Pump Data Sheet-31.doc
DOC document 48 KB Posted
- Attached to
- J041--Chiller Maintenance Services Federal contract opportunity
- Solicitation number
- 36C25622Q1302
About this file
This document contains a federal contract opportunity solicitation for chiller maintenance services and a related pump data sheet. The solicitation seeks quotes for chiller maintenance services as specified in the attached performance work statement for the Southeast Louisiana Veteran Healthcare System. Quotes are due no later than August 8, 2022 at 1:00PM Central Time and should be emailed to Rachel Babin. This is a 100% set-aside for service-disabled veteran-owned small businesses. The NAICS code is 238220 for plumbing, heating, and air conditioning contractors and the size standard is $16.5 million. The pump data sheet provides test data for two pumps used in the chilled water system, including design specifications, actual test results, and motor information.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment 0001 Q_A.pdf | ||
| 36C25622Q1302 0002.docx | DOCX document | |
| Pump Data Sheet-32.doc | DOC document | |
| Pump Data Sheet-33.doc | DOC document | |
| 36C25622Q1302 0001.docx | DOCX document | |
| Cooling Tower Dimensions.pdf | ||
| Pump Data Sheet-35.doc | DOC document | |
| Pump Data Sheet-34.doc | DOC document | |
| Site Visit.pdf | ||
| 36C25622Q1302.pdf | ||
| WAGE DETERMINATION.pdf | ||
| 36C25622Q1302.docx | DOCX document |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BAABC
Precision Balance, Inc.
Telephone: 407-876-4112
Fax: 407-876-4338
Date: 10-15
Page: 31
Project: Building 7 CEP
PUMP DATA SHEET
| Pump No. |
| 07-3.5N2-CHP-1 |
| Pump No. |
| 07-3.5N2-CHP-2 |
| Manufacturer |
| B & G |
| Manufacturer |
| B & G |
| Size |
| 10 X 12 X 17.5B |
| Size |
| 10 X 12 X 17.5 |
| Impeller |
| 14.75 |
| Impeller |
| 14.75 |
| Service |
| Chilled Water |
| Service |
| Chilled Water |
| Test Data |
| GPM |
| FT. HD |
| BHP |
| Test Data |
| GPM |
| FT. HD. |
| BHP |
| Design |
| 4500 |
| 170 |
| 227 |
| Design |
| 4500 |
| 170 |
| 227 |
| Actual |
| 4611 |
| 124.95 |
| 260.33 |
| Actual |
| *4563 |
| 124.28 |
| 259.99 |
| Discharge |
| 91.24 |
| Discharge |
| 92.2 |
| Suction |
| 37.15 |
| Suction |
| 38.4 |
| ΔP X 2.31=Ft. HD |
| 54.09 x 2.31 = 124.95 |
| ΔP X 2.31=Ft. HD |
| 53.8 x 2.31 = 124.28 |
| Block Off |
| ------ |
| Block Off |
| ------ |
| Discharge |
| 140.2 |
| Discharge |
| 140.3 |
| Suction |
| 40.87 |
| Suction |
| 41.7 |
| ΔP X 2.31= Ft. HD |
| 99.33 x 2.31 = 229.45 |
| ΔP X 2.31=Ft. HD |
| 98.6 x 2.31 = 227.76 |
| Motor Mfg. |
| Marathon |
| Motor Mfg. |
| Marathon |
| Frame |
| 445T |
| Frame |
| 445T |
| H.P. |
| 300 |
| H.P. |
| 300 |
| RPM |
| 1780 |
| RPM |
| 1780 |
| AMPS Design |
| 300 |
| Act: 259/260/262 |
| AMPS Design |
| 300 |
| Act: 259/258/263 |
| Volts Design |
| 480 |
| Act: 495/499/502 |
| Volts Design |
| 480 |
| Act: 492/503/491 |
| @ 57 htz |
| @ 57 htz |
· GPM reading off of Trane’s computer screen confirmed with Trane’s onsite technician.