Pump Data Sheet-34.doc

DOC document 47 KB Posted

Attached to
J041--Chiller Maintenance Services Federal contract opportunity
Solicitation number
36C25622Q1302
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16

About this file

This document contains a pump data sheet and related federal contract opportunity solicitation. The pump data sheet provides specifications for two condenser water pumps to be used in Building 7 of a project, including manufacturer, size, impeller size, service type, design and test flow rates, head pressures, horsepower requirements, and motor information.

The federal contract opportunity solicitation is seeking quotes for chiller maintenance services at the Southeast Louisiana Veteran Healthcare System, as defined in the attached performance work statement. Quotes are due no later than August 8, 2022 at 1:00PM Central Time and shall be submitted to Rachel Babin via email. This requirement is reserved as a 100% set-aside for service-disabled veteran-owned small businesses. The associated NAICS code is 238220 for plumbing, heating, and air conditioning contractors, with a size standard of $16.5 million.

View the file

Other files for this federal contract opportunity

Other files attached to J041--Chiller Maintenance Services, newest first.
File Type Posted
Amendment 0001 Q_A.pdf PDF
36C25622Q1302 0002.docx DOCX document
Pump Data Sheet-32.doc DOC document
Pump Data Sheet-31.doc DOC document
Pump Data Sheet-33.doc DOC document
36C25622Q1302 0001.docx DOCX document
Cooling Tower Dimensions.pdf PDF
Pump Data Sheet-35.doc DOC document
Site Visit.pdf PDF
36C25622Q1302.pdf PDF
WAGE DETERMINATION.pdf PDF
36C25622Q1302.docx DOCX document
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AABC

Precision Balance, Inc.

Telephone: 407-876-4112

Fax: 407-876-4338

Date:

10-15

Page: 33

Project: Building 7 CEP

PUMP DATA SHEET

Pump No.
07-3.5N2-CWP-3
Pump No.
07-3.5N2-CWP-4
Manufacturer
B & G
Manufacturer
B & G
Size
12 X 14 X 17.5B
Size
12 X 14 X 17.5B
Impeller
16.875
Impeller
16.875
Service
Condenser Water
Service
Condenser Water
Test Data
GPM
FT. HD
BHP
Test Data
GPM
FT. HD.
BHP
Design
4500
105
141.52
Design
4500
105
141.52
Actual
4409
105.86
124.62
Actual
4470
105.24
124.35
Discharge
56.35
Discharge
55.39
Suction
10.52
Suction
9.83
ΔP X 2.31=Ft. HD
45.83 x 2.31 = 105.86
ΔP X 2.31=Ft. HD
45.56 x 2.31 =105.24
Block Off
------
Block Off
------
Discharge
73.8
Discharge
74.1
Suction
15.5
Suction
15.2
ΔP X 2.31= Ft. HD
58.3 x 2.31 = 134.67
ΔP X 2.31=Ft. HD
58.9 x 2.31 = 136.06
Motor Mfg.
Marathon
Motor Mfg.
Marathon
Frame
447T
Frame
447T
H.P.
200
H.P.
200
RPM
1190
RPM
1190
AMPS Design
245
Act: 151 / 153 / 154
AMPS Design
245
Act: 152 / 153 / 152
Volts Design
480
Act: 492 / 493 / 493
Volts Design
480
Act: 492 / 493 / 492
@ 49 htz
@ 52 htz