20.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (550A)
110-CB-ERNL-MAIN
SIEMENS
BLH, 2 & 3-Pole
BLH
Trip 30.0 A Plug 30.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (425A)
110-CBL-MSB-3
110-CBL-ERNH-1
110-XF-T1
Pri: 480 V Sec: 208 V
9.0 kVA
110-CBL-ERNL
110-CB-MSB-3
SIEMENS
DG, ETU 555 GF Mod
HDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 14 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.5 (I^s T Off) INST (Ii) 11 (1100A)
110-CB-ERNH-MAIN
SIEMENS
ED6 Sentron, 2 & 3-Pole
ED6
Trip 100.0 A Plug 100.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (800A)
110-CB-ERNH-1
SIEMENS
ED6 Sentron, 2 & 3-Pole
ED6
Trip 20.0 A Plug 20.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (550A)
110-CB-ERNL-MAIN
SIEMENS
BLH, 2 & 3-Pole
BLH
Trip 30.0 A Plug 30.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (425A)
110-CBL-MSB-3
110-CBL-ERNH-1
110-XF-T1
Pri: 480 V Sec: 208 V
9.0 kVA
110-CBL-ERNL
110-CB-MSB-3
110-CB-MSB-3 (GF)
110-CBL-MSB-3
110-BUS-ERNH
110-CB-ERNH-MAIN
110-CB-ERNH-1
110-CBL-ERNH-1
S
P
110-XF-T1
110-BUS-XF T1-PRI
110-CBL-ERNL
110-BUS-XF T1-SEC
110-CB-ERNL-MAIN
110-BUS-ERNL
TCC Comments: No adjustments required.
TCC: 110_MSB - ERNH Current Scale x 1 Reference Voltage: 480
110-CBL-MSB-6
110-XF-T12110-CBL-NL4110-CBL-XF T12
0.5
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
110-CB-MSB-6
SIEMENS
DG, ETU 555 Non-GF Mod
HDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 40A (40A) LTD (tr) 4 STPU (Isd) 1.5 (60A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 125A (125A)
110-SW-XF T12 DISC
BUSSMANN
FRS-R, 600V Class RK5
FRS-R
Trip 100.0 A
110-CBL-MSB-6
110-XF-T12
Pri: 480 V Sec: 208 V
75.0 kVA
110-CBL-NL4
110-CBL-XF T12
110-CB-MSB-6
SIEMENS
DG, ETU 555 Non-GF Mod
HDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 40A (40A) LTD (tr) 4 STPU (Isd) 1.5 (60A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 125A (125A)
110-SW-XF T12 DISC
BUSSMANN
FRS-R, 600V Class RK5
FRS-R
Trip 100.0 A
110-CBL-MSB-6
110-XF-T12
Pri: 480 V Sec: 208 V
75.0 kVA
110-CBL-NL4
110-CBL-XF T12
110-CB-MSB-6
110-CBL-MSB-6
110-BUS-XF T12-PRI
S
P
110-XF-T12
110-CBL-NL4
110-BUS-XF T12-SEC
110-BUS-XF T12 DISC
110-CBL-XF T12
110-SW-XF T12 DISC
110-BUS-NL4
TCC Comments: Adjustment to 110-CB-MSB-6 trip settings suggested for improved coordination.
TCC: 110_MSB - NL4 Current Scale x 1 Reference Voltage: 480
110-CBL-MSB-6
110-XF-T12110-CBL-NL4110-CBL-XF T12
0.5
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
110-CB-MSB-6
SIEMENS
DG, ETU 555 Non-GF Mod
HDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 1000A (1000A)
110-SW-XF T12 DISC
BUSSMANN
FRS-R, 600V Class RK5
FRS-R
Trip 100.0 A
110-CBL-MSB-6
110-XF-T12
Pri: 480 V Sec: 208 V
75.0 kVA
110-CBL-NL4
110-CBL-XF T12
110-CB-MSB-6
SIEMENS
DG, ETU 555 Non-GF Mod
HDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 1000A (1000A)
110-SW-XF T12 DISC
BUSSMANN
FRS-R, 600V Class RK5
FRS-R
Trip 100.0 A
110-CBL-MSB-6
110-XF-T12
Pri: 480 V Sec: 208 V
75.0 kVA
110-CBL-NL4
110-CBL-XF T12
110-CB-MSB-6
110-CBL-MSB-6
110-BUS-XF T12-PRI
S
P
110-XF-T12
110-CBL-NL4
110-BUS-XF T12-SEC
110-BUS-XF T12 DISC
110-CBL-XF T12
110-SW-XF T12 DISC
110-BUS-NL4
TCC Comments: 110-CB-MSB-6 adjustments include LTPU from 40A to 100A, STPU from 1.5 to 10, and INST from 125A to 1000A.
TCC: 110_MSB - NL4 Current Scale x 1 Reference Voltage: 480
110-CBL-INV 1110-CBL-INV 2110-CBL-INV 3110-CBL-PV DISC110-CBL-MSB-5
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S 110-CB-INV 1
SIEMENS
BQD
BQD
Trip 25.0 A Plug 25.0 A Settings Phase Fixed
110-CB-INV 2
SIEMENS
BQD
BQD
Trip 40.0 A Plug 40.0 A Settings Phase Fixed
110-CB-INV 3
SIEMENS
BQD
BQD
Trip 40.0 A Plug 40.0 A Settings Phase Fixed
110-SW-PV DISC
BUSSMANN
FRS-R, 600V Class RK5
FRS-R
Trip 100.0 A
110-CB-MSB-5
SIEMENS
DG, ETU 555 GF Mod
NDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 1.5 (150A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 5 (500A)
110-CBL-INV 1
110-CBL-INV 2
110-CBL-INV 3
110-CBL-PV DISC
110-CBL-MSB-5
110-CB-INV 1
SIEMENS
BQD
BQD
Trip 25.0 A Plug 25.0 A Settings Phase Fixed
110-CB-INV 2
SIEMENS
BQD
BQD
Trip 40.0 A Plug 40.0 A Settings Phase Fixed
110-CB-INV 3
SIEMENS
BQD
BQD
Trip 40.0 A Plug 40.0 A Settings Phase Fixed
110-SW-PV DISC
BUSSMANN
FRS-R, 600V Class RK5
FRS-R
Trip 100.0 A
110-CB-MSB-5
SIEMENS
DG, ETU 555 GF Mod
NDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 1.5 (150A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 5 (500A)
110-CBL-INV 1
110-CBL-INV 2
110-CBL-INV 3
110-CBL-PV DISC
110-CBL-MSB-5
110-PV INVERTER 1
110-PV INVERTER 2
110-PV INVERTER 3
110-CBL-INV 1
110-CBL-INV 2
110-BUS-PV INV 2
110-CBL-INV 3
110-BUS-PV INV 3
110-BUS-PV INV 1
110-CB-INV 1
110-CB-INV 2 110-CB-INV 3
110-BUS-PV COMBINER
110-CBL-PV DISC
110-SW-PV DISC
110-BUS-PV DISC
110-CBL-MSB-5
110-CB-MSB-5 (GF)
110-CB-MSB-5
TCC Comments: Adjustment to 110-CB-MSB-5 trip settings suggested for improved coordination.
TCC: 110_MSB - PV INPUT Current Scale x 1 Reference Voltage: 480
110-CBL-INV 1110-CBL-INV 2110-CBL-INV 3110-CBL-PV DISC110-CBL-MSB-5
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S 110-CB-INV 1
SIEMENS
BQD
BQD
Trip 25.0 A Plug 25.0 A Settings Phase Fixed
110-CB-INV 2
SIEMENS
BQD
BQD
Trip 40.0 A Plug 40.0 A Settings Phase Fixed
110-CB-INV 3
SIEMENS
BQD
BQD
Trip 40.0 A Plug 40.0 A Settings Phase Fixed
110-SW-PV DISC
BUSSMANN
FRS-R, 600V Class RK5
FRS-R
Trip 100.0 A
110-CB-MSB-5
SIEMENS
DG, ETU 555 GF Mod
HDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 11 (1100A)
110-CBL-INV 1
110-CBL-INV 2
110-CBL-INV 3
110-CBL-PV DISC
110-CBL-MSB-5
110-CB-INV 1
SIEMENS
BQD
BQD
Trip 25.0 A Plug 25.0 A Settings Phase Fixed
110-CB-INV 2
SIEMENS
BQD
BQD
Trip 40.0 A Plug 40.0 A Settings Phase Fixed
110-CB-INV 3
SIEMENS
BQD
BQD
Trip 40.0 A Plug 40.0 A Settings Phase Fixed
110-SW-PV DISC
BUSSMANN
FRS-R, 600V Class RK5
FRS-R
Trip 100.0 A
110-CB-MSB-5
SIEMENS
DG, ETU 555 GF Mod
HDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 11 (1100A)
110-CBL-INV 1
110-CBL-INV 2
110-CBL-INV 3
110-CBL-PV DISC
110-CBL-MSB-5
110-PV INVERTER 1
110-PV INVERTER 2
110-PV INVERTER 3
110-CBL-INV 1
110-CBL-INV 2
110-BUS-PV INV 2
110-CBL-INV 3
110-BUS-PV INV 3
110-BUS-PV INV 1
110-CB-INV 1
110-CB-INV 2 110-CB-INV 3
110-BUS-PV COMBINER
110-CBL-PV DISC
110-SW-PV DISC
110-BUS-PV DISC
110-CBL-MSB-5
110-CB-MSB-5 (GF)
110-CB-MSB-5
TCC Comments: 110-CB-MSB-5 adjustments include STPU from 1.5 to 10 and INST from 5 to 11.
TCC: 110_MSB - PV INPUT Current Scale x 1 Reference Voltage: 480
110-XF-BLDG 110110-CBL-MSB
0.5
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
110-CB-MSB-MAIN
SIEMENS
SHMD6, Sensitrip III
SHMD6
Trip 800.0 A Plug 800.0 A Settings Phase LTPU (20-100% x P) 90 % (720A) LTD (2.2-27 Sec.) 27 STPU (1.5-10 x LTPU) 7 (5040A) STD (0.05-0.5 Sec.) 0.3 Sec. (I^s T Off) INST (2-40 x LTPU) 10 (7200A) INST Override (Max) Max (10000A)
110-CB-MSB-1
SIEMENS
SHMD6, Sensitrip III
SHMD6
Trip 800.0 A Plug 600.0 A Settings Phase LTPU (20-100% x P) 100 % (600A) LTD (2.2-27 Sec.) 20 STPU (1.5-10 x LTPU) 5 (3000A) STD (0.05-0.5 Sec.) 0.1 Sec. (I^s T Off) INST (2-40 x LTPU) 15 (9000A) INST Override (Max) Max (10000A)
110-CB-MSB-2
SIEMENS
FG, ETU 555 GF Mod
HFG
Trip 250.0 A Plug 250.0 A Settings Phase LTPU (Ir) 250A (250A) LTD (tr) 14 STPU (Isd) 8 (2000A) STD (tsd) I2T-OFF 0.1 (I^s T Off) INST (Ii) 11 (2750A)
110-CB-MSB-3
SIEMENS
DG, ETU 555 GF Mod
HDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 14 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.5 (I^s T Off) INST (Ii) 11 (1100A)
110-FS-XF BLDG 110 (1)
ABB
DO-III Dual Element
DO-III
Trip 50.0 A Settings Phase
50.0 Amps
110-FS-XF BLDG 110 (2)
COOPER
ELSP, 15.5kV, (2/03)
ELSP
Trip 100.0 A Settings Phase
100.0 Amps
110-XF-BLDG 110
Pri: 11500 V Sec: 480 V
500.0 kVA
110-CBL-MSB
110-CB-MSB-MAIN
SIEMENS
SHMD6, Sensitrip III
SHMD6
Trip 800.0 A Plug 800.0 A Settings Phase LTPU (20-100% x P) 90 % (720A) LTD (2.2-27 Sec.) 27 STPU (1.5-10 x LTPU) 7 (5040A) STD (0.05-0.5 Sec.) 0.3 Sec. (I^s T Off) INST (2-40 x LTPU) 10 (7200A) INST Override (Max) Max (10000A)
110-CB-MSB-1
SIEMENS
SHMD6, Sensitrip III
SHMD6
Trip 800.0 A Plug 600.0 A Settings Phase LTPU (20-100% x P) 100 % (600A) LTD (2.2-27 Sec.) 20 STPU (1.5-10 x LTPU) 5 (3000A) STD (0.05-0.5 Sec.) 0.1 Sec. (I^s T Off) INST (2-40 x LTPU) 15 (9000A) INST Override (Max) Max (10000A)
110-CB-MSB-2
SIEMENS
FG, ETU 555 GF Mod
HFG
Trip 250.0 A Plug 250.0 A Settings Phase LTPU (Ir) 250A (250A) LTD (tr) 14 STPU (Isd) 8 (2000A) STD (tsd) I2T-OFF 0.1 (I^s T Off) INST (Ii) 11 (2750A)
110-CB-MSB-3
SIEMENS
DG, ETU 555 GF Mod
HDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 14 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.5 (I^s T Off) INST (Ii) 11 (1100A)
110-FS-XF BLDG 110 (1)
ABB
DO-III Dual Element
DO-III
Trip 50.0 A Settings Phase
50.0 Amps
110-FS-XF BLDG 110 (2)
COOPER
ELSP, 15.5kV, (2/03)
ELSP
Trip 100.0 A Settings Phase
100.0 Amps
110-XF-BLDG 110
Pri: 11500 V Sec: 480 V
500.0 kVA
110-CBL-MSB
S
P
110-XF-BLDG 110
110-BUS-XF BLDG 110-PRI
110-CBL-MSB
110-BUS-XF BLDG 110-SEC
110-CB-MSB-MAIN
110-CB-MSB-MAIN (GF)
110-BUS-MSB
110-CB-MSB-1
110-CB-MSB-1 (GF)
110-CB-MSB-2
110-CB-MSB-2 (GF)
110-CB-MSB-3
110-CB-MSB-3 (GF)
110-FS-XF BLDG 110 (2)
110-FS-XF BLDG 110 (1)
TCC Comments: Adjustment to 110-CB-MSB-MAIN, 110-CB-MSB-1, and 110-CB-MSB-2 trip settings suggested for improved coordination.
TCC: 110_MSB (1) Current Scale x 1 Reference Voltage: 480
0.5
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
110-CB-MSB-MAIN
SIEMENS
SHMD6, Sensitrip III
SHMD6
Trip 800.0 A Plug 800.0 A Settings Phase LTPU (20-100% x P) 100 % (800A) LTD (2.2-27 Sec.) 7 STPU (1.5-10 x LTPU) 6 (4800A) STD (0.05-0.5 Sec.) 0.3 Sec. (I^s T Off) INST (2-40 x LTPU) 15 (12000A) INST Override (Max) Max (10000A)
110-CB-MSB-1
SIEMENS
SHMD6, Sensitrip III
SHMD6
Trip 800.0 A Plug 600.0 A Settings Phase LTPU (20-100% x P) 100 % (600A) LTD (2.2-27 Sec.) 7 STPU (1.5-10 x LTPU) 6 (3600A) STD (0.05-0.5 Sec.) 0.2 Sec. (I^s T Off) INST (2-40 x LTPU) 10 (6000A) INST Override (Max) Max (10000A)
110-CB-MSB-2
SIEMENS
FG, ETU 555 GF Mod
HFG
Trip 250.0 A Plug 250.0 A Settings Phase LTPU (Ir) 200A (200A) LTD (tr) 14 STPU (Isd) 10 (2000A) STD (tsd) I2T-OFF 0.1 (I^s T Off) INST (Ii) 11 (2750A)
110-CB-MSB-3
SIEMENS
DG, ETU 555 GF Mod
HDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 14 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.5 (I^s T Off) INST (Ii) 11 (1100A)
110-FS-XF BLDG 110 (1)
ABB
DO-III Dual Element
DO-III
Trip 50.0 A Settings Phase
50.0 Amps
110-FS-XF BLDG 110 (2)
COOPER
ELSP, 15.5kV, (2/03)
ELSP
Trip 100.0 A Settings Phase
100.0 Amps
110-XF-BLDG 110
Pri: 11500 V Sec: 480 V
500.0 kVA
110-CBL-MSB
110-CB-MSB-MAIN
SIEMENS
SHMD6, Sensitrip III
SHMD6
Trip 800.0 A Plug 800.0 A Settings Phase LTPU (20-100% x P) 100 % (800A) LTD (2.2-27 Sec.) 7 STPU (1.5-10 x LTPU) 6 (4800A) STD (0.05-0.5 Sec.) 0.3 Sec. (I^s T Off) INST (2-40 x LTPU) 15 (12000A) INST Override (Max) Max (10000A)
110-CB-MSB-1
SIEMENS
SHMD6, Sensitrip III
SHMD6
Trip 800.0 A Plug 600.0 A Settings Phase LTPU (20-100% x P) 100 % (600A) LTD (2.2-27 Sec.) 7 STPU (1.5-10 x LTPU) 6 (3600A) STD (0.05-0.5 Sec.) 0.2 Sec. (I^s T Off) INST (2-40 x LTPU) 10 (6000A) INST Override (Max) Max (10000A)
110-CB-MSB-2
SIEMENS
FG, ETU 555 GF Mod
HFG
Trip 250.0 A Plug 250.0 A Settings Phase LTPU (Ir) 200A (200A) LTD (tr) 14 STPU (Isd) 10 (2000A) STD (tsd) I2T-OFF 0.1 (I^s T Off) INST (Ii) 11 (2750A)
110-CB-MSB-3
SIEMENS
DG, ETU 555 GF Mod
HDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 14 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.5 (I^s T Off) INST (Ii) 11 (1100A)
110-FS-XF BLDG 110 (1)
ABB
DO-III Dual Element
DO-III
Trip 50.0 A Settings Phase
50.0 Amps
110-FS-XF BLDG 110 (2)
COOPER
ELSP, 15.5kV, (2/03)
ELSP
Trip 100.0 A Settings Phase
100.0 Amps
110-XF-BLDG 110
Pri: 11500 V Sec: 480 V
500.0 kVA
110-CBL-MSB
S
P
110-XF-BLDG 110
110-BUS-XF BLDG 110-PRI
110-CBL-MSB
110-BUS-XF BLDG 110-SEC
110-CB-MSB-MAIN
110-CB-MSB-MAIN (GF)
110-BUS-MSB
110-CB-MSB-1
110-CB-MSB-1 (GF)
110-CB-MSB-2
110-CB-MSB-2 (GF)
110-CB-MSB-3
110-CB-MSB-3 (GF)
110-FS-XF BLDG 110 (2)
110-FS-XF BLDG 110 (1)
TCC Comments: 110-CB-MSB-MAIN adjustments include LTPU from 90% to 100%, LTD from 27 to 7, STPU from 7 to 6, and INST from 10 to 15.
110-CB-MSB-1 adjustments include LTD from 20 to 7, STPU from 5 to 6, STD from 0.1 to 0.2, and INST from 15 to 10.
110-CB-MSB-2 adjustments include LTPU from 250A to 200A and STPU from 8 to 10.
TCC: 110_MSB (1) Current Scale x 1 Reference Voltage: 480
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
110-CB-MSB-MAIN (GF)
SIEMENS
SHMD6, Sensitrip III
SHMD6
Trip 800.0 A Plug 800.0 A Settings Phase
70% GFPU 70 % (560A)
GFD (0.1-0.4 Sec.) 0.4 (I^s T On)
110-CB-MSB-1 (GF)
SIEMENS
SHMD6, Sensitrip III
SHMD6
Trip 800.0 A Plug 600.0 A Settings Phase
70% GFPU 70 % (420A)
GFD (0.1-0.4 Sec.) 0.2 (I^s T On)
110-CB-MSB-2 (GF)
SIEMENS
FG, ETU 555
HFG
Trip 250.0 A Plug 250.0 A Settings Phase GFPU (Ig) 250A (250A) GFD (tg) 0.2 (I^s T On)
110-CB-MSB-3 (GF)
SIEMENS
DG, ETU 555
HDG
Trip 100.0 A Plug 100.0 A Settings Phase GFPU (Ig) 100A (100A) GFD (tg) 0.2 (I^s T On)
110-CB-MSB-MAIN (GF)
SIEMENS
SHMD6, Sensitrip III
SHMD6
Trip 800.0 A Plug 800.0 A Settings Phase
70% GFPU 70 % (560A)
GFD (0.1-0.4 Sec.) 0.4 (I^s T On)
110-CB-MSB-1 (GF)
SIEMENS
SHMD6, Sensitrip III
SHMD6
Trip 800.0 A Plug 600.0 A Settings Phase
70% GFPU 70 % (420A)
GFD (0.1-0.4 Sec.) 0.2 (I^s T On)
110-CB-MSB-2 (GF)
SIEMENS
FG, ETU 555
HFG
Trip 250.0 A Plug 250.0 A Settings Phase GFPU (Ig) 250A (250A) GFD (tg) 0.2 (I^s T On)
110-CB-MSB-3 (GF)
SIEMENS
DG, ETU 555
HDG
Trip 100.0 A Plug 100.0 A Settings Phase GFPU (Ig) 100A (100A) GFD (tg) 0.2 (I^s T On)
S
P
110-XF-BLDG 110
110-BUS-XF BLDG 110-PRI
110-CBL-MSB
110-BUS-XF BLDG 110-SEC
110-CB-MSB-MAIN
110-CB-MSB-MAIN (GF)
110-BUS-MSB
110-CB-MSB-1
110-CB-MSB-1 (GF)
110-CB-MSB-2
110-CB-MSB-2 (GF)
110-CB-MSB-3
110-CB-MSB-3 (GF)
TCC Comments: No adjustments required.
TCC: 110_MSB (1)-GF Current Scale x 1 Reference Voltage: 480
0.5
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
110-CB-MSB-MAIN
SIEMENS
SHMD6, Sensitrip III
SHMD6
Trip 800.0 A Plug 800.0 A Settings Phase LTPU (20-100% x P) 90 % (720A) LTD (2.2-27 Sec.) 27 STPU (1.5-10 x LTPU) 7 (5040A) STD (0.05-0.5 Sec.) 0.3 Sec. (I^s T Off) INST (2-40 x LTPU) 10 (7200A) INST Override (Max) Max (10000A)
110-CB-MSB-4
SIEMENS
DG, ETU 555 GF Mod
HDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 8 (800A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 11 (1100A)
110-CB-MSB-5
SIEMENS
DG, ETU 555 GF Mod
NDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 1.5 (150A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 5 (500A)
110-CB-MSB-6
SIEMENS
DG, ETU 555 Non-GF Mod
HDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 40A (40A) LTD (tr) 4 STPU (Isd) 1.5 (60A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 125A (125A)
110-FS-XF BLDG 110 (1)
ABB
DO-III Dual Element
DO-III
Trip 50.0 A Settings Phase
50.0 Amps
110-FS-XF BLDG 110 (2)
COOPER
ELSP, 15.5kV, (2/03)
ELSP
Trip 100.0 A Settings Phase
100.0 Amps
110-XF-BLDG 110
Pri: 11500 V Sec: 480 V
500.0 kVA
110-CBL-MSB
110-CB-MSB-MAIN
SIEMENS
SHMD6, Sensitrip III
SHMD6
Trip 800.0 A Plug 800.0 A Settings Phase LTPU (20-100% x P) 90 % (720A) LTD (2.2-27 Sec.) 27 STPU (1.5-10 x LTPU) 7 (5040A) STD (0.05-0.5 Sec.) 0.3 Sec. (I^s T Off) INST (2-40 x LTPU) 10 (7200A) INST Override (Max) Max (10000A)
110-CB-MSB-4
SIEMENS
DG, ETU 555 GF Mod
HDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 8 (800A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 11 (1100A)
110-CB-MSB-5
SIEMENS
DG, ETU 555 GF Mod
NDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 1.5 (150A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 5 (500A)
110-CB-MSB-6
SIEMENS
DG, ETU 555 Non-GF Mod
HDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 40A (40A) LTD (tr) 4 STPU (Isd) 1.5 (60A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 125A (125A)
110-FS-XF BLDG 110 (1)
ABB
DO-III Dual Element
DO-III
Trip 50.0 A Settings Phase
50.0 Amps
110-FS-XF BLDG 110 (2)
COOPER
ELSP, 15.5kV, (2/03)
ELSP
Trip 100.0 A Settings Phase
100.0 Amps
110-XF-BLDG 110
Pri: 11500 V Sec: 480 V
500.0 kVA
110-CBL-MSB
S
P
110-XF-BLDG 110
110-BUS-XF BLDG 110-PRI
110-CBL-MSB
110-BUS-XF BLDG 110-SEC
110-CB-MSB-MAIN
110-CB-MSB-MAIN (GF)
110-BUS-MSB
110-CB-MSB-4
110-CB-MSB-4 (GF)
110-CB-MSB-5
110-CB-MSB-5 (GF)
110-CB-MSB-6
110-FS-XF BLDG 110 (2)
110-FS-XF BLDG 110 (1)
TCC Comments: Adjustment to 110-CB-MSB-MAIN, 110-CB-MSB-4, 110-CB-MSB-5, and 110-CB-MSB-6 trip settings suggested for improved coordination.
TCC: 110_MSB (2) Current Scale x 1 Reference Voltage: 480
0.5
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
110-CB-MSB-MAIN
SIEMENS
SHMD6, Sensitrip III
SHMD6
Trip 800.0 A Plug 800.0 A Settings Phase LTPU (20-100% x P) 100 % (800A) LTD (2.2-27 Sec.) 7 STPU (1.5-10 x LTPU) 6 (4800A) STD (0.05-0.5 Sec.) 0.3 Sec. (I^s T Off) INST (2-40 x LTPU) 15 (12000A) INST Override (Max) Max (10000A)
110-CB-MSB-4
SIEMENS
DG, ETU 555 GF Mod
HDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 14 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 11 (1100A)
110-CB-MSB-5
SIEMENS
DG, ETU 555 GF Mod
HDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 11 (1100A)
110-CB-MSB-6
SIEMENS
DG, ETU 555 Non-GF Mod
HDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 1000A (1000A)
110-FS-XF BLDG 110 (1)
ABB
DO-III Dual Element
DO-III
Trip 50.0 A Settings Phase
50.0 Amps
110-FS-XF BLDG 110 (2)
COOPER
ELSP, 15.5kV, (2/03)
ELSP
Trip 100.0 A Settings Phase
100.0 Amps
110-XF-BLDG 110
Pri: 11500 V Sec: 480 V
500.0 kVA
110-CBL-MSB
110-CB-MSB-MAIN
SIEMENS
SHMD6, Sensitrip III
SHMD6
Trip 800.0 A Plug 800.0 A Settings Phase LTPU (20-100% x P) 100 % (800A) LTD (2.2-27 Sec.) 7 STPU (1.5-10 x LTPU) 6 (4800A) STD (0.05-0.5 Sec.) 0.3 Sec. (I^s T Off) INST (2-40 x LTPU) 15 (12000A) INST Override (Max) Max (10000A)
110-CB-MSB-4
SIEMENS
DG, ETU 555 GF Mod
HDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 14 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 11 (1100A)
110-CB-MSB-5
SIEMENS
DG, ETU 555 GF Mod
HDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 11 (1100A)
110-CB-MSB-6
SIEMENS
DG, ETU 555 Non-GF Mod
HDG
Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 1000A (1000A)
110-FS-XF BLDG 110 (1)
ABB
DO-III Dual Element
DO-III
Trip 50.0 A Settings Phase
50.0 Amps
110-FS-XF BLDG 110 (2)
COOPER
ELSP, 15.5kV, (2/03)
ELSP
Trip 100.0 A Settings Phase
100.0 Amps
110-XF-BLDG 110
Pri: 11500 V Sec: 480 V
500.0 kVA
110-CBL-MSB
S
P
110-XF-BLDG 110
110-BUS-XF BLDG 110-PRI
110-CBL-MSB
110-BUS-XF BLDG 110-SEC
110-CB-MSB-MAIN
110-CB-MSB-MAIN (GF)
110-BUS-MSB
110-CB-MSB-4
110-CB-MSB-4 (GF)
110-CB-MSB-5
110-CB-MSB-5 (GF)
110-CB-MSB-6
110-FS-XF BLDG 110 (2)
110-FS-XF BLDG 110 (1)
TCC Comments: 110-CB-MSB-MAIN adjustments include LTPU from 90% to 100%, LTD from 27 to 7, STPU from 7 to 6, and INST from 10 to 15.
110-CB-MSB-4 adjustments include LTD from 4 to 14 and STPU from 8 to 10.
110-CB-MSB-5 adjustments include STPU from 1.5 to 10 and INST from 5 to 11.
110-CB-MSB-6 adjustments include LTPU from 40A to 100A, STPU from 1.5 to 10, and INST from 125A to 1000A.
TCC: 110_MSB (2) Current Scale x 1 Reference Voltage: 480
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
110-CB-MSB-MAIN (GF)
SIEMENS
SHMD6, Sensitrip III
SHMD6
Trip 800.0 A Plug 800.0 A Settings Phase
70% GFPU 70 % (560A)
GFD (0.1-0.4 Sec.) 0.4 (I^s T On)
110-CB-MSB-4 (GF)
SIEMENS
DG, ETU 555
HDG
Trip 100.0 A Plug 100.0 A Settings Phase GFPU (Ig) 100A (100A) GFD (tg) 0.2 (I^s T On)
110-CB-MSB-5 (GF)
SIEMENS
DG, ETU 555
NDG
Trip 100.0 A Plug 100.0 A Settings Phase GFPU (Ig) 80A (80A) GFD (tg) 0.07 (I^s T On)
110-CB-MSB-MAIN (GF)
SIEMENS
SHMD6, Sensitrip III
SHMD6
Trip 800.0 A Plug 800.0 A Settings Phase
70% GFPU 70 % (560A)
GFD (0.1-0.4 Sec.) 0.4 (I^s T On)
110-CB-MSB-4 (GF)
SIEMENS
DG, ETU 555
HDG
Trip 100.0 A Plug 100.0 A Settings Phase GFPU (Ig) 100A (100A) GFD (tg) 0.2 (I^s T On)
110-CB-MSB-5 (GF)
SIEMENS
DG, ETU 555
NDG
Trip 100.0 A Plug 100.0 A Settings Phase GFPU (Ig) 80A (80A) GFD (tg) 0.07 (I^s T On)
S
P
110-XF-BLDG 110
110-BUS-XF BLDG 110-PRI
110-CBL-MSB
110-BUS-XF BLDG 110-SEC
110-CB-MSB-MAIN
110-CB-MSB-MAIN (GF)
110-BUS-MSB
110-CB-MSB-4
110-CB-MSB-4 (GF)
110-CB-MSB-5
110-CB-MSB-5 (GF)
110-CB-MSB-6
TCC Comments: No adjustments required.
TCC: 110_MSB (2)-GF Current Scale x 1 Reference Voltage: 480
30-CBL-A2EH1-1
30-XF-TA2-230-CBL-A2EL1
0.5
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
30-CB-A2EH1-MAIN
SQUARE D
KA
KA
Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve
INST HI (1750A)
30-CB-A2EH1-1
SQUARE D
ED
ED
Trip 50.0 A Plug 50.0 A Settings Phase Fixed
30-CB-A2EL1-MAIN
SQUARE D
QO-VH, 3-Pole
QO-VH
Trip 100.0 A Plug 100.0 A Settings Phase Fixed (730-8)
30-CBL-A2EH1-1
30-XF-TA2-2
Pri: 480 V Sec: 208 V
30.0 kVA
30-CBL-A2EL1
30-CB-A2EH1-MAIN
SQUARE D
KA
KA
Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve
INST HI (1750A)
30-CB-A2EH1-1
SQUARE D
ED
ED
Trip 50.0 A Plug 50.0 A Settings Phase Fixed
30-CB-A2EL1-MAIN
SQUARE D
QO-VH, 3-Pole
QO-VH
Trip 100.0 A Plug 100.0 A Settings Phase Fixed (730-8)
30-CBL-A2EH1-1
30-XF-TA2-2
Pri: 480 V Sec: 208 V
30.0 kVA
30-CBL-A2EL1
30-CB-A2EH1-MAIN
30-BUS-A2EH1
30-CB-A2EH1-1
30-CBL-A2EH1-1
S
P
30-XF-TA2-2
30-BUS-XF TA2-2-PRI
30-CBL-A2EL1
30-BUS-XF TA2-2-SEC
30-BUS-A2EL1
30-CB-A2EL1-MAIN
TCC Comments: Adjustment to 30-CB-A2EH1-MAIN trip settings suggested for improved coordination.
TCC: 30_E - A RISER - A2EH1 - A2EL1 Current Scale x 1 Reference Voltage: 480
30-CBL-A2EH1-1
30-XF-TA2-230-CBL-A2EL1
0.5
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
30-CB-A2EH1-MAIN
SQUARE D
KA
KA
Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve
INST 3 (1191.75A)
30-CB-A2EH1-1
SQUARE D
ED
ED
Trip 50.0 A Plug 50.0 A Settings Phase Fixed
30-CB-A2EL1-MAIN
SQUARE D
QO-VH, 3-Pole
QO-VH
Trip 100.0 A Plug 100.0 A Settings Phase Fixed (730-8)
30-CBL-A2EH1-1
30-XF-TA2-2
Pri: 480 V Sec: 208 V
30.0 kVA
30-CBL-A2EL1
30-CB-A2EH1-MAIN
SQUARE D
KA
KA
Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve
INST 3 (1191.75A)
30-CB-A2EH1-1
SQUARE D
ED
ED
Trip 50.0 A Plug 50.0 A Settings Phase Fixed
30-CB-A2EL1-MAIN
SQUARE D
QO-VH, 3-Pole
QO-VH
Trip 100.0 A Plug 100.0 A Settings Phase Fixed (730-8)
30-CBL-A2EH1-1
30-XF-TA2-2
Pri: 480 V Sec: 208 V
30.0 kVA
30-CBL-A2EL1
30-CB-A2EH1-MAIN
30-BUS-A2EH1
30-CB-A2EH1-1
30-CBL-A2EH1-1
S
P
30-XF-TA2-2
30-BUS-XF TA2-2-PRI
30-CBL-A2EL1
30-BUS-XF TA2-2-SEC
30-BUS-A2EL1
30-CB-A2EL1-MAIN
TCC Comments: 30-CB-A2EH1-MAIN adjustments include INST from HI to 3.
TCC: 30_E - A RISER - A2EH1 - A2EL1 Current Scale x 1 Reference Voltage: 480
30-CBL-A2EH1-2
30-XF-TA2EL230-CBL-A2EL2
0.5
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
30-CB-A2EH1-MAIN
SQUARE D
KA
KA
Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve
INST HI (1750A)
30-CB-A2EH1-2
SQUARE D
EG
EG
Trip 70.0 A Plug 70.0 A Settings Phase Fixed
30-CB-A2EL2-MAIN
SQUARE D
QB
QB
Trip 150.0 A Plug 150.0 A Settings Phase Fixed
30-CBL-A2EH1-2
30-XF-TA2EL2
Pri: 480 V Sec: 208 V
45.0 kVA
30-CBL-A2EL2
30-CB-A2EH1-MAIN
SQUARE D
KA
KA
Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve
INST HI (1750A)
30-CB-A2EH1-2
SQUARE D
EG
EG
Trip 70.0 A Plug 70.0 A Settings Phase Fixed
30-CB-A2EL2-MAIN
SQUARE D
QB
QB
Trip 150.0 A Plug 150.0 A Settings Phase Fixed
30-CBL-A2EH1-2
30-XF-TA2EL2
Pri: 480 V Sec: 208 V
45.0 kVA
30-CBL-A2EL2
30-CB-A2EH1-MAIN
30-BUS-A2EH1
30-CB-A2EH1-2
30-CBL-A2EH1-2
S
P
30-XF-TA2EL2
30-BUS-XF TA2EL2-PRI
30-CBL-A2EL2
30-BUS-XF TA2EL2-SEC
30-BUS-A2EL2
30-CB-A2EL2-MAIN
TCC Comments: Adjustment to 30-CB-A2EH1-MAIN trip settings suggested for improved coordination.
TCC: 30_E - A RISER - A2EH1 - A2EL2 Current Scale x 1 Reference Voltage: 480
30-CBL-A2EH1-2
30-XF-TA2EL230-CBL-A2EL2
0.5
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
30-CB-A2EH1-MAIN
SQUARE D
KA
KA
Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve
INST 3 (1191.75A)
30-CB-A2EH1-2
SQUARE D
EG
EG
Trip 70.0 A Plug 70.0 A Settings Phase Fixed
30-CB-A2EL2-MAIN
SQUARE D
QB
QB
Trip 150.0 A Plug 150.0 A Settings Phase Fixed
30-CBL-A2EH1-2
30-XF-TA2EL2
Pri: 480 V Sec: 208 V
45.0 kVA
30-CBL-A2EL2
30-CB-A2EH1-MAIN
SQUARE D
KA
KA
Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve
INST 3 (1191.75A)
30-CB-A2EH1-2
SQUARE D
EG
EG
Trip 70.0 A Plug 70.0 A Settings Phase Fixed
30-CB-A2EL2-MAIN
SQUARE D
QB
QB
Trip 150.0 A Plug 150.0 A Settings Phase Fixed
30-CBL-A2EH1-2
30-XF-TA2EL2
Pri: 480 V Sec: 208 V
45.0 kVA
30-CBL-A2EL2
30-CB-A2EH1-MAIN
30-BUS-A2EH1
30-CB-A2EH1-2
30-CBL-A2EH1-2
S
P
30-XF-TA2EL2
30-BUS-XF TA2EL2-PRI
30-CBL-A2EL2
30-BUS-XF TA2EL2-SEC
30-BUS-A2EL2
30-CB-A2EL2-MAIN
TCC Comments: 30-CB-A2EH1-MAIN adjustments include INST from HI to 3.
TCC: 30_E - A RISER - A2EH1 - A2EL2 Current Scale x 1 Reference Voltage: 480
30-CBL-A3EH1-1
30-XF-TA3-230-CBL-A3EL1
0.5
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
30-CB-A3EH1-MAIN
SQUARE D
KA
KA
Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve
INST HI (1750A)
30-CB-A3EH1-1
SQUARE D
ED
ED
Trip 50.0 A Plug 50.0 A Settings Phase Fixed
30-CB-A3EL1-MAIN
SQUARE D
QO-VH, 3-Pole
QO-VH
Trip 100.0 A Plug 100.0 A Settings Phase Fixed (730-8)
30-CBL-A3EH1-1
30-XF-TA3-2
Pri: 480 V Sec: 208 V
30.0 kVA
30-CBL-A3EL1
30-CB-A3EH1-MAIN
SQUARE D
KA
KA
Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve
INST HI (1750A)
30-CB-A3EH1-1
SQUARE D
ED
ED
Trip 50.0 A Plug 50.0 A Settings Phase Fixed
30-CB-A3EL1-MAIN
SQUARE D
QO-VH, 3-Pole
QO-VH
Trip 100.0 A Plug 100.0 A Settings Phase Fixed (730-8)
30-CBL-A3EH1-1
30-XF-TA3-2
Pri: 480 V Sec: 208 V
30.0 kVA
30-CBL-A3EL1
30-CB-A3EH1-MAIN
30-BUS-A3EH1
30-CB-A3EH1-1
30-CBL-A3EH1-1
S
P
30-XF-TA3-2
30-BUS-XF TA3-2-PRI
30-CBL-A3EL1
30-BUS-XF TA3-2-SEC
30-BUS-A3EL1
30-CB-A3EL1-MAIN
TCC Comments: Adjustment to 30-CB-A3EH1-MAIN trip settings suggested for improved coordination.
TCC: 30_E - A RISER - A3EH1 - A3EL1 Current Scale x 1 Reference Voltage: 480
30-CBL-A3EH1-1
30-XF-TA3-230-CBL-A3EL1
0.5
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
30-CB-A3EH1-MAIN
SQUARE D
KA
KA
Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve
INST 3 (1191.75A)
30-CB-A3EH1-1
SQUARE D
ED
ED
Trip 50.0 A Plug 50.0 A Settings Phase Fixed
30-CB-A3EL1-MAIN
SQUARE D
QO-VH, 3-Pole
QO-VH
Trip 100.0 A Plug 100.0 A Settings Phase Fixed (730-8)
30-CBL-A3EH1-1
30-XF-TA3-2
Pri: 480 V Sec: 208 V
30.0 kVA
30-CBL-A3EL1
30-CB-A3EH1-MAIN
SQUARE D
KA
KA
Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve
INST 3 (1191.75A)
30-CB-A3EH1-1
SQUARE D
ED
ED
Trip 50.0 A Plug 50.0 A Settings Phase Fixed
30-CB-A3EL1-MAIN
SQUARE D
QO-VH, 3-Pole
QO-VH
Trip 100.0 A Plug 100.0 A Settings Phase Fixed (730-8)
30-CBL-A3EH1-1
30-XF-TA3-2
Pri: 480 V Sec: 208 V
30.0 kVA
30-CBL-A3EL1
30-CB-A3EH1-MAIN
30-BUS-A3EH1
30-CB-A3EH1-1
30-CBL-A3EH1-1
S
P
30-XF-TA3-2
30-BUS-XF TA3-2-PRI
30-CBL-A3EL1
30-BUS-XF TA3-2-SEC
30-BUS-A3EL1
30-CB-A3EL1-MAIN
TCC Comments: 30-CB-A3EH1-MAIN adjustments include INST from HI to 3.
TCC: 30_E - A RISER - A3EH1 - A3EL1 Current Scale x 1 Reference Voltage: 480
30-CBL-A3EH1-2
30-XF-TA3EL230-CBL-A3EL2
0.5
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
30-CB-A3EH1-MAIN
SQUARE D
KA
KA
Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve
INST HI (1750A)
30-CB-A3EH1-2
SQUARE D
ED
ED
Trip 70.0 A Plug 70.0 A Settings Phase Fixed
30-CB-A3EL2-MAIN
SQUARE D
QB
QB
Trip 150.0 A Plug 150.0 A Settings Phase Fixed
30-CBL-A3EH1-2
30-XF-TA3EL2
Pri: 480 V Sec: 208 V
45.0 kVA
30-CBL-A3EL2
30-CB-A3EH1-MAIN
SQUARE D
KA
KA
Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve
INST HI (1750A)
30-CB-A3EH1-2
SQUARE D
ED
ED
Trip 70.0 A Plug 70.0 A Settings Phase Fixed
30-CB-A3EL2-MAIN
SQUARE D
QB
QB
Trip 150.0 A Plug 150.0 A Settings Phase Fixed
30-CBL-A3EH1-2
30-XF-TA3EL2
Pri: 480 V Sec: 208 V
45.0 kVA
30-CBL-A3EL2
30-CB-A3EH1-MAIN
30-BUS-A3EH1
30-CB-A3EH1-2
30-CBL-A3EH1-2
S
P
30-XF-TA3EL2
30-BUS-XF TA3EL2-PRI
30-CBL-A3EL2
30-BUS-XF TA3EL2-SEC
30-BUS-A3EL2
30-CB-A3EL2-MAIN
TCC Comments: Adjustment to 30-CB-A3EH1-MAIN trip settings suggested for improved coordination.
TCC: 30_E - A RISER - A3EH1 - A3EL2 Current Scale x 1 Reference Voltage: 480
30-CBL-A3EH1-2
30-XF-TA3EL230-CBL-A3EL2
0.5
0.5
1K 1K
K
K
0K
0K
1M 0.01
0.10
CURRENT IN AMPERES
CURRENT IN AMPERES
TI
ME
I
N
SE
CO
ND
S
30-CB-A3EH1-MAIN
SQUARE D
KA
KA
Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve
INST 3 (1191.75A)
30-CB-A3EH1-…
This is the start of the file's text. The full file is on GovTribe.