Pump Data Sheet-33.doc
DOC document 47 KB Posted
- Attached to
- J041--Chiller Maintenance Services
- Solicitation number
- 36C25622Q1302
About this file
This document contains a pump data sheet and related federal contract opportunity solicitation. The pump data sheet provides specifications for two pumps used in a condenser water system, including manufacturer, size, impeller size, service, test and design data, and motor details.
The federal contract opportunity solicitation is seeking a contractor to provide chiller maintenance services at the Southeast Louisiana Veteran Healthcare System in accordance with the included performance work statement. Responses are due no later than August 8, 2022. This solicitation is reserved exclusively for service-disabled veteran-owned small businesses. The associated North American Industry Classification code is 238220 for plumbing, heating, and air conditioning contractors, with a size standard of $16.5 million.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25622Q1302 0002.docx | DOCX document | |
| Amendment 0001 Q_A.pdf | ||
| Pump Data Sheet-32.doc | DOC document | |
| Pump Data Sheet-35.doc | DOC document | |
| 36C25622Q1302 0001.docx | DOCX document | |
| Pump Data Sheet-34.doc | DOC document | |
| Pump Data Sheet-31.doc | DOC document | |
| Site Visit.pdf | ||
| Cooling Tower Dimensions.pdf | ||
| WAGE DETERMINATION.pdf | ||
| 36C25622Q1302.pdf | ||
| 36C25622Q1302.docx | DOCX document |
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AABC
Precision Balance, Inc.
Telephone: 407-876-4112
Fax: 407-876-4338
Date: 10-15
Page: 34
Project: Building 7 CEP
PUMP DATA SHEET
| Pump No. |
| 07-3.5N2-CWP-1 |
| Pump No. |
| 07-3.5N2-CWP-2 |
| Manufacturer |
| B & G |
| Manufacturer |
| B & G |
| Size |
| 12 X 14 X 17.5B |
| Size |
| 12 X 14 X 17.5B |
| Impeller |
| 16.875 |
| Impeller |
| 16.875 |
| Service |
| Condenser Water |
| Service |
| Condenser Water |
| Test Data |
| GPM |
| FT. HD |
| BHP |
| Test Data |
| GPM |
| FT. HD. |
| BHP |
| Design |
| 4500 |
| 105 |
| 141.52 |
| Design |
| 4500 |
| 105 |
| 141.52 |
| Actual |
| 4481 |
| 105.82 |
| 127.6 |
| Actual |
| 4519 |
| 104.59 |
| 121.90 |
| Discharge |
| 56.84 |
| Discharge |
| 55.85 |
| Suction |
| 11.03 |
| Suction |
| 10.51 |
| ΔP X 2.31=Ft. HD |
| 45.81 X 2.31 = 105.82 |
| ΔP X 2.31=Ft. HD |
| 45.28 X 2.31 =104.59 |
| Block Off |
| ------ |
| Block Off |
| ------ |
| Discharge |
| 78.90 |
| Discharge |
| 76.81 |
| Suction |
| 14.87 |
| Suction |
| 14.0 |
| ΔP X 2.31= Ft. HD |
| 64.03 X 2.31 = 147.90 |
| ΔP X 2.31=Ft. HD |
| 62.81 X 2.31 = 145.09 |
| Motor Mfg. |
| Marathon |
| Motor Mfg. |
| Marathon |
| Frame |
| 447T |
| Frame |
| 447T |
| H.P. |
| 200 |
| H.P. |
| 200 |
| RPM |
| 1190 |
| RPM |
| 1190 |
| AMPS Design |
| 245 |
| Act: 156 / 156 /157 |
| AMPS Design |
| 245 |
| Act: 145 / 149 / 150 |
| Volts Design |
| 480 |
| Act: 409 / 409 / 410 |
| Volts Design |
| 480 |
| Act: 415 / 415 / 416 |
@ 49 htz @ 50 htz
File details come from the government source that posted it. Updated .