Pump Data Sheet-35.doc

DOC document 47 KB Posted

Attached to
J041--Chiller Maintenance Services Federal contract opportunity
Solicitation number
36C25622Q1302
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16

About this file

This document contains a pump data sheet and information on a federal contract opportunity for chiller maintenance services. The pump data sheet provides test and specification data for two pumps used on a building project, including manufacturer, size, impeller size, design and actual performance data, and motor information.

The federal contract opportunity is a solicitation seeking a contractor to provide chiller maintenance services at the Southeast Louisiana Veteran Healthcare System, as specified in the attached performance work statement. Responses are due by August 8, 2022 at 1:00PM CST and the solicitation is fully set aside for service-disabled veteran owned small businesses. The requirement is classified under NAICS code 238220 for plumbing, heating, and air conditioning contractors and has a size standard of $16.5 million.

View the file

Other files for this federal contract opportunity

Other files attached to J041--Chiller Maintenance Services, newest first.
File Type Posted
Amendment 0001 Q_A.pdf PDF
36C25622Q1302 0002.docx DOCX document
Pump Data Sheet-33.doc DOC document
36C25622Q1302 0001.docx DOCX document
Pump Data Sheet-32.doc DOC document
Pump Data Sheet-31.doc DOC document
Cooling Tower Dimensions.pdf PDF
Pump Data Sheet-34.doc DOC document
Site Visit.pdf PDF
36C25622Q1302.pdf PDF
WAGE DETERMINATION.pdf PDF
36C25622Q1302.docx DOCX document
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AABC

Precision Balance, Inc.

Telephone: 407-876-4112

Fax: 407-876-4338

Date:

10-15

Page: 35

Project: Building 7 CEP

PUMP DATA SHEET

Pump No.
07-2N2-HWP-1
Pump No.
07-2N2-HWP-2
Manufacturer
B & G
Manufacturer
B & G
Size
1510
Size
1510
Impeller
8.125
Impeller
8.125
Service
Hot Water
Service
Hot Water
Test Data
GPM
FT. HD
BHP
Test Data
GPM
FT. HD.
BHP
Design
200
60
4.2
Design
200
60
4.2
Actual
200
60.06
4.97
Actual
205
59.59
4.95
Discharge
70.8
Discharge
70.7
Suction
44.8
Suction
46.1
ΔP X 2.31=Ft. HD
26 X 2.31 = 60.06
ΔP X 2.31=Ft. HD
29.0 X 2.31 = 66.99
Block Off
------
Block Off
------
Discharge
74.8
Discharge
75.1
Suction
45.9
Suction
46.1
ΔP X 2.31= Ft. HD
28.9 X 2.31 = 66.76
ΔP X 2.31=Ft. HD
29.0 X 2.31 = 66.99
Motor Mfg.
Marathon
Motor Mfg.
Marathon
Frame
213T
Frame
213T
H.P.
7.5
H.P.
7.5
RPM
1760
RPM
1760
AMPS Design
9.9
Act: 6.6 / 6.6 / 6.5
AMPS Design
9.9
Act: 6.5 / 6.5 / 6.6
Volts Design
480
Act: 491 / 491 / 487
Volts Design
480
Act: 486 / 490 / 490