Pump Data Sheet-32.doc

DOC document 47 KB Posted

Attached to
J041--Chiller Maintenance Services Federal contract opportunity
Solicitation number
36C25622Q1302
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16

About this file

This document contains a pump data sheet and related federal contract opportunity solicitation. The pump data sheet provides test data for two pumps used in a chilled water system, including design and actual flow rates, head pressures, horsepower requirements, and motor specifications.

The federal contract opportunity solicitation is seeking quotes for chiller maintenance services at the Southeast Louisiana Veteran Healthcare System, as defined in the attached performance work statement. Quotes are due no later than August 8, 2022 at 1:00PM Central Time and must be submitted via email. This requirement is reserved as a 100% set-aside for service-disabled veteran-owned small businesses. The associated NAICS code is 238220 for plumbing, heating, and air conditioning contractors, with a size standard of $16.5 million.

View the file

Other files for this federal contract opportunity

Other files attached to J041--Chiller Maintenance Services, newest first.
File Type Posted
36C25622Q1302 0002.docx DOCX document
Amendment 0001 Q_A.pdf PDF
Pump Data Sheet-35.doc DOC document
Pump Data Sheet-34.doc DOC document
Site Visit.pdf PDF
Pump Data Sheet-31.doc DOC document
Cooling Tower Dimensions.pdf PDF
Pump Data Sheet-33.doc DOC document
36C25622Q1302 0001.docx DOCX document
36C25622Q1302.pdf PDF
WAGE DETERMINATION.pdf PDF
36C25622Q1302.docx DOCX document
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AABC

Precision Balance, Inc.

Telephone: 407-876-4112

Fax: 407-876-4338

Date: 10-15

Page: 32

Project: Building 7 CEP

PUMP DATA SHEET

Pump No.
07-3.5N2-CHP-3
Pump No.
07-3.5N2-CHP-4
Manufacturer
B & G
Manufacturer
B & G
Size
10 X 12 X 17.5B
Size
10 X 12 X 17.5B
Impeller
14.75
Impeller
14.75
Service
Chilled Water
Service
Chilled Water
Test Data
GPM
FT. HD
BHP
Test Data
GPM
FT. HD.
BHP
Design
4500
170
240
Design
4500
170
240
Actual
*4519
128.27
235.45
Actual
4619
122.89
235.75
Discharge
94.04
Discharge
90.9
Suction
38.27
Suction
37.7
ΔP X 2.31=Ft. HD
55.81 x 2.31 = 128.92
ΔP X 2.31=Ft. HD
95.3 x 2.31 = 122.89
Block Off
------
Block Off
------
Discharge
135.7
Discharge
136.7
Suction
37.01
Suction
41.4
ΔP X 2.31= Ft. HD
98.69 x 2.31 = 227.97
ΔP X 2.31=Ft. HD
95.3 x 2.31 = 220.143
Motor Mfg.
Marathon
Motor Mfg.
Marathon
Frame
445T
Frame
445T
H.P.
300
H.P.
300
RPM
1780
RPM
1780
AMPS Design
330
Act: 260/259/258
AMPS Design
330
Act: 258/259/261
Volts Design
480
Act: 476/477/482
Volts Design
480
Act: 489/484/501
@ 57 htz
@ 57 htz

· GPM was read through the chiller.