Cooling Tower Dimensions.pdf
PDF 72 KB Posted
- Attached to
- J041--Chiller Maintenance Services Federal contract opportunity
- Solicitation number
- 36C25622Q1302
About this file
This document contains a submittal for cooling tower dimensions and specifications along with a related federal contract opportunity for chiller maintenance services. The cooling tower submittal provides technical details for a Marley NC8414CILN4 tower model including performance conditions, motor data, dimensions, weights, construction materials, and accessories. The federal contract opportunity is a Request for Quote issued by the Southeast Louisiana Veteran Healthcare System seeking a contractor to provide chiller maintenance services as specified in the attached Performance Work Statement. Responses are due by August 8, 2022 at 1:00PM CST. This requirement is set aside 100% for Service-Disabled Veteran-Owned Small Businesses with a NAICS code of 238220 for plumbing, heating, and air conditioning contractors and a size standard of $16.5 million.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25622Q1302 0002.docx | DOCX document | |
| Amendment 0001 Q_A.pdf | ||
| Pump Data Sheet-32.doc | DOC document | |
| Pump Data Sheet-31.doc | DOC document | |
| Pump Data Sheet-35.doc | DOC document | |
| Pump Data Sheet-34.doc | DOC document | |
| Site Visit.pdf | ||
| Pump Data Sheet-33.doc | DOC document | |
| 36C25622Q1302 0001.docx | DOCX document | |
| 36C25622Q1302.pdf | ||
| WAGE DETERMINATION.pdf | ||
| 36C25622Q1302.docx | DOCX document |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Commercial & Industrial Sales, 4931 Bloomfield Sire -
Jefferson, LA 7 (504)8184, email: ime@ci-sales.com
Submittal to: Project: Engineer:
MCC Group NOVA
BRFA Consulting Engineers
Opportunity / Quote No. (Ver): Mike Eshenour 111221_111826365 / Mike Eshenour 111221_112043121 (1) Rep Quote No.: 100659 March 29, 2012
Marley NC8414CILN4
TOWER MODEL PERFORMANCE
CONDITIONS
MOTOR DATA TOWER DIMENSIONS WEIGHTS
Quantity of (3) Marley NC Per 4-cell tower NEMA 20 HP 1 speed / Each cell: (without options) Per cell:
Class Diamond Series 4,500 gpm 1 wind Length 13'- 103/4" Shipping: 30,472 lb model Nc8414QLN 104.0 °F Hot Water 3 phase / 60 Hz / Width 22'- 5" Operating: 56,728 lb factory assembled 4-Cell 85.0 °F Cold Water 230/460v Height 22'- 7 1/4° crossflow cooling 82.0 °F Entering WB 1.15sf I TEFC
Per 4-cell tower tower(s)
1200 RPM Per 4-cell tower (with options) Shipping: 121,889 lb
Premium Efficiency Length 61' - 7 9/16" Operating: 226,913 lb
Inverter duty nameplated Width 22'- 5" Height 25'- 85/16" Heaviest Lift: 17,118 lb
Quantities shown below are per tower.
Base Tower Construction/Equipment:
Stainless Steel casing.
Stainless Steel struchire'.-;
Stainless Steel colle'64-onibasin.
Stainless Steel distribution basin All stainless steel is series 300.
Tower Structure Level?IS`16cted to meet customer specified design requirtrnnts fo.r.Onditip&-cifa3wIL11-'1 Anchorage design selected to meet cliStOmer:*ikified,ligtio,tequfrerrientiff6r wind load of 100 0 psf Quiet fan with alufr,itijiin blades.
Marley designed Geareducer® with 5:Year warranty.
15 mil PVC film fill with integral louvers and drift eliminators designed and manufactured by Marley.
Drift rate guaranteed to be no greater than .005% of the design flow rate.
HOG steel fan guard.
Collection Basin Connections and Accessories:
All flanges are to Class 125 ANSI 516.1 standard.
All threads are to American Standard Pipe Taper Thread.
(4) 12 in (305 mm) diameter depressed side sump outlet(s) with trash screen(s).
12 in (305 mm) diameter hole and bolt circle(s) for equalization, One per Cell 4 in (102 mm) diameter combination drain and overflow in each cell 4 in (102 mm) additional drain with plug in each cell
(4) 2 in (50.8 mm) water make-up float valve(s) Probe type electronic water level sensor with the following events: low-alarm, high-alarm Factory installed basin sweeper piping (requires 20 psi (138 kPa) inlet pressure).
For (1) 4ce11 tower only:
12 kW per cell 480/3 volt/phase electric immersion heater for freeze protection of the collection basin during cold weather system shutdown Includes heater elements, water temperature sensor probe and control box
Heater system circuit breaker
Distribution Basin Inlet and Accessories:
(1) self-balancing 12 in (305 mm) diameter PVC bottom inlet connection per cell.
All internal piping is PVC. External piping is PVC.
Maintenance & Maintenance Access Features:
Tower is designed in accordance with OSHA safety standards.
Efi. S 4' vhanolmeyerb1 Highlight