This document contains specifications for aluminum windows required for a construction project and a pre-solicitation notice for the related federal contract opportunity. The construction project involves renovating pathology and laboratory space at the Michael E. DeBakey VA Medical Center and requires fixed aluminum windows that meet specifications for materials, fabrication, thermal performance, and finishes. The pre-solicitation notice is for a construction contract set aside for Service-Disabled Veteran-Owned Small Businesses to construct approximately 12,400 square feet of pathology and laboratory space including demolition, structural work, mechanical, electrical and plumbing systems, and interior finishes. The solicitation will be issued as a request for proposals with a 90-day proposal acceptance period and requirements for bid bonds, performance bonds, and payment bonds. The contract value is estimated between $2 million and $5 million. Offerors must register in various systems and have online representations and certifications completed by the solicitation due date.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Michael E. DeBakey VA Medical Center VA Project No: 580-18-118

Network Contracting Office 16
Renovation of Pathology and Laboratory, Phase III

SECTION 08 51 13

ALUMINUM WINDOWS

PART 1 - GENERAL

1.1 DESCRIPTION

A.

Aluminum windows of type and size shown, complete with hardware, related components and accessories.

B.

Type:

1.

Fixed

1.2 DEFINITIONS

A.

Accessories: Mullions, staff beads, casings, closures, trim, moldings, panning systems, sub-sills, clips anchors, fasteners, and other necessary components required for fabrication and installation of window units.

B.

Uncontrolled Water: Water not drained to the exterior, or water appearing on the room side of the window.

1.3 RELATED WORK

A.

Steel subframes: Section 05 50 00, METAL FABRICATIONS B.

Glazing: Section 08 80 00, GLAZING C.

Color of finish: As indicated in Drawings.

1.4 DELIVERY, STORAGE AND HANDLING

A.

Protect windows from damage during handling and construction operations before, during and after installation.

B.

Store windows under cover, setting upright.

C.

Do not stack windows flat.

D.

Do not lay building materials or equipment on windows.

1.5 QUALITY ASSURANCE

A.

Approval by Contracting Officer is required of products or service of proposed manufacturers and installers.

B.

Approval will be based on submission of certification by Contractor that:

1.

Manufacturer regularly and presently manufactures the specified windows as one of its principal products.

2.

Installer has technical qualifications, experience, trained personnel and facilities to install specified items.

C.

Provide each type of window produced from one source of manufacture.

D.

Quality Certified Labels or certificate:

1.

Architectural Aluminum Manufacturers Association, "AAMA label" affixed to each window indicating compliance with specification.

2.

Certificates in lieu of label with copy of recent test report (not more than 4 years old) from an independent testing laboratory and certificate signed by window manufacturer stating that windows provided comply with specified requirements and AAMA 101/I.S.2 for type of window specified.

1.6 SUBMITTAL

A.

Shop Drawings:

1.

Minimum of 1/2 full scale, all types of windows on project.

2.

Identifying parts of window units by name and kind of metal or material, show construction, trim, installation and anchorages.

3.

Include glazing details and standards for factory glazed units.

B.

Manufacturer's Literature and Data: Window C.

Certificates:

1.

Indicating manufacturers and installers qualifications.

2.

Manufacturer's Certification that windows delivered to project are identical to windows tested.

D.

Test Reports:

Copies of test reports as specified in paragraph QUALITY ASSURANCE.

E.

Samples: Provide 150 mm (6-inch) length samples showing finishes specified.

1.7 WARRANTY

A.

Warrant windows against malfunctions due to defects in thermal breaks, hardware, materials and workmanship, subject to the terms of Article “WARRANTY OF CONSTRUCTION”, FAR clause 52.246-21, except provide 5 year warranty period.

1.8 APPLICABLE PUBLICATIONS

A.

Publications listed below form a part of this specification to extent referenced. Publications are referenced in text by basic designation only.

B.

American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) 90.1-07 Energy Standard of Buildings

C.

American Architectural Manufacturers Association (AAMA):

101/I.S.2/A440-08 Windows, Doors, and Unit Skylights 505-09 Dry Shrinkage and Composite Performance Thermal Cycling Test Procedures

2605-05 Superior Performing Organic Coatings on Architectural Aluminum Extrusions and Panels

TIR-A8-08

Structural Performance of Poured and Debridged Framing Systems

D.

American Society for Testing and Materials (ASTM):

A653/A653M-09 Steel Sheet, Zinc Coated (Galvanized), Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-dip Process

E 90-09 Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions

E.

National Fenestration Rating Council (NFRC):

NFRC 100-10

Determining Fenestration Product U-Factors

NFRC 200-10

Determining Fenestration Product Solar Heat Gain Coefficient and Visible Transmittance at Normal Incidence

F.

National Association of Architectural Metal Manufacturers (NAAMM):

AMP 500-06

Metal Finishes Manual

PART 2- PRODUCTS

2.1 MATERIALS

A.

Basis of Design: Kawneer “AA 3350 ISOPORT.”

1.

Products of other manufacturers satisfying the requirements of this specification shall be acceptable.

B.

Aluminum Extrusions; Sheet and Plate: AAMA 101/I.S.2 C.

Sheet Steel, Galvanized: ASTM A653; G90 galvanized coating D.

Weather-strips: AAMA 101/I.S.2; except leaf type weather-stripping is not permitted.

E.

Fasteners: AAMA 101/I.S.2. Screws, bolts, nuts, rivets, and other fastening devices to be non-magnetic stainless steel.

1.

Fasteners to be concealed when window is closed. Where wall thickness is less than 3 mm (0.125 inch) thick, provide backup plates or similar reinforcements for fasteners.

2.

Stainless steel self tapping screws may be used to secure Venetian blind hanger clips, vent guide blocks, friction adjuster, and limit opening device.

3.

Attach locking and hold-open devices to windows with concealed fasteners. Provide reinforcing plates where wall thickness is less than 3 mm (0.125 inch) thick.

2.2 THERMAL PERFORMANCE

A.

Thermal Transmittance:

1.

Maximum U value class for insulating glass windows: 50 (U=0.50) 2.

Maximum U value class for dual glazed windows: 70 (U=0.70), or as required by ASHRAE 90.1.

B.

Solar Heat Gain Coefficient (SHGC): SHGC shall comply with state or local energy code requirement.

2.3 FABRICATION

A.

Fabrication to exceed or meet requirements of Physical Load Tests, Air Infiltration Test, and Water Resistance Test of AAMA 101/I.S.2.

B.

Glazing:

1.

Factory or field glazing optional 2.

Glaze in accordance with Section 08 80 00, GLAZING.

3.

Windows reglazable without dismantling sash framing.

4.

Design rabbet to suit glass thickness and glazing method specified.

5.

Glaze from interior except where not accessible.

6.

Provide removable fin type glazing beads.

C.

Trim:

1.

Trim includes casings, closures, and panning.

2.

Fabricate to shapes shown of aluminum not less than 1.6 mm (0.062 inch) thick

3.

Extruded or formed sections, straight, true, and smooth on exposed surfaces. Curved sections true to line.

4.

Exposed external corners mitered and internal corners coped; fitted with hairline joints.

5.

Reinforce 1.6 mm (0.062 inch) thick members with not less than 3 mm (1/8-inch) thick aluminum.

6.

Except for strap anchors, provide reinforcing for fastening near ends and at intervals not more than 305 mm (12 inches) between ends.

7.

Design to allow unrestricted expansion and contraction of members and window frames.

8.

Secure to window frames with machine screws or expansion rivets.

9.

Exposed screws, fasteners or pop rivets are not acceptable on exterior of the casing or trim cover system.

D.

Thermal-Break Construction:

1.

Manufacturer’s standard 2.

Low conductance thermal barrier 3.

Capable of structurally holding sash in position and together.

4.

All Thermal Break Assemblies (Pour & Debridge, Insulbar or others) shall be tested as per AAMA TIR A8 and AAMA 505 for Dry Shrinkage and Composite Performance.

5.

Location of thermal barrier and design of window shall be such that, in closed position, outside air shall not come in direct contact with interior frame of the window.

E.

Mullions: AAMA 101 F.

Subsills and Stools:

1.

Fabricate to shapes shown of not less than 2 mm (0.080 inch) thick extruded aluminum.

2.

One piece full length of opening with concealed anchors.

3.

Sills turned up back edge not less than 6 mm (1/4 inch). Front edge provide with drip.

4.

Sill back edge behind face of window frame. Do not extend to interior surface or bridge thermal breaks.

5.

Do not perforate for anchorage, clip screws, or other requirements.

2.9 Fixed Windows

A.

CLASS CW-PG50-FW / AW-PG50-FW

B.

AAMA / WDMA / CSA / 101 / I.S.2 / A440-08 (NAFS-08)

2.10 FINISH

A.

In accordance with NAAMM AMP 500 series B.

Finish exposed aluminum surfaces as follows:

1.

Anodized Aluminum:

a.

Finish in accordance with AMP 501 letters and numbers.

b.

Colored anodized Finish: AA-C22A42 (anodized) or AA-C22A44 (electrolytically deposited metallic compound) medium matte, integrally colored coating, Class 1 Architectural, 0.7 mils thick.

1) Dyes not accepted.

2) Variation of more than 50 percent of maximum shade range approved will not be accepted in a single window or in adjacent windows and mullions on a continuous series.

a) AMP 501 and 505 b) Steel: AMP 504 c) Stainless steel: AMP 503 i.

Concealed: 2B or 2D ii.

Exposed: No. 4 unless specified otherwise.

C.

Hardware: Finish hardware exposed when window is in the closed position: Match window color.

PART 3 - EXECUTION

3.1 PROTECTION (DISSIMILAR MATERIALS)

A.

AAMA 101/I.S.2

3.2 INSTALLATION, GENERAL

A.

Install window units in accordance with manufacturer's specifications and recommendations for installation of window units, hardware, operators and other components of work.

B.

Where type, size or spacing of fastenings for securing window accessories or equipment to building construction is not shown or specified, use expansion or toggle bolts or screws, as best suited to construction material.

1.

Provide bolts or screws minimum 6 mm (1/4-inch) in diameter.

2.

Sized and spaced to resist the tensile and shear loads imposed.

3.

Do not use exposed fasteners on exterior, except when unavoidable for application of hardware.

4.

Provide non-magnetic stainless steel Phillips flat-head machine screws for exposed fasteners, where required, or special tamper-proof fasteners.

5.

Locate fasteners to not disturb the thermal break construction of windows.

C.

Set windows plumb, level, true, and in alignment; without warp or rack of frames or sash.

D.

Anchor windows on four sides with anchor clips or fin trim.

1.

Do not allow anchor clips to bridge thermal breaks.

2.

Use separate clips for each side of thermal breaks.

3.

Make connections to allow for thermal and other movements.

4.

Do not allow building load to bear on windows.

5.

Use manufacturer's standard clips at corners and not over 600 mm (24 inches) on center.

E.

Sills and Stools:

1.

Set in bed of mortar or other compound to fully support, true to line shown.

2.

Do not extend sill to inside window surface or past thermal break.

3.

Leave space for sealants at ends and to window frame unless shown otherwise.

4.

Do not leave openings uncovered at end of working day, during precipitation or temperatures below 16 degrees C (60 degrees F).

3.3 MULLIONS CLOSURES, TRIM, AND PANNING

A.

Cut mullion full height of opening and anchor directly to window frame on each side.

B.

Closures, Trim, and Panning: External corners mitered and internal corners coped, fitted with hairline, tightly closed joints.

C.

Screwed to metal.

D.

Fasten except for strap anchors, near ends and corners and at intervals not more than 300 mm (12 inches) between.

E.

Seal units following installation to provide weathertight system.

3.4 ADJUST AND CLEAN

A.

Clean aluminum surfaces promptly after installation of windows, exercising care to avoid damage to protective coatings and finishes.

B.

Remove excess glazing and sealant compounds, dirt, and other substances.

C.

Clean glass promptly after installation of windows. Remove glazing and sealant compound, dirt and other substances.

- - - E N D - - -

ALUMINUM WINDOWS

08 51 13 - 6