Pump Data Sheet-33.doc

DOC document 47 KB Posted

Attached to
J041--Chiller Maintenance Services Federal contract opportunity
Solicitation number
36C25622Q1302
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16

About this file

This document contains a pump data sheet and related federal contract opportunity solicitation. The pump data sheet provides specifications for two pumps used in a condenser water system, including manufacturer, size, impeller size, service, test and design data, and motor details.

The federal contract opportunity solicitation is seeking a contractor to provide chiller maintenance services at the Southeast Louisiana Veteran Healthcare System in accordance with the included performance work statement. Responses are due no later than August 8, 2022. This solicitation is reserved exclusively for service-disabled veteran-owned small businesses. The associated North American Industry Classification code is 238220 for plumbing, heating, and air conditioning contractors, with a size standard of $16.5 million.

View the file

Other files for this federal contract opportunity

Other files attached to J041--Chiller Maintenance Services, newest first.
File Type Posted
Amendment 0001 Q_A.pdf PDF
36C25622Q1302 0002.docx DOCX document
36C25622Q1302 0001.docx DOCX document
Pump Data Sheet-32.doc DOC document
Pump Data Sheet-31.doc DOC document
Cooling Tower Dimensions.pdf PDF
Pump Data Sheet-35.doc DOC document
Pump Data Sheet-34.doc DOC document
Site Visit.pdf PDF
36C25622Q1302.pdf PDF
WAGE DETERMINATION.pdf PDF
36C25622Q1302.docx DOCX document
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AABC

Precision Balance, Inc.

Telephone: 407-876-4112

Fax: 407-876-4338

Date: 10-15

Page: 34

Project: Building 7 CEP

PUMP DATA SHEET

Pump No.
07-3.5N2-CWP-1
Pump No.
07-3.5N2-CWP-2
Manufacturer
B & G
Manufacturer
B & G
Size
12 X 14 X 17.5B
Size
12 X 14 X 17.5B
Impeller
16.875
Impeller
16.875
Service
Condenser Water
Service
Condenser Water
Test Data
GPM
FT. HD
BHP
Test Data
GPM
FT. HD.
BHP
Design
4500
105
141.52
Design
4500
105
141.52
Actual
4481
105.82
127.6
Actual
4519
104.59
121.90
Discharge
56.84
Discharge
55.85
Suction
11.03
Suction
10.51
ΔP X 2.31=Ft. HD
45.81 X 2.31 = 105.82
ΔP X 2.31=Ft. HD
45.28 X 2.31 =104.59
Block Off
------
Block Off
------
Discharge
78.90
Discharge
76.81
Suction
14.87
Suction
14.0
ΔP X 2.31= Ft. HD
64.03 X 2.31 = 147.90
ΔP X 2.31=Ft. HD
62.81 X 2.31 = 145.09
Motor Mfg.
Marathon
Motor Mfg.
Marathon
Frame
447T
Frame
447T
H.P.
200
H.P.
200
RPM
1190
RPM
1190
AMPS Design
245
Act: 156 / 156 /157
AMPS Design
245
Act: 145 / 149 / 150
Volts Design
480
Act: 409 / 409 / 410
Volts Design
480
Act: 415 / 415 / 416

@ 49 htz @ 50 htz