Pump Data Sheet-32.doc
DOC document 47 KB Posted
- Attached to
- J041--Chiller Maintenance Services Federal contract opportunity
- Solicitation number
- 36C25622Q1302
About this file
This document contains a pump data sheet and related federal contract opportunity solicitation. The pump data sheet provides test data for two pumps used in a chilled water system, including design and actual flow rates, head pressures, horsepower requirements, and motor specifications.
The federal contract opportunity solicitation is seeking quotes for chiller maintenance services at the Southeast Louisiana Veteran Healthcare System, as defined in the attached performance work statement. Quotes are due no later than August 8, 2022 at 1:00PM Central Time and must be submitted via email. This requirement is reserved as a 100% set-aside for service-disabled veteran-owned small businesses. The associated NAICS code is 238220 for plumbing, heating, and air conditioning contractors, with a size standard of $16.5 million.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25622Q1302 0002.docx | DOCX document | |
| Amendment 0001 Q_A.pdf | ||
| Pump Data Sheet-35.doc | DOC document | |
| Pump Data Sheet-34.doc | DOC document | |
| Site Visit.pdf | ||
| Pump Data Sheet-31.doc | DOC document | |
| Cooling Tower Dimensions.pdf | ||
| Pump Data Sheet-33.doc | DOC document | |
| 36C25622Q1302 0001.docx | DOCX document | |
| 36C25622Q1302.pdf | ||
| WAGE DETERMINATION.pdf | ||
| 36C25622Q1302.docx | DOCX document |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AABC
Precision Balance, Inc.
Telephone: 407-876-4112
Fax: 407-876-4338
Date: 10-15
Page: 32
Project: Building 7 CEP
PUMP DATA SHEET
| Pump No. |
| 07-3.5N2-CHP-3 |
| Pump No. |
| 07-3.5N2-CHP-4 |
| Manufacturer |
| B & G |
| Manufacturer |
| B & G |
| Size |
| 10 X 12 X 17.5B |
| Size |
| 10 X 12 X 17.5B |
| Impeller |
| 14.75 |
| Impeller |
| 14.75 |
| Service |
| Chilled Water |
| Service |
| Chilled Water |
| Test Data |
| GPM |
| FT. HD |
| BHP |
| Test Data |
| GPM |
| FT. HD. |
| BHP |
| Design |
| 4500 |
| 170 |
| 240 |
| Design |
| 4500 |
| 170 |
| 240 |
| Actual |
| *4519 |
| 128.27 |
| 235.45 |
| Actual |
| 4619 |
| 122.89 |
| 235.75 |
| Discharge |
| 94.04 |
| Discharge |
| 90.9 |
| Suction |
| 38.27 |
| Suction |
| 37.7 |
| ΔP X 2.31=Ft. HD |
| 55.81 x 2.31 = 128.92 |
| ΔP X 2.31=Ft. HD |
| 95.3 x 2.31 = 122.89 |
| Block Off |
| ------ |
| Block Off |
| ------ |
| Discharge |
| 135.7 |
| Discharge |
| 136.7 |
| Suction |
| 37.01 |
| Suction |
| 41.4 |
| ΔP X 2.31= Ft. HD |
| 98.69 x 2.31 = 227.97 |
| ΔP X 2.31=Ft. HD |
| 95.3 x 2.31 = 220.143 |
| Motor Mfg. |
| Marathon |
| Motor Mfg. |
| Marathon |
| Frame |
| 445T |
| Frame |
| 445T |
| H.P. |
| 300 |
| H.P. |
| 300 |
| RPM |
| 1780 |
| RPM |
| 1780 |
| AMPS Design |
| 330 |
| Act: 260/259/258 |
| AMPS Design |
| 330 |
| Act: 258/259/261 |
| Volts Design |
| 480 |
| Act: 476/477/482 |
| Volts Design |
| 480 |
| Act: 489/484/501 |
| @ 57 htz |
| @ 57 htz |
· GPM was read through the chiller.
File details come from the government source that posted it. Updated .