07 60 00 - Flashing and Sheet Metal.pdf

PDF 19 KB Posted

Attached to
Z2FB--NRM 640-24-116 | Repair Aquatic Center, Palo Alto Bldg 530
Solicitation number
36C26124R0053
Issued by

About this file

This document appears to be a technical specification for flashing and sheet metal work for the Aquatic Therapy Center and Therapy Center project at the Department of Veterans Affairs facility in Palo Alto, California.

The specification covers requirements for materials, fabrication, and installation of various sheet metal components including flashings, edge strips, and expansion/contraction joints. It references related work in other specification sections such as roofing, glazing, and plumbing. Key requirements include the use of stainless steel, pre-tinning of mating surfaces, and specific jointing and fastener details. The specification cites industry standards from organizations like SMACNA and NAAMM for sheet metal fabrication and finishes.

View the file

Other files

File Type Posted
36C26124R0053 0004.pdf PDF
07 54 23 - Thermoplastic Polyolefin Roofing TPO.pdf PDF
RM 117 revised Photograph Library 28 Jun 2024.pdf PDF
Rev SOW 6.28.2024 Aquatic Center.pdf PDF
07 22 00 - Roof and Deck Insulation.pdf PDF
07 92 00 - Joint Sealants.pdf PDF
36C26124R0053 0003.pdf PDF
07 54 23 - Thermoplastic Polyolefin Roofing.pdf PDF
36C26124R0053 0002.pdf PDF
36C26124R0053 0001.pdf PDF
FINAL SOW B530 Rev 052224.pdf PDF
Exhibit 4 B530 Specifications Rev 052324_Part1.pdf PDF
DIVISION CONSTRUCTION COSTS- Repair Aquatic Center 640-24-116.docx DOCX document
Exhibit 5 B530 Drawings Rev 052324_Part2.pdf PDF
Wage Determination CA20240018 4.26.24.pdf PDF
Exhibit 5 B530 Drawings Rev 052324_Part1.pdf PDF
Evaluation Report.docx DOCX document
CONTRACTOR CERTIFICATION REGARDING SAFETY AND ENVIRONMENTAL.docx DOCX document
Key Personnel Attachment for Evaluation 02.docx DOCX document
36C26124R0053 Repair Aquatic Center.pdf PDF
S02 - RFI Form.docx DOCX document
Photo Library.pdf PDF
Exhibit 4 B530 Specifications Rev 052324_Part3.pdf PDF
S02 - Past Performance Questionnaire.docx DOCX document
Exhibit 5 B530 Drawings Rev 052324_Part3.pdf PDF
ILSM - B530 Aquatic Center - 03.21.24.pdf PDF
Palo Alto Campus Map Site Visit.pdf PDF
Exhibit 4 B530 Specifications Rev 052324_Part2.pdf PDF
Exhibit 5 B530 Drawings Rev 052324_Part4.pdf PDF
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Aquatic Therapy Center and Therapy Center DVA Project Nos.

Building 530 640-370 / 640-CSI-100 VAPAHCS Palo Alto, CA

07 60 00 - 1

SECTION 07 60 00

FLASHING AND SHEET METAL

PART 1 - GENERAL

1.1 DESCRIPTION

A. This section specifies formed sheet metal work for.

1.2 RELATED WORK

A. Single ply base flashing system: Section 07 54 23, THERMOPLASTIC

POLYOLEFIN (TPO) ROOFING.

B. TPO coated sheet metal flashing: Section 07 54 23, THERMOPLASTIC

POLYOLEFIN (TPO) ROOFING.

C. Sealant compound and installation: Section 07 92 00, JOINT SEALANTS.

D. Sheet metal flashing integral with glazed aluminum curtain wall:

Section 08 44 13, GLAZED ALUMINUM CURTIN WALL.

E. Sheet metal flashing integral with fire rated glazed curtain wall:

Section 08 44 19, FIRE RATED GLAZED CURTIN WALL.

F. Color of factory coated metal and anodized aluminum: Section 09 06 00, SCHEDULE FOR FINISHES.

G. Integral flashing component of manufactured roof specialties and accessories or equipment: Section 07 71 00, ROOF SPECIALTIES and Division 22, PLUMBING.

H. Paint materials and application: Section 09 91 00, PAINTING.

I. Flashing of Roof Drains: Section 22 05 19, METERS AND GAGES FOR PLUMBING PIPING, Section 22 05 23, GENERAL-DUTY VALVES FOR PLUMBING PIPING, Section 22 11 00, FACILITY WATER DISTRIBUTION, Section 22 13 00, FACILITY SANITARY SEWERAGE, Section 22 14 00, FACILITY STORM DRAINAGE, and Section 23 11 23, FACILITY NATURAL-GAS PIPING.

1.3 SUBMITTALS

A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT

DATA, AND SAMPLES.

B. Shop Drawings:

1. Flashings

1.4 APPLICABLE PUBLICATIONS

A. The publications listed below for a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.

VAPAHCS Palo Alto, CA

07 60 00 - 2

B. ASTM International (ASTM):

A167-99(R 2004).........Stainless and Heat-Resisting Chromium-Nickel Steel Plate, Sheet, and Strip

B32-04..................Solder Metal

C. Sheet Metal and Air Conditioning Contractors National Association (SMACNA): Architectural Sheet Metal Manual (2003 Edition).

D. National Association of Architectural Metal Manufacturers (NAAMM):

AMP 500-505-88..........Metal Finishes Manual

E. Federal Specification (Fed. Spec):

A-A-1925A...............Shield, Expansion; (Nail Anchors)

F. International Building Code (IBC):

2007 Edition

PART 2 - PRODUCTS

2.1 MATERIALS

A. Solder: ASTM B32; flux type and alloy composition as required for use with metals to be soldered.

B. Stainless Steel: ASTM A167, Type 302B, dead soft temper.

C. Fasteners:

1. Use stainless steel for stainless steel.

2. Nails:

a. Minimum diameter for stainless steel nails: 2 mm (0.095 inch) and annular threaded.

b. Length to provide not less than 22 mm (7/8 inch) penetration into anchorage.

3. Rivets: Not less than 3 mm (1/8 inch) diameter.

4. Expansion Shields: Fed Spec A-A-1925A.

D. Sealant: As specified in Section 07 92 00, JOINT SEALANTS for exterior locations.

2.2 SHEET METAL THICKNESS

A. Except as otherwise shown or specified use thickness or weight of sheet metal as follows:

B. Concealed Locations (Built into Construction):

1. Stainless steel: 0.25 mm (0.010 inch) thick.

C. Exposed Locations:

1. Stainless steel: 0.4 mm (0.015 inch).

VAPAHCS Palo Alto, CA

07 60 00 - 3

2.3 FABRICATION, GENERAL

A. Jointing:

1. In general stainless steel joints, except expansion and contraction joints, shall be locked and soldered.

2. Joints shall conform to following requirements:

a. Flat-lock joints shall finish not less than 19 mm (3/4 inch) wide.

b. Lap joints subject to stress shall finish not less than 25 mm (one inch) wide and shall be soldered and riveted.

c. Unsoldered lap joints shall finish not less than 100 mm (4 inches) wide.

3. Flat and lap joints shall be made in direction of flow.

4. Soldering:

a. Pre tin both mating surfaces with solder for a width not less than 38 mm (1 1/2 inches) of stainless steel.

b. Wire brush to produce a bright surface before soldering lead coated copper.

c. Treat in accordance with metal producers recommendations other sheet metal required to be soldered.

d. Completely remove acid and flux after soldering is completed.

B. Expansion and Contraction Joints:

1. Fabricate in accordance with the Architectural Sheet Metal Manual recommendations for expansion and contraction of sheet metal work in continuous runs.

2. Space joints as shown or as specified.

3. Space expansion and contraction joints for stainless steel at intervals not exceeding 7200 mm (24 feet).

4. Fabricate slip-type or loose locked joints and fill with sealant unless otherwise specified.

5. Fabricate joint covers of same thickness material as sheet metal served.

C. Cleats:

1. Fabricate cleats to secure flashings and sheet metal work over 300 mm (12 inches) wide and where specified.

2. Provide cleats for maximum spacing of 300 mm (12 inch) centers unless specified otherwise.

3. Form cleats of same metal and weights or thickness as the sheet metal being installed unless specified otherwise.

4. Fabricate cleats from 50 mm (2 inch) wide strip. Form end with not less than 19 mm (3/4 inch) wide loose lock to item for anchorage.

Form other end of length to receive nails free of item to be anchored and end edge to be folded over and cover nail heads.

D. Edge Strips or Continuous Cleats:

1. Fabricate continuous edge strips where shown and specified to secure loose edges of the sheet metal work.

2. Except as otherwise specified, fabricate edge strips of minimum 0.6 mm (0.024 inch) thick stainless steel.

3. Use material compatible with sheet metal to be secured by the edge strip.

VAPAHCS Palo Alto, CA

07 60 00 - 4

4. Fabricate in 3000 mm (10 feet) maximum lengths with not less than 19 mm (3/4 inch) loose lock into metal secured by edge strip.

5. Fabricate Strips for fascia anchorage to extend below the supporting wood construction to form a drip and to allow the flashing to be hooked over the lower edge at least 19 mm (3/4-inch).

6. Fabricate anchor edge maximum width of 75 mm (3 inches) or of sufficient width to provide adequate bearing area to insure a rigid installation using 0.8 mm (0.031 inch) thick stainless.

E. Drips:

1. Form drips at lower edge of sheet metal counter-flashings (cap flashings), fascias, gravel stops, wall copings, by folding edge back 13 mm (1/2 inch) and bending out 45 degrees from vertical to carry water away from the wall.

2. Form drip to provide hook to engage cleat or edge strip for fastening for not less than 19 mm (3/4 inch) loose lock where shown.

F. Edges:

1. Edges of flashings concealed in masonry joints opposite drain side shall be turned up 6 mm (1/4 inch) to form dam, unless otherwise specified or shown otherwise.

2. Finish exposed edges of flashing with a 6 mm (1/4 inch) hem formed by folding edge of flashing back on itself when not hooked to edge strip or cleat. Use 6 mm (1/4 inch) minimum penetration beyond wall face with drip for through-wall flashing exposed edge.

3. All metal roof edges shall meet requirements of IBC 2003.

2.4 FINISH

A. Use same finish on adjacent metal or components and exposed metal surfaces unless specified or shown otherwise.

B. In accordance with NAAMM Metal Finishes Manual, unless otherwise specified.

C. Finish exposed metal surfaces as follows, unless specified otherwise:

1. Stainless Steel: Finish No. 2B or 2D.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Install flashing and sheet metal items as shown in Sheet Metal and Air Conditioning Contractors National Association, Inc., publication, ARCHITECTURAL SHEET METAL MANUAL, except as otherwise shown or specified.

B. Apply Sealant as specified in Section 07 92 00, JOINT SEALANTS.

C. Apply sheet metal and other flashing material to surfaces which are smooth, sound, clean, dry and free from defects that might affect the application.

VAPAHCS Palo Alto, CA

07 60 00 - 5

D. Remove projections which would puncture the materials and fill holes and depressions with material compatible with the substrate. Cover holes or cracks in wood wider than 6 mm (1/4 inch) with sheet metal compatible with the roofing and flashing material used.

E. Coordinate with masonry work for the application of a skim coat of mortar to surfaces of unit masonry to receive flashing material before the application of flashing.

F. Apply a layer of 7 Kg (15 pound) saturated felt followed by a layer of rosin paper to wood surfaces to be covered with copper. Lap each ply 50 mm (2 inch) with the slope and nail with large headed copper nails.

G. Confine direct nailing of sheet metal to strips 300 mm (12 inch) or less wide. Nail flashing along one edge only. Space nail not over 100 mm (4 inches) on center unless specified otherwise.

H. Install bolts, rivets, and screws where indicated, specified, or required in accordance with the SMACNA Sheet Metal Manual. Space rivets at 75 mm (3 inch) on centers in two rows in a staggered position. Use neoprene washers under fastener heads when fastener head is exposed.

I. Coordinate with roofing work for the installation of metal base flashings and other metal items having roof flanges for anchorage and watertight installation.

J. Nail continuous cleats on 75 mm (3 inch) on centers in two rows in a staggered position.

K. Nail individual cleats with two nails and bend end tab over nail heads.

Lock other end of cleat into hemmed edge.

L. Install flashings in conjunction with other trades so that flashings are inserted in other materials and joined together to provide a water tight installation.

M. Where required to prevent galvanic action between dissimilar metal isolate the contact areas of dissimilar metal with sheet lead, waterproof building paper, or a coat of bituminous paint.

- - - E N D - - -