Electrical Distribution System Condition Assessment/ARC Flash
Solicitation number
36C26126Q0232
Issued by

About this file

This file is an electrical distribution system condition assessment report for the Honolulu Veterans Affairs Medical Center (VAMC), prepared by E.K. Fox & Associates, Ltd. The comprehensive assessment evaluates the condition of the facility's electrical infrastructure, including medium and low voltage distribution systems, grounding systems, emergency/standby electrical systems, and transformer components. The report provides a detailed analysis of equipment conditions using a grading methodology ranging from A (like new) to F (critical), with specific focus on identifying components that require replacement or upgrades.

Key findings include a total recommended correction cost of $261,488 across four buildings (E-Wing, ACC, Parking Garage, and CFA), with priority ratings assigned to various electrical system components. Notable recommendations include replacing generators, automatic transfer switches, circuit breakers, and transformers that are past their service life or have specific technical deficiencies. The assessment highlights that while most of the electrical system is in good condition, several components need attention, particularly around ground fault protection, equipment clearances, and coordination of electrical protective devices. The report provides a systematic breakdown of equipment conditions, useful life remaining, and estimated replacement costs to support future maintenance and upgrade planning.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

110-CB-DPLSH

SIEMENS

FXD6-A Sentron

FXD6-A

Trip 100.0 A Plug 100.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) HI (1200A)

110-CB-DPLSH-1

SIEMENS

BQD

BQD

Trip 30.0 A Plug 30.0 A Settings Phase Fixed

110-CB-DPLSH-2

SIEMENS

BQD

BQD

Trip 100.0 A Plug 100.0 A Settings Phase Fixed

110-CB-DPLSH-3

SIEMENS

BQD

BQD

Trip 50.0 A Plug 50.0 A Settings Phase Fixed

110-CB-DPLSH

SIEMENS

FXD6-A Sentron

FXD6-A

Trip 100.0 A Plug 100.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) HI (1200A)

110-CB-DPLSH-1

SIEMENS

BQD

BQD

Trip 30.0 A Plug 30.0 A Settings Phase Fixed

110-CB-DPLSH-2

SIEMENS

BQD

BQD

Trip 100.0 A Plug 100.0 A Settings Phase Fixed

110-CB-DPLSH-3

SIEMENS

BQD

BQD

Trip 50.0 A Plug 50.0 A Settings Phase Fixed

110-CB-DPLSH

110-BUS-DPLSH

110-CB-DPLSH-1

110-CB-DPLSH-2

110-CB-DPLSH-3

TCC Comments: Replacement of 110-CB-DPLSH-2 suggested for improved coordination.

TCC: 110_DPLSH Current Scale x 1 Reference Voltage: 480 January 27, 2020 VAMC Honolulu (Existing) SKM Systems Analysis, Inc.

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

110-CB-DPLSH

SIEMENS

FXD6-A Sentron

FXD6-A

Trip 100.0 A Plug 100.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) HI (1200A)

110-CB-DPLSH-1

SIEMENS

BQD

BQD

Trip 30.0 A Plug 30.0 A Settings Phase Fixed

110-CB-DPLSH-2

SIEMENS

BQD

BQD

Trip 70.0 A Plug 70.0 A Settings Phase Fixed

110-CB-DPLSH-3

SIEMENS

BQD

BQD

Trip 50.0 A Plug 50.0 A Settings Phase Fixed

110-CB-DPLSH

SIEMENS

FXD6-A Sentron

FXD6-A

Trip 100.0 A Plug 100.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) HI (1200A)

110-CB-DPLSH-1

SIEMENS

BQD

BQD

Trip 30.0 A Plug 30.0 A Settings Phase Fixed

110-CB-DPLSH-2

SIEMENS

BQD

BQD

Trip 70.0 A Plug 70.0 A Settings Phase Fixed

110-CB-DPLSH-3

SIEMENS

BQD

BQD

Trip 50.0 A Plug 50.0 A Settings Phase Fixed

110-CB-DPLSH

110-BUS-DPLSH

110-CB-DPLSH-1

110-CB-DPLSH-2

110-CB-DPLSH-3

TCC Comments: 110-CB-DPLSH-2 replaced with 70A equivalent breaker.

TCC: 110_DPLSH Current Scale x 1 Reference Voltage: 480 January 27, 2020 VAMC Honolulu (Recommended) SKM Systems Analysis, Inc.

110-CBL-NL1 (2)110-CBL-NL1 (2)-1110-CBL-NL1 (2)-2

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

110-CB-NL1 (1)-MAIN

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) 3 (2570A)

110-CB-NL1 (2)-1

SIEMENS

QJH2

QJH2

Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (2650A)

110-CB-NL1 (2)-2

SIEMENS

QJH2

QJH2

Trip 150.0 A Plug 150.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (1750A)

110-CB-NKL1-MAIN

SIEMENS

QJH2

QJH2

Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (2650A)

110-CB-NDL1-MAIN

SIEMENS

QJH2

QJH2

Trip 150.0 A Plug 150.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (1750A)

110-CBL-NL1 (2)

110-CBL-NL1 (2)-1

110-CBL-NL1 (2)-2

110-CB-NL1 (1)-MAIN

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) 3 (2570A)

110-CB-NL1 (2)-1

SIEMENS

QJH2

QJH2

Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (2650A)

110-CB-NL1 (2)-2

SIEMENS

QJH2

QJH2

Trip 150.0 A Plug 150.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (1750A)

110-CB-NKL1-MAIN

SIEMENS

QJH2

QJH2

Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (2650A)

110-CB-NDL1-MAIN

SIEMENS

QJH2

QJH2

Trip 150.0 A Plug 150.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (1750A)

110-CBL-NL1 (2)

110-CBL-NL1 (2)-1

110-CBL-NL1 (2)-2

110-CB-NL1 (1)-MAIN

110-BUS-NL1 (1)

110-CBL-NL1 (2)

110-BUS-NL1 (2)

110-CB-NL1 (2)-1 110-CB-NL1 (2)-2

110-CBL-NL1 (2)-1

110-CB-NKL1-MAIN

110-BUS-NKL1 110-BUS-NDL1

110-CB-NDL1-MAIN

110-CBL-NL1 (2)-2

TCC Comments: Adjustment to 110-CB-NL1 (1)-MAIN trip settings suggested for improved coordination.

TCC: 110_MSB - DPNH - NH1 - NL1 Current Scale x 1 Reference Voltage: 208 January 29, 2020 VAMC Honolulu (Existing) SKM Systems Analysis, Inc.

110-CBL-NL1 (2)110-CBL-NL1 (2)-1110-CBL-NL1 (2)-2

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

110-CB-NL1 (1)-MAIN

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) HI (4000A)

110-CB-NL1 (2)-1

SIEMENS

QJH2

QJH2

Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (2650A)

110-CB-NL1 (2)-2

SIEMENS

QJH2

QJH2

Trip 150.0 A Plug 150.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (1750A)

110-CB-NKL1-MAIN

SIEMENS

QJH2

QJH2

Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (2650A)

110-CB-NDL1-MAIN

SIEMENS

QJH2

QJH2

Trip 150.0 A Plug 150.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (1750A)

110-CBL-NL1 (2)

110-CBL-NL1 (2)-1

110-CBL-NL1 (2)-2

110-CB-NL1 (1)-MAIN

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) HI (4000A)

110-CB-NL1 (2)-1

SIEMENS

QJH2

QJH2

Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (2650A)

110-CB-NL1 (2)-2

SIEMENS

QJH2

QJH2

Trip 150.0 A Plug 150.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (1750A)

110-CB-NKL1-MAIN

SIEMENS

QJH2

QJH2

Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (2650A)

110-CB-NDL1-MAIN

SIEMENS

QJH2

QJH2

Trip 150.0 A Plug 150.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (1750A)

110-CBL-NL1 (2)

110-CBL-NL1 (2)-1

110-CBL-NL1 (2)-2

110-CB-NL1 (1)-MAIN

110-BUS-NL1 (1)

110-CBL-NL1 (2)

110-BUS-NL1 (2)

110-CB-NL1 (2)-1 110-CB-NL1 (2)-2

110-CBL-NL1 (2)-1

110-CB-NKL1-MAIN

110-BUS-NKL1 110-BUS-NDL1

110-CB-NDL1-MAIN

110-CBL-NL1 (2)-2

TCC Comments: 110-CB-NL1 (1)-MAIN adjustments include INST from 3 to HI.

TCC: 110_MSB - DPNH - NH1 - NL1 Current Scale x 1 Reference Voltage: 208 January 29, 2020 VAMC Honolulu (Recommended) SKM Systems Analysis, Inc.

110-CBL-DPNH-1110-CBL-NH1-1

TX Inrush

110-XF-T3110-CBL-NL1 (1)

0.5

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

110-CB-DPNH-1

SIEMENS

JG, ETU 555 GF Mod

NJG

Trip 400.0 A Plug 400.0 A Settings Phase LTPU (Ir) 400A (400A) LTD (tr) 20 STPU (Isd) 8 (3200A) STD (tsd) I2T-OFF 0.1 (I^s T Off) INST (Ii) 11 (4400A)

110-CB-NH1-MAIN

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (2000A)

110-CB-NH1-1

SIEMENS

FD6-A Sentron

FD6-A

Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) 5 (1900A)

110-CB-NL1 (1)-MAIN

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) 3 (2570A)

110-CBL-DPNH-1

110-CBL-NH1-1

110-XF-T3

Pri: 480 V Sec: 208 V

112.5 kVA

110-CBL-NL1 (1)

110-CB-DPNH-1

SIEMENS

JG, ETU 555 GF Mod

NJG

Trip 400.0 A Plug 400.0 A Settings Phase LTPU (Ir) 400A (400A) LTD (tr) 20 STPU (Isd) 8 (3200A) STD (tsd) I2T-OFF 0.1 (I^s T Off) INST (Ii) 11 (4400A)

110-CB-NH1-MAIN

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (2000A)

110-CB-NH1-1

SIEMENS

FD6-A Sentron

FD6-A

Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) 5 (1900A)

110-CB-NL1 (1)-MAIN

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) 3 (2570A)

110-CBL-DPNH-1

110-CBL-NH1-1

110-XF-T3

Pri: 480 V Sec: 208 V

112.5 kVA

110-CBL-NL1 (1)

110-CB-DPNH-1

110-CB-DPNH-12 (GF)

110-CBL-DPNH-1

110-CB-NH1-MAIN

110-BUS-NH1

110-CB-NH1-1

110-CBL-NH1-1

110-BUS-XF T3-PRI

S

P

110-XF-T3

110-BUS-XF T3-SEC

110-CBL-NL1 (1)

110-CB-NL1 (1)-MAIN

110-BUS-NL1 (1)

TCC Comments: Adjustment to 110-CB-DPNH-1, 110-CB-NH1-MAIN, and 110-CB-NL1 (1)-MAIN trip settings suggested for improved coordination.

TCC: 110_MSB - DPNH - NH1 Current Scale x 1 Reference Voltage: 480 January 31, 2020 VAMC Honolulu (Existing) SKM Systems Analysis, Inc.

110-CBL-DPNH-1110-CBL-NH1-1

110-XF-T3110-CBL-NL1 (1)

0.5

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

110-CB-DPNH-1

SIEMENS

JG, ETU 555 GF Mod

HJG

Trip 400.0 A Plug 400.0 A Settings Phase LTPU (Ir) 400A (400A) LTD (tr) 10 STPU (Isd) 6 (2400A) STD (tsd) I2T-OFF 0.1 (I^s T Off) INST (Ii) 11 (4400A)

110-CB-NH1-MAIN

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) 5 (3140A)

110-CB-NH1-1

SIEMENS

FD6-A Sentron

FD6-A

Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) 5 (1900A)

110-CB-NL1 (1)-MAIN

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) HI (4000A)

110-CBL-DPNH-1

110-CBL-NH1-1

110-XF-T3

Pri: 480 V Sec: 208 V

112.5 kVA

110-CBL-NL1 (1)

110-CB-DPNH-1

SIEMENS

JG, ETU 555 GF Mod

HJG

Trip 400.0 A Plug 400.0 A Settings Phase LTPU (Ir) 400A (400A) LTD (tr) 10 STPU (Isd) 6 (2400A) STD (tsd) I2T-OFF 0.1 (I^s T Off) INST (Ii) 11 (4400A)

110-CB-NH1-MAIN

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) 5 (3140A)

110-CB-NH1-1

SIEMENS

FD6-A Sentron

FD6-A

Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) 5 (1900A)

110-CB-NL1 (1)-MAIN

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) HI (4000A)

110-CBL-DPNH-1

110-CBL-NH1-1

110-XF-T3

Pri: 480 V Sec: 208 V

112.5 kVA

110-CBL-NL1 (1)

110-CB-DPNH-1

110-CB-DPNH-12 (GF)

110-CBL-DPNH-1

110-CB-NH1-MAIN

110-BUS-NH1

110-CB-NH1-1

110-CBL-NH1-1

110-BUS-XF T3-PRI

S

P

110-XF-T3

110-BUS-XF T3-SEC

110-CBL-NL1 (1)

110-CB-NL1 (1)-MAIN

110-BUS-NL1 (1)

TCC Comments: 110-CB-DPNH-1 adjustments include LTD from 20 to 10 and STPU from 8 to 6.

110-CB-NH1-MAIN adjustments include INST from LO to 5.

110-CB-NL1 (1)-MAIN adjustments include INST from 3 to HI.

TCC: 110_MSB - DPNH - NH1 Current Scale x 1 Reference Voltage: 480 January 31, 2020 VAMC Honolulu (Recommended) SKM Systems Analysis, Inc.

110-CBL-NL2 (2)110-CBL-NL2 (2)-1110-CBL-NL2 (2)-2

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

110-CB-NL2 (1)-MAIN

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) 3 (2570A)

110-CB-NL2 (2)-1

SIEMENS

BLH, 2 & 3-Pole

BLH

Trip 70.0 A Plug 70.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (675A)

110-CB-NL2A-MAIN

SIEMENS

BLH, 2 & 3-Pole

BLH

Trip 70.0 A Plug 70.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (675A)

110-CB-NL2B-MAIN

SIEMENS

BLH, 2 & 3-Pole

BLH

Trip 70.0 A Plug 70.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (675A)

110-CB-NL2 (2)-2

SIEMENS

BLH, 2 & 3-Pole

BLH

Trip 70.0 A Plug 70.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (675A)

110-CBL-NL2 (2)

110-CBL-NL2 (2)-1

110-CBL-NL2 (2)-2

110-CB-NL2 (1)-MAIN

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) 3 (2570A)

110-CB-NL2 (2)-1

SIEMENS

BLH, 2 & 3-Pole

BLH

Trip 70.0 A Plug 70.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (675A)

110-CB-NL2A-MAIN

SIEMENS

BLH, 2 & 3-Pole

BLH

Trip 70.0 A Plug 70.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (675A)

110-CB-NL2B-MAIN

SIEMENS

BLH, 2 & 3-Pole

BLH

Trip 70.0 A Plug 70.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (675A)

110-CB-NL2 (2)-2

SIEMENS

BLH, 2 & 3-Pole

BLH

Trip 70.0 A Plug 70.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (675A)

110-CBL-NL2 (2)

110-CBL-NL2 (2)-1

110-CBL-NL2 (2)-2

110-CB-NL2 (1)-MAIN

110-BUS-NL2 (1)

110-CBL-NL2 (2)

110-BUS-NL2 (2)

110-CB-NL2 (2)-1

110-CBL-NL2 (2)-1

110-CB-NL2A-MAIN

110-BUS-NL2A 110-BUS-NL2B

110-CB-NL2B-MAIN

110-CBL-NL2 (2)-2

110-CB-NL2 (2)-2

TCC Comments: No adjustments required.

TCC: 110_MSB - DPNH - NH2 - NL2 Current Scale x 1 Reference Voltage: 208

110-CBL-DPNH-2110-CBL-NH2-1

110-XF-T5110-CBL-NL2 (1)

0.5

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

110-CB-DPNH-2

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 350.0 A Plug 350.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (2000A)

110-CB-NH2-MAIN

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 350.0 A Plug 350.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (2000A)

110-CB-NH2-1

SIEMENS

FD6-A Sentron

FD6-A

Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) 5 (1900A)

110-CB-NL2 (1)-MAIN

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) 3 (2570A)

110-CBL-DPNH-2

110-CBL-NH2-1

110-XF-T5

Pri: 480 V Sec: 208 V

112.5 kVA

110-CBL-NL2 (1)

110-CB-DPNH-2

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 350.0 A Plug 350.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (2000A)

110-CB-NH2-MAIN

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 350.0 A Plug 350.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (2000A)

110-CB-NH2-1

SIEMENS

FD6-A Sentron

FD6-A

Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) 5 (1900A)

110-CB-NL2 (1)-MAIN

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) 3 (2570A)

110-CBL-DPNH-2

110-CBL-NH2-1

110-XF-T5

Pri: 480 V Sec: 208 V

112.5 kVA

110-CBL-NL2 (1)

110-CB-DPNH-2

110-CBL-DPNH-2

110-BUS-NH2

110-CB-NH2-MAIN

110-CB-NH2-1

110-CBL-NH2-1

S

P

110-XF-T5

110-BUS-XF T5-PRI

110-BUS-XF T5-SEC

110-CBL-NL2 (1)

110-CB-NL2 (1)-MAIN

110-BUS-NL2 (1)

TCC Comments: Adjustment to 110-CB-NH2-1 trip settings suggested for improved coordination.

TCC: 110_MSB - DPNH - NH2 Current Scale x 1 Reference Voltage: 480

110-CBL-DPNH-2110-CBL-NH2-1

110-XF-T5110-CBL-NL2 (1)

0.5

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

110-CB-DPNH-2

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 350.0 A Plug 350.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (2000A)

110-CB-NH2-MAIN

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 350.0 A Plug 350.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (2000A)

110-CB-NH2-1

SIEMENS

FD6-A Sentron

FD6-A

Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (1100A)

110-CB-NL2 (1)-MAIN

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) 3 (2570A)

110-CBL-DPNH-2

110-CBL-NH2-1

110-XF-T5

Pri: 480 V Sec: 208 V

112.5 kVA

110-CBL-NL2 (1)

110-CB-DPNH-2

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 350.0 A Plug 350.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (2000A)

110-CB-NH2-MAIN

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 350.0 A Plug 350.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (2000A)

110-CB-NH2-1

SIEMENS

FD6-A Sentron

FD6-A

Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (1100A)

110-CB-NL2 (1)-MAIN

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 400.0 A Plug 400.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) 3 (2570A)

110-CBL-DPNH-2

110-CBL-NH2-1

110-XF-T5

Pri: 480 V Sec: 208 V

112.5 kVA

110-CBL-NL2 (1)

110-CB-DPNH-2

110-CBL-DPNH-2

110-BUS-NH2

110-CB-NH2-MAIN

110-CB-NH2-1

110-CBL-NH2-1

S

P

110-XF-T5

110-BUS-XF T5-PRI

110-BUS-XF T5-SEC

110-CBL-NL2 (1)

110-CB-NL2 (1)-MAIN

110-BUS-NL2 (1)

TCC Comments: 110-CB-NH2-1 adjustments include INST from 5 to LO.

TCC: 110_MSB - DPNH - NH2 Current Scale x 1 Reference Voltage: 480

110-CBL-NL3 (2)110-CBL-NL3 (2)-1

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

110-CB-NL3 (1)-MAIN

SIEMENS

QJH2

QJH2

Trip 150.0 A Plug 150.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (1750A)

110-CB-NL3 (2)-1

SIEMENS

BLH, 2 & 3-Pole

BLH

Trip 50.0 A Plug 50.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (425A)

110-CB-NL3A-MAIN

GE

THQB

THQB

Trip 50.0 A Plug 50.0 A Settings Phase Fixed

110-CBL-NL3 (2)

110-CBL-NL3 (2)-1

110-CB-NL3 (1)-MAIN

SIEMENS

QJH2

QJH2

Trip 150.0 A Plug 150.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (1750A)

110-CB-NL3 (2)-1

SIEMENS

BLH, 2 & 3-Pole

BLH

Trip 50.0 A Plug 50.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (425A)

110-CB-NL3A-MAIN

GE

THQB

THQB

Trip 50.0 A Plug 50.0 A Settings Phase Fixed

110-CBL-NL3 (2)

110-CBL-NL3 (2)-1

110-CB-NL3 (1)-MAIN

110-BUS-NL3 (1)

110-CBL-NL3 (2)

110-BUS-NL3 (2)

110-CB-NL3 (2)-1

110-CBL-NL3 (2)-1

110-CB-NL3A-MAIN

110-BUS-NL3A

TCC Comments: No adjustments required.

TCC: 110_MSB - DPNH - NH3 - NL3 Current Scale x 1 Reference Voltage: 208

110-CBL-DPNH-3110-CBL-NH3-1

110-XF-T7110-CBL-NL3 (1)

0.5

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

110-CB-DPNH-3

SIEMENS

FXD6 Sentron

FXD6

Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (1100A)

110-CB-NH3-MAIN

SIEMENS

FXD6-A Sentron

FXD6-A

Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (1100A)

110-CB-NH3-1

SIEMENS

BQD

BQD

Trip 70.0 A Plug 70.0 A Settings Phase Fixed

110-CB-NL3 (1)-MAIN

SIEMENS

QJH2

QJH2

Trip 150.0 A Plug 150.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (1750A)

110-CBL-DPNH-3

110-CBL-NH3-1

110-XF-T7

Pri: 480 V Sec: 208 V

45.0 kVA

110-CBL-NL3 (1)

110-CB-DPNH-3

SIEMENS

FXD6 Sentron

FXD6

Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (1100A)

110-CB-NH3-MAIN

SIEMENS

FXD6-A Sentron

FXD6-A

Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (1100A)

110-CB-NH3-1

SIEMENS

BQD

BQD

Trip 70.0 A Plug 70.0 A Settings Phase Fixed

110-CB-NL3 (1)-MAIN

SIEMENS

QJH2

QJH2

Trip 150.0 A Plug 150.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (1750A)

110-CBL-DPNH-3

110-CBL-NH3-1

110-XF-T7

Pri: 480 V Sec: 208 V

45.0 kVA

110-CBL-NL3 (1)

110-CB-DPNH-3

110-CBL-DPNH-3

110-BUS-NH3

110-CB-NH3-MAIN

110-CB-NH3-1

110-CBL-NH3-1

S

P

110-XF-T7

110-BUS-XF T7-PRI

110-BUS-XF T7-SEC

110-CBL-NL3 (1)

110-CB-NL3 (1)-MAIN

110-BUS-NL3 (1)

TCC Comments: No adjustments required.

TCC: 110_MSB - DPNH - NH3 Current Scale x 1 Reference Voltage: 480

110-CBL-MSB-1

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

110-CB-MSB-1

SIEMENS

SHMD6, Sensitrip III

SHMD6

Trip 800.0 A Plug 600.0 A Settings Phase LTPU (20-100% x P) 100 % (600A) LTD (2.2-27 Sec.) 20 STPU (1.5-10 x LTPU) 5 (3000A) STD (0.05-0.5 Sec.) 0.1 Sec. (I^s T Off) INST (2-40 x LTPU) 15 (9000A) INST Override (Max) Max (10000A)

110-CB-DPNH-MAIN

SIEMENS

LXD6-A Sentron

LXD6-A

Trip 600.0 A Plug 600.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (3000A)

110-CB-DPNH-1

SIEMENS

JG, ETU 555 GF Mod

NJG

Trip 400.0 A Plug 400.0 A Settings Phase LTPU (Ir) 400A (400A) LTD (tr) 20 STPU (Isd) 8 (3200A) STD (tsd) I2T-OFF 0.1 (I^s T Off) INST (Ii) 11 (4400A)

110-CB-DPNH-2

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 350.0 A Plug 350.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (2000A)

110-CB-DPNH-3

SIEMENS

FXD6 Sentron

FXD6

Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (1100A)

110-CBL-MSB-1

110-CB-MSB-1

SIEMENS

SHMD6, Sensitrip III

SHMD6

Trip 800.0 A Plug 600.0 A Settings Phase LTPU (20-100% x P) 100 % (600A) LTD (2.2-27 Sec.) 20 STPU (1.5-10 x LTPU) 5 (3000A) STD (0.05-0.5 Sec.) 0.1 Sec. (I^s T Off) INST (2-40 x LTPU) 15 (9000A) INST Override (Max) Max (10000A)

110-CB-DPNH-MAIN

SIEMENS

LXD6-A Sentron

LXD6-A

Trip 600.0 A Plug 600.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (3000A)

110-CB-DPNH-1

SIEMENS

JG, ETU 555 GF Mod

NJG

Trip 400.0 A Plug 400.0 A Settings Phase LTPU (Ir) 400A (400A) LTD (tr) 20 STPU (Isd) 8 (3200A) STD (tsd) I2T-OFF 0.1 (I^s T Off) INST (Ii) 11 (4400A)

110-CB-DPNH-2

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 350.0 A Plug 350.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (2000A)

110-CB-DPNH-3

SIEMENS

FXD6 Sentron

FXD6

Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (1100A)

110-CBL-MSB-1

110-CB-MSB-1

110-CB-MSB-1 (GF)

110-CBL-MSB-1

110-CB-DPNH-MAIN

110-BUS-DPNH

110-CB-DPNH-1

110-CB-DPNH-2

110-CB-DPNH-3

TCC Comments: Adjustment to 110-CB-MSB-1, 110-CB-DPNH-MAIN, and 110-CB-DPNH-1 trip settings suggested for improved coordination.

TCC: 110_MSB - DPNH Current Scale x 1 Reference Voltage: 480

110-CBL-MSB-1

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

110-CB-MSB-1

SIEMENS

SHMD6, Sensitrip III

SHMD6

Trip 800.0 A Plug 600.0 A Settings Phase LTPU (20-100% x P) 100 % (600A) LTD (2.2-27 Sec.) 7 STPU (1.5-10 x LTPU) 6 (3600A) STD (0.05-0.5 Sec.) 0.2 Sec. (I^s T Off) INST (2-40 x LTPU) 10 (6000A) INST Override (Max) Max (10000A)

110-CB-DPNH-MAIN

SIEMENS

LXD6-A Sentron

LXD6-A

Trip 600.0 A Plug 600.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) 7 (5570A)

110-CB-DPNH-1

SIEMENS

JG, ETU 555 GF Mod

HJG

Trip 400.0 A Plug 400.0 A Settings Phase LTPU (Ir) 400A (400A) LTD (tr) 10 STPU (Isd) 6 (2400A) STD (tsd) I2T-OFF 0.1 (I^s T Off) INST (Ii) 11 (4400A)

110-CB-DPNH-2

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 350.0 A Plug 350.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (2000A)

110-CB-DPNH-3

SIEMENS

FXD6 Sentron

FXD6

Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (1100A)

110-CBL-MSB-1

110-CB-MSB-1

SIEMENS

SHMD6, Sensitrip III

SHMD6

Trip 800.0 A Plug 600.0 A Settings Phase LTPU (20-100% x P) 100 % (600A) LTD (2.2-27 Sec.) 7 STPU (1.5-10 x LTPU) 6 (3600A) STD (0.05-0.5 Sec.) 0.2 Sec. (I^s T Off) INST (2-40 x LTPU) 10 (6000A) INST Override (Max) Max (10000A)

110-CB-DPNH-MAIN

SIEMENS

LXD6-A Sentron

LXD6-A

Trip 600.0 A Plug 600.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) 7 (5570A)

110-CB-DPNH-1

SIEMENS

JG, ETU 555 GF Mod

HJG

Trip 400.0 A Plug 400.0 A Settings Phase LTPU (Ir) 400A (400A) LTD (tr) 10 STPU (Isd) 6 (2400A) STD (tsd) I2T-OFF 0.1 (I^s T Off) INST (Ii) 11 (4400A)

110-CB-DPNH-2

SIEMENS

JXD6-A Sentron

JXD6-A

Trip 350.0 A Plug 350.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (2000A)

110-CB-DPNH-3

SIEMENS

FXD6 Sentron

FXD6

Trip 225.0 A Plug 225.0 A Settings Phase Thermal Curve (Fixed)

INST (LO-HI) LO (1100A)

110-CBL-MSB-1

110-CB-MSB-1

110-CB-MSB-1 (GF)

110-CBL-MSB-1

110-CB-DPNH-MAIN

110-BUS-DPNH

110-CB-DPNH-1

110-CB-DPNH-2

110-CB-DPNH-3

TCC Comments: 110-CB-MSB-1 adjustments include LTD from 20 to 7, STPU from 5 to 7, STD from 0.1 to 0.2, and INST from 15 to 10.

110-CB-DPNH-MAIN adjustments include INST from LO to 7.

110-CB-DPNH-1 adjustments include LTD from 20 to 10 and STPU from 8 to 6.

TCC: 110_MSB - DPNH Current Scale x 1 Reference Voltage: 480

110-CBL-MSB-3110-CBL-ERNH-1

110-XF-T1110-CBL-ERNL

0.5

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

110-CB-MSB-3

SIEMENS

DG, ETU 555 GF Mod

HDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 14 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.5 (I^s T Off) INST (Ii) 11 (1100A)

110-CB-ERNH-MAIN

SIEMENS

ED6 Sentron, 2 & 3-Pole

ED6

Trip 100.0 A Plug 100.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (800A)

110-CB-ERNH-1

SIEMENS

ED6 Sentron, 2 & 3-Pole

ED6

Trip 20.0 A Plug 20.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (550A)

110-CB-ERNL-MAIN

SIEMENS

BLH, 2 & 3-Pole

BLH

Trip 30.0 A Plug 30.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (425A)

110-CBL-MSB-3

110-CBL-ERNH-1

110-XF-T1

Pri: 480 V Sec: 208 V

9.0 kVA

110-CBL-ERNL

110-CB-MSB-3

SIEMENS

DG, ETU 555 GF Mod

HDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 14 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.5 (I^s T Off) INST (Ii) 11 (1100A)

110-CB-ERNH-MAIN

SIEMENS

ED6 Sentron, 2 & 3-Pole

ED6

Trip 100.0 A Plug 100.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (800A)

110-CB-ERNH-1

SIEMENS

ED6 Sentron, 2 & 3-Pole

ED6

Trip 20.0 A Plug 20.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (550A)

110-CB-ERNL-MAIN

SIEMENS

BLH, 2 & 3-Pole

BLH

Trip 30.0 A Plug 30.0 A Settings Phase Thermal Curve (Fixed) INST Fixed (425A)

110-CBL-MSB-3

110-CBL-ERNH-1

110-XF-T1

Pri: 480 V Sec: 208 V

9.0 kVA

110-CBL-ERNL

110-CB-MSB-3

110-CB-MSB-3 (GF)

110-CBL-MSB-3

110-BUS-ERNH

110-CB-ERNH-MAIN

110-CB-ERNH-1

110-CBL-ERNH-1

S

P

110-XF-T1

110-BUS-XF T1-PRI

110-CBL-ERNL

110-BUS-XF T1-SEC

110-CB-ERNL-MAIN

110-BUS-ERNL

TCC Comments: No adjustments required.

TCC: 110_MSB - ERNH Current Scale x 1 Reference Voltage: 480

110-CBL-MSB-6

110-XF-T12110-CBL-NL4110-CBL-XF T12

0.5

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

110-CB-MSB-6

SIEMENS

DG, ETU 555 Non-GF Mod

HDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 40A (40A) LTD (tr) 4 STPU (Isd) 1.5 (60A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 125A (125A)

110-SW-XF T12 DISC

BUSSMANN

FRS-R, 600V Class RK5

FRS-R

Trip 100.0 A

110-CBL-MSB-6

110-XF-T12

Pri: 480 V Sec: 208 V

75.0 kVA

110-CBL-NL4

110-CBL-XF T12

110-CB-MSB-6

SIEMENS

DG, ETU 555 Non-GF Mod

HDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 40A (40A) LTD (tr) 4 STPU (Isd) 1.5 (60A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 125A (125A)

110-SW-XF T12 DISC

BUSSMANN

FRS-R, 600V Class RK5

FRS-R

Trip 100.0 A

110-CBL-MSB-6

110-XF-T12

Pri: 480 V Sec: 208 V

75.0 kVA

110-CBL-NL4

110-CBL-XF T12

110-CB-MSB-6

110-CBL-MSB-6

110-BUS-XF T12-PRI

S

P

110-XF-T12

110-CBL-NL4

110-BUS-XF T12-SEC

110-BUS-XF T12 DISC

110-CBL-XF T12

110-SW-XF T12 DISC

110-BUS-NL4

TCC Comments: Adjustment to 110-CB-MSB-6 trip settings suggested for improved coordination.

TCC: 110_MSB - NL4 Current Scale x 1 Reference Voltage: 480

110-CBL-MSB-6

110-XF-T12110-CBL-NL4110-CBL-XF T12

0.5

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

110-CB-MSB-6

SIEMENS

DG, ETU 555 Non-GF Mod

HDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 1000A (1000A)

110-SW-XF T12 DISC

BUSSMANN

FRS-R, 600V Class RK5

FRS-R

Trip 100.0 A

110-CBL-MSB-6

110-XF-T12

Pri: 480 V Sec: 208 V

75.0 kVA

110-CBL-NL4

110-CBL-XF T12

110-CB-MSB-6

SIEMENS

DG, ETU 555 Non-GF Mod

HDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 1000A (1000A)

110-SW-XF T12 DISC

BUSSMANN

FRS-R, 600V Class RK5

FRS-R

Trip 100.0 A

110-CBL-MSB-6

110-XF-T12

Pri: 480 V Sec: 208 V

75.0 kVA

110-CBL-NL4

110-CBL-XF T12

110-CB-MSB-6

110-CBL-MSB-6

110-BUS-XF T12-PRI

S

P

110-XF-T12

110-CBL-NL4

110-BUS-XF T12-SEC

110-BUS-XF T12 DISC

110-CBL-XF T12

110-SW-XF T12 DISC

110-BUS-NL4

TCC Comments: 110-CB-MSB-6 adjustments include LTPU from 40A to 100A, STPU from 1.5 to 10, and INST from 125A to 1000A.

TCC: 110_MSB - NL4 Current Scale x 1 Reference Voltage: 480

110-CBL-INV 1110-CBL-INV 2110-CBL-INV 3110-CBL-PV DISC110-CBL-MSB-5

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S 110-CB-INV 1

SIEMENS

BQD

BQD

Trip 25.0 A Plug 25.0 A Settings Phase Fixed

110-CB-INV 2

SIEMENS

BQD

BQD

Trip 40.0 A Plug 40.0 A Settings Phase Fixed

110-CB-INV 3

SIEMENS

BQD

BQD

Trip 40.0 A Plug 40.0 A Settings Phase Fixed

110-SW-PV DISC

BUSSMANN

FRS-R, 600V Class RK5

FRS-R

Trip 100.0 A

110-CB-MSB-5

SIEMENS

DG, ETU 555 GF Mod

NDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 1.5 (150A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 5 (500A)

110-CBL-INV 1

110-CBL-INV 2

110-CBL-INV 3

110-CBL-PV DISC

110-CBL-MSB-5

110-CB-INV 1

SIEMENS

BQD

BQD

Trip 25.0 A Plug 25.0 A Settings Phase Fixed

110-CB-INV 2

SIEMENS

BQD

BQD

Trip 40.0 A Plug 40.0 A Settings Phase Fixed

110-CB-INV 3

SIEMENS

BQD

BQD

Trip 40.0 A Plug 40.0 A Settings Phase Fixed

110-SW-PV DISC

BUSSMANN

FRS-R, 600V Class RK5

FRS-R

Trip 100.0 A

110-CB-MSB-5

SIEMENS

DG, ETU 555 GF Mod

NDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 1.5 (150A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 5 (500A)

110-CBL-INV 1

110-CBL-INV 2

110-CBL-INV 3

110-CBL-PV DISC

110-CBL-MSB-5

110-PV INVERTER 1

110-PV INVERTER 2

110-PV INVERTER 3

110-CBL-INV 1

110-CBL-INV 2

110-BUS-PV INV 2

110-CBL-INV 3

110-BUS-PV INV 3

110-BUS-PV INV 1

110-CB-INV 1

110-CB-INV 2 110-CB-INV 3

110-BUS-PV COMBINER

110-CBL-PV DISC

110-SW-PV DISC

110-BUS-PV DISC

110-CBL-MSB-5

110-CB-MSB-5 (GF)

110-CB-MSB-5

TCC Comments: Adjustment to 110-CB-MSB-5 trip settings suggested for improved coordination.

TCC: 110_MSB - PV INPUT Current Scale x 1 Reference Voltage: 480

110-CBL-INV 1110-CBL-INV 2110-CBL-INV 3110-CBL-PV DISC110-CBL-MSB-5

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S 110-CB-INV 1

SIEMENS

BQD

BQD

Trip 25.0 A Plug 25.0 A Settings Phase Fixed

110-CB-INV 2

SIEMENS

BQD

BQD

Trip 40.0 A Plug 40.0 A Settings Phase Fixed

110-CB-INV 3

SIEMENS

BQD

BQD

Trip 40.0 A Plug 40.0 A Settings Phase Fixed

110-SW-PV DISC

BUSSMANN

FRS-R, 600V Class RK5

FRS-R

Trip 100.0 A

110-CB-MSB-5

SIEMENS

DG, ETU 555 GF Mod

HDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 11 (1100A)

110-CBL-INV 1

110-CBL-INV 2

110-CBL-INV 3

110-CBL-PV DISC

110-CBL-MSB-5

110-CB-INV 1

SIEMENS

BQD

BQD

Trip 25.0 A Plug 25.0 A Settings Phase Fixed

110-CB-INV 2

SIEMENS

BQD

BQD

Trip 40.0 A Plug 40.0 A Settings Phase Fixed

110-CB-INV 3

SIEMENS

BQD

BQD

Trip 40.0 A Plug 40.0 A Settings Phase Fixed

110-SW-PV DISC

BUSSMANN

FRS-R, 600V Class RK5

FRS-R

Trip 100.0 A

110-CB-MSB-5

SIEMENS

DG, ETU 555 GF Mod

HDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 11 (1100A)

110-CBL-INV 1

110-CBL-INV 2

110-CBL-INV 3

110-CBL-PV DISC

110-CBL-MSB-5

110-PV INVERTER 1

110-PV INVERTER 2

110-PV INVERTER 3

110-CBL-INV 1

110-CBL-INV 2

110-BUS-PV INV 2

110-CBL-INV 3

110-BUS-PV INV 3

110-BUS-PV INV 1

110-CB-INV 1

110-CB-INV 2 110-CB-INV 3

110-BUS-PV COMBINER

110-CBL-PV DISC

110-SW-PV DISC

110-BUS-PV DISC

110-CBL-MSB-5

110-CB-MSB-5 (GF)

110-CB-MSB-5

TCC Comments: 110-CB-MSB-5 adjustments include STPU from 1.5 to 10 and INST from 5 to 11.

TCC: 110_MSB - PV INPUT Current Scale x 1 Reference Voltage: 480

110-XF-BLDG 110110-CBL-MSB

0.5

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

110-CB-MSB-MAIN

SIEMENS

SHMD6, Sensitrip III

SHMD6

Trip 800.0 A Plug 800.0 A Settings Phase LTPU (20-100% x P) 90 % (720A) LTD (2.2-27 Sec.) 27 STPU (1.5-10 x LTPU) 7 (5040A) STD (0.05-0.5 Sec.) 0.3 Sec. (I^s T Off) INST (2-40 x LTPU) 10 (7200A) INST Override (Max) Max (10000A)

110-CB-MSB-1

SIEMENS

SHMD6, Sensitrip III

SHMD6

Trip 800.0 A Plug 600.0 A Settings Phase LTPU (20-100% x P) 100 % (600A) LTD (2.2-27 Sec.) 20 STPU (1.5-10 x LTPU) 5 (3000A) STD (0.05-0.5 Sec.) 0.1 Sec. (I^s T Off) INST (2-40 x LTPU) 15 (9000A) INST Override (Max) Max (10000A)

110-CB-MSB-2

SIEMENS

FG, ETU 555 GF Mod

HFG

Trip 250.0 A Plug 250.0 A Settings Phase LTPU (Ir) 250A (250A) LTD (tr) 14 STPU (Isd) 8 (2000A) STD (tsd) I2T-OFF 0.1 (I^s T Off) INST (Ii) 11 (2750A)

110-CB-MSB-3

SIEMENS

DG, ETU 555 GF Mod

HDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 14 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.5 (I^s T Off) INST (Ii) 11 (1100A)

110-FS-XF BLDG 110 (1)

ABB

DO-III Dual Element

DO-III

Trip 50.0 A Settings Phase

50.0 Amps

110-FS-XF BLDG 110 (2)

COOPER

ELSP, 15.5kV, (2/03)

ELSP

Trip 100.0 A Settings Phase

100.0 Amps

110-XF-BLDG 110

Pri: 11500 V Sec: 480 V

500.0 kVA

110-CBL-MSB

110-CB-MSB-MAIN

SIEMENS

SHMD6, Sensitrip III

SHMD6

Trip 800.0 A Plug 800.0 A Settings Phase LTPU (20-100% x P) 90 % (720A) LTD (2.2-27 Sec.) 27 STPU (1.5-10 x LTPU) 7 (5040A) STD (0.05-0.5 Sec.) 0.3 Sec. (I^s T Off) INST (2-40 x LTPU) 10 (7200A) INST Override (Max) Max (10000A)

110-CB-MSB-1

SIEMENS

SHMD6, Sensitrip III

SHMD6

Trip 800.0 A Plug 600.0 A Settings Phase LTPU (20-100% x P) 100 % (600A) LTD (2.2-27 Sec.) 20 STPU (1.5-10 x LTPU) 5 (3000A) STD (0.05-0.5 Sec.) 0.1 Sec. (I^s T Off) INST (2-40 x LTPU) 15 (9000A) INST Override (Max) Max (10000A)

110-CB-MSB-2

SIEMENS

FG, ETU 555 GF Mod

HFG

Trip 250.0 A Plug 250.0 A Settings Phase LTPU (Ir) 250A (250A) LTD (tr) 14 STPU (Isd) 8 (2000A) STD (tsd) I2T-OFF 0.1 (I^s T Off) INST (Ii) 11 (2750A)

110-CB-MSB-3

SIEMENS

DG, ETU 555 GF Mod

HDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 14 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.5 (I^s T Off) INST (Ii) 11 (1100A)

110-FS-XF BLDG 110 (1)

ABB

DO-III Dual Element

DO-III

Trip 50.0 A Settings Phase

50.0 Amps

110-FS-XF BLDG 110 (2)

COOPER

ELSP, 15.5kV, (2/03)

ELSP

Trip 100.0 A Settings Phase

100.0 Amps

110-XF-BLDG 110

Pri: 11500 V Sec: 480 V

500.0 kVA

110-CBL-MSB

S

P

110-XF-BLDG 110

110-BUS-XF BLDG 110-PRI

110-CBL-MSB

110-BUS-XF BLDG 110-SEC

110-CB-MSB-MAIN

110-CB-MSB-MAIN (GF)

110-BUS-MSB

110-CB-MSB-1

110-CB-MSB-1 (GF)

110-CB-MSB-2

110-CB-MSB-2 (GF)

110-CB-MSB-3

110-CB-MSB-3 (GF)

110-FS-XF BLDG 110 (2)

110-FS-XF BLDG 110 (1)

TCC Comments: Adjustment to 110-CB-MSB-MAIN, 110-CB-MSB-1, and 110-CB-MSB-2 trip settings suggested for improved coordination.

TCC: 110_MSB (1) Current Scale x 1 Reference Voltage: 480

0.5

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

110-CB-MSB-MAIN

SIEMENS

SHMD6, Sensitrip III

SHMD6

Trip 800.0 A Plug 800.0 A Settings Phase LTPU (20-100% x P) 100 % (800A) LTD (2.2-27 Sec.) 7 STPU (1.5-10 x LTPU) 6 (4800A) STD (0.05-0.5 Sec.) 0.3 Sec. (I^s T Off) INST (2-40 x LTPU) 15 (12000A) INST Override (Max) Max (10000A)

110-CB-MSB-1

SIEMENS

SHMD6, Sensitrip III

SHMD6

Trip 800.0 A Plug 600.0 A Settings Phase LTPU (20-100% x P) 100 % (600A) LTD (2.2-27 Sec.) 7 STPU (1.5-10 x LTPU) 6 (3600A) STD (0.05-0.5 Sec.) 0.2 Sec. (I^s T Off) INST (2-40 x LTPU) 10 (6000A) INST Override (Max) Max (10000A)

110-CB-MSB-2

SIEMENS

FG, ETU 555 GF Mod

HFG

Trip 250.0 A Plug 250.0 A Settings Phase LTPU (Ir) 200A (200A) LTD (tr) 14 STPU (Isd) 10 (2000A) STD (tsd) I2T-OFF 0.1 (I^s T Off) INST (Ii) 11 (2750A)

110-CB-MSB-3

SIEMENS

DG, ETU 555 GF Mod

HDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 14 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.5 (I^s T Off) INST (Ii) 11 (1100A)

110-FS-XF BLDG 110 (1)

ABB

DO-III Dual Element

DO-III

Trip 50.0 A Settings Phase

50.0 Amps

110-FS-XF BLDG 110 (2)

COOPER

ELSP, 15.5kV, (2/03)

ELSP

Trip 100.0 A Settings Phase

100.0 Amps

110-XF-BLDG 110

Pri: 11500 V Sec: 480 V

500.0 kVA

110-CBL-MSB

110-CB-MSB-MAIN

SIEMENS

SHMD6, Sensitrip III

SHMD6

Trip 800.0 A Plug 800.0 A Settings Phase LTPU (20-100% x P) 100 % (800A) LTD (2.2-27 Sec.) 7 STPU (1.5-10 x LTPU) 6 (4800A) STD (0.05-0.5 Sec.) 0.3 Sec. (I^s T Off) INST (2-40 x LTPU) 15 (12000A) INST Override (Max) Max (10000A)

110-CB-MSB-1

SIEMENS

SHMD6, Sensitrip III

SHMD6

Trip 800.0 A Plug 600.0 A Settings Phase LTPU (20-100% x P) 100 % (600A) LTD (2.2-27 Sec.) 7 STPU (1.5-10 x LTPU) 6 (3600A) STD (0.05-0.5 Sec.) 0.2 Sec. (I^s T Off) INST (2-40 x LTPU) 10 (6000A) INST Override (Max) Max (10000A)

110-CB-MSB-2

SIEMENS

FG, ETU 555 GF Mod

HFG

Trip 250.0 A Plug 250.0 A Settings Phase LTPU (Ir) 200A (200A) LTD (tr) 14 STPU (Isd) 10 (2000A) STD (tsd) I2T-OFF 0.1 (I^s T Off) INST (Ii) 11 (2750A)

110-CB-MSB-3

SIEMENS

DG, ETU 555 GF Mod

HDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 14 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.5 (I^s T Off) INST (Ii) 11 (1100A)

110-FS-XF BLDG 110 (1)

ABB

DO-III Dual Element

DO-III

Trip 50.0 A Settings Phase

50.0 Amps

110-FS-XF BLDG 110 (2)

COOPER

ELSP, 15.5kV, (2/03)

ELSP

Trip 100.0 A Settings Phase

100.0 Amps

110-XF-BLDG 110

Pri: 11500 V Sec: 480 V

500.0 kVA

110-CBL-MSB

S

P

110-XF-BLDG 110

110-BUS-XF BLDG 110-PRI

110-CBL-MSB

110-BUS-XF BLDG 110-SEC

110-CB-MSB-MAIN

110-CB-MSB-MAIN (GF)

110-BUS-MSB

110-CB-MSB-1

110-CB-MSB-1 (GF)

110-CB-MSB-2

110-CB-MSB-2 (GF)

110-CB-MSB-3

110-CB-MSB-3 (GF)

110-FS-XF BLDG 110 (2)

110-FS-XF BLDG 110 (1)

TCC Comments: 110-CB-MSB-MAIN adjustments include LTPU from 90% to 100%, LTD from 27 to 7, STPU from 7 to 6, and INST from 10 to 15.

110-CB-MSB-1 adjustments include LTD from 20 to 7, STPU from 5 to 6, STD from 0.1 to 0.2, and INST from 15 to 10.

110-CB-MSB-2 adjustments include LTPU from 250A to 200A and STPU from 8 to 10.

TCC: 110_MSB (1) Current Scale x 1 Reference Voltage: 480

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

110-CB-MSB-MAIN (GF)

SIEMENS

SHMD6, Sensitrip III

SHMD6

Trip 800.0 A Plug 800.0 A Settings Phase

70% GFPU 70 % (560A)

GFD (0.1-0.4 Sec.) 0.4 (I^s T On)

110-CB-MSB-1 (GF)

SIEMENS

SHMD6, Sensitrip III

SHMD6

Trip 800.0 A Plug 600.0 A Settings Phase

70% GFPU 70 % (420A)

GFD (0.1-0.4 Sec.) 0.2 (I^s T On)

110-CB-MSB-2 (GF)

SIEMENS

FG, ETU 555

HFG

Trip 250.0 A Plug 250.0 A Settings Phase GFPU (Ig) 250A (250A) GFD (tg) 0.2 (I^s T On)

110-CB-MSB-3 (GF)

SIEMENS

DG, ETU 555

HDG

Trip 100.0 A Plug 100.0 A Settings Phase GFPU (Ig) 100A (100A) GFD (tg) 0.2 (I^s T On)

110-CB-MSB-MAIN (GF)

SIEMENS

SHMD6, Sensitrip III

SHMD6

Trip 800.0 A Plug 800.0 A Settings Phase

70% GFPU 70 % (560A)

GFD (0.1-0.4 Sec.) 0.4 (I^s T On)

110-CB-MSB-1 (GF)

SIEMENS

SHMD6, Sensitrip III

SHMD6

Trip 800.0 A Plug 600.0 A Settings Phase

70% GFPU 70 % (420A)

GFD (0.1-0.4 Sec.) 0.2 (I^s T On)

110-CB-MSB-2 (GF)

SIEMENS

FG, ETU 555

HFG

Trip 250.0 A Plug 250.0 A Settings Phase GFPU (Ig) 250A (250A) GFD (tg) 0.2 (I^s T On)

110-CB-MSB-3 (GF)

SIEMENS

DG, ETU 555

HDG

Trip 100.0 A Plug 100.0 A Settings Phase GFPU (Ig) 100A (100A) GFD (tg) 0.2 (I^s T On)

S

P

110-XF-BLDG 110

110-BUS-XF BLDG 110-PRI

110-CBL-MSB

110-BUS-XF BLDG 110-SEC

110-CB-MSB-MAIN

110-CB-MSB-MAIN (GF)

110-BUS-MSB

110-CB-MSB-1

110-CB-MSB-1 (GF)

110-CB-MSB-2

110-CB-MSB-2 (GF)

110-CB-MSB-3

110-CB-MSB-3 (GF)

TCC Comments: No adjustments required.

TCC: 110_MSB (1)-GF Current Scale x 1 Reference Voltage: 480

0.5

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

110-CB-MSB-MAIN

SIEMENS

SHMD6, Sensitrip III

SHMD6

Trip 800.0 A Plug 800.0 A Settings Phase LTPU (20-100% x P) 90 % (720A) LTD (2.2-27 Sec.) 27 STPU (1.5-10 x LTPU) 7 (5040A) STD (0.05-0.5 Sec.) 0.3 Sec. (I^s T Off) INST (2-40 x LTPU) 10 (7200A) INST Override (Max) Max (10000A)

110-CB-MSB-4

SIEMENS

DG, ETU 555 GF Mod

HDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 8 (800A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 11 (1100A)

110-CB-MSB-5

SIEMENS

DG, ETU 555 GF Mod

NDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 1.5 (150A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 5 (500A)

110-CB-MSB-6

SIEMENS

DG, ETU 555 Non-GF Mod

HDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 40A (40A) LTD (tr) 4 STPU (Isd) 1.5 (60A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 125A (125A)

110-FS-XF BLDG 110 (1)

ABB

DO-III Dual Element

DO-III

Trip 50.0 A Settings Phase

50.0 Amps

110-FS-XF BLDG 110 (2)

COOPER

ELSP, 15.5kV, (2/03)

ELSP

Trip 100.0 A Settings Phase

100.0 Amps

110-XF-BLDG 110

Pri: 11500 V Sec: 480 V

500.0 kVA

110-CBL-MSB

110-CB-MSB-MAIN

SIEMENS

SHMD6, Sensitrip III

SHMD6

Trip 800.0 A Plug 800.0 A Settings Phase LTPU (20-100% x P) 90 % (720A) LTD (2.2-27 Sec.) 27 STPU (1.5-10 x LTPU) 7 (5040A) STD (0.05-0.5 Sec.) 0.3 Sec. (I^s T Off) INST (2-40 x LTPU) 10 (7200A) INST Override (Max) Max (10000A)

110-CB-MSB-4

SIEMENS

DG, ETU 555 GF Mod

HDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 8 (800A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 11 (1100A)

110-CB-MSB-5

SIEMENS

DG, ETU 555 GF Mod

NDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 1.5 (150A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 5 (500A)

110-CB-MSB-6

SIEMENS

DG, ETU 555 Non-GF Mod

HDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 40A (40A) LTD (tr) 4 STPU (Isd) 1.5 (60A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 125A (125A)

110-FS-XF BLDG 110 (1)

ABB

DO-III Dual Element

DO-III

Trip 50.0 A Settings Phase

50.0 Amps

110-FS-XF BLDG 110 (2)

COOPER

ELSP, 15.5kV, (2/03)

ELSP

Trip 100.0 A Settings Phase

100.0 Amps

110-XF-BLDG 110

Pri: 11500 V Sec: 480 V

500.0 kVA

110-CBL-MSB

S

P

110-XF-BLDG 110

110-BUS-XF BLDG 110-PRI

110-CBL-MSB

110-BUS-XF BLDG 110-SEC

110-CB-MSB-MAIN

110-CB-MSB-MAIN (GF)

110-BUS-MSB

110-CB-MSB-4

110-CB-MSB-4 (GF)

110-CB-MSB-5

110-CB-MSB-5 (GF)

110-CB-MSB-6

110-FS-XF BLDG 110 (2)

110-FS-XF BLDG 110 (1)

TCC Comments: Adjustment to 110-CB-MSB-MAIN, 110-CB-MSB-4, 110-CB-MSB-5, and 110-CB-MSB-6 trip settings suggested for improved coordination.

TCC: 110_MSB (2) Current Scale x 1 Reference Voltage: 480

0.5

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

110-CB-MSB-MAIN

SIEMENS

SHMD6, Sensitrip III

SHMD6

Trip 800.0 A Plug 800.0 A Settings Phase LTPU (20-100% x P) 100 % (800A) LTD (2.2-27 Sec.) 7 STPU (1.5-10 x LTPU) 6 (4800A) STD (0.05-0.5 Sec.) 0.3 Sec. (I^s T Off) INST (2-40 x LTPU) 15 (12000A) INST Override (Max) Max (10000A)

110-CB-MSB-4

SIEMENS

DG, ETU 555 GF Mod

HDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 14 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 11 (1100A)

110-CB-MSB-5

SIEMENS

DG, ETU 555 GF Mod

HDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 11 (1100A)

110-CB-MSB-6

SIEMENS

DG, ETU 555 Non-GF Mod

HDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 1000A (1000A)

110-FS-XF BLDG 110 (1)

ABB

DO-III Dual Element

DO-III

Trip 50.0 A Settings Phase

50.0 Amps

110-FS-XF BLDG 110 (2)

COOPER

ELSP, 15.5kV, (2/03)

ELSP

Trip 100.0 A Settings Phase

100.0 Amps

110-XF-BLDG 110

Pri: 11500 V Sec: 480 V

500.0 kVA

110-CBL-MSB

110-CB-MSB-MAIN

SIEMENS

SHMD6, Sensitrip III

SHMD6

Trip 800.0 A Plug 800.0 A Settings Phase LTPU (20-100% x P) 100 % (800A) LTD (2.2-27 Sec.) 7 STPU (1.5-10 x LTPU) 6 (4800A) STD (0.05-0.5 Sec.) 0.3 Sec. (I^s T Off) INST (2-40 x LTPU) 15 (12000A) INST Override (Max) Max (10000A)

110-CB-MSB-4

SIEMENS

DG, ETU 555 GF Mod

HDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 14 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 11 (1100A)

110-CB-MSB-5

SIEMENS

DG, ETU 555 GF Mod

HDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 11 (1100A)

110-CB-MSB-6

SIEMENS

DG, ETU 555 Non-GF Mod

HDG

Trip 100.0 A Plug 100.0 A Settings Phase LTPU (Ir) 100A (100A) LTD (tr) 4 STPU (Isd) 10 (1000A) STD (tsd) I2T-OFF 0.0 (I^s T Off) INST (Ii) 1000A (1000A)

110-FS-XF BLDG 110 (1)

ABB

DO-III Dual Element

DO-III

Trip 50.0 A Settings Phase

50.0 Amps

110-FS-XF BLDG 110 (2)

COOPER

ELSP, 15.5kV, (2/03)

ELSP

Trip 100.0 A Settings Phase

100.0 Amps

110-XF-BLDG 110

Pri: 11500 V Sec: 480 V

500.0 kVA

110-CBL-MSB

S

P

110-XF-BLDG 110

110-BUS-XF BLDG 110-PRI

110-CBL-MSB

110-BUS-XF BLDG 110-SEC

110-CB-MSB-MAIN

110-CB-MSB-MAIN (GF)

110-BUS-MSB

110-CB-MSB-4

110-CB-MSB-4 (GF)

110-CB-MSB-5

110-CB-MSB-5 (GF)

110-CB-MSB-6

110-FS-XF BLDG 110 (2)

110-FS-XF BLDG 110 (1)

TCC Comments: 110-CB-MSB-MAIN adjustments include LTPU from 90% to 100%, LTD from 27 to 7, STPU from 7 to 6, and INST from 10 to 15.

110-CB-MSB-4 adjustments include LTD from 4 to 14 and STPU from 8 to 10.

110-CB-MSB-5 adjustments include STPU from 1.5 to 10 and INST from 5 to 11.

110-CB-MSB-6 adjustments include LTPU from 40A to 100A, STPU from 1.5 to 10, and INST from 125A to 1000A.

TCC: 110_MSB (2) Current Scale x 1 Reference Voltage: 480

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

110-CB-MSB-MAIN (GF)

SIEMENS

SHMD6, Sensitrip III

SHMD6

Trip 800.0 A Plug 800.0 A Settings Phase

70% GFPU 70 % (560A)

GFD (0.1-0.4 Sec.) 0.4 (I^s T On)

110-CB-MSB-4 (GF)

SIEMENS

DG, ETU 555

HDG

Trip 100.0 A Plug 100.0 A Settings Phase GFPU (Ig) 100A (100A) GFD (tg) 0.2 (I^s T On)

110-CB-MSB-5 (GF)

SIEMENS

DG, ETU 555

NDG

Trip 100.0 A Plug 100.0 A Settings Phase GFPU (Ig) 80A (80A) GFD (tg) 0.07 (I^s T On)

110-CB-MSB-MAIN (GF)

SIEMENS

SHMD6, Sensitrip III

SHMD6

Trip 800.0 A Plug 800.0 A Settings Phase

70% GFPU 70 % (560A)

GFD (0.1-0.4 Sec.) 0.4 (I^s T On)

110-CB-MSB-4 (GF)

SIEMENS

DG, ETU 555

HDG

Trip 100.0 A Plug 100.0 A Settings Phase GFPU (Ig) 100A (100A) GFD (tg) 0.2 (I^s T On)

110-CB-MSB-5 (GF)

SIEMENS

DG, ETU 555

NDG

Trip 100.0 A Plug 100.0 A Settings Phase GFPU (Ig) 80A (80A) GFD (tg) 0.07 (I^s T On)

S

P

110-XF-BLDG 110

110-BUS-XF BLDG 110-PRI

110-CBL-MSB

110-BUS-XF BLDG 110-SEC

110-CB-MSB-MAIN

110-CB-MSB-MAIN (GF)

110-BUS-MSB

110-CB-MSB-4

110-CB-MSB-4 (GF)

110-CB-MSB-5

110-CB-MSB-5 (GF)

110-CB-MSB-6

TCC Comments: No adjustments required.

TCC: 110_MSB (2)-GF Current Scale x 1 Reference Voltage: 480

30-CBL-A2EH1-1

30-XF-TA2-230-CBL-A2EL1

0.5

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

30-CB-A2EH1-MAIN

SQUARE D

KA

KA

Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve

INST HI (1750A)

30-CB-A2EH1-1

SQUARE D

ED

ED

Trip 50.0 A Plug 50.0 A Settings Phase Fixed

30-CB-A2EL1-MAIN

SQUARE D

QO-VH, 3-Pole

QO-VH

Trip 100.0 A Plug 100.0 A Settings Phase Fixed (730-8)

30-CBL-A2EH1-1

30-XF-TA2-2

Pri: 480 V Sec: 208 V

30.0 kVA

30-CBL-A2EL1

30-CB-A2EH1-MAIN

SQUARE D

KA

KA

Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve

INST HI (1750A)

30-CB-A2EH1-1

SQUARE D

ED

ED

Trip 50.0 A Plug 50.0 A Settings Phase Fixed

30-CB-A2EL1-MAIN

SQUARE D

QO-VH, 3-Pole

QO-VH

Trip 100.0 A Plug 100.0 A Settings Phase Fixed (730-8)

30-CBL-A2EH1-1

30-XF-TA2-2

Pri: 480 V Sec: 208 V

30.0 kVA

30-CBL-A2EL1

30-CB-A2EH1-MAIN

30-BUS-A2EH1

30-CB-A2EH1-1

30-CBL-A2EH1-1

S

P

30-XF-TA2-2

30-BUS-XF TA2-2-PRI

30-CBL-A2EL1

30-BUS-XF TA2-2-SEC

30-BUS-A2EL1

30-CB-A2EL1-MAIN

TCC Comments: Adjustment to 30-CB-A2EH1-MAIN trip settings suggested for improved coordination.

TCC: 30_E - A RISER - A2EH1 - A2EL1 Current Scale x 1 Reference Voltage: 480

30-CBL-A2EH1-1

30-XF-TA2-230-CBL-A2EL1

0.5

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

30-CB-A2EH1-MAIN

SQUARE D

KA

KA

Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve

INST 3 (1191.75A)

30-CB-A2EH1-1

SQUARE D

ED

ED

Trip 50.0 A Plug 50.0 A Settings Phase Fixed

30-CB-A2EL1-MAIN

SQUARE D

QO-VH, 3-Pole

QO-VH

Trip 100.0 A Plug 100.0 A Settings Phase Fixed (730-8)

30-CBL-A2EH1-1

30-XF-TA2-2

Pri: 480 V Sec: 208 V

30.0 kVA

30-CBL-A2EL1

30-CB-A2EH1-MAIN

SQUARE D

KA

KA

Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve

INST 3 (1191.75A)

30-CB-A2EH1-1

SQUARE D

ED

ED

Trip 50.0 A Plug 50.0 A Settings Phase Fixed

30-CB-A2EL1-MAIN

SQUARE D

QO-VH, 3-Pole

QO-VH

Trip 100.0 A Plug 100.0 A Settings Phase Fixed (730-8)

30-CBL-A2EH1-1

30-XF-TA2-2

Pri: 480 V Sec: 208 V

30.0 kVA

30-CBL-A2EL1

30-CB-A2EH1-MAIN

30-BUS-A2EH1

30-CB-A2EH1-1

30-CBL-A2EH1-1

S

P

30-XF-TA2-2

30-BUS-XF TA2-2-PRI

30-CBL-A2EL1

30-BUS-XF TA2-2-SEC

30-BUS-A2EL1

30-CB-A2EL1-MAIN

TCC Comments: 30-CB-A2EH1-MAIN adjustments include INST from HI to 3.

TCC: 30_E - A RISER - A2EH1 - A2EL1 Current Scale x 1 Reference Voltage: 480

30-CBL-A2EH1-2

30-XF-TA2EL230-CBL-A2EL2

0.5

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

30-CB-A2EH1-MAIN

SQUARE D

KA

KA

Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve

INST HI (1750A)

30-CB-A2EH1-2

SQUARE D

EG

EG

Trip 70.0 A Plug 70.0 A Settings Phase Fixed

30-CB-A2EL2-MAIN

SQUARE D

QB

QB

Trip 150.0 A Plug 150.0 A Settings Phase Fixed

30-CBL-A2EH1-2

30-XF-TA2EL2

Pri: 480 V Sec: 208 V

45.0 kVA

30-CBL-A2EL2

30-CB-A2EH1-MAIN

SQUARE D

KA

KA

Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve

INST HI (1750A)

30-CB-A2EH1-2

SQUARE D

EG

EG

Trip 70.0 A Plug 70.0 A Settings Phase Fixed

30-CB-A2EL2-MAIN

SQUARE D

QB

QB

Trip 150.0 A Plug 150.0 A Settings Phase Fixed

30-CBL-A2EH1-2

30-XF-TA2EL2

Pri: 480 V Sec: 208 V

45.0 kVA

30-CBL-A2EL2

30-CB-A2EH1-MAIN

30-BUS-A2EH1

30-CB-A2EH1-2

30-CBL-A2EH1-2

S

P

30-XF-TA2EL2

30-BUS-XF TA2EL2-PRI

30-CBL-A2EL2

30-BUS-XF TA2EL2-SEC

30-BUS-A2EL2

30-CB-A2EL2-MAIN

TCC Comments: Adjustment to 30-CB-A2EH1-MAIN trip settings suggested for improved coordination.

TCC: 30_E - A RISER - A2EH1 - A2EL2 Current Scale x 1 Reference Voltage: 480

30-CBL-A2EH1-2

30-XF-TA2EL230-CBL-A2EL2

0.5

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

30-CB-A2EH1-MAIN

SQUARE D

KA

KA

Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve

INST 3 (1191.75A)

30-CB-A2EH1-2

SQUARE D

EG

EG

Trip 70.0 A Plug 70.0 A Settings Phase Fixed

30-CB-A2EL2-MAIN

SQUARE D

QB

QB

Trip 150.0 A Plug 150.0 A Settings Phase Fixed

30-CBL-A2EH1-2

30-XF-TA2EL2

Pri: 480 V Sec: 208 V

45.0 kVA

30-CBL-A2EL2

30-CB-A2EH1-MAIN

SQUARE D

KA

KA

Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve

INST 3 (1191.75A)

30-CB-A2EH1-2

SQUARE D

EG

EG

Trip 70.0 A Plug 70.0 A Settings Phase Fixed

30-CB-A2EL2-MAIN

SQUARE D

QB

QB

Trip 150.0 A Plug 150.0 A Settings Phase Fixed

30-CBL-A2EH1-2

30-XF-TA2EL2

Pri: 480 V Sec: 208 V

45.0 kVA

30-CBL-A2EL2

30-CB-A2EH1-MAIN

30-BUS-A2EH1

30-CB-A2EH1-2

30-CBL-A2EH1-2

S

P

30-XF-TA2EL2

30-BUS-XF TA2EL2-PRI

30-CBL-A2EL2

30-BUS-XF TA2EL2-SEC

30-BUS-A2EL2

30-CB-A2EL2-MAIN

TCC Comments: 30-CB-A2EH1-MAIN adjustments include INST from HI to 3.

TCC: 30_E - A RISER - A2EH1 - A2EL2 Current Scale x 1 Reference Voltage: 480

30-CBL-A3EH1-1

30-XF-TA3-230-CBL-A3EL1

0.5

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

30-CB-A3EH1-MAIN

SQUARE D

KA

KA

Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve

INST HI (1750A)

30-CB-A3EH1-1

SQUARE D

ED

ED

Trip 50.0 A Plug 50.0 A Settings Phase Fixed

30-CB-A3EL1-MAIN

SQUARE D

QO-VH, 3-Pole

QO-VH

Trip 100.0 A Plug 100.0 A Settings Phase Fixed (730-8)

30-CBL-A3EH1-1

30-XF-TA3-2

Pri: 480 V Sec: 208 V

30.0 kVA

30-CBL-A3EL1

30-CB-A3EH1-MAIN

SQUARE D

KA

KA

Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve

INST HI (1750A)

30-CB-A3EH1-1

SQUARE D

ED

ED

Trip 50.0 A Plug 50.0 A Settings Phase Fixed

30-CB-A3EL1-MAIN

SQUARE D

QO-VH, 3-Pole

QO-VH

Trip 100.0 A Plug 100.0 A Settings Phase Fixed (730-8)

30-CBL-A3EH1-1

30-XF-TA3-2

Pri: 480 V Sec: 208 V

30.0 kVA

30-CBL-A3EL1

30-CB-A3EH1-MAIN

30-BUS-A3EH1

30-CB-A3EH1-1

30-CBL-A3EH1-1

S

P

30-XF-TA3-2

30-BUS-XF TA3-2-PRI

30-CBL-A3EL1

30-BUS-XF TA3-2-SEC

30-BUS-A3EL1

30-CB-A3EL1-MAIN

TCC Comments: Adjustment to 30-CB-A3EH1-MAIN trip settings suggested for improved coordination.

TCC: 30_E - A RISER - A3EH1 - A3EL1 Current Scale x 1 Reference Voltage: 480

30-CBL-A3EH1-1

30-XF-TA3-230-CBL-A3EL1

0.5

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

30-CB-A3EH1-MAIN

SQUARE D

KA

KA

Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve

INST 3 (1191.75A)

30-CB-A3EH1-1

SQUARE D

ED

ED

Trip 50.0 A Plug 50.0 A Settings Phase Fixed

30-CB-A3EL1-MAIN

SQUARE D

QO-VH, 3-Pole

QO-VH

Trip 100.0 A Plug 100.0 A Settings Phase Fixed (730-8)

30-CBL-A3EH1-1

30-XF-TA3-2

Pri: 480 V Sec: 208 V

30.0 kVA

30-CBL-A3EL1

30-CB-A3EH1-MAIN

SQUARE D

KA

KA

Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve

INST 3 (1191.75A)

30-CB-A3EH1-1

SQUARE D

ED

ED

Trip 50.0 A Plug 50.0 A Settings Phase Fixed

30-CB-A3EL1-MAIN

SQUARE D

QO-VH, 3-Pole

QO-VH

Trip 100.0 A Plug 100.0 A Settings Phase Fixed (730-8)

30-CBL-A3EH1-1

30-XF-TA3-2

Pri: 480 V Sec: 208 V

30.0 kVA

30-CBL-A3EL1

30-CB-A3EH1-MAIN

30-BUS-A3EH1

30-CB-A3EH1-1

30-CBL-A3EH1-1

S

P

30-XF-TA3-2

30-BUS-XF TA3-2-PRI

30-CBL-A3EL1

30-BUS-XF TA3-2-SEC

30-BUS-A3EL1

30-CB-A3EL1-MAIN

TCC Comments: 30-CB-A3EH1-MAIN adjustments include INST from HI to 3.

TCC: 30_E - A RISER - A3EH1 - A3EL1 Current Scale x 1 Reference Voltage: 480

30-CBL-A3EH1-2

30-XF-TA3EL230-CBL-A3EL2

0.5

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

30-CB-A3EH1-MAIN

SQUARE D

KA

KA

Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve

INST HI (1750A)

30-CB-A3EH1-2

SQUARE D

ED

ED

Trip 70.0 A Plug 70.0 A Settings Phase Fixed

30-CB-A3EL2-MAIN

SQUARE D

QB

QB

Trip 150.0 A Plug 150.0 A Settings Phase Fixed

30-CBL-A3EH1-2

30-XF-TA3EL2

Pri: 480 V Sec: 208 V

45.0 kVA

30-CBL-A3EL2

30-CB-A3EH1-MAIN

SQUARE D

KA

KA

Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve

INST HI (1750A)

30-CB-A3EH1-2

SQUARE D

ED

ED

Trip 70.0 A Plug 70.0 A Settings Phase Fixed

30-CB-A3EL2-MAIN

SQUARE D

QB

QB

Trip 150.0 A Plug 150.0 A Settings Phase Fixed

30-CBL-A3EH1-2

30-XF-TA3EL2

Pri: 480 V Sec: 208 V

45.0 kVA

30-CBL-A3EL2

30-CB-A3EH1-MAIN

30-BUS-A3EH1

30-CB-A3EH1-2

30-CBL-A3EH1-2

S

P

30-XF-TA3EL2

30-BUS-XF TA3EL2-PRI

30-CBL-A3EL2

30-BUS-XF TA3EL2-SEC

30-BUS-A3EL2

30-CB-A3EL2-MAIN

TCC Comments: Adjustment to 30-CB-A3EH1-MAIN trip settings suggested for improved coordination.

TCC: 30_E - A RISER - A3EH1 - A3EL2 Current Scale x 1 Reference Voltage: 480

30-CBL-A3EH1-2

30-XF-TA3EL230-CBL-A3EL2

0.5

0.5

1K 1K

K

K

0K

0K

1M 0.01

0.10

CURRENT IN AMPERES

CURRENT IN AMPERES

TI

ME

I

N

SE

CO

ND

S

30-CB-A3EH1-MAIN

SQUARE D

KA

KA

Trip 175.0 A Plug 175.0 A Settings Phase Thermal Curve

INST 3 (1191.75A)

30-CB-A3EH1-…