Pump Data Sheet-35.doc
DOC document 47 KB Posted
- Attached to
- J041--Chiller Maintenance Services
- Solicitation number
- 36C25622Q1302
About this file
This document contains a pump data sheet and information on a federal contract opportunity for chiller maintenance services. The pump data sheet provides test and specification data for two pumps used on a building project, including manufacturer, size, impeller size, design and actual performance data, and motor information.
The federal contract opportunity is a solicitation seeking a contractor to provide chiller maintenance services at the Southeast Louisiana Veteran Healthcare System, as specified in the attached performance work statement. Responses are due by August 8, 2022 at 1:00PM CST and the solicitation is fully set aside for service-disabled veteran owned small businesses. The requirement is classified under NAICS code 238220 for plumbing, heating, and air conditioning contractors and has a size standard of $16.5 million.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25622Q1302 0002.docx | DOCX document | |
| Amendment 0001 Q_A.pdf | ||
| Pump Data Sheet-32.doc | DOC document | |
| 36C25622Q1302 0001.docx | DOCX document | |
| Pump Data Sheet-34.doc | DOC document | |
| Pump Data Sheet-31.doc | DOC document | |
| Pump Data Sheet-33.doc | DOC document | |
| Site Visit.pdf | ||
| Cooling Tower Dimensions.pdf | ||
| WAGE DETERMINATION.pdf | ||
| 36C25622Q1302.pdf | ||
| 36C25622Q1302.docx | DOCX document |
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AABC
Precision Balance, Inc.
Telephone: 407-876-4112
Fax: 407-876-4338
Date:
10-15
Page: 35
Project: Building 7 CEP
PUMP DATA SHEET
| Pump No. |
| 07-2N2-HWP-1 |
| Pump No. |
| 07-2N2-HWP-2 |
| Manufacturer |
| B & G |
| Manufacturer |
| B & G |
| Size |
| 1510 |
| Size |
| 1510 |
| Impeller |
| 8.125 |
| Impeller |
| 8.125 |
| Service |
| Hot Water |
| Service |
| Hot Water |
| Test Data |
| GPM |
| FT. HD |
| BHP |
| Test Data |
| GPM |
| FT. HD. |
| BHP |
| Design |
| 200 |
| 60 |
| 4.2 |
| Design |
| 200 |
| 60 |
| 4.2 |
| Actual |
| 200 |
| 60.06 |
| 4.97 |
| Actual |
| 205 |
| 59.59 |
| 4.95 |
| Discharge |
| 70.8 |
| Discharge |
| 70.7 |
| Suction |
| 44.8 |
| Suction |
| 46.1 |
| ΔP X 2.31=Ft. HD |
| 26 X 2.31 = 60.06 |
| ΔP X 2.31=Ft. HD |
| 29.0 X 2.31 = 66.99 |
| Block Off |
| ------ |
| Block Off |
| ------ |
| Discharge |
| 74.8 |
| Discharge |
| 75.1 |
| Suction |
| 45.9 |
| Suction |
| 46.1 |
| ΔP X 2.31= Ft. HD |
| 28.9 X 2.31 = 66.76 |
| ΔP X 2.31=Ft. HD |
| 29.0 X 2.31 = 66.99 |
| Motor Mfg. |
| Marathon |
| Motor Mfg. |
| Marathon |
| Frame |
| 213T |
| Frame |
| 213T |
| H.P. |
| 7.5 |
| H.P. |
| 7.5 |
| RPM |
| 1760 |
| RPM |
| 1760 |
| AMPS Design |
| 9.9 |
| Act: 6.6 / 6.6 / 6.5 |
| AMPS Design |
| 9.9 |
| Act: 6.5 / 6.5 / 6.6 |
| Volts Design |
| 480 |
| Act: 491 / 491 / 487 |
| Volts Design |
| 480 |
| Act: 486 / 490 / 490 |